Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
       netBotz_prd_bot_temp 1.3.6.1.4.1.5528.30.10.1 integer read-only
The reading of the temperature probe, in degrees F or degrees C (depends on netBotz-ismetric).
       netBotz_prd_bot_humidity 1.3.6.1.4.1.5528.30.10.2 integer read-only
The reading of the humidity probe, in percent.
       netBotz_prd_bot_airflow 1.3.6.1.4.1.5528.30.10.3 integer read-only
The reading of the airflow probe. Each unit represents approximately 40 feet/minute or 13 meters/minute of airflow velocity.
       netBotz_prd_bot_audio 1.3.6.1.4.1.5528.30.10.4 integer read-only
The reading of the audio alarm probe on/off.
       netBotz_prd_bot_doorajar 1.3.6.1.4.1.5528.30.10.5 integer read-only
The reading of the door switch probe open(0) or closed(1).
       netBotz_prd_bot_temp_min 1.3.6.1.4.1.5528.30.10.6 integer read-write
The temperature probe minimum, from 35 to 120 degrees F, or 1 to 50 degrees C (depends on netBotz-ismetric).
       netBotz_prd_bot_temp_max 1.3.6.1.4.1.5528.30.10.7 integer read-write
The temperature probe maximum, from 35 to 120 degrees F, or 1 to 50 degrees C (depends on netBotz-ismetric).
       netBotz_prd_bot_humidity_min 1.3.6.1.4.1.5528.30.10.8 integer read-write
The humidity probe minimum, from 10 to 90 percent.
       netBotz_prd_bot_humidity_max 1.3.6.1.4.1.5528.30.10.9 integer read-write
The humidity probe maximum, from 10 to 90 percent.
       netBotz_prd_bot_airflow_mins 1.3.6.1.4.1.5528.30.10.10 integer read-write
Minutes without airflow before alarm set.
       netBotz_prd_bot_audio_secs 1.3.6.1.4.1.5528.30.10.11 integer read-write
Seconds of alarm audio before alarm set.
       netBotz_prd_bot_temp_enabled 1.3.6.1.4.1.5528.30.10.12 integer read-write
Temperature probe alarm enabled(1) or disabled(0).
       netBotz_prd_bot_hum_enabled 1.3.6.1.4.1.5528.30.10.13 integer read-write
Humidity probe alarm enabled(1) or disabled(0).
       netBotz_prd_bot_air_enabled 1.3.6.1.4.1.5528.30.10.14 integer read-write
Airflow probe alarm enabled(1) or disabled(0).
       netBotz_prd_bot_audio_enabled 1.3.6.1.4.1.5528.30.10.15 integer read-write
Audio probe alarm enabled(1) or disabled(0).
       netBotz_prd_bot_switch_state 1.3.6.1.4.1.5528.30.10.16 integer read-write
Switch state setting. The state controls which condition of the door switch indicates an alarm. If set to 0, alarm is set when the switch is closed. If set to 1, alarm is set when the switch is open.
       netBotz_prd_bot_switch_enabled 1.3.6.1.4.1.5528.30.10.17 integer read-write
Door switch enabled(1) or disabled(0).
       netBotz_prd_bot_audio_level 1.3.6.1.4.1.5528.30.10.18 integer read-write
Audio level setting. This is the relative audio level, from 0-11, above which an alarm will be sent.
       netBotz_prd_bot_doorpic_delay 1.3.6.1.4.1.5528.30.10.19 integer read-write
Number of seconds between door alert and first picture.
       netBotz_prd_bot_trap_index 1.3.6.1.4.1.5528.30.10.20 integer read-only
The crawler ID of the last trap.
       netBotz_prd_bot_trap_address 1.3.6.1.4.1.5528.30.10.21 ipaddress read-only
The IP address of the last trap.
       netBotz_prd_bot_trap_oid 1.3.6.1.4.1.5528.30.10.22 object identifier read-only
The object id of the last trap.
       netBotz_prd_bot_trap_value 1.3.6.1.4.1.5528.30.10.23 integer read-only
The value of the last object trap.
       netBotz_prd_bot_trap_date 1.3.6.1.4.1.5528.30.10.24 integer read-only
The date and time of a specific trap. This field contains the number of seconds elapsed since midnight (00:00:00), January 1, 1970
       netBotz_prd_bot_refresh 1.3.6.1.4.1.5528.30.10.26 integer read-write
Rate of web page refresh, in seconds. This must be greater than 5 seconds.
       netBotz_prd_bot_airflow_level 1.3.6.1.4.1.5528.30.10.27 integer read-write
Airflow alert level. This is the relative level of airflow below which an alarm will be sent. The range is 1-11. Each unit is approximately 40 feet/second or 13 meters/second of airflow velocity.
       netBotz_prd_bot_doorpic_count 1.3.6.1.4.1.5528.30.10.28 integer read-write
Number of pictures to take when door activated. These pictures will be sent as attachments to the door alert e-mail. The range is from 0 to 5 pictures.
       netBotz_prd_bot_amps1 1.3.6.1.4.1.5528.30.10.29 integer read-only
The reading of the first amperage probe, in milliamps.
       netBotz_prd_bot_amps1_enabled 1.3.6.1.4.1.5528.30.10.30 integer read-write
Amperage[1] probe alarm enabled(1) or disabled(0).
       netBotz_prd_bot_amps1_min 1.3.6.1.4.1.5528.30.10.31 integer read-write
The amperage[1] probe minimum, from 0 to 30000 milliamps.
       netBotz_prd_bot_amps1_max 1.3.6.1.4.1.5528.30.10.32 integer read-write
The amperage[1] probe maximum, from 0 to 30000 milliamps.
       netBotz_prd_bot_amps2 1.3.6.1.4.1.5528.30.10.34 integer read-only
The reading of the second amperage probe, in milliamps.
       netBotz_prd_bot_amps2_enabled 1.3.6.1.4.1.5528.30.10.35 integer read-write
Amperage[2] probe alarm enabled(1) or disabled(0).
       netBotz_prd_bot_amps2_min 1.3.6.1.4.1.5528.30.10.36 integer read-write
The amperage[2] probe minimum, from 0 to 30000 milliamps.
       netBotz_prd_bot_amps2_max 1.3.6.1.4.1.5528.30.10.37 integer read-write
The amperage[2] probe maximum, from 0 to 30000 milliamps.
       netBotz_prd_bot_amps3 1.3.6.1.4.1.5528.30.10.39 integer read-only
The reading of the third amperage probe, in milliamps.
       netBotz_prd_bot_amps3_enabled 1.3.6.1.4.1.5528.30.10.40 integer read-write
Amperage[3] probe alarm enabled(1) or disabled(0).
       netBotz_prd_bot_amps3_min 1.3.6.1.4.1.5528.30.10.41 integer read-write
The amperage[3] probe minimum, from 0 to 30000 milliamps.
       netBotz_prd_bot_amps3_max 1.3.6.1.4.1.5528.30.10.42 integer read-write
The amperage[3] probe maximum, from 0 to 30000 milliamps.
       netBotz_prd_bot_amps_total 1.3.6.1.4.1.5528.30.10.44 integer read-only
The total of the readings of all amperage probes, in milliamps.
       netBotz_prd_bot_amps_total_enabled 1.3.6.1.4.1.5528.30.10.45 integer read-write
Total amperage alarm enabled(1) or disabled(0).
       netBotz_prd_bot_amps_total_min 1.3.6.1.4.1.5528.30.10.46 integer read-write
The total amperage minimum, from 0 to 90000 milliamps.
       netBotz_prd_bot_amps_total_max 1.3.6.1.4.1.5528.30.10.47 integer read-write
The total amperage maximum, from 0 to 90000 milliamps.
       netBotz_prd_bot_amps_total_support_enabled 1.3.6.1.4.1.5528.30.10.48 displaystring read-write
Total Amperage Support enabled(Y) or disabled(N).
       netBotz_prd_bot_amps1_uV_per_10mA 1.3.6.1.4.1.5528.30.10.49 integer read-write
The scaling factor used for the first amperage probe to convert microvolts measured from the Amp Detect into 10s of milliamps of current. Needs to be set based on the type of Amp Detect module installed.
       netBotz_prd_bot_amps2_uV_per_10mA 1.3.6.1.4.1.5528.30.10.50 integer read-write
The scaling factor used for the second amperage probe to convert microvolts measured from the Amp Detect into 10s of milliamps of current. Needs to be set based on the type of Amp Detect module installed.
       netBotz_prd_bot_amps3_uV_per_mA 1.3.6.1.4.1.5528.30.10.51 integer read-write
The scaling factor used for the third amperage probe to convert microvolts measured from the Amp Detect into 10s of milliamps of current. Needs to be set based on the type of Amp Detect module installed.
       netBotz_prd_bot_amps1_max_range 1.3.6.1.4.1.5528.30.10.52 integer read-write
The maximum RMS milliamps measureable by the first Amp Detect.
       netBotz_prd_bot_amps2_max_range 1.3.6.1.4.1.5528.30.10.53 integer read-write
The maximum RMS milliamps measureable by the second Amp Detect.
       netBotz_prd_bot_amps3_max_range 1.3.6.1.4.1.5528.30.10.54 integer read-write
The maximum RMS milliamps measureable by the third Amp Detect.
       netBotz_prd_bot_amps4 1.3.6.1.4.1.5528.30.10.55 integer read-only
The reading of the fourth amperage probe, in milliamps.
       netBotz_prd_bot_amps4_enabled 1.3.6.1.4.1.5528.30.10.56 integer read-write
Amperage[4] probe alarm enabled(1) or disabled(0).
       netBotz_prd_bot_amps4_min 1.3.6.1.4.1.5528.30.10.57 integer read-write
The amperage[4] probe minimum, in milliamps.
       netBotz_prd_bot_amps4_max 1.3.6.1.4.1.5528.30.10.58 integer read-write
The amperage[4] probe maximum, in milliamps.
       netBotz_prd_bot_amps4_uV_per_10mA 1.3.6.1.4.1.5528.30.10.60 integer read-write
The scaling factor used for the fourth amperage probe to convert microvolts measured from the Amp Detect into 10s of milliamps of current. Needs to be set based on the type of Amp Detect module installed.
       netBotz_prd_bot_amps4_max_range 1.3.6.1.4.1.5528.30.10.61 integer read-write
The maximum RMS milliamps measureable by the fourth Amp Detect.
       netBotz_prd_bot_ext_temp1 1.3.6.1.4.1.5528.30.10.62 integer read-only
The reading of the external temperature probe on port 1, in degrees F or degrees C (depends on netBotz-ismetric).
       netBotz_prd_bot_ext_temp2 1.3.6.1.4.1.5528.30.10.63 integer read-only
The reading of the external temperature probe on port 2, in degrees F or degrees C (depends on netBotz-ismetric).
       netBotz_prd_bot_ext_temp3 1.3.6.1.4.1.5528.30.10.64 integer read-only
The reading of the external temperature probe on port 3, in degrees F or degrees C (depends on netBotz-ismetric).
       netBotz_prd_bot_ext_temp4 1.3.6.1.4.1.5528.30.10.65 integer read-only
The reading of the external temperature probe on port 4, in degrees F or degrees C (depends on netBotz-ismetric).
       netBotz_prd_bot_ext_temp1_enabled 1.3.6.1.4.1.5528.30.10.66 integer read-write
External temperature probe on port 1 alarm enabled(1) or disabled(0).
       netBotz_prd_bot_ext_temp1_min 1.3.6.1.4.1.5528.30.10.67 integer read-write
The external temperature probe on port 1 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).
       netBotz_prd_bot_ext_temp1_max 1.3.6.1.4.1.5528.30.10.68 integer read-write
The external temperature probe on port 1 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).
       netBotz_prd_bot_ext_temp2_enabled 1.3.6.1.4.1.5528.30.10.69 integer read-write
External temperature probe on port 2 alarm enabled(1) or disabled(0).
       netBotz_prd_bot_ext_temp2_min 1.3.6.1.4.1.5528.30.10.70 integer read-write
The external temperature probe on port 2 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).
       netBotz_prd_bot_ext_temp2_max 1.3.6.1.4.1.5528.30.10.71 integer read-write
The external temperature probe on port 2 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).
       netBotz_prd_bot_ext_temp3_enabled 1.3.6.1.4.1.5528.30.10.72 integer read-write
External temperature probe on port 3 alarm enabled(1) or disabled(0).
       netBotz_prd_bot_ext_temp3_min 1.3.6.1.4.1.5528.30.10.73 integer read-write
The external temperature probe on port 3 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).
       netBotz_prd_bot_ext_temp3_max 1.3.6.1.4.1.5528.30.10.74 integer read-write
The external temperature probe on port 3 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).
       netBotz_prd_bot_ext_temp4_enabled 1.3.6.1.4.1.5528.30.10.75 integer read-write
External temperature probe on port 4 alarm enabled(1) or disabled(0).
       netBotz_prd_bot_ext_temp4_min 1.3.6.1.4.1.5528.30.10.76 integer read-write
The external temperature probe on port 4 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).
       netBotz_prd_bot_ext_temp4_max 1.3.6.1.4.1.5528.30.10.77 integer read-write
The external temperature probe on port 4 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).
       netBotz_prd_bot_ext_temp1_uV_per_degreeC 1.3.6.1.4.1.5528.30.10.78 integer read-write
The scaling factor used for the external temperature probe on port 1 to convert microvolts measured from the temperature sensor into degrees C. Needs to be set based on the type of temperature sensor module installed.
       netBotz_prd_bot_ext_temp1_uV_at_0_degreeC 1.3.6.1.4.1.5528.30.10.79 integer read-write
The offset used for the external temperature probe on port 1 of microvolts measured from the temperature sensor at zero degrees C. Needs to be set based on the type of temperature sensor module installed.
       netBotz_prd_bot_ext_temp1_min_range 1.3.6.1.4.1.5528.30.10.80 integer read-write
The minimum temperature measureable by the temperature sensor installed on port 1, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installed.
       netBotz_prd_bot_ext_temp1_max_range 1.3.6.1.4.1.5528.30.10.81 integer read-write
The maximum temperature measureable by the temperature sensor installed on port 1, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installed.
       netBotz_prd_bot_ext_temp2_uV_per_degreeC 1.3.6.1.4.1.5528.30.10.82 integer read-write
The scaling factor used for the external temperature probe on port 2 to convert microvolts measured from the temperature sensor into degrees C. Needs to be set based on the type of temperature sensor module installed.
       netBotz_prd_bot_ext_temp2_uV_at_0_degreeC 1.3.6.1.4.1.5528.30.10.83 integer read-write
The offset used for the external temperature probe on port 2 of microvolts measured from the temperature sensor at zero degrees C. Needs to be set based on the type of temperature sensor module installed.
       netBotz_prd_bot_ext_temp2_min_range 1.3.6.1.4.1.5528.30.10.84 integer read-write
The minimum temperature measureable by the temperature sensor installed on port 2, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installed.
       netBotz_prd_bot_ext_temp2_max_range 1.3.6.1.4.1.5528.30.10.85 integer read-write
The maximum temperature measureable by the temperature sensor installed on port 2, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installed.
       netBotz_prd_bot_ext_temp3_uV_per_degreeC 1.3.6.1.4.1.5528.30.10.86 integer read-write
The scaling factor used for the external temperature probe on port 3 to convert microvolts measured from the temperature sensor into degrees C. Needs to be set based on the type of temperature sensor module installed.
       netBotz_prd_bot_ext_temp3_uV_at_0_degreeC 1.3.6.1.4.1.5528.30.10.87 integer read-write
The offset used for the external temperature probe on port 3 of microvolts measured from the temperature sensor at zero degrees C. Needs to be set based on the type of temperature sensor module installed.
       netBotz_prd_bot_ext_temp3_min_range 1.3.6.1.4.1.5528.30.10.88 integer read-write
The minimum temperature measureable by the temperature sensor installed on port 3, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installed.
       netBotz_prd_bot_ext_temp3_max_range 1.3.6.1.4.1.5528.30.10.89 integer read-write
The maximum temperature measureable by the temperature sensor installed on port 3, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installed.
       netBotz_prd_bot_ext_temp4_uV_per_degreeC 1.3.6.1.4.1.5528.30.10.90 integer read-write
The scaling factor used for the external temperature probe on port 4 to convert microvolts measured from the temperature sensor into degrees C. Needs to be set based on the type of temperature sensor module installed.
       netBotz_prd_bot_ext_temp4_uV_at_0_degreeC 1.3.6.1.4.1.5528.30.10.91 integer read-write
The offset used for the external temperature probe on port 4 of microvolts measured from the temperature sensor at zero degrees C. Needs to be set based on the type of temperature sensor module installed.
       netBotz_prd_bot_ext_temp4_min_range 1.3.6.1.4.1.5528.30.10.92 integer read-write
The minimum temperature measureable by the temperature sensor installed on port 4, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installed.
       netBotz_prd_bot_ext_temp4_max_range 1.3.6.1.4.1.5528.30.10.93 integer read-write
The maximum temperature measureable by the temperature sensor installed on port 4, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installed.
       netBotz_prd_bot_ext_port1_module_id 1.3.6.1.4.1.5528.30.10.94 displaystring read-write
The module ID of the sensor module installed on port 1. Blank string indicates that no module is installed.
       netBotz_prd_bot_ext_port1_module_type 1.3.6.1.4.1.5528.30.10.95 displaystring read-write
The type of sensor module installed on port 1. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor.
       netBotz_prd_bot_ext_port2_module_id 1.3.6.1.4.1.5528.30.10.96 displaystring read-write
The module ID of the sensor module installed on port 2. Blank string indicates that no module is installed.
       netBotz_prd_bot_ext_port2_module_type 1.3.6.1.4.1.5528.30.10.97 displaystring read-write
The type of sensor module installed on port 2. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor.
       netBotz_prd_bot_ext_port3_module_id 1.3.6.1.4.1.5528.30.10.98 displaystring read-write
The module ID of the sensor module installed on port 3. Blank string indicates that no module is installed.
       netBotz_prd_bot_ext_port3_module_type 1.3.6.1.4.1.5528.30.10.99 displaystring read-write
The type of sensor module installed on port 3. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor.
       netBotz_prd_bot_ext_port4_module_id 1.3.6.1.4.1.5528.30.10.100 displaystring read-write
The module ID of the sensor module installed on port 4. Blank string indicates that no module is installed.
       netBotz_prd_bot_ext_port4_module_type 1.3.6.1.4.1.5528.30.10.101 displaystring read-write
The type of sensor module installed on port 4. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor.
       netBotz_prd_bot_amp1_total_amp_seconds 1.3.6.1.4.1.5528.30.10.102 integer read-only
The accumulated total of amp-seconds on the AmpDetect on port 1.
       netBotz_prd_bot_amp1_total_amp_seconds_since_time 1.3.6.1.4.1.5528.30.10.103 integer read-write
The UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 1. Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time.
       netBotz_prd_bot_amp2_total_amp_seconds 1.3.6.1.4.1.5528.30.10.104 integer read-only
The accumulated total of amp-seconds on the AmpDetect on port 2.
       netBotz_prd_bot_amp2_total_amp_seconds_since_time 1.3.6.1.4.1.5528.30.10.105 integer read-write
The UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 2. Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time.
       netBotz_prd_bot_amp3_total_amp_seconds 1.3.6.1.4.1.5528.30.10.106 integer read-only
The accumulated total of amp-seconds on the AmpDetect on port 3.
       netBotz_prd_bot_amp3_total_amp_seconds_since_time 1.3.6.1.4.1.5528.30.10.107 integer read-write
The UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 3. Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time.
       netBotz_prd_bot_amp4_total_amp_seconds 1.3.6.1.4.1.5528.30.10.108 integer read-only
The accumulated total of amp-seconds on the AmpDetect on port 4.
       netBotz_prd_bot_amp4_total_amp_seconds_since_time 1.3.6.1.4.1.5528.30.10.109 integer read-write
The UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 4. Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time.
       netBotz_prd_bot_amptotal_total_amp_seconds 1.3.6.1.4.1.5528.30.10.110 integer read-only
The accumulated total of amp-seconds on the total of all AmpDetects.
       netBotz_prd_bot_amptotal_total_amp_seconds_since_time 1.3.6.1.4.1.5528.30.10.111 integer read-write
The UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds for all AmpDetects. Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time.
       netBotz_prd_bot_ext_dry1 1.3.6.1.4.1.5528.30.10.112 integer read-only
The current value of the external dry contact sensor on Ext1: 0=Open, 1=Closed, -1=N/A
       netBotz_prd_bot_ext_dry2 1.3.6.1.4.1.5528.30.10.113 integer read-only
The current value of the external dry contact sensor on Ext2: 0=Open, 1=Closed, -1=N/A
       netBotz_prd_bot_ext_dry3 1.3.6.1.4.1.5528.30.10.114 integer read-only
The current value of the external dry contact sensor on Ext3: 0=Open, 1=Closed, -1=N/A
       netBotz_prd_bot_ext_dry4 1.3.6.1.4.1.5528.30.10.115 integer read-only
The current value of the external dry contact sensor on Ext4: 0=Open, 1=Closed, -1=N/A
       netBotz_prd_bot_ext_dry1_alarm_value 1.3.6.1.4.1.5528.30.10.116 integer read-write
The value to generate alarms on for the external dry contact sensor on Ext1: 0=Open, 1=Closed
       netBotz_prd_bot_ext_dry1_enabled 1.3.6.1.4.1.5528.30.10.117 integer read-write
External dry contact sensor on Ext1 alarm enabled(1) or disabled(0).
       netBotz_prd_bot_ext_dry2_alarm_value 1.3.6.1.4.1.5528.30.10.118 integer read-write
The value to generate alarms on for the external dry contact sensor on Ext2: 0=Open, 1=Closed
       netBotz_prd_bot_ext_dry2_enabled 1.3.6.1.4.1.5528.30.10.119 integer read-write
External dry contact sensor on Ext2 alarm enabled(1) or disabled(0).
       netBotz_prd_bot_ext_dry3_alarm_value 1.3.6.1.4.1.5528.30.10.120 integer read-write
The value to generate alarms on for the external dry contact sensor on Ext3: 0=Open, 1=Closed
       netBotz_prd_bot_ext_dry3_enabled 1.3.6.1.4.1.5528.30.10.121 integer read-write
External dry contact sensor on Ext3 alarm enabled(1) or disabled(0).
       netBotz_prd_bot_ext_dry4_alarm_value 1.3.6.1.4.1.5528.30.10.122 integer read-write
The value to generate alarms on for the external dry contact sensor on Ext4: 0=Open, 1=Closed
       netBotz_prd_bot_ext_dry4_enabled 1.3.6.1.4.1.5528.30.10.123 integer read-write
External dry contact sensor on Ext4 alarm enabled(1) or disabled(0).
       netBotz_prd_bot_ext_dry1_label 1.3.6.1.4.1.5528.30.10.124 displaystring read-write
The sensor name/label for the dry contact sensor on Ext1
       netBotz_prd_bot_ext_dry1_open_label 1.3.6.1.4.1.5528.30.10.125 displaystring read-write
The sensor name/label for the open(0) state for the dry contact sensor on Ext1
       netBotz_prd_bot_ext_dry1_closed_label 1.3.6.1.4.1.5528.30.10.126 displaystring read-write
The sensor name/label for the closed(0) state for the dry contact sensor on Ext1
       netBotz_prd_bot_ext_dry1_open_to_close_millis 1.3.6.1.4.1.5528.30.10.127 integer read-write
The minimum number of milliseconds that the dry contact sensor on Ext1 must read closed before the state is changed from open to closed.
       netBotz_prd_bot_ext_dry1_close_to_open_millis 1.3.6.1.4.1.5528.30.10.128 integer read-write
The minimum number of milliseconds that the dry contact sensor on Ext1 must read openbefore the state is changed from closed to open.
       netBotz_prd_bot_ext_dry1_response 1.3.6.1.4.1.5528.30.10.129 displaystring read-write
The type of alert response for the dry contact sensor on Ext1: ALERT=e-mail with no pictures, CAMERA=e-mail with pictures from camera.
       netBotz_prd_bot_ext_dry2_label 1.3.6.1.4.1.5528.30.10.130 displaystring read-write
The sensor name/label for the dry contact sensor on Ext2
       netBotz_prd_bot_ext_dry2_open_label 1.3.6.1.4.1.5528.30.10.131 displaystring read-write
The sensor name/label for the open(0) state for the dry contact sensor on Ext2
       netBotz_prd_bot_ext_dry2_closed_label 1.3.6.1.4.1.5528.30.10.132 displaystring read-write
The sensor name/label for the closed(0) state for the dry contact sensor on Ext2
       netBotz_prd_bot_ext_dry2_open_to_close_millis 1.3.6.1.4.1.5528.30.10.133 integer read-write
The minimum number of milliseconds that the dry contact sensor on Ext2 must read closed before the state is changed from open to closed.
       netBotz_prd_bot_ext_dry2_close_to_open_millis 1.3.6.1.4.1.5528.30.10.134 integer read-write
The minimum number of milliseconds that the dry contact sensor on Ext2 must read openbefore the state is changed from closed to open.
       netBotz_prd_bot_ext_dry2_response 1.3.6.1.4.1.5528.30.10.135 displaystring read-write
The type of alert response for the dry contact sensor on Ext2: ALERT=e-mail with no pictures, CAMERA=e-mail with pictures from camera.
       netBotz_prd_bot_ext_dry3_label 1.3.6.1.4.1.5528.30.10.136 displaystring read-write
The sensor name/label for the dry contact sensor on Ext3
       netBotz_prd_bot_ext_dry3_open_label 1.3.6.1.4.1.5528.30.10.137 displaystring read-write
The sensor name/label for the open(0) state for the dry contact sensor on Ext3
       netBotz_prd_bot_ext_dry3_closed_label 1.3.6.1.4.1.5528.30.10.138 displaystring read-write
The sensor name/label for the closed(0) state for the dry contact sensor on Ext3
       netBotz_prd_bot_ext_dry3_open_to_close_millis 1.3.6.1.4.1.5528.30.10.139 integer read-write
The minimum number of milliseconds that the dry contact sensor on Ext3 must read closed before the state is changed from open to closed.
       netBotz_prd_bot_ext_dry3_close_to_open_millis 1.3.6.1.4.1.5528.30.10.140 integer read-write
The minimum number of milliseconds that the dry contact sensor on Ext3 must read openbefore the state is changed from closed to open.
       netBotz_prd_bot_ext_dry3_response 1.3.6.1.4.1.5528.30.10.141 displaystring read-write
The type of alert response for the dry contact sensor on Ext3: ALERT=e-mail with no pictures, CAMERA=e-mail with pictures from camera.
       netBotz_prd_bot_ext_dry4_label 1.3.6.1.4.1.5528.30.10.142 displaystring read-write
The sensor name/label for the dry contact sensor on Ext4
       netBotz_prd_bot_ext_dry4_open_label 1.3.6.1.4.1.5528.30.10.143 displaystring read-write
The sensor name/label for the open(0) state for the dry contact sensor on Ext4
       netBotz_prd_bot_ext_dry4_closed_label 1.3.6.1.4.1.5528.30.10.144 displaystring read-write
The sensor name/label for the closed(0) state for the dry contact sensor on Ext4
       netBotz_prd_bot_ext_dry4_open_to_close_millis 1.3.6.1.4.1.5528.30.10.145 integer read-write
The minimum number of milliseconds that the dry contact sensor on Ext4 must read closed before the state is changed from open to closed.
       netBotz_prd_bot_ext_dry4_close_to_open_millis 1.3.6.1.4.1.5528.30.10.146 integer read-write
The minimum number of milliseconds that the dry contact sensor on Ext4 must read openbefore the state is changed from closed to open.
       netBotz_prd_bot_ext_dry4_response 1.3.6.1.4.1.5528.30.10.147 displaystring read-write
The type of alert response for the dry contact sensor on Ext4: ALERT=e-mail with no pictures, CAMERA=e-mail with pictures from camera.
 netBotz_prd_bot_traps 1.3.6.1.4.1.5528.30.100
         netBotz_prd_bot_temperature_traps 1.3.6.1.4.1.5528.30.100.1
         netBotz_prd_bot_low_trap 1.3.6.1.4.1.5528.30.100.1
Netbotz Low Trap. This trap indicates that a lower limit has been exceeded.
         netBotz_prd_bot_humidity_traps 1.3.6.1.4.1.5528.30.100.2
         netBotz_prd_bot_high_trap 1.3.6.1.4.1.5528.30.100.2
Netbotz High Trap. This trap indicates that an upper limit has been exceeded.
         netBotz_prd_bot_trap_clear 1.3.6.1.4.1.5528.30.100.3
Netbotz Cleared Trap. The trap has been cleared because the value has returned to acceptable limits.
         netBotz_prd_bot_airflow_traps 1.3.6.1.4.1.5528.30.100.3
         netBotz_prd_bot_audio_traps 1.3.6.1.4.1.5528.30.100.4
         netBotz_prd_bot_offline_trap 1.3.6.1.4.1.5528.30.100.4
Netbotz Device Offline Trap. This trap indicates that a device or function has been determined to be offline.
         netBotz_prd_bot_online_trap 1.3.6.1.4.1.5528.30.100.5
Netbotz Device Online Trap. This trap indicates that a device or function has been determined to be online.
         netBotz_prd_bot_door_traps 1.3.6.1.4.1.5528.30.100.5
         netBotz_prd_bot_amp1_traps 1.3.6.1.4.1.5528.30.100.6
         netBotz_prd_bot_amp2_traps 1.3.6.1.4.1.5528.30.100.7
         netBotz_prd_bot_amp3_traps 1.3.6.1.4.1.5528.30.100.8
         netBotz_prd_bot_amp4_traps 1.3.6.1.4.1.5528.30.100.9
         netBotz_prd_bot_amp_total_traps 1.3.6.1.4.1.5528.30.100.10
               netBotz_prd_bot_temperature_low_trap 1.3.6.1.4.1.5528.30.100.10.1
Netbotz Temperature Low Trap. This trap indicates that the lower limit for temperature has been exceeded.
               netBotz_prd_bot_temperature_high_trap 1.3.6.1.4.1.5528.30.100.10.2
Netbotz Temperature High Trap. This trap indicates that the upper limit for temperature has been exceeded.
               netBotz_prd_bot_temperature_trap_clear 1.3.6.1.4.1.5528.30.100.10.3
Netbotz Temperature Cleared Trap. The trap has been cleared because the temperature value has returned to acceptable limits.
         netBotz_prd_bot_ext_temp1_traps 1.3.6.1.4.1.5528.30.100.11
         netBotz_prd_bot_ext_temp2_traps 1.3.6.1.4.1.5528.30.100.12
         netBotz_prd_bot_ext_temp3_traps 1.3.6.1.4.1.5528.30.100.13
         netBotz_prd_bot_ext_temp4_traps 1.3.6.1.4.1.5528.30.100.14
         netBotz_prd_bot_ext_dry1_traps 1.3.6.1.4.1.5528.30.100.15
         netBotz_prd_bot_ext_dry2_traps 1.3.6.1.4.1.5528.30.100.16
         netBotz_prd_bot_ext_dry3_traps 1.3.6.1.4.1.5528.30.100.17
         netBotz_prd_bot_ext_dry4_traps 1.3.6.1.4.1.5528.30.100.18
               netBotz_prd_bot_humidity_low_trap 1.3.6.1.4.1.5528.30.100.20.1
Netbotz Humidity Low Trap. This trap indicates that the lower limit for humidity has been exceeded.
               netBotz_prd_bot_humidity_high_trap 1.3.6.1.4.1.5528.30.100.20.2
Netbotz Humidity High Trap. This trap indicates that the upper limit for humidity has been exceeded.
               netBotz_prd_bot_humidity_trap_clear 1.3.6.1.4.1.5528.30.100.20.3
Netbotz Humidity Cleared Trap. The trap has been cleared because the humidity value has returned to acceptable limits.
               netBotz_prd_bot_airflow_low_trap 1.3.6.1.4.1.5528.30.100.30.1
Netbotz Airflow Low Trap. This trap indicates that the lower limit for airflow has been exceeded.
               netBotz_prd_bot_airflow_trap_clear 1.3.6.1.4.1.5528.30.100.30.3
Netbotz Airflow Cleared Trap. The trap has been cleared because the airflow value has returned to acceptable limits.
               netBotz_prd_bot_audio_high_trap 1.3.6.1.4.1.5528.30.100.40.2
Netbotz Audio High Trap. This trap indicates that the upper limit for audio has been exceeded.
               netBotz_prd_bot_audio_trap_clear 1.3.6.1.4.1.5528.30.100.40.3
Netbotz Audio Cleared Trap. The trap has been cleared because the audio value has returned to acceptable limits.
               netBotz_prd_bot_door_trap_tripped 1.3.6.1.4.1.5528.30.100.50.2
Netbotz Door Sensor Tripped Trap. This trap indicates that the door sensor has been triggered (i.e. opened, if the thresdhold has been set to trip on open, closed if otherwise).
               netBotz_prd_bot_door_trap_clear 1.3.6.1.4.1.5528.30.100.50.3
Netbotz Door Cleared Trap. The trap has been cleared because the door sensor has returned to normal (i.e. been closed, if the threshold has been set to trip on open).
               netBotz_prd_bot_amp1_low_trap 1.3.6.1.4.1.5528.30.100.60.1
Netbotz Amp1 Low Trap. This trap indicates that the lower limit for the first amp detect has been exceeded.
               netBotz_prd_bot_amp1_high_trap 1.3.6.1.4.1.5528.30.100.60.2
Netbotz Amp1 High Trap. This trap indicates that the upper limit for the first amp detect has been exceeded.
               netBotz_prd_bot_amp1_trap_clear 1.3.6.1.4.1.5528.30.100.60.3
Netbotz Amp1 Cleared Trap. The trap has been cleared because the first amp detect value has returned to acceptable limits.
               netBotz_prd_bot_amp1_sensor_unplugged 1.3.6.1.4.1.5528.30.100.60.6
Netbotz Amp 1 Sensor Unplugged Trap. The sensor for the first AmpDetect is unplugged or malfunctioning.
               netBotz_prd_bot_amp1_sensor_replugged 1.3.6.1.4.1.5528.30.100.60.7
Netbotz Amp 1 Sensor Replugged Trap. The sensor for the first AmpDetect was unplugged, but has been reconnected.
               netBotz_prd_bot_amp2_low_trap 1.3.6.1.4.1.5528.30.100.70.1
Netbotz Amp2 Low Trap. This trap indicates that the lower limit for the second amp detect has been exceeded.
               netBotz_prd_bot_amp2_high_trap 1.3.6.1.4.1.5528.30.100.70.2
Netbotz Amp2 High Trap. This trap indicates that the upper limit for the second amp detect has been exceeded.
               netBotz_prd_bot_amp2_trap_clear 1.3.6.1.4.1.5528.30.100.70.3
Netbotz Amp2 Cleared Trap. The trap has been cleared because the second amp detect value has returned to acceptable limits.
               netBotz_prd_bot_amp2_sensor_unplugged 1.3.6.1.4.1.5528.30.100.70.6
Netbotz Amp 2 Sensor Unplugged Trap. The sensor for the second AmpDetect is unplugged or malfunctioning.
               netBotz_prd_bot_amp2_sensor_replugged 1.3.6.1.4.1.5528.30.100.70.7
Netbotz Amp 2 Sensor Replugged Trap. The sensor for the second AmpDetect was unplugged, but has been reconnected.
               netBotz_prd_bot_amp3_low_trap 1.3.6.1.4.1.5528.30.100.80.1
Netbotz Amp3 Low Trap. This trap indicates that the lower limit for the third amp detect has been exceeded.
               netBotz_prd_bot_amp3_high_trap 1.3.6.1.4.1.5528.30.100.80.2
Netbotz Amp3 High Trap. This trap indicates that the upper limit for the third amp detect has been exceeded.
               netBotz_prd_bot_amp3_trap_clear 1.3.6.1.4.1.5528.30.100.80.3
Netbotz Amp3 Cleared Trap. The trap has been cleared because the third amp detect value has returned to acceptable limits.
               netBotz_prd_bot_amp3_sensor_unplugged 1.3.6.1.4.1.5528.30.100.80.6
Netbotz Amp 3 Sensor Unplugged Trap. The sensor for the third AmpDetect is unplugged or malfunctioning.
               netBotz_prd_bot_amp3_sensor_replugged 1.3.6.1.4.1.5528.30.100.80.7
Netbotz Amp 3 Sensor Replugged Trap. The sensor for the third AmpDetect was unplugged, but has been reconnected.
               netBotz_prd_bot_amp4_low_trap 1.3.6.1.4.1.5528.30.100.90.1
Netbotz Amp4 Low Trap. This trap indicates that the lower limit for the fourth amp detect has been exceeded.
               netBotz_prd_bot_amp4_high_trap 1.3.6.1.4.1.5528.30.100.90.2
Netbotz Amp4 High Trap. This trap indicates that the upper limit for the fourth amp detect has been exceeded.
               netBotz_prd_bot_amp4_trap_clear 1.3.6.1.4.1.5528.30.100.90.3
Netbotz Amp4 Cleared Trap. The trap has been cleared because the fourth amp detect value has returned to acceptable limits.
               netBotz_prd_bot_amp4_sensor_unplugged 1.3.6.1.4.1.5528.30.100.90.6
Netbotz Amp 4 Sensor Unplugged Trap. The sensor for the fourth AmpDetect is unplugged or malfunctioning.
               netBotz_prd_bot_amp4_sensor_replugged 1.3.6.1.4.1.5528.30.100.90.7
Netbotz Amp 4 Sensor Replugged Trap. The sensor for the fourth AmpDetect was unplugged, but has been reconnected.
                 netBotz_prd_bot_amp_total_low_trap 1.3.6.1.4.1.5528.30.100.100.1
Netbotz Total Amps Low Trap. This trap indicates that the lower limit for the total amperage has been exceeded.
                 netBotz_prd_bot_amp_total_high_trap 1.3.6.1.4.1.5528.30.100.100.2
Netbotz Total Amps High Trap. This trap indicates that the upper limit for the total amperage has been exceeded.
                 netBotz_prd_bot_amp_total_trap_clear 1.3.6.1.4.1.5528.30.100.100.3
Netbotz Total Amps Cleared Trap. The trap has been cleared because the total amperage value has returned to acceptable limits.
                 netBotz_prd_bot_ext_temp1_low_trap 1.3.6.1.4.1.5528.30.100.110.1
Netbotz External Temperature 1 Low Trap. This trap indicates that the lower limit for external temperature probe on port 1 has been exceeded.
                 netBotz_prd_bot_ext_temp1_high_trap 1.3.6.1.4.1.5528.30.100.110.2
Netbotz External Temperature 1 High Trap. This trap indicates that the upper limit for external temperature probe on port 1 has been exceeded.
                 netBotz_prd_bot_ext_temp1_trap_clear 1.3.6.1.4.1.5528.30.100.110.3
Netbotz External Temperature 1 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 1 has returned to acceptable limits.
                 netBotz_prd_bot_ext_temp1_sensor_unplugged 1.3.6.1.4.1.5528.30.100.110.6
Netbotz External Temperature 1 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
                 netBotz_prd_bot_ext_temp1_sensor_replugged 1.3.6.1.4.1.5528.30.100.110.7
Netbotz External Temperature 1 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
                 netBotz_prd_bot_ext_temp2_low_trap 1.3.6.1.4.1.5528.30.100.120.1
Netbotz External Temperature 2 Low Trap. This trap indicates that the lower limit for external temperature probe on port 2 has been exceeded.
                 netBotz_prd_bot_ext_temp2_high_trap 1.3.6.1.4.1.5528.30.100.120.2
Netbotz External Temperature 2 High Trap. This trap indicates that the upper limit for external temperature probe on port 2 has been exceeded.
                 netBotz_prd_bot_ext_temp2_trap_clear 1.3.6.1.4.1.5528.30.100.120.3
Netbotz External Temperature 2 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 2 has returned to acceptable limits.
                 netBotz_prd_bot_ext_temp2_sensor_unplugged 1.3.6.1.4.1.5528.30.100.120.6
Netbotz External Temperature 2 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
                 netBotz_prd_bot_ext_temp2_sensor_replugged 1.3.6.1.4.1.5528.30.100.120.7
Netbotz External Temperature 2 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
                 netBotz_prd_bot_ext_temp3_low_trap 1.3.6.1.4.1.5528.30.100.130.1
Netbotz External Temperature 3 Low Trap. This trap indicates that the lower limit for external temperature probe on port 3 has been exceeded.
                 netBotz_prd_bot_ext_temp3_high_trap 1.3.6.1.4.1.5528.30.100.130.2
Netbotz External Temperature 3 High Trap. This trap indicates that the upper limit for external temperature probe on port 3 has been exceeded.
                 netBotz_prd_bot_ext_temp3_trap_clear 1.3.6.1.4.1.5528.30.100.130.3
Netbotz External Temperature 3 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 3 has returned to acceptable limits.
                 netBotz_prd_bot_ext_temp3_sensor_unplugged 1.3.6.1.4.1.5528.30.100.130.6
Netbotz External Temperature 3 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
                 netBotz_prd_bot_ext_temp3_sensor_replugged 1.3.6.1.4.1.5528.30.100.130.7
Netbotz External Temperature 3 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
                 netBotz_prd_bot_ext_temp4_low_trap 1.3.6.1.4.1.5528.30.100.140.1
Netbotz External Temperature 4 Low Trap. This trap indicates that the lower limit for external temperature probe on port 4 has been exceeded.
                 netBotz_prd_bot_ext_temp4_high_trap 1.3.6.1.4.1.5528.30.100.140.2
Netbotz External Temperature 4 High Trap. This trap indicates that the upper limit for external temperature probe on port 4 has been exceeded.
                 netBotz_prd_bot_ext_temp4_trap_clear 1.3.6.1.4.1.5528.30.100.140.3
Netbotz External Temperature 4 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 4 has returned to acceptable limits.
                 netBotz_prd_bot_ext_temp4_sensor_unplugged 1.3.6.1.4.1.5528.30.100.140.6
Netbotz External Temperature 4 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
                 netBotz_prd_bot_ext_temp4_sensor_replugged 1.3.6.1.4.1.5528.30.100.140.7
Netbotz External Temperature 4 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
                 netBotz_prd_bot_ext_dry1_triggered_trap 1.3.6.1.4.1.5528.30.100.150.2
Netbotz External Dry Contact 1 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext1 matches the alarm value.
                 netBotz_prd_bot_ext_dry1_trap_clear 1.3.6.1.4.1.5528.30.100.150.3
Netbotz External Dry Contact 1 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext1 no longer matches the alarm value.
                 netBotz_prd_bot_ext_dry2_triggered_trap 1.3.6.1.4.1.5528.30.100.160.2
Netbotz External Dry Contact 2 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext2 matches the alarm value.
                 netBotz_prd_bot_ext_dry2_trap_clear 1.3.6.1.4.1.5528.30.100.160.3
Netbotz External Dry Contact 2 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext2 no longer matches the alarm value.
                 netBotz_prd_bot_ext_dry3_triggered_trap 1.3.6.1.4.1.5528.30.100.170.2
Netbotz External Dry Contact 3 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext3 matches the alarm value.
                 netBotz_prd_bot_ext_dry3_trap_clear 1.3.6.1.4.1.5528.30.100.170.3
Netbotz External Dry Contact 3 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext3 no longer matches the alarm value.
                 netBotz_prd_bot_ext_dry4_triggered_trap 1.3.6.1.4.1.5528.30.100.180.2
Netbotz External Dry Contact 4 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext4 matches the alarm value.
                 netBotz_prd_bot_ext_dry4_trap_clear 1.3.6.1.4.1.5528.30.100.180.3
Netbotz External Dry Contact 4 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext4 no longer matches the alarm value.