Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 vertiv 1.3.6.1.4.1.21239
The MIB for Vertiv products
             v5 1.3.6.1.4.1.21239.5
                 imd 1.3.6.1.4.1.21239.5.2
                     deviceInfo 1.3.6.1.4.1.21239.5.2.1
                         productTitle 1.3.6.1.4.1.21239.5.2.1.1 snmpadminstring read-only
Product name
                         productVersion 1.3.6.1.4.1.21239.5.2.1.2 snmpadminstring read-only
Product version
                         productFriendlyName 1.3.6.1.4.1.21239.5.2.1.3 snmpadminstring read-only
User-assigned name
                         productMacAddress 1.3.6.1.4.1.21239.5.2.1.4 macaddress read-only
Product's unique MAC address
                         deviceCount 1.3.6.1.4.1.21239.5.2.1.6 integer32 read-only
Total number of devices on unit
                         temperatureUnits 1.3.6.1.4.1.21239.5.2.1.7 integer read-write
Current units for temperature/dewpoint values: 0 = Degrees Fahrenheit 1 = Degrees Celsius Enumeration: 'fahrenheit': 0, 'celsius': 1.
                         productModelNumber 1.3.6.1.4.1.21239.5.2.1.8 snmpadminstring read-only
Product model number (factory-assigned)
                         productPartNumber 1.3.6.1.4.1.21239.5.2.1.9 snmpadminstring read-only
Product part number (factory-assigned)
                         productSerialNumber 1.3.6.1.4.1.21239.5.2.1.10 snmpadminstring read-only
Product serial number (factory-assigned)
                         productPlatform 1.3.6.1.4.1.21239.5.2.1.11 snmpadminstring read-only
Product platform
                         productHostname 1.3.6.1.4.1.21239.5.2.1.12 snmpadminstring read-only
Product hostname
                         productAlarmCount 1.3.6.1.4.1.21239.5.2.1.13 integer32 read-only
Number of alarms currently tripped
                         productWarnCount 1.3.6.1.4.1.21239.5.2.1.14 integer32 read-only
Number of warnings currently tripped
                         productManufacturer 1.3.6.1.4.1.21239.5.2.1.15 snmpadminstring read-only
Product manufacturer
                     pdu 1.3.6.1.4.1.21239.5.2.3
                         pduMainTable 1.3.6.1.4.1.21239.5.2.3.1 no-access
PDU general information
                             pduMainEntry 1.3.6.1.4.1.21239.5.2.3.1.1 no-access
Entry in the pduMainTable table: each entry contains an index and other sensor details
                                 pduMainIndex 1.3.6.1.4.1.21239.5.2.3.1.1.1 integer32 no-access
Table entry index value
                                 pduMainSerial 1.3.6.1.4.1.21239.5.2.3.1.1.2 displaystring read-only
Serial number
                                 pduMainName 1.3.6.1.4.1.21239.5.2.3.1.1.3 snmpadminstring read-only
PDU name (factory-assigned)
                                 pduMainLabel 1.3.6.1.4.1.21239.5.2.3.1.1.4 snmpadminstring read-write
PDU label (user-defined)
                                 pduMainAvail 1.3.6.1.4.1.21239.5.2.3.1.1.5 gauge32 read-only
Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable
                                 pduMeterType 1.3.6.1.4.1.21239.5.2.3.1.1.6 integer read-only
Current meter type: 0 = Wye 1 = Delta Enumeration: 'wye': 0, 'delta': 1.
                                 pduTotalName 1.3.6.1.4.1.21239.5.2.3.1.1.7 snmpadminstring read-only
Total name (factory-assigned)
                                 pduTotalLabel 1.3.6.1.4.1.21239.5.2.3.1.1.8 snmpadminstring read-write
Total label (user-defined)
                                 pduTotalRealPower 1.3.6.1.4.1.21239.5.2.3.1.1.9 gauge32 read-only
PDU total real power
                                 pduTotalApparentPower 1.3.6.1.4.1.21239.5.2.3.1.1.10 gauge32 read-only
PDU total apparent power
                                 pduTotalPowerFactor 1.3.6.1.4.1.21239.5.2.3.1.1.11 gauge32 read-only
PDU total power factor
                                 pduTotalEnergy 1.3.6.1.4.1.21239.5.2.3.1.1.12 gauge32 read-only
PDU total accumulated energy in watt-hours
                         pduPhaseTable 1.3.6.1.4.1.21239.5.2.3.2 no-access
PDU phases information
                             pduPhaseEntry 1.3.6.1.4.1.21239.5.2.3.2.1 no-access
Entry in the pduPhaseTable table: each entry contains an index and other sensor details
                                 pduPhaseIndex 1.3.6.1.4.1.21239.5.2.3.2.1.1 integer32 no-access
Table entry index value
                                 pduPhaseName 1.3.6.1.4.1.21239.5.2.3.2.1.2 snmpadminstring read-only
PDU phase name (factory-assigned)
                                 pduPhaseLabel 1.3.6.1.4.1.21239.5.2.3.2.1.3 snmpadminstring read-write
PDU phase label (user-defined)
                                 pduPhaseVoltage 1.3.6.1.4.1.21239.5.2.3.2.1.4 gauge32 read-only
PDU phase voltage in tenths of a volt
                                 pduPhaseCurrent 1.3.6.1.4.1.21239.5.2.3.2.1.8 gauge32 read-only
PDU phase current reading in hundredths of an amp
                                 pduPhaseRealPower 1.3.6.1.4.1.21239.5.2.3.2.1.12 gauge32 read-only
Real power for phase in watts
                                 pduPhaseApparentPower 1.3.6.1.4.1.21239.5.2.3.2.1.13 gauge32 read-only
Apparent power for phase in volt-amps
                                 pduPhasePowerFactor 1.3.6.1.4.1.21239.5.2.3.2.1.14 gauge32 read-only
Power factor for phase
                                 pduPhaseEnergy 1.3.6.1.4.1.21239.5.2.3.2.1.15 gauge32 read-only
Accumulated energy for phase in watt-hours
                                 pduPhaseBalance 1.3.6.1.4.1.21239.5.2.3.2.1.17 gauge32 read-only
Phase balance as percent
                                 pduPhaseCurrentCrestFactor 1.3.6.1.4.1.21239.5.2.3.2.1.19 gauge32 read-only
Current crest factor for phase, in hundredths
                         pduBreakerTable 1.3.6.1.4.1.21239.5.2.3.3 no-access
PDU breaker information
                             pduBreakerEntry 1.3.6.1.4.1.21239.5.2.3.3.1 no-access
Entry in the pduBreakerTable table: each entry contains an index and other sensor details
                                 pduBreakerIndex 1.3.6.1.4.1.21239.5.2.3.3.1.1 integer32 no-access
Table entry index value
                                 pduBreakerName 1.3.6.1.4.1.21239.5.2.3.3.1.2 snmpadminstring read-only
PDU breaker name (factory-assigned)
                                 pduBreakerLabel 1.3.6.1.4.1.21239.5.2.3.3.1.3 snmpadminstring read-write
PDU breaker label (user-defined)
                                 pduBreakerCurrent 1.3.6.1.4.1.21239.5.2.3.3.1.4 gauge32 read-only
PDU breaker current reading in hundredths of an amp
                                 pduBreakerVoltage 1.3.6.1.4.1.21239.5.2.3.3.1.8 gauge32 read-only
PDU breaker voltage in tenths of a volt. This object may not exist on all platforms, due to hardware differences.
                                 pduBreakerRealPower 1.3.6.1.4.1.21239.5.2.3.3.1.12 gauge32 read-only
Real power for breaker in watts. This object may not exist on all platforms, due to hardware differences.
                                 pduBreakerApparentPower 1.3.6.1.4.1.21239.5.2.3.3.1.13 gauge32 read-only
Apparent power for breaker in volt-amps. This object may not exist on all platforms, due to hardware differences.
                                 pduBreakerPowerFactor 1.3.6.1.4.1.21239.5.2.3.3.1.14 gauge32 read-only
Power factor for breaker. This object may not exist on all platforms, due to hardware differences.
                                 pduBreakerEnergy 1.3.6.1.4.1.21239.5.2.3.3.1.15 gauge32 read-only
Accumulated energy for breaker in watt-hours. This object may not exist on all platforms, due to hardware differences.
                         pduLineTable 1.3.6.1.4.1.21239.5.2.3.4 no-access
PDU line current information
                             pduLineEntry 1.3.6.1.4.1.21239.5.2.3.4.1 no-access
Entry in the pduLineTable table: each entry contains an index and other sensor details
                                 pduLineIndex 1.3.6.1.4.1.21239.5.2.3.4.1.1 integer32 no-access
Table entry index value
                                 pduLineName 1.3.6.1.4.1.21239.5.2.3.4.1.2 snmpadminstring read-only
PDU line name (factory-assigned)
                                 pduLineLabel 1.3.6.1.4.1.21239.5.2.3.4.1.3 snmpadminstring read-write
PDU line label (user-defined)
                                 pduLineCurrent 1.3.6.1.4.1.21239.5.2.3.4.1.4 gauge32 read-only
PDU line current reading in hundredths of an amp
                         pduOutletSwitchTable 1.3.6.1.4.1.21239.5.2.3.5 no-access
Data, config and control for outlets with switching
                             pduOutletSwitchEntry 1.3.6.1.4.1.21239.5.2.3.5.1 no-access
Entry in the pduOutletSwitchTable table: each entry contains an index and other sensor details
                                 pduOutletSwitchIndex 1.3.6.1.4.1.21239.5.2.3.5.1.1 integer32 no-access
Table entry index value
                                 pduOutletSwitchName 1.3.6.1.4.1.21239.5.2.3.5.1.2 snmpadminstring read-only
PDU outlet name (factory-assigned)
                                 pduOutletSwitchLabel 1.3.6.1.4.1.21239.5.2.3.5.1.3 snmpadminstring read-write
PDU outlet label (user-defined)
                                 pduOutletSwitchState 1.3.6.1.4.1.21239.5.2.3.5.1.4 integer read-only
Switch state of the outlet: 1 = Outlet is on 2 = Outlet is off 3 = Outlet is on, but will turn off after a delay 4 = Outlet is off, but will turn on after a delay 5 = Starting reboot cycle, outlet is on, but will go to the rebootOff(6) state after a delay 6 = Rebooting, outlet is off, but it will turn on after a delay 7 = Cannot get outlet state Enumeration: 'on': 1, 'off': 2, 'unavailable': 7, 'off2on': 4, 'rebootOff': 6, 'rebootOn': 5, 'on2off': 3.
                                 pduOutletSwitchRelayFailure 1.3.6.1.4.1.21239.5.2.3.5.1.5 truthvalue read-only
Tells if the outlet relay has failed. In normal operation, the value will be false(2).
                                 pduOutletSwitchControl 1.3.6.1.4.1.21239.5.2.3.5.1.6 integer read-write
Used for manual control of the outlet. If the outlet is in manual mode, this field can be set to one of the following values: 1 = Cancel pending operation 2 = Turn outlet on 3 = After delay (pduOutletSwitchOnDelay), turn outlet on 4 = Turn outlet off 5 = After delay (pduOutletSwitchOffDelay), turn outlet off 6 = Reboot: turn off, delay (pduOutletSwitchRebootHoldDelay), turn outlet back on 7 = After delay (pduOutletSwitchRebootDelay), reboot outlet When not in manual mode, setting this field will give an inconsistentValue error. Returns none(8) for all get requests. Enumeration: 'on': 2, 'none': 8, 'off': 4, 'onAfterDelay': 3, 'reboot': 6, 'rebootAfterDelay': 7, 'cancel': 1, 'offAfterDelay': 5.
                                 pduOutletSwitchTimeToAction 1.3.6.1.4.1.21239.5.2.3.5.1.7 integer32 read-only
Seconds until an outlet state change. The value of pduOutletSwitchState tells what state the outlet will be set, after the delay.
                                 pduOutletSwitchOnDelay 1.3.6.1.4.1.21239.5.2.3.5.1.8 integer32 read-write
Seconds to wait before powering on the outlet, during onAfterDelay(3) operation. Changing this value has no effect on pending actions.
                                 pduOutletSwitchOffDelay 1.3.6.1.4.1.21239.5.2.3.5.1.9 integer32 read-write
Seconds to wait before powering off the outlet, during offAfterDelay(5) operation. Changing this value has no effect on pending actions.
                                 pduOutletSwitchRebootDelay 1.3.6.1.4.1.21239.5.2.3.5.1.10 integer32 read-write
Seconds to wait before powering off the outlet, during rebootAfterDelay(7) operation. Changing this value has no effect on pending actions. See pduOutletSwitchControl for more info.
                                 pduOutletSwitchRebootHoldDelay 1.3.6.1.4.1.21239.5.2.3.5.1.11 integer32 read-write
Seconds to hold the outlet off, before powering on the outlet, during rebootAfterDelay(7) operation. Changing this value has no effect on pending actions. See pduOutletSwitchControl for more info.
                                 pduOutletSwitchPoaAction 1.3.6.1.4.1.21239.5.2.3.5.1.12 integer read-write
The outlet is set to this state during power-up. The action can be have one the following values: 1 = Outlet will be turned on 2 = Outlet will stay off 3 = Outlet will be set to last known state Enumeration: 'on': 1, 'off': 2, 'last': 3.
                                 pduOutletSwitchPoaDelay 1.3.6.1.4.1.21239.5.2.3.5.1.13 integer32 read-write
Seconds to wait before setting the outlet to the pduOutletSwitchPoaAction state. The delay starts at power-up.
                         pduOutletMeterTable 1.3.6.1.4.1.21239.5.2.3.6 no-access
Metering data for outlets that support this feature
                             pduOutletMeterEntry 1.3.6.1.4.1.21239.5.2.3.6.1 no-access
Entry in the pduOutletMeterTable table: each entry contains an index and other sensor details
                                 pduOutletMeterIndex 1.3.6.1.4.1.21239.5.2.3.6.1.1 integer32 no-access
Table entry index value
                                 pduOutletMeterName 1.3.6.1.4.1.21239.5.2.3.6.1.2 snmpadminstring read-only
PDU outlet name (factory-assigned)
                                 pduOutletMeterLabel 1.3.6.1.4.1.21239.5.2.3.6.1.3 snmpadminstring read-write
PDU outlet label (user-defined)
                                 pduOutletMeterVoltage 1.3.6.1.4.1.21239.5.2.3.6.1.4 gauge32 read-only
PDU outlet voltage in tenths of a volt
                                 pduOutletMeterCurrent 1.3.6.1.4.1.21239.5.2.3.6.1.8 gauge32 read-only
PDU outlet current reading in hundredths of an amp
                                 pduOutletMeterRealPower 1.3.6.1.4.1.21239.5.2.3.6.1.12 gauge32 read-only
Real power for outlet in watts
                                 pduOutletMeterApparentPower 1.3.6.1.4.1.21239.5.2.3.6.1.13 gauge32 read-only
Apparent power for outlet in volt-amps
                                 pduOutletMeterPowerFactor 1.3.6.1.4.1.21239.5.2.3.6.1.14 gauge32 read-only
Power factor for outlet
                                 pduOutletMeterEnergy 1.3.6.1.4.1.21239.5.2.3.6.1.15 gauge32 read-only
Accumulated energy for outlet in watt-hours
                                 pduOutletMeterReset 1.3.6.1.4.1.21239.5.2.3.6.1.16 integer read-write
Used to reset energy. If read, the value is none(8). It can be set to resetEnergy(1), which sets outlet energy to 0 Enumeration: 'resetEnergy': 1, 'none': 8.
                                 pduOutletCurrentCrestFactor 1.3.6.1.4.1.21239.5.2.3.6.1.19 gauge32 read-only
Current crest factor for outlet, in hundredths
                     tempSensorTable 1.3.6.1.4.1.21239.5.2.4 no-access
Remote Temperature (RT) sensor
                         tempSensorEntry 1.3.6.1.4.1.21239.5.2.4.1 no-access
Entry in the tempSensorTable table: each entry contains an index and other sensor details
                             tempSensorIndex 1.3.6.1.4.1.21239.5.2.4.1.1 integer32 no-access
Table entry index value
                             tempSensorSerial 1.3.6.1.4.1.21239.5.2.4.1.2 displaystring read-only
Serial number
                             tempSensorLabel 1.3.6.1.4.1.21239.5.2.4.1.3 snmpadminstring read-write
User-defined label
                             tempSensorAvail 1.3.6.1.4.1.21239.5.2.4.1.4 gauge32 read-only
Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable
                             tempSensorTemp 1.3.6.1.4.1.21239.5.2.4.1.5 integer32 read-only
Temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
                     airFlowSensorTable 1.3.6.1.4.1.21239.5.2.5 no-access
Remote Airflow, Humidity, Temperature and Dewpoint (AFHT3) Sensor
                         airFlowSensorEntry 1.3.6.1.4.1.21239.5.2.5.1 no-access
Entry in the airFlowSensorTable table: each entry contains an index and other sensor details
                             airFlowSensorIndex 1.3.6.1.4.1.21239.5.2.5.1.1 integer32 no-access
Table entry index value
                             airFlowSensorSerial 1.3.6.1.4.1.21239.5.2.5.1.2 displaystring read-only
Serial number
                             airFlowSensorLabel 1.3.6.1.4.1.21239.5.2.5.1.3 snmpadminstring read-write
User-defined label
                             airFlowSensorAvail 1.3.6.1.4.1.21239.5.2.5.1.4 gauge32 read-only
Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable
                             airFlowSensorTemp 1.3.6.1.4.1.21239.5.2.5.1.5 integer32 read-only
Temperature reading in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
                             airFlowSensorFlow 1.3.6.1.4.1.21239.5.2.5.1.6 integer32 read-only
Airflow reading. Still air will be less than 20, while rushing air will be around 100.
                             airFlowSensorHumidity 1.3.6.1.4.1.21239.5.2.5.1.7 integer32 read-only
Humidity reading
                             airFlowSensorDewPoint 1.3.6.1.4.1.21239.5.2.5.1.8 integer32 read-only
Dewpoint reading in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
                     t3hdSensorTable 1.3.6.1.4.1.21239.5.2.8 no-access
Remote Temperature x 3, Humidity and Dewpoint Sensor
                         t3hdSensorEntry 1.3.6.1.4.1.21239.5.2.8.1 no-access
Entry in the t3hdSensorTable table: each entry contains an index and other sensor details
                             t3hdSensorIndex 1.3.6.1.4.1.21239.5.2.8.1.1 integer32 no-access
Table entry index value
                             t3hdSensorSerial 1.3.6.1.4.1.21239.5.2.8.1.2 displaystring read-only
Serial number
                             t3hdSensorLabel 1.3.6.1.4.1.21239.5.2.8.1.3 snmpadminstring read-write
User-defined label
                             t3hdSensorAvail 1.3.6.1.4.1.21239.5.2.8.1.4 gauge32 read-only
Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable
                             t3hdSensorIntLabel 1.3.6.1.4.1.21239.5.2.8.1.5 snmpadminstring read-write
Internal label (user-defined)
                             t3hdSensorIntTemp 1.3.6.1.4.1.21239.5.2.8.1.6 integer32 read-only
Internal temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
                             t3hdSensorIntHumidity 1.3.6.1.4.1.21239.5.2.8.1.7 integer32 read-only
Internal humidity
                             t3hdSensorIntDewPoint 1.3.6.1.4.1.21239.5.2.8.1.8 integer32 read-only
Internal dewpoint in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
                             t3hdSensorExtAAvail 1.3.6.1.4.1.21239.5.2.8.1.9 gauge32 read-only
External A status: 0 = Unavailable 1 = Available
                             t3hdSensorExtALabel 1.3.6.1.4.1.21239.5.2.8.1.10 snmpadminstring read-write
External A label (user-defined)
                             t3hdSensorExtATemp 1.3.6.1.4.1.21239.5.2.8.1.11 integer32 read-only
External A temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
                             t3hdSensorExtBAvail 1.3.6.1.4.1.21239.5.2.8.1.12 gauge32 read-only
External B status: 0 = Unavailable 1 = Available
                             t3hdSensorExtBLabel 1.3.6.1.4.1.21239.5.2.8.1.13 snmpadminstring read-write
External B label (user-defined)
                             t3hdSensorExtBTemp 1.3.6.1.4.1.21239.5.2.8.1.14 integer32 read-only
External B temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
                     thdSensorTable 1.3.6.1.4.1.21239.5.2.9 no-access
Remote Temperature, Humidity, and Dewpoint (THD) Sensor
                         thdSensorEntry 1.3.6.1.4.1.21239.5.2.9.1 no-access
Entry in the thdSensorTable table: each entry contains an index and other sensor details
                             thdSensorIndex 1.3.6.1.4.1.21239.5.2.9.1.1 integer32 no-access
Table entry index value
                             thdSensorSerial 1.3.6.1.4.1.21239.5.2.9.1.2 displaystring read-only
Serial number
                             thdSensorLabel 1.3.6.1.4.1.21239.5.2.9.1.3 snmpadminstring read-write
User-defined label
                             thdSensorAvail 1.3.6.1.4.1.21239.5.2.9.1.4 gauge32 read-only
Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable
                             thdSensorTemp 1.3.6.1.4.1.21239.5.2.9.1.5 integer32 read-only
Temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
                             thdSensorHumidity 1.3.6.1.4.1.21239.5.2.9.1.6 integer32 read-only
Humidity value
                             thdSensorDewPoint 1.3.6.1.4.1.21239.5.2.9.1.7 integer32 read-only
Dewpoint value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
                     a2dSensorTable 1.3.6.1.4.1.21239.5.2.11 no-access
Analog measurement (A2D) sensor (voltage, current, or dry-contact)
                           a2dSensorEntry 1.3.6.1.4.1.21239.5.2.11.1 no-access
Entry in the a2dSensorTable table: each entry contains an index and other sensor details
                               a2dSensorIndex 1.3.6.1.4.1.21239.5.2.11.1.1 integer32 no-access
Table entry index value
                               a2dSensorSerial 1.3.6.1.4.1.21239.5.2.11.1.2 displaystring read-only
Serial number
                               a2dSensorLabel 1.3.6.1.4.1.21239.5.2.11.1.3 snmpadminstring read-write
User-defined label
                               a2dSensorAvail 1.3.6.1.4.1.21239.5.2.11.1.4 gauge32 read-only
Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable
                               a2dSensorValue 1.3.6.1.4.1.21239.5.2.11.1.5 integer32 read-only
Analog measurement value, within either a user-defined or preset range, depending on a2dSensorMode.
                               a2dSensorDisplayValue 1.3.6.1.4.1.21239.5.2.11.1.6 snmpadminstring read-only
For current/voltage modes, the analog value is given as a string. In binary modes, the value is either a2dSensorLowLabel or a2dSensorHighLabel, based on a2dSensorValue.
                               a2dSensorMode 1.3.6.1.4.1.21239.5.2.11.1.7 integer read-write
Binary modes have two states represented by the values 0 (low) or 1 (high). These correspond to a2dSensorLowLabel and a2dSensorHighLabel. Current and voltage modes provide a scaled value from a2dSensorMin to a2dSensorMax. Analog modes: 1 = Door (binary) 2 = Power failure (binary) 3 = Flood (binary) 4 = Water-sensing cable leak (binary) 5 = Water-sensing cable fault (binary) 6 = Smoke alarm (binary) 7 = Isolated voltage negative ground (voltage) 8 = Isolated voltage positive ground (voltage) 9 = Custom voltage (voltage) 10 = Custom binary (binary) 11 = Custom current (current) Enumeration: 'powerFailure': 2, 'door': 1, 'ivsNegGnd': 7, 'wscLeak': 4, 'customCurrent': 11, 'customVoltage': 9, 'wscFault': 5, 'flood': 3, 'smoke': 6, 'ivsPosGnd': 8, 'customBinary': 10.
                               a2dSensorUnits 1.3.6.1.4.1.21239.5.2.11.1.8 snmpadminstring read-write
The units for the analog value. If a2dSensorMode is customVoltage(9) or customCurrent(11), then this field has a user-defined value. Otherwise, the value is fixed, based on mode.
                               a2dSensorMin 1.3.6.1.4.1.21239.5.2.11.1.9 integer32 read-write
Minimum analog value, given as an integer. The analog measurement is scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is customVoltage(9) or customCurrent(11), then this field has a user- defined value. Otherwise, the value is fixed, based on mode.
                               a2dSensorMax 1.3.6.1.4.1.21239.5.2.11.1.10 integer32 read-write
Maximum analog value, given as an integer. The analog measurement is scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is customVoltage(9) or customCurrent(11), then this field has a user- defined value. Otherwise, the value is fixed, based on mode.
                               a2dSensorLowLabel 1.3.6.1.4.1.21239.5.2.11.1.11 snmpadminstring read-write
Label for 0 (low) binary value. This field is only applicable if a2dSensorMode is one of the binary modes. If a2dSensorMode is customBinary(10), then this field is user-defined. Otherwise, it has a pre-defined value based on the mode.
                               a2dSensorHighLabel 1.3.6.1.4.1.21239.5.2.11.1.12 snmpadminstring read-write
Label for 1 (high) binary value. The field is only applicable if a2dSensorMode is one of the binary modes. If a2dSensorMode is customBinary(10), then this field is user-defined. Otherwise, it has a pre-defined value based on the mode.
                               a2dSensorAnalogLabel 1.3.6.1.4.1.21239.5.2.11.1.13 snmpadminstring read-write
Label for the analog measurement
                     humiditySensorTable 1.3.6.1.4.1.21239.5.2.12 no-access
Remote humidity sensor
                           humiditySensorEntry 1.3.6.1.4.1.21239.5.2.12.1 no-access
Entry in the humiditySensorTable table: each entry contains an index and other sensor details
                               humiditySensorIndex 1.3.6.1.4.1.21239.5.2.12.1.1 integer32 no-access
Table entry index value
                               humiditySensorSerial 1.3.6.1.4.1.21239.5.2.12.1.2 displaystring read-only
Serial number
                               humiditySensorLabel 1.3.6.1.4.1.21239.5.2.12.1.3 snmpadminstring read-write
User-defined label
                               humiditySensorAvail 1.3.6.1.4.1.21239.5.2.12.1.4 gauge32 read-only
Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable
                               humiditySensorValue 1.3.6.1.4.1.21239.5.2.12.1.5 integer32 read-only
Humidity value
                     sn2dSensorTable 1.3.6.1.4.1.21239.5.2.13 no-access
2 Door Switch Sensor (SN-2D)
                           sn2dSensorEntry 1.3.6.1.4.1.21239.5.2.13.1 no-access
Entry in the sn2dSensorTable table: each entry contains an index and other sensor details
                               sn2dSensorIndex 1.3.6.1.4.1.21239.5.2.13.1.1 integer32 no-access
Table entry index value
                               sn2dSensorSerial 1.3.6.1.4.1.21239.5.2.13.1.2 displaystring read-only
Serial number
                               sn2dSensorLabel 1.3.6.1.4.1.21239.5.2.13.1.3 snmpadminstring read-write
User-defined label
                               sn2dSensorAvail 1.3.6.1.4.1.21239.5.2.13.1.4 gauge32 read-only
Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable
                               sn2dSensorDoor1Label 1.3.6.1.4.1.21239.5.2.13.1.5 snmpadminstring read-write
Door switch 1 label
                               sn2dSensorDoor1State 1.3.6.1.4.1.21239.5.2.13.1.6 integer read-only
Door switch 1 state: 1 = open 2 = closed Enumeration: 'open': 1, 'closed': 2.
                               sn2dSensorDoor1DisplayState 1.3.6.1.4.1.21239.5.2.13.1.7 snmpadminstring read-only
Door switch 1 state given as a string
                               sn2dSensorDoor2Label 1.3.6.1.4.1.21239.5.2.13.1.8 snmpadminstring read-write
Door switch 2 label
                               sn2dSensorDoor2State 1.3.6.1.4.1.21239.5.2.13.1.9 integer read-only
Door switch 2 state: 1 = open 2 = closed Enumeration: 'open': 1, 'closed': 2.
                               sn2dSensorDoor2DisplayState 1.3.6.1.4.1.21239.5.2.13.1.10 snmpadminstring read-only
Door switch 2 state given as a string
                     cooling 1.3.6.1.4.1.21239.5.2.30
                           vrc 1.3.6.1.4.1.21239.5.2.30.1
                               vrcMainTable 1.3.6.1.4.1.21239.5.2.30.1.1 no-access
Table that contains general VRC information
                                   vrcMainEntry 1.3.6.1.4.1.21239.5.2.30.1.1.1 no-access
Entry in the vrcMainTable: each entry represents a VRC device
                                       vrcMainIndex 1.3.6.1.4.1.21239.5.2.30.1.1.1.1 integer32 no-access
Unique id for each entry in the table
                                       vrcMainSerial 1.3.6.1.4.1.21239.5.2.30.1.1.1.2 displaystring read-only
Serial number
                                       vrcMainName 1.3.6.1.4.1.21239.5.2.30.1.1.1.3 snmpadminstring read-only
VRC name (factory-assigned)
                                       vrcMainLabel 1.3.6.1.4.1.21239.5.2.30.1.1.1.4 snmpadminstring read-write
VRC label (user-defined)
                                       vrcMainAvail 1.3.6.1.4.1.21239.5.2.30.1.1.1.5 gauge32 read-only
Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable
                               vrcMainPtTable 1.3.6.1.4.1.21239.5.2.30.1.2 no-access
Table that contains general VRC status
                                   vrcMainPtEntry 1.3.6.1.4.1.21239.5.2.30.1.2.1 no-access
Entry in the vrcMainPtTable: each entry contains status data for a VRC device
                                       vrcMainPtIndex 1.3.6.1.4.1.21239.5.2.30.1.2.1.1 integer32 no-access
Unique id for each entry in the table
                                       vrcMainPtRunState 1.3.6.1.4.1.21239.5.2.30.1.2.1.2 integer read-only
VRC run state: 1 = on 2 = off Enumeration: 'on': 1, 'off': 2.
                                       vrcMainPtEevOpened 1.3.6.1.4.1.21239.5.2.30.1.2.1.3 integer32 read-only
Eev opened value (percent)
                                       vrcMainPtAlarmNumbers 1.3.6.1.4.1.21239.5.2.30.1.2.1.4 integer32 read-only
Alarm numbers value
                                       vrcMainPtHistoryAlarmNumbers 1.3.6.1.4.1.21239.5.2.30.1.2.1.5 integer32 read-only
History alarm numbers value
                                       vrcMainPtHpAbnRecordCnt 1.3.6.1.4.1.21239.5.2.30.1.2.1.6 integer32 read-only
Hp Abnormal record count
                                       vrcMainPtMonitorBaudrate 1.3.6.1.4.1.21239.5.2.30.1.2.1.7 integer read-only
Monitor baud rate: 1 = error 2 = 1200 3 = 2400 4 = 4800 5 = 9600 6 = 19200 Enumeration: 'baud1200': 2, 'baud19200': 6, 'baud2400': 3, 'error': 1, 'baud4800': 4, 'baud9600': 5.
                                       vrcMainPtMonitorAddress 1.3.6.1.4.1.21239.5.2.30.1.2.1.8 integer32 read-only
Monitor address
                                       vrcMainPtLp 1.3.6.1.4.1.21239.5.2.30.1.2.1.9 truthvalue read-only
Lp status
                                       vrcMainPtFilterMaintRemind 1.3.6.1.4.1.21239.5.2.30.1.2.1.10 truthvalue read-only
Filter maintenance reminder status
                                       vrcMainPtCoolingFlag 1.3.6.1.4.1.21239.5.2.30.1.2.1.11 truthvalue read-only
Cooling flag
                                       vrcMainPtFirstOnFlag 1.3.6.1.4.1.21239.5.2.30.1.2.1.12 truthvalue read-only
First on flag
                                       vrcMainPtNewAlarmFlag 1.3.6.1.4.1.21239.5.2.30.1.2.1.13 truthvalue read-only
New alarm flag
                                       vrcMainPtComAlarmOutState 1.3.6.1.4.1.21239.5.2.30.1.2.1.14 truthvalue read-only
Common alarm output state
                                       vrcMainPtHighWaterInput 1.3.6.1.4.1.21239.5.2.30.1.2.1.15 truthvalue read-only
High water input
                                       vrcMainPtHighWaterAlarm 1.3.6.1.4.1.21239.5.2.30.1.2.1.16 truthvalue read-only
High water alarm status
                                       vrcMainPtWaterUnderFloorAlarm 1.3.6.1.4.1.21239.5.2.30.1.2.1.17 truthvalue read-only
Water under floor alarm status
                                       vrcMainPtSwShutDownStatus 1.3.6.1.4.1.21239.5.2.30.1.2.1.18 truthvalue read-only
Software shutdown status
                                       vrcMainPtRemoteShutdown 1.3.6.1.4.1.21239.5.2.30.1.2.1.19 truthvalue read-only
Remote shutdown status
                                       vrcMainPtRemoteShutDownFlag 1.3.6.1.4.1.21239.5.2.30.1.2.1.20 truthvalue read-only
Remote shutdown flag
                                       vrcMainPtRemoteShutDownAlarm 1.3.6.1.4.1.21239.5.2.30.1.2.1.21 truthvalue read-only
Remote shutdown alarm status
                                       vrcMainPtHmiShutDownFlag 1.3.6.1.4.1.21239.5.2.30.1.2.1.22 truthvalue read-only
Hmi shutdown flag
                                       vrcMainPtLpAlarm 1.3.6.1.4.1.21239.5.2.30.1.2.1.23 truthvalue read-only
Low pressure alarm status
                                       vrcMainPtHpAlarm 1.3.6.1.4.1.21239.5.2.30.1.2.1.24 truthvalue read-only
High pressure alarm status
                                       vrcMainPtLpFreqAlarm 1.3.6.1.4.1.21239.5.2.30.1.2.1.25 truthvalue read-only
Low pressure frequently alarm status
                                       vrcMainPtHpFreqAlarm 1.3.6.1.4.1.21239.5.2.30.1.2.1.26 truthvalue read-only
High pressure frequently alarm status
                                       vrcMainPtLpSensorFailAlarm 1.3.6.1.4.1.21239.5.2.30.1.2.1.27 truthvalue read-only
Low pressure sensor failure alarm status
                                       vrcMainPtHpSensorFailAlarm 1.3.6.1.4.1.21239.5.2.30.1.2.1.28 truthvalue read-only
High pressure sensor failure alarm status
                                       vrcMainPtEevCommFailAlarm 1.3.6.1.4.1.21239.5.2.30.1.2.1.29 truthvalue read-only
Eev communication failure alarm status
                               vrcMainCfgTable 1.3.6.1.4.1.21239.5.2.30.1.3 no-access
Table that contains general VRC configuration
                                   vrcMainCfgEntry 1.3.6.1.4.1.21239.5.2.30.1.3.1 no-access
Entry in the vrcMainCfgTable: each entry contains general config fields for a VRC device
                                       vrcMainCfgIndex 1.3.6.1.4.1.21239.5.2.30.1.3.1.1 integer32 no-access
Unique id for each entry in the table
                                       vrcMainCfgModelSelect 1.3.6.1.4.1.21239.5.2.30.1.3.1.2 integer read-write
Model Selection: 1 = TMM-Local 220V 50/60HZ 2 = TMM-Global 208/230V 50/60HZ 3 = TMM-Global 120V 50/60HZ 4 = SC 220V 50/60HZ 5 = 0U 220V 50/60HZ 6 = SS 208/230V 50/60HZ 7 = SS 120V 50/60HZ Enumeration: 'r035Ep': 6, 'r035Ak': 3, 'tmLoc': 1, 'zeroULoc': 5, 'r035Ek': 7, 'scLoc': 4, 'r035Ap': 2.
                                       vrcMainCfgSystemTimeYear 1.3.6.1.4.1.21239.5.2.30.1.3.1.3 integer32 read-write
System time - year
                                       vrcMainCfgSystemTimeMonth 1.3.6.1.4.1.21239.5.2.30.1.3.1.4 integer32 read-write
System time - month
                                       vrcMainCfgSystemTimeDay 1.3.6.1.4.1.21239.5.2.30.1.3.1.5 integer32 read-write
System time - day
                                       vrcMainCfgSystemTimeHour 1.3.6.1.4.1.21239.5.2.30.1.3.1.6 integer32 read-write
System time - hour
                                       vrcMainCfgSystemTimeMin 1.3.6.1.4.1.21239.5.2.30.1.3.1.7 integer32 read-write
System time - minutes
                                       vrcMainCfgSystemTimeSec 1.3.6.1.4.1.21239.5.2.30.1.3.1.8 integer32 read-write
System time - seconds
                                       vrcMainCfgEevShtSettingMin 1.3.6.1.4.1.21239.5.2.30.1.3.1.9 integer32 read-write
Min Eev sht in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 50 to 200 Fahrenheit: 90 to 359
                                       vrcMainCfgEevShtSettingMax 1.3.6.1.4.1.21239.5.2.30.1.3.1.10 integer32 read-write
Max Eev sht in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 50 to 200 Fahrenheit: 90 to 359
                                       vrcMainCfgEevValveCloseSht 1.3.6.1.4.1.21239.5.2.30.1.3.1.11 integer32 read-write
Eev valve close sht in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 0 to 100 Fahrenheit: 0 to 179
                                       vrcMainCfgEevMopPressSetting 1.3.6.1.4.1.21239.5.2.30.1.3.1.12 integer32 read-write
Eev mop pressure setting in tenths of a bar.
                                       vrcMainCfgLpdt 1.3.6.1.4.1.21239.5.2.30.1.3.1.13 integer32 read-write
Low pressure dt in seconds
                                       vrcMainCfgDeadBand 1.3.6.1.4.1.21239.5.2.30.1.3.1.14 integer32 read-write
Dead band in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 0 to 20 Fahrenheit: 0 to 35
                                       vrcMainCfgOnOffSwitch 1.3.6.1.4.1.21239.5.2.30.1.3.1.15 truthvalue read-write
On-off switch
                                       vrcMainCfgVacuumState 1.3.6.1.4.1.21239.5.2.30.1.3.1.16 truthvalue read-write
Vacuum state
                                       vrcMainCfgControlMode 1.3.6.1.4.1.21239.5.2.30.1.3.1.17 integer read-write
Control mode: 1 = supply 2 = return Enumeration: 'return': 2, 'supply': 1.
                                       vrcMainCfgManualRunEnable 1.3.6.1.4.1.21239.5.2.30.1.3.1.18 truthvalue read-write
Manual run enable
                                       vrcMainCfgRemShutdownInput 1.3.6.1.4.1.21239.5.2.30.1.3.1.19 truthvalue read-write
Remote shutdown input
                                       vrcMainCfgMonitorShutDownFlag 1.3.6.1.4.1.21239.5.2.30.1.3.1.20 truthvalue read-write
Monitor shutdown flag
                                       vrcMainCfgFirstOnPassword 1.3.6.1.4.1.21239.5.2.30.1.3.1.21 integer32 read-write
First on password value
                                       vrcMainCfgFilterMaintSetting 1.3.6.1.4.1.21239.5.2.30.1.3.1.22 truthvalue read-write
Filter maintenance setting
                                       vrcMainCfgFilterMaintRemindTime 1.3.6.1.4.1.21239.5.2.30.1.3.1.23 integer32 read-write
Time between filter maintenance reminders in days
                                       vrcMainCfgFilterMaintRemindCtrl 1.3.6.1.4.1.21239.5.2.30.1.3.1.24 integer read-write
Filter maintenance reminder: 1 = close 2 = suspend 3 = open Enumeration: 'close': 1, 'suspend': 2, 'open': 3.
                                       vrcMainCfgCommonAlarmOutputDir 1.3.6.1.4.1.21239.5.2.30.1.3.1.25 truthvalue read-write
Common alarm output direction
                                       vrcMainCfgHpAbnAlarmSetting 1.3.6.1.4.1.21239.5.2.30.1.3.1.26 integer32 read-write
Abnormal high pressure alarm value in tenths of a bar
                                       vrcMainCfgLpAlarmCtrl 1.3.6.1.4.1.21239.5.2.30.1.3.1.27 integer read-write
Low pressure alarm control: 2 = suspend 3 = open Enumeration: 'suspend': 2, 'open': 3.
                                       vrcMainCfgHpAlarmCtrl 1.3.6.1.4.1.21239.5.2.30.1.3.1.28 integer read-write
High pressure alarm control: 2 = suspend 3 = open Enumeration: 'suspend': 2, 'open': 3.
                                       vrcMainCfgLpFreqAlarmCtrl 1.3.6.1.4.1.21239.5.2.30.1.3.1.29 integer read-write
Low pressure frequently alarm control: 2 = suspend 3 = open Enumeration: 'suspend': 2, 'open': 3.
                                       vrcMainCfgHpFreqAlarmCtrl 1.3.6.1.4.1.21239.5.2.30.1.3.1.30 integer read-write
High pressure frequently alarm control: 2 = suspend 3 = open Enumeration: 'suspend': 2, 'open': 3.
                                       vrcMainCfgLpSensorFailAlarmCtrl 1.3.6.1.4.1.21239.5.2.30.1.3.1.31 integer read-write
Low pressure sensor failure alarm control: 2 = suspend 3 = open Enumeration: 'suspend': 2, 'open': 3.
                                       vrcMainCfgHpSensorFailAlarmCtrl 1.3.6.1.4.1.21239.5.2.30.1.3.1.32 integer read-write
High pressure sensor failure alarm control: 2 = suspend 3 = open Enumeration: 'suspend': 2, 'open': 3.
                                       vrcMainCfgHighWaterAlarmCtrl 1.3.6.1.4.1.21239.5.2.30.1.3.1.33 integer read-write
High water alarm control: 1 = close 2 = suspend 3 = open Enumeration: 'close': 1, 'suspend': 2, 'open': 3.
                                       vrcMainCfgRemShutdownAlarmCtrl 1.3.6.1.4.1.21239.5.2.30.1.3.1.34 integer read-write
Remote shutdown alarm control: 2 = suspend 3 = open Enumeration: 'suspend': 2, 'open': 3.
                                       vrcMainCfgEevCommFailAlarmCtrl 1.3.6.1.4.1.21239.5.2.30.1.3.1.35 integer read-write
Eev communication failure alarm: 2 = suspend 3 = open Enumeration: 'suspend': 2, 'open': 3.
                               vrcOutFanPtTable 1.3.6.1.4.1.21239.5.2.30.1.4 no-access
Table that contains VRC out-fan status
                                   vrcOutFanPtEntry 1.3.6.1.4.1.21239.5.2.30.1.4.1 no-access
Entry in the vrcOutFanPtTable: each entry represents data for a VRC out-fan
                                       vrcOutFanPtIndex 1.3.6.1.4.1.21239.5.2.30.1.4.1.1 integer32 no-access
Unique id for each entry in the table
                                       vrcOutFanPtName 1.3.6.1.4.1.21239.5.2.30.1.4.1.2 snmpadminstring read-only
Out-fan name (factory-assigned)
                                       vrcOutFanPtSpeed 1.3.6.1.4.1.21239.5.2.30.1.4.1.3 integer32 read-only
Fan speed (percent)
                               vrcOutFanCfgTable 1.3.6.1.4.1.21239.5.2.30.1.5 no-access
Table used for VRC out-fan configuration
                                   vrcOutFanCfgEntry 1.3.6.1.4.1.21239.5.2.30.1.5.1 no-access
Entry in the vrcOutFanCfgTable: each entry contains config fields for a VRC out-fan
                                       vrcOutFanCfgIndex 1.3.6.1.4.1.21239.5.2.30.1.5.1.1 integer32 no-access
Unique id for each entry in the table
                                       vrcOutFanCfgStartPress 1.3.6.1.4.1.21239.5.2.30.1.5.1.2 integer32 read-write
Out-fan start pressure in tenths of a bar
                                       vrcOutFanCfgPressSetting 1.3.6.1.4.1.21239.5.2.30.1.5.1.3 integer32 read-write
Out-fan pressure setting in tenths of a bar
                                       vrcOutFanCfgMinPowerVoltage 1.3.6.1.4.1.21239.5.2.30.1.5.1.4 integer32 read-write
Min out-fan voltage (percent)
                                       vrcOutFanCfgMaxPowerVoltage 1.3.6.1.4.1.21239.5.2.30.1.5.1.5 integer32 read-write
Max out-fan voltage (percent)
                                       vrcOutFanCfgSpeed 1.3.6.1.4.1.21239.5.2.30.1.5.1.6 integer32 read-write
Out-fan speed (percent)
                               vrcInFanPtTable 1.3.6.1.4.1.21239.5.2.30.1.6 no-access
Table that contains VRC in-fan status
                                   vrcInFanPtEntry 1.3.6.1.4.1.21239.5.2.30.1.6.1 no-access
Entry in the vrcInFanPtTable: each entry represents data for a VRC in- fan
                                       vrcInFanPtIndex 1.3.6.1.4.1.21239.5.2.30.1.6.1.1 integer32 no-access
Unique id for each entry in the table
                                       vrcInFanPtName 1.3.6.1.4.1.21239.5.2.30.1.6.1.2 snmpadminstring read-only
In-fan name (factory-assigned)
                                       vrcInFanPtRunTimeHours 1.3.6.1.4.1.21239.5.2.30.1.6.1.3 integer32 read-only
In-fan run time in hours
                                       vrcInFanPtStartStopCount 1.3.6.1.4.1.21239.5.2.30.1.6.1.4 integer32 read-only
In-fan start/stop count
                               vrcInFanCfgTable 1.3.6.1.4.1.21239.5.2.30.1.7 no-access
Table used for VRC in-fan configuration
                                   vrcInFanCfgEntry 1.3.6.1.4.1.21239.5.2.30.1.7.1 no-access
Entry in the vrcInFanCfgTable: each entry contains config fields for a VRC in-fan
                                       vrcInFanCfgIndex 1.3.6.1.4.1.21239.5.2.30.1.7.1.1 integer32 no-access
Unique id for each entry in the table
                                       vrcInFanCfgOutputStatus 1.3.6.1.4.1.21239.5.2.30.1.7.1.2 truthvalue read-write
In-fan output status
                                       vrcInFanCfgLowSpeedStep 1.3.6.1.4.1.21239.5.2.30.1.7.1.3 integer32 read-write
In-fan low speed step in tenths of a percent per second
                                       vrcInFanCfgHighSpeedStep 1.3.6.1.4.1.21239.5.2.30.1.7.1.4 integer32 read-write
In-fan high speed step in tenths of a percent per second
                                       vrcInFanCfgMinSpeed 1.3.6.1.4.1.21239.5.2.30.1.7.1.5 integer32 read-write
Min in-fan speed (percent)
                                       vrcInFanCfgStandardSpeed 1.3.6.1.4.1.21239.5.2.30.1.7.1.6 integer32 read-write
Standard in-fan speed (percent)
                                       vrcInFanCfgMinCfc 1.3.6.1.4.1.21239.5.2.30.1.7.1.7 integer32 read-write
Min in-fan cfc (percent)
                                       vrcInFanCfgStandardCfc 1.3.6.1.4.1.21239.5.2.30.1.7.1.8 integer32 read-write
Standard in-fan cfc (percent)
                                       vrcInFanCfgStartDelay 1.3.6.1.4.1.21239.5.2.30.1.7.1.9 integer32 read-write
In-fan start delay in seconds
                                       vrcInFanCfgStopDelay 1.3.6.1.4.1.21239.5.2.30.1.7.1.10 integer32 read-write
In-fan stop delay in seconds
                                       vrcInFanCfgReduceSpeedDelay 1.3.6.1.4.1.21239.5.2.30.1.7.1.11 integer32 read-write
In-fan reduce speed delay in seconds
                                       vrcInFanCfgJumpBand1 1.3.6.1.4.1.21239.5.2.30.1.7.1.12 integer32 read-write
In-fan jump band 1 in tenths of a percent
                                       vrcInFanCfgJumpBand2 1.3.6.1.4.1.21239.5.2.30.1.7.1.13 integer32 read-write
In-fan jump band 2 in tenths of a percent
                                       vrcInFanCfgJumpBand3 1.3.6.1.4.1.21239.5.2.30.1.7.1.14 integer32 read-write
In-fan jump band 3 in tenths of a percent
                                       vrcInFanCfgJumpBand4 1.3.6.1.4.1.21239.5.2.30.1.7.1.15 integer32 read-write
In-fan jump band 4 in tenths of a percent
                                       vrcInFanCfgJumpBand5 1.3.6.1.4.1.21239.5.2.30.1.7.1.16 integer32 read-write
In-fan jump band 5 in tenths of a percent
                                       vrcInFanCfgJumpFreq1 1.3.6.1.4.1.21239.5.2.30.1.7.1.17 integer32 read-write
In-fan jump frequency 1 in tenths of a percent
                                       vrcInFanCfgJumpFreq2 1.3.6.1.4.1.21239.5.2.30.1.7.1.18 integer32 read-write
In-fan jump frequency 2 in tenths of a percent
                                       vrcInFanCfgJumpFreq3 1.3.6.1.4.1.21239.5.2.30.1.7.1.19 integer32 read-write
In-fan jump frequency 3 in tenths of a percent
                                       vrcInFanCfgJumpFreq4 1.3.6.1.4.1.21239.5.2.30.1.7.1.20 integer32 read-write
In-fan jump frequency 4 in tenths of a percent
                                       vrcInFanCfgJumpFreq5 1.3.6.1.4.1.21239.5.2.30.1.7.1.21 integer32 read-write
In-fan jump frequency 5 in tenths of a percent
                                       vrcInFanCfgTempP 1.3.6.1.4.1.21239.5.2.30.1.7.1.22 integer32 read-write
In-fan temperature P in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
                                       vrcInFanCfgTempI 1.3.6.1.4.1.21239.5.2.30.1.7.1.23 integer32 read-write
In-fan temperature I in seconds
                                       vrcInFanCfgTempD 1.3.6.1.4.1.21239.5.2.30.1.7.1.24 integer32 read-write
In-fan temperature D in seconds
                               vrcCompPtTable 1.3.6.1.4.1.21239.5.2.30.1.8 no-access
Table that contains VRC compressor status
                                   vrcCompPtEntry 1.3.6.1.4.1.21239.5.2.30.1.8.1 no-access
Entry in the vrcCompPtTable: each entry represents data for a VRC compressor
                                       vrcCompPtIndex 1.3.6.1.4.1.21239.5.2.30.1.8.1.1 integer32 no-access
Unique id for each entry in the table
                                       vrcCompPtName 1.3.6.1.4.1.21239.5.2.30.1.8.1.2 snmpadminstring read-only
Compressor name (factory-assigned)
                                       vrcCompPtCapacity 1.3.6.1.4.1.21239.5.2.30.1.8.1.3 integer32 read-only
Compressor capacity value (percent)
                                       vrcCompPtRunTimeHours 1.3.6.1.4.1.21239.5.2.30.1.8.1.4 integer32 read-only
Compressor run time in hours
                                       vrcCompPtStartStopCount 1.3.6.1.4.1.21239.5.2.30.1.8.1.5 integer32 read-only
Compressor start/stop count
                                       vrcCompPtDriverFaultU00 1.3.6.1.4.1.21239.5.2.30.1.8.1.6 truthvalue read-only
Compressor driver fault alarm U00 state
                                       vrcCompPtDriverFaultU01 1.3.6.1.4.1.21239.5.2.30.1.8.1.7 truthvalue read-only
Compressor driver fault alarm U01 state
                                       vrcCompPtDriverFaultU02 1.3.6.1.4.1.21239.5.2.30.1.8.1.8 truthvalue read-only
Compressor driver fault alarm U02 state
                                       vrcCompPtDriverFaultU03 1.3.6.1.4.1.21239.5.2.30.1.8.1.9 truthvalue read-only
Compressor driver fault alarm U03 state
                                       vrcCompPtDriverFaultU04 1.3.6.1.4.1.21239.5.2.30.1.8.1.10 truthvalue read-only
Compressor driver fault alarm U04 state
                                       vrcCompPtDriverFaultU05 1.3.6.1.4.1.21239.5.2.30.1.8.1.11 truthvalue read-only
Compressor driver fault alarm U05 state
                                       vrcCompPtDriverFaultU06 1.3.6.1.4.1.21239.5.2.30.1.8.1.12 truthvalue read-only
Compressor driver fault alarm U06 state
                                       vrcCompPtDriverFaultU07 1.3.6.1.4.1.21239.5.2.30.1.8.1.13 truthvalue read-only
Compressor driver fault alarm U07 state
                                       vrcCompPtDriverFaultU08 1.3.6.1.4.1.21239.5.2.30.1.8.1.14 truthvalue read-only
Compressor driver fault alarm U08 state
                                       vrcCompPtDriverFaultU09 1.3.6.1.4.1.21239.5.2.30.1.8.1.15 truthvalue read-only
Compressor driver fault alarm U09 state
                                       vrcCompPtDriverFaultU10 1.3.6.1.4.1.21239.5.2.30.1.8.1.16 truthvalue read-only
Compressor driver fault alarm U10 state
                                       vrcCompPtDriverFaultU11 1.3.6.1.4.1.21239.5.2.30.1.8.1.17 truthvalue read-only
Compressor driver fault alarm U11 state
                                       vrcCompPtDriverFaultU12 1.3.6.1.4.1.21239.5.2.30.1.8.1.18 truthvalue read-only
Compressor driver fault alarm U12 state
                                       vrcCompPtDriverFaultU13 1.3.6.1.4.1.21239.5.2.30.1.8.1.19 truthvalue read-only
Compressor driver fault alarm U13 state
                                       vrcCompPtDriverFaultU14 1.3.6.1.4.1.21239.5.2.30.1.8.1.20 truthvalue read-only
Compressor driver fault alarm U14 state
                                       vrcCompPtDriverFaultU15 1.3.6.1.4.1.21239.5.2.30.1.8.1.21 truthvalue read-only
Compressor driver fault alarm U15 state
                                       vrcCompPtDriverCommFailAlarm 1.3.6.1.4.1.21239.5.2.30.1.8.1.22 truthvalue read-only
Compressor driver communication failure alarm state
                                       vrcCompPtFaultLockAlarm 1.3.6.1.4.1.21239.5.2.30.1.8.1.23 truthvalue read-only
Compressor fault lock alarm state
                               vrcCompCfgTable 1.3.6.1.4.1.21239.5.2.30.1.9 no-access
Table used for VRC compressor configuration
                                   vrcCompCfgEntry 1.3.6.1.4.1.21239.5.2.30.1.9.1 no-access
Entry in the vrcCompCfgTable: each entry contains config fields for a VRC compressor
                                       vrcCompCfgIndex 1.3.6.1.4.1.21239.5.2.30.1.9.1.1 integer32 no-access
Unique id for each entry in the table
                                       vrcCompCfgOutputStatus 1.3.6.1.4.1.21239.5.2.30.1.9.1.2 truthvalue read-write
Compressor output status
                                       vrcCompCfgOutputDeadBand 1.3.6.1.4.1.21239.5.2.30.1.9.1.3 integer32 read-write
Compressor output dead band in tenths of a percent
                                       vrcCompCfgCapacityOutputValue 1.3.6.1.4.1.21239.5.2.30.1.9.1.4 integer32 read-write
Compressor capacity output (percent)
                                       vrcCompCfgMinCapacity 1.3.6.1.4.1.21239.5.2.30.1.9.1.5 integer32 read-write
Compressor min capacity (percent)
                                       vrcCompCfgStartCapacity 1.3.6.1.4.1.21239.5.2.30.1.9.1.6 integer32 read-write
Compressor start capacity (percent)
                                       vrcCompCfgStandardCapacity 1.3.6.1.4.1.21239.5.2.30.1.9.1.7 integer32 read-write
Compressor standard capacity (percent)
                                       vrcCompCfgStartCfc 1.3.6.1.4.1.21239.5.2.30.1.9.1.8 integer32 read-write
Compressor start cfc (percent)
                                       vrcCompCfgStopCfc 1.3.6.1.4.1.21239.5.2.30.1.9.1.9 integer32 read-write
Compressor stop cfc (percent)
                                       vrcCompCfgMinRunTime 1.3.6.1.4.1.21239.5.2.30.1.9.1.10 integer32 read-write
Compressor min run time in minutes
                                       vrcCompCfgMinStopTime 1.3.6.1.4.1.21239.5.2.30.1.9.1.11 integer32 read-write
Compressor min stop time in minutes
                                       vrcCompCfgJumpBand1 1.3.6.1.4.1.21239.5.2.30.1.9.1.12 integer32 read-write
Compressor jump band 1 in tenths of a percent
                                       vrcCompCfgJumpBand2 1.3.6.1.4.1.21239.5.2.30.1.9.1.13 integer32 read-write
Compressor jump band 2 in tenths of a percent
                                       vrcCompCfgJumpBand3 1.3.6.1.4.1.21239.5.2.30.1.9.1.14 integer32 read-write
Compressor jump band 3 in tenths of a percent
                                       vrcCompCfgJumpBand4 1.3.6.1.4.1.21239.5.2.30.1.9.1.15 integer32 read-write
Compressor jump band 4 in tenths of a percent
                                       vrcCompCfgJumpBand5 1.3.6.1.4.1.21239.5.2.30.1.9.1.16 integer32 read-write
Compressor jump band 5 in tenths of a percent
                                       vrcCompCfgJumpFreq1 1.3.6.1.4.1.21239.5.2.30.1.9.1.17 integer32 read-write
Compressor jump frequency 1 in tenths of a percent
                                       vrcCompCfgJumpFreq2 1.3.6.1.4.1.21239.5.2.30.1.9.1.18 integer32 read-write
Compressor jump frequency 2 in tenths of a percent
                                       vrcCompCfgJumpFreq3 1.3.6.1.4.1.21239.5.2.30.1.9.1.19 integer32 read-write
Compressor jump frequency 3 in tenths of a percent
                                       vrcCompCfgJumpFreq4 1.3.6.1.4.1.21239.5.2.30.1.9.1.20 integer32 read-write
Compressor jump frequency 4 in tenths of a percent
                                       vrcCompCfgJumpFreq5 1.3.6.1.4.1.21239.5.2.30.1.9.1.21 integer32 read-write
Compressor jump frequency 5 in tenths of a percent
                                       vrcCompCfgTempP 1.3.6.1.4.1.21239.5.2.30.1.9.1.22 integer32 read-write
Compressor temperature P in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 10 to 150 Fahrenheit: 18 to 269
                                       vrcCompCfgTempI 1.3.6.1.4.1.21239.5.2.30.1.9.1.23 integer32 read-write
Compressor temperature I in seconds
                                       vrcCompCfgTempD 1.3.6.1.4.1.21239.5.2.30.1.9.1.24 integer32 read-write
Compressor temperature D in seconds
                                       vrcCompCfgDriverFaultAlmCtrl 1.3.6.1.4.1.21239.5.2.30.1.9.1.25 integer read-write
Compressor driver fault alarm control: 2 = suspend 3 = open Enumeration: 'suspend': 2, 'open': 3.
                                       vrcCompCfgDriverCommFailAlmCtrl 1.3.6.1.4.1.21239.5.2.30.1.9.1.26 integer read-write
Compressor driver communication failure alarm control: 2 = suspend 3 = open Enumeration: 'suspend': 2, 'open': 3.
                                       vrcCompCfgFaultLockAlmCtrl 1.3.6.1.4.1.21239.5.2.30.1.9.1.27 integer read-write
Compressor fault lock alarm control: 2 = suspend 3 = open Enumeration: 'suspend': 2, 'open': 3.
                               vrcReturnPtTable 1.3.6.1.4.1.21239.5.2.30.1.10 no-access
Table that contains VRC return status
                                     vrcReturnPtEntry 1.3.6.1.4.1.21239.5.2.30.1.10.1 no-access
Entry in the vrcReturnPtTable: each entry represents return data for a VRC
                                         vrcReturnPtIndex 1.3.6.1.4.1.21239.5.2.30.1.10.1.1 integer32 no-access
Unique id for each entry in the table
                                         vrcReturnPtName 1.3.6.1.4.1.21239.5.2.30.1.10.1.2 snmpadminstring read-only
Return name (factory-assigned)
                                         vrcReturnPtTemp 1.3.6.1.4.1.21239.5.2.30.1.10.1.3 integer32 read-only
Return temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1000 Fahrenheit: -400 to 2120
                                         vrcReturnPtHighTempAlarm 1.3.6.1.4.1.21239.5.2.30.1.10.1.4 truthvalue read-only
Return high temperature alarm state
                                         vrcReturnPtTempSensorFailAlarm 1.3.6.1.4.1.21239.5.2.30.1.10.1.5 truthvalue read-only
Return temperature sensor failure alarm state
                               vrcReturnCfgTable 1.3.6.1.4.1.21239.5.2.30.1.11 no-access
Table used for VRC return configuration
                                     vrcReturnCfgEntry 1.3.6.1.4.1.21239.5.2.30.1.11.1 no-access
Entry in the vrcReturnCfgTable: each entry contains config fields for VRC return
                                         vrcReturnCfgIndex 1.3.6.1.4.1.21239.5.2.30.1.11.1.1 integer32 no-access
Unique id for each entry in the table
                                         vrcReturnCfgOilCycle 1.3.6.1.4.1.21239.5.2.30.1.11.1.2 integer32 read-write
Return oil cycle in tenths of an hour
                                         vrcReturnCfgOilRunCapacity 1.3.6.1.4.1.21239.5.2.30.1.11.1.3 integer32 read-write
Return Oil run capacity (percent)
                                         vrcReturnCfgOilRunTime 1.3.6.1.4.1.21239.5.2.30.1.11.1.4 integer32 read-write
Return oil run time in minutes
                                         vrcReturnCfgTempCalValue 1.3.6.1.4.1.21239.5.2.30.1.11.1.5 integer32 read-write
Return temperature calibration value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: -100 to 100 Fahrenheit: -179 to 179
                                         vrcReturnCfgTempSetting 1.3.6.1.4.1.21239.5.2.30.1.11.1.6 integer32 read-write
Return temperature setting in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 250 to 350 Fahrenheit: 770 to 949
                                         vrcReturnCfgHighTempAlarmValue 1.3.6.1.4.1.21239.5.2.30.1.11.1.7 integer32 read-write
Return high temperature alarm value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 300 to 450 Fahrenheit: 860 to 1129
                                         vrcReturnCfgHighTempAlarmCtrl 1.3.6.1.4.1.21239.5.2.30.1.11.1.8 integer read-write
Return high temperature alarm control: 1 = close 2 = suspend 3 = open Enumeration: 'close': 1, 'suspend': 2, 'open': 3.
                                         vrcReturnCfgTempSensFailAlmCtrl 1.3.6.1.4.1.21239.5.2.30.1.11.1.9 integer read-write
Return temperature sensor failure alarm control: 1 = close 2 = suspend 3 = open Enumeration: 'close': 1, 'suspend': 2, 'open': 3.
                               vrcSupplyPtTable 1.3.6.1.4.1.21239.5.2.30.1.12 no-access
Table that contains VRC supply status
                                     vrcSupplyPtEntry 1.3.6.1.4.1.21239.5.2.30.1.12.1 no-access
Entry in the vrcSupplyPtTable: each entry represents supply data for a VRC
                                         vrcSupplyPtIndex 1.3.6.1.4.1.21239.5.2.30.1.12.1.1 integer32 no-access
Unique id for each entry in the table
                                         vrcSupplyPtName 1.3.6.1.4.1.21239.5.2.30.1.12.1.2 snmpadminstring read-only
Supply name (factory-assigned)
                                         vrcSupplyPtTemp 1.3.6.1.4.1.21239.5.2.30.1.12.1.3 integer32 read-only
Supply temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1000 Fahrenheit: -400 to 2120
                                         vrcSupplyPtLowTempAlarm 1.3.6.1.4.1.21239.5.2.30.1.12.1.4 truthvalue read-only
Supply low temperature alarm state
                                         vrcSupplyPtHighTempAlarm 1.3.6.1.4.1.21239.5.2.30.1.12.1.5 truthvalue read-only
Supply high temperature alarm state
                                         vrcSupplyPtTempSensorFailAlarm 1.3.6.1.4.1.21239.5.2.30.1.12.1.6 truthvalue read-only
Supply temperature sensor failure alarm state
                               vrcSupplyCfgTable 1.3.6.1.4.1.21239.5.2.30.1.13 no-access
Table used for VRC supply configuration
                                     vrcSupplyCfgEntry 1.3.6.1.4.1.21239.5.2.30.1.13.1 no-access
Entry in the vrcSupplyCfgTable: each entry contains config fields for a VRC supply
                                         vrcSupplyCfgIndex 1.3.6.1.4.1.21239.5.2.30.1.13.1.1 integer32 no-access
Unique id for each entry in the table
                                         vrcSupplyCfgTempCalValue 1.3.6.1.4.1.21239.5.2.30.1.13.1.2 integer32 read-write
Supply temperature calibration value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: -100 to 100 Fahrenheit: -179 to 179
                                         vrcSupplyCfgTempSetting 1.3.6.1.4.1.21239.5.2.30.1.13.1.3 integer32 read-write
Supply temperature setting in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 130 to 280 Fahrenheit: 554 to 823
                                         vrcSupplyCfgLowTempAlarmValue 1.3.6.1.4.1.21239.5.2.30.1.13.1.4 integer32 read-write
Supply low temperature alarm value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 50 to 200 Fahrenheit: 410 to 679
                                         vrcSupplyCfgHighTempAlarmValue 1.3.6.1.4.1.21239.5.2.30.1.13.1.5 integer32 read-write
Supply high temperature alarm value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 200 to 350 Fahrenheit: 680 to 949
                                         vrcSupplyCfgLowTempAlmCtrl 1.3.6.1.4.1.21239.5.2.30.1.13.1.6 integer read-write
Supply low temperature alarm control: 1 = close 2 = suspend 3 = open Enumeration: 'close': 1, 'suspend': 2, 'open': 3.
                                         vrcSupplyCfgHighTempAlmCtrl 1.3.6.1.4.1.21239.5.2.30.1.13.1.7 integer read-write
Supply high temperature alarm control: 1 = close 2 = suspend 3 = open Enumeration: 'close': 1, 'suspend': 2, 'open': 3.
                                         vrcSupplyCfgTempSensFailAlmCtrl 1.3.6.1.4.1.21239.5.2.30.1.13.1.8 integer read-write
Supply temperature sensor failure alarm control: 1 = close 2 = suspend 3 = open Enumeration: 'close': 1, 'suspend': 2, 'open': 3.
                               vrcPowerPtTable 1.3.6.1.4.1.21239.5.2.30.1.14 no-access
Table that contains VRC power status
                                     vrcPowerPtEntry 1.3.6.1.4.1.21239.5.2.30.1.14.1 no-access
Entry in the vrcPowerPtTable: each entry represents power data for a VRC
                                         vrcPowerPtIndex 1.3.6.1.4.1.21239.5.2.30.1.14.1.1 integer32 no-access
Unique id for each entry in the table
                                         vrcPowerPtName 1.3.6.1.4.1.21239.5.2.30.1.14.1.2 snmpadminstring read-only
Power name (factory-assigned)
                                         vrcPowerPtVoltage 1.3.6.1.4.1.21239.5.2.30.1.14.1.3 integer32 read-only
Power voltage measurement in tenths of a volt
                                         vrcPowerPtFrequency 1.3.6.1.4.1.21239.5.2.30.1.14.1.4 integer32 read-only
Power frequency measurement in tenths of hertz
                                         vrcPowerPtLowVoltageAlarm 1.3.6.1.4.1.21239.5.2.30.1.14.1.5 truthvalue read-only
Power low voltage alarm state
                                         vrcPowerPtHighVoltageAlarm 1.3.6.1.4.1.21239.5.2.30.1.14.1.6 truthvalue read-only
Power high voltage alarm state
                                         vrcPowerPtLossOfPhasePowerAlarm 1.3.6.1.4.1.21239.5.2.30.1.14.1.7 truthvalue read-only
Phase power loss alarm state
                                         vrcPowerPtLossOfPowerAlarm 1.3.6.1.4.1.21239.5.2.30.1.14.1.8 truthvalue read-only
Power loss alarm state
                                         vrcPowerPtFrequencyErrorAlarm 1.3.6.1.4.1.21239.5.2.30.1.14.1.9 truthvalue read-only
Power frequency error alarm state
                               vrcPowerCfgTable 1.3.6.1.4.1.21239.5.2.30.1.15 no-access
Table used for VRC power configuration
                                     vrcPowerCfgEntry 1.3.6.1.4.1.21239.5.2.30.1.15.1 no-access
Entry in the vrcPowerCfgTable: each entry contains config fields for VRC power
                                         vrcPowerCfgIndex 1.3.6.1.4.1.21239.5.2.30.1.15.1.1 integer32 no-access
Unique id for each entry in the table
                                         vrcPowerCfgLowVoltageSetting 1.3.6.1.4.1.21239.5.2.30.1.15.1.2 integer32 read-write
Power low voltage setting in volts
                                         vrcPowerCfgHighVoltageSetting 1.3.6.1.4.1.21239.5.2.30.1.15.1.3 integer32 read-write
Power high voltage setting in volts
                                         vrcPowerCfgLowVoltageAlarmCtrl 1.3.6.1.4.1.21239.5.2.30.1.15.1.4 integer read-write
Power low voltage alarm control: 1 = close 2 = suspend 3 = open Enumeration: 'close': 1, 'suspend': 2, 'open': 3.
                                         vrcPowerCfgHighVoltageAlarmCtrl 1.3.6.1.4.1.21239.5.2.30.1.15.1.5 integer read-write
Power high voltage alarm control: 1 = close 2 = suspend 3 = open Enumeration: 'close': 1, 'suspend': 2, 'open': 3.
                                         vrcPowerCfgLossOfPowerAlarmCtrl 1.3.6.1.4.1.21239.5.2.30.1.15.1.6 integer read-write
Power loss alarm control: 1 = close 2 = suspend 3 = open Enumeration: 'close': 1, 'suspend': 2, 'open': 3.
                                         vrcPowerCfgFreqErrorAlarmCtrl 1.3.6.1.4.1.21239.5.2.30.1.15.1.7 integer read-write
Power frequency error alarm control: 1 = close 2 = suspend 3 = open Enumeration: 'close': 1, 'suspend': 2, 'open': 3.
                               vrcOutdoorPtTable 1.3.6.1.4.1.21239.5.2.30.1.16 no-access
Table that contains VRC outdoor status
                                     vrcOutdoorPtEntry 1.3.6.1.4.1.21239.5.2.30.1.16.1 no-access
Entry in the vrcOutdoorPtTable: each entry represents data for a VRC outdoor
                                         vrcOutdoorPtIndex 1.3.6.1.4.1.21239.5.2.30.1.16.1.1 integer32 no-access
Unique id for each entry in the table
                                         vrcOutdoorPtName 1.3.6.1.4.1.21239.5.2.30.1.16.1.2 snmpadminstring read-only
Outdoor name (factory-assigned)
                                         vrcOutdoorPtTemp 1.3.6.1.4.1.21239.5.2.30.1.16.1.3 integer32 read-only
Outdoor temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1000 Fahrenheit: -400 to 2120
                               vrcDischPtTable 1.3.6.1.4.1.21239.5.2.30.1.18 no-access
Table that contains VRC discharge status
                                     vrcDischPtEntry 1.3.6.1.4.1.21239.5.2.30.1.18.1 no-access
Entry in the vrcDischPtTable: each entry represents discharge data for a VRC
                                         vrcDischPtIndex 1.3.6.1.4.1.21239.5.2.30.1.18.1.1 integer32 no-access
Unique id for each entry in the table
                                         vrcDischPtName 1.3.6.1.4.1.21239.5.2.30.1.18.1.2 snmpadminstring read-only
Discharge name (factory-assigned)
                                         vrcDischPtTemp 1.3.6.1.4.1.21239.5.2.30.1.18.1.3 integer32 read-write
Discharge temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1560 Fahrenheit: -400 to 3128
                                         vrcDischPtPressure 1.3.6.1.4.1.21239.5.2.30.1.18.1.4 integer32 read-write
Discharge air pressure value in tenths of a bar
                                         vrcDischPtHighTempAlarm 1.3.6.1.4.1.21239.5.2.30.1.18.1.5 truthvalue read-only
Discharge high temperature alarm state
                                         vrcDischPtHighTempFreqAlarm 1.3.6.1.4.1.21239.5.2.30.1.18.1.6 truthvalue read-only
Discharge high temperature frequently alarm state
                                         vrcDischPtTempSensorFailAlarm 1.3.6.1.4.1.21239.5.2.30.1.18.1.7 truthvalue read-only
Discharge temperature sensor failure alarm state
                               vrcDischCfgTable 1.3.6.1.4.1.21239.5.2.30.1.19 no-access
Table used for VRC discharge configuration
                                     vrcDischCfgEntry 1.3.6.1.4.1.21239.5.2.30.1.19.1 no-access
Entry in the vrcDischCfgTable: each entry contains config fields for VRC discharge
                                         vrcDischCfgIndex 1.3.6.1.4.1.21239.5.2.30.1.19.1.1 integer32 no-access
Unique id for each entry in the table
                                         vrcDischCfgTempCalValue 1.3.6.1.4.1.21239.5.2.30.1.19.1.2 integer32 read-write
Discharge temperature calibration value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: -100 to 100 Fahrenheit: -179 to 179
                                         vrcDischCfgPressCalValue 1.3.6.1.4.1.21239.5.2.30.1.19.1.3 integer32 read-write
Discharge pressure calibration value in tenths of a bar
                                         vrcDischCfgHighTempAlmCtrl 1.3.6.1.4.1.21239.5.2.30.1.19.1.4 integer read-write
Discharge high temperature alarm control: 2 = suspend 3 = open Enumeration: 'suspend': 2, 'open': 3.
                                         vrcDischCfgHighTempFreqAlmCtrl 1.3.6.1.4.1.21239.5.2.30.1.19.1.5 integer read-write
Discharge high temperature frequenctly alarm control: 2 = suspend 3 = open Enumeration: 'suspend': 2, 'open': 3.
                                         vrcDischCfgTempSensFailAlmCtrl 1.3.6.1.4.1.21239.5.2.30.1.19.1.6 integer read-write
Discharge temperature sensor failure alarm control: 2 = suspend 3 = open Enumeration: 'suspend': 2, 'open': 3.
                               vrcSuctPtTable 1.3.6.1.4.1.21239.5.2.30.1.20 no-access
Table that contains VRC suction status
                                     vrcSuctPtEntry 1.3.6.1.4.1.21239.5.2.30.1.20.1 no-access
Entry in the vrcSuctPtTable: each entry represents suction data for a VRC
                                         vrcSuctPtIndex 1.3.6.1.4.1.21239.5.2.30.1.20.1.1 integer32 no-access
Unique id for each entry in the table
                                         vrcSuctPtName 1.3.6.1.4.1.21239.5.2.30.1.20.1.2 snmpadminstring read-only
Suction name (factory-assigned)
                                         vrcSuctPtTemp 1.3.6.1.4.1.21239.5.2.30.1.20.1.3 integer32 read-only
Suction temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1000 Fahrenheit: -400 to 2120
                                         vrcSuctPtPressure 1.3.6.1.4.1.21239.5.2.30.1.20.1.4 integer32 read-only
Suction air pressure in tenths of a bar
                                         vrcSuctPtSuperHeatTemp 1.3.6.1.4.1.21239.5.2.30.1.20.1.5 integer32 read-only
Suction super heat temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1000 Fahrenheit: -400 to 2120
                                         vrcSuctPtTempSensorFailAlarm 1.3.6.1.4.1.21239.5.2.30.1.20.1.6 truthvalue read-only
Suction temperature sensor failure alarm state
                               vrcSuctCfgTable 1.3.6.1.4.1.21239.5.2.30.1.21 no-access
Table used for VRC suction configuration
                                     vrcSuctCfgEntry 1.3.6.1.4.1.21239.5.2.30.1.21.1 no-access
Entry in the vrcSuctCfgTable: each entry contains config fields for VRC suction
                                         vrcSuctCfgIndex 1.3.6.1.4.1.21239.5.2.30.1.21.1.1 integer32 no-access
Unique id for each entry in the table
                                         vrcSuctCfgPressCalValue 1.3.6.1.4.1.21239.5.2.30.1.21.1.2 integer32 read-write
Suction pressure calibration value in tenths of a bar
                                         vrcSuctCfgTempSensFailAlmCtrl 1.3.6.1.4.1.21239.5.2.30.1.21.1.3 integer read-write
Suction temperature sensor failure alarm control: 2 = suspend 3 = open Enumeration: 'suspend': 2, 'open': 3.
                     trap 1.3.6.1.4.1.21239.5.2.32767
                                 trapPrefix 1.3.6.1.4.1.21239.5.2.32767.0
                                     internalTestNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10101
Test SNMP Trap
                                     pduMainAvailNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10305
PDU availability trap
                                     pduTotalRealPowerNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10309
PDU total real power trap
                                     pduTotalApparentPowerNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10310
PDU total apparent power trap
                                     pduTotalPowerFactorNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10311
PDU total power factor trap
                                     pduTotalEnergyNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10312
PDU total energy trap
                                     pduPhaseVoltageNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10324
PDU phase voltage trap
                                     pduPhaseCurrentNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10328
PDU phase current trap
                                     pduPhaseRealPowerNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10332
PDU phase real power trap
                                     pduPhaseApparentPowerNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10333
PDU phase apparent power trap
                                     pduPhasePowerFactorNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10334
PDU phase power factor trap
                                     pduPhaseEnergyNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10335
PDU phase energy trap
                                     pduPhaseBalanceNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10337
PDU phase balance trap
                                     pduPhaseCurrentCrestFactorNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10339
PDU phase current crest factor trap
                                     pduBreakerCurrentNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10354
PDU breaker current trap
                                     pduBreakerVoltageNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10358
PDU breaker voltage trap
                                     pduBreakerRealPowerNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10362
PDU breaker real power trap
                                     pduBreakerApparentPowerNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10363
PDU breaker apparent power trap
                                     pduBreakerPowerFactorNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10364
PDU breaker power factor trap
                                     pduBreakerEnergyNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10365
PDU breaker energy trap
                                     pduLineCurrentNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10374
PDU line current trap
                                     pduOutletMeterVoltageNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10385
PDU outlet voltage trap
                                     pduOutletMeterCurrentNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10389
PDU outlet current trap
                                     pduOutletMeterRealPowerNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10393
PDU outlet real power trap
                                     pduOutletMeterApparentPowerNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10394
PDU outlet apparent power trap
                                     pduOutletMeterPowerFactorNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10395
PDU outlet power factor trap
                                     pduOutletMeterEnergyNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10396
PDU outlet energy trap
                                     pduOutletCurrentCrestFactorNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10400
PDU outlet current crest factor trap
                                     tempSensorAvailNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10404
RT availability trap
                                     tempSensorTempNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10405
RT temperature trap
                                     airFlowSensorAvailNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10504
AFHT3 availability trap
                                     airFlowSensorTempNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10505
AFHT3 temperature trap
                                     airFlowSensorFlowNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10506
AFHT3 airflow trap
                                     airFlowSensorHumidityNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10507
AFHT3 humidity trap
                                     airFlowSensorDewPointNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10508
AFHT3 dewpoint trap
                                     t3hdSensorAvailNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10804
T3HD availability trap
                                     t3hdSensorIntTempNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10806
T3HD Internal temperature trap
                                     t3hdSensorIntHumidityNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10807
T3HD Internal humidity trap
                                     t3hdSensorIntDewPointNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10808
T3HD Internal dewpoint trap
                                     t3hdSensorExtATempNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10811
T3HD External A temperature trap
                                     t3hdSensorExtBTempNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10814
T3HD External B temperature trap
                                     thdSensorAvailNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10904
THD availability trap
                                     thdSensorTempNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10905
THD temperature trap
                                     thdSensorHumidityNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10906
THD humidity trap
                                     thdSensorDewPointNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10907
THD dewpoint trap
                                     a2dSensorAvailNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.11104
A2D availability trap
                                     a2dSensorValueNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.11105
A2D measurement trap
                                     humiditySensorAvailNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.11204
Remote humidity availability trap
                                     humiditySensorValueNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.11205
Remote humidity value trap
                                     sn2dSensorAvailNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.11304
SN-2D availability trap
                                     sn2dSensorDoor1StateNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.11306
SN-2D Door switch 1 state trap
                                     sn2dSensorDoor2StateNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.11309
SN-2D Door switch 2 state trap
                                     vrcMainAvailNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.13001
VRC availability trap
                                     vrcOutFanPtSpeedNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.13002
VRC out-fan speed trap
                                     vrcCompPtCapacityNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.13003
VRC compressor capacity trap
                                     vrcReturnPtTempNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.13004
VRC return temperature trap
                                     vrcSupplyPtTempNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.13005
VRC supply temperature trap
                                     vrcPowerPtVoltageNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.13006
VRC power voltage trap
                                     vrcPowerPtFrequencyNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.13007
VRC power frequency trap
                                     vrcOutdoorPtTempNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.13008
VRC outdoor temperature trap
                                     vrcDischPtTempNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.13009
VRC discharge temperature trap
                                     vrcDischPtPressureNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.13010
VRC discharge pressure trap
                                     vrcSuctPtTempNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.13011
VRC suction temperature trap
                                     vrcSuctPtPressureNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.13012
VRC suction pressure trap
                                     pduMainAvailCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20305
PDU availability clear trap
                                     pduTotalRealPowerCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20309
PDU total real power clear trap
                                     pduTotalApparentPowerCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20310
PDU total apparent power clear trap
                                     pduTotalPowerFactorCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20311
PDU total power factor clear trap
                                     pduTotalEnergyCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20312
PDU total energy clear trap
                                     pduPhaseVoltageCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20324
PDU phase voltage clear trap
                                     pduPhaseCurrentCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20328
PDU phase current clear trap
                                     pduPhaseRealPowerCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20332
PDU phase real power clear trap
                                     pduPhaseApparentPowerCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20333
PDU phase apparent power clear trap
                                     pduPhasePowerFactorCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20334
PDU phase power factor clear trap
                                     pduPhaseEnergyCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20335
PDU phase energy clear trap
                                     pduPhaseBalanceCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20337
PDU phase balance clear trap
                                     pduPhaseCurrentCrestFactorCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20339
PDU phase current crest factor clear trap
                                     pduBreakerCurrentCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20354
PDU breaker current clear trap
                                     pduBreakerVoltageCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20358
PDU breaker voltage clear trap
                                     pduBreakerRealPowerCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20362
PDU breaker real power clear trap
                                     pduBreakerApparentPowerCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20363
PDU breaker apparent power clear trap
                                     pduBreakerPowerFactorCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20364
PDU breaker power factor clear trap
                                     pduBreakerEnergyCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20365
PDU breaker energy clear trap
                                     pduLineCurrentCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20374
PDU line current clear trap
                                     pduOutletMeterVoltageCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20385
PDU outlet voltage clear trap
                                     pduOutletMeterCurrentCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20389
PDU outlet current clear trap
                                     pduOutletMeterRealPowerCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20393
PDU outlet real power clear trap
                                     pduOutletMeterApparentPowerCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20394
PDU outlet apparent power clear trap
                                     pduOutletMeterPowerFactorCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20395
PDU outlet power factor clear trap
                                     pduOutletMeterEnergyCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20396
PDU outlet energy clear trap
                                     pduOutletCurrentCrestFactorCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20400
PDU outlet current crest factor clear trap
                                     tempSensorAvailCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20404
RT availability clear trap
                                     tempSensorTempCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20405
RT temperature clear trap
                                     airFlowSensorAvailCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20504
AFHT3 availability clear trap
                                     airFlowSensorTempCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20505
AFHT3 temperature clear trap
                                     airFlowSensorFlowCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20506
AFHT3 airflow clear trap
                                     airFlowSensorHumidityCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20507
AFHT3 humidity clear trap
                                     airFlowSensorDewPointCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20508
AFHT3 dewpoint clear trap
                                     t3hdSensorAvailCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20804
T3HD availability clear trap
                                     t3hdSensorIntTempCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20806
T3HD Internal temperature clear trap
                                     t3hdSensorIntHumidityCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20807
T3HD Internal humidity clear trap
                                     t3hdSensorIntDewPointCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20808
T3HD Internal dewpoint clear trap
                                     t3hdSensorExtATempCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20811
T3HD External A temperature clear trap
                                     t3hdSensorExtBTempCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20814
T3HD External B temperature clear trap
                                     thdSensorAvailCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20904
THD availability clear trap
                                     thdSensorTempCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20905
THD temperature clear trap
                                     thdSensorHumidityCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20906
THD humidity clear trap
                                     thdSensorDewPointCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20907
THD dewpoint clear trap
                                     a2dSensorAvailCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.21104
A2D availability clear trap
                                     a2dSensorValueCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.21105
A2D measurement clear trap
                                     humiditySensorAvailCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.21204
Remote humidity availability clear trap
                                     humiditySensorValueCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.21205
Remote humidity value clear trap
                                     sn2dSensorAvailCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.21304
SN-2D availability clear trap
                                     sn2dSensorDoor1StateCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.21306
SN-2D Door switch 1 state clear trap
                                     sn2dSensorDoor2StateCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.21309
SN-2D Door switch 2 state clear trap
                                     vrcMainAvailCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.23001
VRC availability clear trap
                                     vrcOutFanPtSpeedCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.23002
VRC out-fan speed clear trap
                                     vrcCompPtCapacityCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.23003
VRC compressor capacity clear trap
                                     vrcReturnPtTempCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.23004
VRC return temperature clear trap
                                     vrcSupplyPtTempCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.23005
VRC supply temperature clear trap
                                     vrcPowerPtVoltageCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.23006
VRC power voltage clear trap
                                     vrcPowerPtFrequencyCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.23007
VRC power frequency clear trap
                                     vrcOutdoorPtTempCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.23008
VRC outdoor temperature clear trap
                                     vrcDischPtTempCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.23009
VRC discharge temperature clear trap
                                     vrcDischPtPressureCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.23010
VRC discharge pressure clear trap
                                     vrcSuctPtTempCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.23011
VRC suction temperature clear trap
                                     vrcSuctPtPressureCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.23012
VRC suction pressure clear trap
                                 trapObj 1.3.6.1.4.1.21239.5.2.32767.1
                                     trapSeverity 1.3.6.1.4.1.21239.5.2.32767.1.1 integer no-access
Indicates the severity of the trap: 0 = None 1 = Warning 2 = Alarm Enumeration: 'none': 0, 'warning': 1, 'alarm': 2.
                                     trapThreshType 1.3.6.1.4.1.21239.5.2.32767.1.2 integer no-access
Only sent for threshold alarms. Identifies the threshold type: 1 = Low 2 = High Enumeration: 'high': 2, 'low': 1.
             common 1.3.6.1.4.1.21239.42
                   identity 1.3.6.1.4.1.21239.42.1
                       r05 1.3.6.1.4.1.21239.42.1.15
Value given for sysObjectID on R-Series units
                       i03 1.3.6.1.4.1.21239.42.1.53
Value given for sysObjectID on IMD3 units