Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 netBotz 1.3.6.1.4.1.5528
           netBotz_reg 1.3.6.1.4.1.5528.10
           netBotz_generic 1.3.6.1.4.1.5528.20
           netBotz_products 1.3.6.1.4.1.5528.30
                 netBotz_prd_bot 1.3.6.1.4.1.5528.30.10
                       netBotz_prd_bot_temp 1.3.6.1.4.1.5528.30.10.1 integer read-only
The reading of the temperature probe, in degrees F or degrees C (depends on netBotz-ismetric).
                       netBotz_prd_bot_humidity 1.3.6.1.4.1.5528.30.10.2 integer read-only
The reading of the humidity probe, in percent.
                       netBotz_prd_bot_airflow 1.3.6.1.4.1.5528.30.10.3 integer read-only
The reading of the airflow probe. Each unit represents approximately 40 feet/minute or 13 meters/minute of airflow velocity.
                       netBotz_prd_bot_audio 1.3.6.1.4.1.5528.30.10.4 integer read-only
The reading of the audio alarm probe on/off.
                       netBotz_prd_bot_doorajar 1.3.6.1.4.1.5528.30.10.5 integer read-only
The reading of the door switch probe open(1) or closed(0).
                       netBotz_prd_bot_temp_min 1.3.6.1.4.1.5528.30.10.6 integer read-write
The temperature probe minimum, from 35 to 120 degrees F, or 1 to 50 degrees C (depends on netBotz-ismetric).
                       netBotz_prd_bot_temp_max 1.3.6.1.4.1.5528.30.10.7 integer read-write
The temperature probe maximum, from 35 to 120 degrees F, or 1 to 50 degrees C (depends on netBotz-ismetric).
                       netBotz_prd_bot_humidity_min 1.3.6.1.4.1.5528.30.10.8 integer read-write
The humidity probe minimum, from 10 to 90 percent.
                       netBotz_prd_bot_humidity_max 1.3.6.1.4.1.5528.30.10.9 integer read-write
The humidity probe maximum, from 10 to 90 percent.
                       netBotz_prd_bot_airflow_mins 1.3.6.1.4.1.5528.30.10.10 integer read-write
Minutes without airflow before alarm set.
                       netBotz_prd_bot_audio_secs 1.3.6.1.4.1.5528.30.10.11 integer read-write
Seconds of alarm audio before alarm set.
                       netBotz_prd_bot_temp_enabled 1.3.6.1.4.1.5528.30.10.12 integer read-write
Temperature probe alarm enabled(1) or disabled(0).
                       netBotz_prd_bot_hum_enabled 1.3.6.1.4.1.5528.30.10.13 integer read-write
Humidity probe alarm enabled(1) or disabled(0).
                       netBotz_prd_bot_air_enabled 1.3.6.1.4.1.5528.30.10.14 integer read-write
Airflow probe alarm enabled(1) or disabled(0).
                       netBotz_prd_bot_audio_enabled 1.3.6.1.4.1.5528.30.10.15 integer read-write
Audio probe alarm enabled(1) or disabled(0).
                       netBotz_prd_bot_switch_state 1.3.6.1.4.1.5528.30.10.16 integer read-write
Switch state setting. The state controls which condition of the door switch indicates an alarm. If set to 0, alarm is set when the switch is closed. If set to 1, alarm is set when the switch is open.
                       netBotz_prd_bot_switch_enabled 1.3.6.1.4.1.5528.30.10.17 integer read-write
Door switch enabled(1) or disabled(0).
                       netBotz_prd_bot_audio_level 1.3.6.1.4.1.5528.30.10.18 integer read-write
Audio level setting. This is the relative audio level, from 0-11, above which an alarm will be sent.
                       netBotz_prd_bot_trap_index 1.3.6.1.4.1.5528.30.10.20 integer read-only
The crawler ID of the last trap.
                       netBotz_prd_bot_trap_address 1.3.6.1.4.1.5528.30.10.21 ipaddress read-only
The IP address of the last trap.
                       netBotz_prd_bot_trap_oid 1.3.6.1.4.1.5528.30.10.22 object identifier read-only
The object id of the last trap.
                       netBotz_prd_bot_trap_value 1.3.6.1.4.1.5528.30.10.23 integer read-only
The value of the last object trap.
                       netBotz_prd_bot_trap_date 1.3.6.1.4.1.5528.30.10.24 integer read-only
The date and time of a specific trap. This field contains the number of seconds elapsed since midnight (00:00:00), January 1, 1970
                       netBotz_prd_bot_refresh 1.3.6.1.4.1.5528.30.10.26 integer read-write
Rate of web page refresh, in seconds. This must be greater than 5 seconds.
                       netBotz_prd_bot_airflow_level 1.3.6.1.4.1.5528.30.10.27 integer read-write
Airflow alert level. This is the relative level of airflow below which an alarm will be sent. The range is 1-11. Each unit is approximately 40 feet/second or 13 meters/second of airflow velocity.
                       netBotz_prd_bot_doorpic_count 1.3.6.1.4.1.5528.30.10.28 integer read-write
Number of pictures to take when door activated. These pictures will be sent as attachments to the door alert e-mail. The range is from 0 to 5 pictures.
                       netBotz_prd_bot_amps1 1.3.6.1.4.1.5528.30.10.29 integer read-only
The reading of the first amperage probe, in milliamps.
                       netBotz_prd_bot_amps1_enabled 1.3.6.1.4.1.5528.30.10.30 integer read-write
Amperage[1] probe alarm enabled(1) or disabled(0).
                       netBotz_prd_bot_amps1_min 1.3.6.1.4.1.5528.30.10.31 integer read-write
The amperage[1] probe minimum, from 0 to 30000 milliamps.
                       netBotz_prd_bot_amps1_max 1.3.6.1.4.1.5528.30.10.32 integer read-write
The amperage[1] probe maximum, from 0 to 30000 milliamps.
                       netBotz_prd_bot_amps2 1.3.6.1.4.1.5528.30.10.34 integer read-only
The reading of the second amperage probe, in milliamps.
                       netBotz_prd_bot_amps2_enabled 1.3.6.1.4.1.5528.30.10.35 integer read-write
Amperage[2] probe alarm enabled(1) or disabled(0).
                       netBotz_prd_bot_amps2_min 1.3.6.1.4.1.5528.30.10.36 integer read-write
The amperage[2] probe minimum, from 0 to 30000 milliamps.
                       netBotz_prd_bot_amps2_max 1.3.6.1.4.1.5528.30.10.37 integer read-write
The amperage[2] probe maximum, from 0 to 30000 milliamps.
                       netBotz_prd_bot_amps3 1.3.6.1.4.1.5528.30.10.39 integer read-only
The reading of the third amperage probe, in milliamps.
                       netBotz_prd_bot_amps3_enabled 1.3.6.1.4.1.5528.30.10.40 integer read-write
Amperage[3] probe alarm enabled(1) or disabled(0).
                       netBotz_prd_bot_amps3_min 1.3.6.1.4.1.5528.30.10.41 integer read-write
The amperage[3] probe minimum, from 0 to 30000 milliamps.
                       netBotz_prd_bot_amps3_max 1.3.6.1.4.1.5528.30.10.42 integer read-write
The amperage[3] probe maximum, from 0 to 30000 milliamps.
                       netBotz_prd_bot_amps_total 1.3.6.1.4.1.5528.30.10.44 integer read-only
The total of the readings of all amperage probes, in milliamps.
                       netBotz_prd_bot_amps_total_enabled 1.3.6.1.4.1.5528.30.10.45 integer read-write
Total amperage alarm enabled(1) or disabled(0).
                       netBotz_prd_bot_amps_total_min 1.3.6.1.4.1.5528.30.10.46 integer read-write
The total amperage minimum, from 0 to 90000 milliamps.
                       netBotz_prd_bot_amps_total_max 1.3.6.1.4.1.5528.30.10.47 integer read-write
The total amperage maximum, from 0 to 90000 milliamps.
                       netBotz_prd_bot_amps_total_support_enabled 1.3.6.1.4.1.5528.30.10.48 displaystring read-write
Total Amperage Support enabled(Y) or disabled(N).
                       netBotz_prd_bot_amps1_uV_per_10mA 1.3.6.1.4.1.5528.30.10.49 integer read-write
The scaling factor used for the first amperage probe to convert microvolts measured from the Amp Detect into 10s of milliamps of current. Needs to be set based on the type of Amp Detect module installed.
                       netBotz_prd_bot_amps2_uV_per_10mA 1.3.6.1.4.1.5528.30.10.50 integer read-write
The scaling factor used for the second amperage probe to convert microvolts measured from the Amp Detect into 10s of milliamps of current. Needs to be set based on the type of Amp Detect module installed.
                       netBotz_prd_bot_amps3_uV_per_mA 1.3.6.1.4.1.5528.30.10.51 integer read-write
The scaling factor used for the third amperage probe to convert microvolts measured from the Amp Detect into 10s of milliamps of current. Needs to be set based on the type of Amp Detect module installed.
                       netBotz_prd_bot_amps1_max_range 1.3.6.1.4.1.5528.30.10.52 integer read-write
The maximum RMS milliamps measureable by the first Amp Detect.
                       netBotz_prd_bot_amps2_max_range 1.3.6.1.4.1.5528.30.10.53 integer read-write
The maximum RMS milliamps measureable by the second Amp Detect.
                       netBotz_prd_bot_amps3_max_range 1.3.6.1.4.1.5528.30.10.54 integer read-write
The maximum RMS milliamps measureable by the third Amp Detect.
                       netBotz_prd_bot_amps4 1.3.6.1.4.1.5528.30.10.55 integer read-only
The reading of the fourth amperage probe, in milliamps.
                       netBotz_prd_bot_amps4_enabled 1.3.6.1.4.1.5528.30.10.56 integer read-write
Amperage[4] probe alarm enabled(1) or disabled(0).
                       netBotz_prd_bot_amps4_min 1.3.6.1.4.1.5528.30.10.57 integer read-write
The amperage[4] probe minimum, in milliamps.
                       netBotz_prd_bot_amps4_max 1.3.6.1.4.1.5528.30.10.58 integer read-write
The amperage[4] probe maximum, in milliamps.
                       netBotz_prd_bot_amps4_uV_per_10mA 1.3.6.1.4.1.5528.30.10.60 integer read-write
The scaling factor used for the fourth amperage probe to convert microvolts measured from the Amp Detect into 10s of milliamps of current. Needs to be set based on the type of Amp Detect module installed.
                       netBotz_prd_bot_amps4_max_range 1.3.6.1.4.1.5528.30.10.61 integer read-write
The maximum RMS milliamps measureable by the fourth Amp Detect.
                       netBotz_prd_bot_ext_temp1 1.3.6.1.4.1.5528.30.10.62 integer read-only
The reading of the external temperature probe on port 1, in degrees F or degrees C (depends on netBotz-ismetric).
                       netBotz_prd_bot_ext_temp2 1.3.6.1.4.1.5528.30.10.63 integer read-only
The reading of the external temperature probe on port 2, in degrees F or degrees C (depends on netBotz-ismetric).
                       netBotz_prd_bot_ext_temp3 1.3.6.1.4.1.5528.30.10.64 integer read-only
The reading of the external temperature probe on port 3, in degrees F or degrees C (depends on netBotz-ismetric).
                       netBotz_prd_bot_ext_temp1_enabled 1.3.6.1.4.1.5528.30.10.66 integer read-write
External temperature probe on port 1 alarm enabled(1) or disabled(0).
                       netBotz_prd_bot_ext_temp1_min 1.3.6.1.4.1.5528.30.10.67 integer read-write
The external temperature probe on port 1 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).
                       netBotz_prd_bot_ext_temp1_max 1.3.6.1.4.1.5528.30.10.68 integer read-write
The external temperature probe on port 1 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).
                       netBotz_prd_bot_ext_temp2_enabled 1.3.6.1.4.1.5528.30.10.69 integer read-write
External temperature probe on port 2 alarm enabled(1) or disabled(0).
                       netBotz_prd_bot_ext_temp2_min 1.3.6.1.4.1.5528.30.10.70 integer read-write
The external temperature probe on port 2 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).
                       netBotz_prd_bot_ext_temp2_max 1.3.6.1.4.1.5528.30.10.71 integer read-write
The external temperature probe on port 2 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).
                       netBotz_prd_bot_ext_temp3_enabled 1.3.6.1.4.1.5528.30.10.72 integer read-write
External temperature probe on port 3 alarm enabled(1) or disabled(0).
                       netBotz_prd_bot_ext_temp3_min 1.3.6.1.4.1.5528.30.10.73 integer read-write
The external temperature probe on port 3 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).
                       netBotz_prd_bot_ext_temp3_max 1.3.6.1.4.1.5528.30.10.74 integer read-write
The external temperature probe on port 3 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).
                       netBotz_prd_bot_ext_temp1_uV_per_degreeC 1.3.6.1.4.1.5528.30.10.78 integer read-write
The scaling factor used for the external temperature probe on port 1 to convert microvolts measured from the temperature sensor into degrees C. Needs to be set based on the type of temperature sensor module installed.
                       netBotz_prd_bot_ext_temp1_uV_at_0_degreeC 1.3.6.1.4.1.5528.30.10.79 integer read-write
The offset used for the external temperature probe on port 1 of microvolts measured from the temperature sensor at zero degrees C. Needs to be set based on the type of temperature sensor module installed.
                       netBotz_prd_bot_ext_temp1_min_range 1.3.6.1.4.1.5528.30.10.80 integer read-write
The minimum temperature measureable by the temperature sensor installed on port 1, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installed.
                       netBotz_prd_bot_ext_temp1_max_range 1.3.6.1.4.1.5528.30.10.81 integer read-write
The maximum temperature measureable by the temperature sensor installed on port 1, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installed.
                       netBotz_prd_bot_ext_temp2_uV_per_degreeC 1.3.6.1.4.1.5528.30.10.82 integer read-write
The scaling factor used for the external temperature probe on port 2 to convert microvolts measured from the temperature sensor into degrees C. Needs to be set based on the type of temperature sensor module installed.
                       netBotz_prd_bot_ext_temp2_uV_at_0_degreeC 1.3.6.1.4.1.5528.30.10.83 integer read-write
The offset used for the external temperature probe on port 2 of microvolts measured from the temperature sensor at zero degrees C. Needs to be set based on the type of temperature sensor module installed.
                       netBotz_prd_bot_ext_temp2_min_range 1.3.6.1.4.1.5528.30.10.84 integer read-write
The minimum temperature measureable by the temperature sensor installed on port 2, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installed.
                       netBotz_prd_bot_ext_temp2_max_range 1.3.6.1.4.1.5528.30.10.85 integer read-write
The maximum temperature measureable by the temperature sensor installed on port 2, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installed.
                       netBotz_prd_bot_ext_temp3_uV_per_degreeC 1.3.6.1.4.1.5528.30.10.86 integer read-write
The scaling factor used for the external temperature probe on port 3 to convert microvolts measured from the temperature sensor into degrees C. Needs to be set based on the type of temperature sensor module installed.
                       netBotz_prd_bot_ext_temp3_uV_at_0_degreeC 1.3.6.1.4.1.5528.30.10.87 integer read-write
The offset used for the external temperature probe on port 3 of microvolts measured from the temperature sensor at zero degrees C. Needs to be set based on the type of temperature sensor module installed.
                       netBotz_prd_bot_ext_temp3_min_range 1.3.6.1.4.1.5528.30.10.88 integer read-write
The minimum temperature measureable by the temperature sensor installed on port 3, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installed.
                       netBotz_prd_bot_ext_temp3_max_range 1.3.6.1.4.1.5528.30.10.89 integer read-write
The maximum temperature measureable by the temperature sensor installed on port 3, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installed.
                       netBotz_prd_bot_ext_port1_module_id 1.3.6.1.4.1.5528.30.10.94 displaystring read-write
The module ID of the sensor module installed on port 1. Blank string indicates that no module is installed.
                       netBotz_prd_bot_ext_port1_module_type 1.3.6.1.4.1.5528.30.10.95 displaystring read-write
The type of sensor module installed on port 1. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor.
                       netBotz_prd_bot_ext_port2_module_id 1.3.6.1.4.1.5528.30.10.96 displaystring read-write
The module ID of the sensor module installed on port 2. Blank string indicates that no module is installed.
                       netBotz_prd_bot_ext_port2_module_type 1.3.6.1.4.1.5528.30.10.97 displaystring read-write
The type of sensor module installed on port 2. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor.
                       netBotz_prd_bot_ext_port3_module_id 1.3.6.1.4.1.5528.30.10.98 displaystring read-write
The module ID of the sensor module installed on port 3. Blank string indicates that no module is installed.
                       netBotz_prd_bot_ext_port3_module_type 1.3.6.1.4.1.5528.30.10.99 displaystring read-write
The type of sensor module installed on port 3. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor.
                       netBotz_prd_bot_amp1_total_amp_seconds 1.3.6.1.4.1.5528.30.10.102 integer read-only
The accumulated total of amp-seconds on the AmpDetect on port 1.
                       netBotz_prd_bot_amp1_total_amp_seconds_since_time 1.3.6.1.4.1.5528.30.10.103 integer read-write
The UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 1. Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time.
                       netBotz_prd_bot_amp2_total_amp_seconds 1.3.6.1.4.1.5528.30.10.104 integer read-only
The accumulated total of amp-seconds on the AmpDetect on port 2.
                       netBotz_prd_bot_amp2_total_amp_seconds_since_time 1.3.6.1.4.1.5528.30.10.105 integer read-write
The UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 2. Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time.
                       netBotz_prd_bot_amp3_total_amp_seconds 1.3.6.1.4.1.5528.30.10.106 integer read-only
The accumulated total of amp-seconds on the AmpDetect on port 3.
                       netBotz_prd_bot_amp3_total_amp_seconds_since_time 1.3.6.1.4.1.5528.30.10.107 integer read-write
The UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 3. Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time.
                       netBotz_prd_bot_amp4_total_amp_seconds 1.3.6.1.4.1.5528.30.10.108 integer read-only
The accumulated total of amp-seconds on the AmpDetect on port 4.
                       netBotz_prd_bot_amp4_total_amp_seconds_since_time 1.3.6.1.4.1.5528.30.10.109 integer read-write
The UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 4. Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time.
                       netBotz_prd_bot_amptotal_total_amp_seconds 1.3.6.1.4.1.5528.30.10.110 integer read-only
The accumulated total of amp-seconds on the total of all AmpDetects.
                       netBotz_prd_bot_amptotal_total_amp_seconds_since_time 1.3.6.1.4.1.5528.30.10.111 integer read-write
The UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds for all AmpDetects. Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time.
                       netBotz_prd_bot_ext_dry1 1.3.6.1.4.1.5528.30.10.112 integer read-only
The current value of the external dry contact sensor on Ext1: 0=Open, 1=Closed, -1=N/A
                       netBotz_prd_bot_ext_dry2 1.3.6.1.4.1.5528.30.10.113 integer read-only
The current value of the external dry contact sensor on Ext2: 0=Open, 1=Closed, -1=N/A
                       netBotz_prd_bot_ext_dry3 1.3.6.1.4.1.5528.30.10.114 integer read-only
The current value of the external dry contact sensor on Ext3: 0=Open, 1=Closed, -1=N/A
                       netBotz_prd_bot_ext_dry4 1.3.6.1.4.1.5528.30.10.115 integer read-only
The current value of the external dry contact sensor on Ext4: 0=Open, 1=Closed, -1=N/A
                       netBotz_prd_bot_ext_dry1_alarm_value 1.3.6.1.4.1.5528.30.10.116 integer read-write
The value to generate alarms on for the external dry contact sensor on Ext1: 0=Open, 1=Closed
                       netBotz_prd_bot_ext_dry1_enabled 1.3.6.1.4.1.5528.30.10.117 integer read-write
External dry contact sensor on Ext1 alarm enabled(1) or disabled(0).
                       netBotz_prd_bot_ext_dry2_alarm_value 1.3.6.1.4.1.5528.30.10.118 integer read-write
The value to generate alarms on for the external dry contact sensor on Ext2: 0=Open, 1=Closed
                       netBotz_prd_bot_ext_dry2_enabled 1.3.6.1.4.1.5528.30.10.119 integer read-write
External dry contact sensor on Ext2 alarm enabled(1) or disabled(0).
                       netBotz_prd_bot_ext_dry3_alarm_value 1.3.6.1.4.1.5528.30.10.120 integer read-write
The value to generate alarms on for the external dry contact sensor on Ext3: 0=Open, 1=Closed
                       netBotz_prd_bot_ext_dry3_enabled 1.3.6.1.4.1.5528.30.10.121 integer read-write
External dry contact sensor on Ext3 alarm enabled(1) or disabled(0).
                       netBotz_prd_bot_ext_dry4_alarm_value 1.3.6.1.4.1.5528.30.10.122 integer read-write
The value to generate alarms on for the external dry contact sensor on Ext4: 0=Open, 1=Closed
                       netBotz_prd_bot_ext_dry4_enabled 1.3.6.1.4.1.5528.30.10.123 integer read-write
External dry contact sensor on Ext4 alarm enabled(1) or disabled(0).
                       netBotz_prd_bot_ext_dry1_label 1.3.6.1.4.1.5528.30.10.124 displaystring read-write
The sensor name/label for the dry contact sensor on Ext1
                       netBotz_prd_bot_ext_dry1_open_label 1.3.6.1.4.1.5528.30.10.125 displaystring read-write
The sensor name/label for the open(0) state for the dry contact sensor on Ext1
                       netBotz_prd_bot_ext_dry1_closed_label 1.3.6.1.4.1.5528.30.10.126 displaystring read-write
The sensor name/label for the closed(0) state for the dry contact sensor on Ext1
                       netBotz_prd_bot_ext_dry1_open_to_close_millis 1.3.6.1.4.1.5528.30.10.127 integer read-write
The minimum number of milliseconds that the dry contact sensor on Ext1 must read closed before the state is changed from open to closed.
                       netBotz_prd_bot_ext_dry1_close_to_open_millis 1.3.6.1.4.1.5528.30.10.128 integer read-write
The minimum number of milliseconds that the dry contact sensor on Ext1 must read openbefore the state is changed from closed to open.
                       netBotz_prd_bot_ext_dry1_response 1.3.6.1.4.1.5528.30.10.129 displaystring read-write
The type of alert response for the dry contact sensor on Ext1: ALERT=e-mail with no pictures, CAMERA=e-mail with pictures from camera.
                       netBotz_prd_bot_ext_dry2_label 1.3.6.1.4.1.5528.30.10.130 displaystring read-write
The sensor name/label for the dry contact sensor on Ext2
                       netBotz_prd_bot_ext_dry2_open_label 1.3.6.1.4.1.5528.30.10.131 displaystring read-write
The sensor name/label for the open(0) state for the dry contact sensor on Ext2
                       netBotz_prd_bot_ext_dry2_closed_label 1.3.6.1.4.1.5528.30.10.132 displaystring read-write
The sensor name/label for the closed(0) state for the dry contact sensor on Ext2
                       netBotz_prd_bot_ext_dry2_open_to_close_millis 1.3.6.1.4.1.5528.30.10.133 integer read-write
The minimum number of milliseconds that the dry contact sensor on Ext2 must read closed before the state is changed from open to closed.
                       netBotz_prd_bot_ext_dry2_close_to_open_millis 1.3.6.1.4.1.5528.30.10.134 integer read-write
The minimum number of milliseconds that the dry contact sensor on Ext2 must read openbefore the state is changed from closed to open.
                       netBotz_prd_bot_ext_dry2_response 1.3.6.1.4.1.5528.30.10.135 displaystring read-write
The type of alert response for the dry contact sensor on Ext2: ALERT=e-mail with no pictures, CAMERA=e-mail with pictures from camera.
                       netBotz_prd_bot_ext_dry3_label 1.3.6.1.4.1.5528.30.10.136 displaystring read-write
The sensor name/label for the dry contact sensor on Ext3
                       netBotz_prd_bot_ext_dry3_open_label 1.3.6.1.4.1.5528.30.10.137 displaystring read-write
The sensor name/label for the open(0) state for the dry contact sensor on Ext3
                       netBotz_prd_bot_ext_dry3_closed_label 1.3.6.1.4.1.5528.30.10.138 displaystring read-write
The sensor name/label for the closed(0) state for the dry contact sensor on Ext3
                       netBotz_prd_bot_ext_dry3_open_to_close_millis 1.3.6.1.4.1.5528.30.10.139 integer read-write
The minimum number of milliseconds that the dry contact sensor on Ext3 must read closed before the state is changed from open to closed.
                       netBotz_prd_bot_ext_dry3_close_to_open_millis 1.3.6.1.4.1.5528.30.10.140 integer read-write
The minimum number of milliseconds that the dry contact sensor on Ext3 must read openbefore the state is changed from closed to open.
                       netBotz_prd_bot_ext_dry3_response 1.3.6.1.4.1.5528.30.10.141 displaystring read-write
The type of alert response for the dry contact sensor on Ext3: ALERT=e-mail with no pictures, CAMERA=e-mail with pictures from camera.
                       netBotz_prd_bot_cam_motion 1.3.6.1.4.1.5528.30.10.148 integer read-only
The current motion reading for the camera motion sensor (0=none, 1=motion detected)
                       netBotz_prd_bot_cam_motion_enabled 1.3.6.1.4.1.5528.30.10.149 integer read-write
Camera motion sensor alarm enabled(1) or disabled(0).
                       netBotz_prd_bot_cam_motion_sensitivity 1.3.6.1.4.1.5528.30.10.150 integer read-write
Camera motion sensor sensitivity: 1=max, 15=min, 0=disabled.
                       netBotz_prd_bot_cam_motion_delay 1.3.6.1.4.1.5528.30.10.151 integer read-write
Camera motion sensor delay. This is the minimum number of milliseconds of detected motion required before the alarm is triggered.
                       netBotz_prd_bot_camera_event_autocycle 1.3.6.1.4.1.5528.30.10.152 integer read-write
Enables (1) or disables (0) the option to have the camera-based responses to alarm conditions automatically cycle as long as the condition persists.
                       netBotz_prd_bot_num_pix_before_alarm 1.3.6.1.4.1.5528.30.10.153 integer read-write
Controls the number of pictures to be captured before any triggered alarm.
                       netBotz_prd_bot_delay_before_event_pix 1.3.6.1.4.1.5528.30.10.154 integer read-write
Controls the number of milliseconds before the first picture is captured after any triggered alarm.
                       netBotz_prd_bot_delay_between_event_pix 1.3.6.1.4.1.5528.30.10.155 integer read-write
Controls the number of milliseconds between pictures captured after any triggered alarm.
                       netBotz_prd_bot_cam_motion_area_of_motion 1.3.6.1.4.1.5528.30.10.156 integer read-write
Camera motion sensor area of motion: 1=max, 15=min, 0=disabled.
                       netBotz_prd_bot_cam_pix_for_duration_of_alerts 1.3.6.1.4.1.5528.30.10.157 integer read-write
Camera images gathered for duration of camera related alert: 0=no, 1=yes.
                       netBotz_prd_bot_camera_enabled 1.3.6.1.4.1.5528.30.10.158 integer read-write
Controls whether the camera is enabled or not: 0=no, 1=yes. Changing this will reboot the appliance.
                       netBotz_prd_bot_camera_is_flipped 1.3.6.1.4.1.5528.30.10.159 integer read-write
Controls whether the camera image is flipped 180 degress or not: 0=no, 1=yes. Changing this will reboot the appliance.
                       netBotz_prd_bot_camera_brightness 1.3.6.1.4.1.5528.30.10.160 integer read-write
Sets the brightness on the camera, from 20 to 180 (20 is low, 180 is high).
                 netBotz_prd_crawlers 1.3.6.1.4.1.5528.30.20
                       netbotz_crawlers 1.3.6.1.4.1.5528.30.20.5528
                                 netBotz_prd_crl_mib2 1.3.6.1.4.1.5528.30.20.5528.1
                                     netBotz_prd_crl_mib2_ping 1.3.6.1.4.1.5528.30.20.5528.1.3 integer read-only
NetBotz device ping. This object indicates the status of a ping on a device monitored by a NetBotz device.
                                     netBotz_prd_crl_mib2_uptime 1.3.6.1.4.1.5528.30.20.5528.1.8 timeticks read-only
The uptime of a device monitored by a NetBotz device.
                                     netBotz_prd_crl_mib2_snmpstatus 1.3.6.1.4.1.5528.30.20.5528.1.9 displaystring read-only
The SNMP status of a device monitored by a NetBotz device.
                                           netBotz_prd_crl_ping_offline_trap 1.3.6.1.4.1.5528.30.20.5528.1.30.4
NetBotz Ping Trap. This trap indicates that replies to a set of pings were not received from a monitored IP address.
                                           netBotz_prd_crl_ping_online_trap 1.3.6.1.4.1.5528.30.20.5528.1.30.5
NetBotz Ping Trap. This trap indicates that replies to a set of pings were received from a monitored IP address after a period when no replies had been received.
                                           netBotz_prd_crl_uptime_online_trap 1.3.6.1.4.1.5528.30.20.5528.1.80.5
NetBotz Uptime Trap. This trap indicates that a device restart has been detected due to the uptime of the device being reported as less than the previously reported reading.
                                           netBotz_prd_crl_snmp_offline_trap 1.3.6.1.4.1.5528.30.20.5528.1.90.4
NetBotz SNMP Offline Trap. This trap indicates that an SNMP request was not possible on an IP address.
                                           netBotz_prd_crl_snmp_online_trap 1.3.6.1.4.1.5528.30.20.5528.1.90.5
NetBotz SNMP Online Trap. This trap indicates that an SNMP request succeeded on an IP address where it had previously failed.
                                 netBotz_prd_crl_mib2if 1.3.6.1.4.1.5528.30.20.5528.2
                                     netBotz_prd_crl_mib2if_opstatus 1.3.6.1.4.1.5528.30.20.5528.2.6 integer read-only
The operational status of a device monitored by a NetBotz device.
                                           netBotz_prd_crl_opstatus_mismatch_trap 1.3.6.1.4.1.5528.30.20.5528.2.60.1
NetBotz Interface Status Mismatch Trap. This trap indicates that the operational status of a device interface does not match the administrative status.
                                           netBotz_prd_crl_opstatus_match_trap 1.3.6.1.4.1.5528.30.20.5528.2.60.2
NetBotz Interface Status Match Trap. This trap indicates that the operational status of a device interface now matches the administrative status. This trap indicates a transition from a state in which the administrative and operational status did not match.
                                           netBotz_prd_crl_opstatus_offline_trap 1.3.6.1.4.1.5528.30.20.5528.2.60.4
NetBotz Interface Offline Trap. This trap indicates that an interface on a device did not respond to an SNMP query on the ifAdminStatus or ifOperStatus objects.
                 netBotz_prd_crltrap 1.3.6.1.4.1.5528.30.21
                       netBotz_prd_crl_trap_index 1.3.6.1.4.1.5528.30.21.20 integer read-only
The ID of the crawler which sent the last trap.
                       netBotz_prd_crl_trap_address 1.3.6.1.4.1.5528.30.21.21 ipaddress read-only
The IP address of the last trap.
                       netBotz_prd_crl_trap_oid 1.3.6.1.4.1.5528.30.21.22 object identifier read-only
The object id of the attribute on the target device which is the concern of the last trap.
                       netBotz_prd_crl_trap_botoid 1.3.6.1.4.1.5528.30.21.23 object identifier read-only
The object id of the attribute on the NetBotz device which is the concern of the last trap.
                       netBotz_prd_crl_trap_value 1.3.6.1.4.1.5528.30.21.24 integer read-only
The value of the attribute associated with the last trap.
                       netBotz_prd_crl_trap_date 1.3.6.1.4.1.5528.30.21.25 integer read-only
The date and time of a specific trap. This field contains the number of seconds elapsed since midnight (00:00:00), January 1, 1970
                       netBotz_prd_crl_trap_attrib 1.3.6.1.4.1.5528.30.21.26 integer read-only
The identification number of the attribute in error
                       netBotz_prd_crl_trap_desc 1.3.6.1.4.1.5528.30.21.27 displaystring read-only
Description or name of the attribute in error
                 netBotz_prd_bot_traps 1.3.6.1.4.1.5528.30.100
                         netBotz_prd_bot_low_trap 1.3.6.1.4.1.5528.30.100.1
NetBotz Low Trap. This trap indicates that a lower limit has been exceeded.
                         netBotz_prd_bot_temperature_traps 1.3.6.1.4.1.5528.30.100.1
                         netBotz_prd_bot_humidity_traps 1.3.6.1.4.1.5528.30.100.2
                         netBotz_prd_bot_high_trap 1.3.6.1.4.1.5528.30.100.2
NetBotz High Trap. This trap indicates that an upper limit has been exceeded.
                         netBotz_prd_bot_airflow_traps 1.3.6.1.4.1.5528.30.100.3
                         netBotz_prd_bot_trap_clear 1.3.6.1.4.1.5528.30.100.3
NetBotz Cleared Trap. The trap has been cleared because the value has returned to acceptable limits.
                         netBotz_prd_bot_audio_traps 1.3.6.1.4.1.5528.30.100.4
                         netBotz_prd_bot_offline_trap 1.3.6.1.4.1.5528.30.100.4
NetBotz Device Offline Trap. This trap indicates that a device or function has been determined to be offline.
                         netBotz_prd_bot_door_traps 1.3.6.1.4.1.5528.30.100.5
                         netBotz_prd_bot_online_trap 1.3.6.1.4.1.5528.30.100.5
NetBotz Device Online Trap. This trap indicates that a device or function has been determined to be online.
                         netBotz_prd_bot_amp1_traps 1.3.6.1.4.1.5528.30.100.6
                         netBotz_prd_bot_amp2_traps 1.3.6.1.4.1.5528.30.100.7
                         netBotz_prd_bot_amp3_traps 1.3.6.1.4.1.5528.30.100.8
                         netBotz_prd_bot_amp4_traps 1.3.6.1.4.1.5528.30.100.9
                         netBotz_prd_bot_amp_total_traps 1.3.6.1.4.1.5528.30.100.10
                               netBotz_prd_bot_temperature_low_trap 1.3.6.1.4.1.5528.30.100.10.1
NetBotz Temperature Low Trap. This trap indicates that the lower limit for temperature has been exceeded.
                               netBotz_prd_bot_temperature_high_trap 1.3.6.1.4.1.5528.30.100.10.2
NetBotz Temperature High Trap. This trap indicates that the upper limit for temperature has been exceeded.
                               netBotz_prd_bot_temperature_trap_clear 1.3.6.1.4.1.5528.30.100.10.3
NetBotz Temperature Cleared Trap. The trap has been cleared because the temperature value has returned to acceptable limits.
                         netBotz_prd_bot_ext_temp1_traps 1.3.6.1.4.1.5528.30.100.11
                         netBotz_prd_bot_ext_temp2_traps 1.3.6.1.4.1.5528.30.100.12
                         netBotz_prd_bot_ext_temp3_traps 1.3.6.1.4.1.5528.30.100.13
                         netBotz_prd_bot_ext_temp4_traps 1.3.6.1.4.1.5528.30.100.14
                         netBotz_prd_bot_ext_dry1_traps 1.3.6.1.4.1.5528.30.100.15
                         netBotz_prd_bot_ext_dry2_traps 1.3.6.1.4.1.5528.30.100.16
                         netBotz_prd_bot_ext_dry3_traps 1.3.6.1.4.1.5528.30.100.17
                         netBotz_prd_bot_ext_dry4_traps 1.3.6.1.4.1.5528.30.100.18
                         netBotz_prd_bot_amp5_traps 1.3.6.1.4.1.5528.30.100.19
                         netBotz_prd_bot_amp6_traps 1.3.6.1.4.1.5528.30.100.20
                               netBotz_prd_bot_humidity_low_trap 1.3.6.1.4.1.5528.30.100.20.1
NetBotz Humidity Low Trap. This trap indicates that the lower limit for humidity has been exceeded.
                               netBotz_prd_bot_humidity_high_trap 1.3.6.1.4.1.5528.30.100.20.2
NetBotz Humidity High Trap. This trap indicates that the upper limit for humidity has been exceeded.
                               netBotz_prd_bot_humidity_trap_clear 1.3.6.1.4.1.5528.30.100.20.3
NetBotz Humidity Cleared Trap. The trap has been cleared because the humidity value has returned to acceptable limits.
                         netBotz_prd_bot_amp7_traps 1.3.6.1.4.1.5528.30.100.21
                         netBotz_prd_bot_ext_temp5_traps 1.3.6.1.4.1.5528.30.100.22
                         netBotz_prd_bot_ext_temp6_traps 1.3.6.1.4.1.5528.30.100.23
                         netBotz_prd_bot_ext_temp7_traps 1.3.6.1.4.1.5528.30.100.24
                         netBotz_prd_bot_ext_dry5_traps 1.3.6.1.4.1.5528.30.100.25
                         netBotz_prd_bot_ext_dry6_traps 1.3.6.1.4.1.5528.30.100.26
                         netBotz_prd_bot_ext_dry7_traps 1.3.6.1.4.1.5528.30.100.27
                         netBotz_prd_bot_camera_motion_traps 1.3.6.1.4.1.5528.30.100.28
                         netBotz_prd_bot_ext_humi1_traps 1.3.6.1.4.1.5528.30.100.29
                         netBotz_prd_bot_ext_humi2_traps 1.3.6.1.4.1.5528.30.100.30
                               netBotz_prd_bot_airflow_low_trap 1.3.6.1.4.1.5528.30.100.30.1
NetBotz Airflow Low Trap. This trap indicates that the lower limit for airflow has been exceeded.
                               netBotz_prd_bot_airflow_trap_clear 1.3.6.1.4.1.5528.30.100.30.3
NetBotz Airflow Cleared Trap. The trap has been cleared because the airflow value has returned to acceptable limits.
                         netBotz_prd_bot_ext_humi3_traps 1.3.6.1.4.1.5528.30.100.31
                         netBotz_prd_bot_ext_humi4_traps 1.3.6.1.4.1.5528.30.100.32
                         netBotz_prd_bot_ext_humi5_traps 1.3.6.1.4.1.5528.30.100.33
                         netBotz_prd_bot_ext_humi6_traps 1.3.6.1.4.1.5528.30.100.34
                         netBotz_prd_bot_ext_humi7_traps 1.3.6.1.4.1.5528.30.100.35
                               netBotz_prd_bot_audio_high_trap 1.3.6.1.4.1.5528.30.100.40.2
NetBotz Audio High Trap. This trap indicates that the upper limit for audio has been exceeded.
                               netBotz_prd_bot_audio_trap_clear 1.3.6.1.4.1.5528.30.100.40.3
NetBotz Audio Cleared Trap. The trap has been cleared because the audio value has returned to acceptable limits.
                               netBotz_prd_bot_door_trap_tripped 1.3.6.1.4.1.5528.30.100.50.2
NetBotz Door Sensor Tripped Trap. This trap indicates that the door sensor has been triggered (i.e. opened, if the thresdhold has been set to trip on open, closed if otherwise).
                               netBotz_prd_bot_door_trap_clear 1.3.6.1.4.1.5528.30.100.50.3
NetBotz Door Cleared Trap. The trap has been cleared because the door sensor has returned to normal (i.e. been closed, if the threshold has been set to trip on open).
                               netBotz_prd_bot_amp1_low_trap 1.3.6.1.4.1.5528.30.100.60.1
NetBotz Amp1 Low Trap. This trap indicates that the lower limit for the first amp detect has been exceeded.
                               netBotz_prd_bot_amp1_high_trap 1.3.6.1.4.1.5528.30.100.60.2
NetBotz Amp1 High Trap. This trap indicates that the upper limit for the first amp detect has been exceeded.
                               netBotz_prd_bot_amp1_trap_clear 1.3.6.1.4.1.5528.30.100.60.3
NetBotz Amp1 Cleared Trap. The trap has been cleared because the first amp detect value has returned to acceptable limits.
                               netBotz_prd_bot_amp1_sensor_unplugged 1.3.6.1.4.1.5528.30.100.60.6
NetBotz Amp 1 Sensor Unplugged Trap. The sensor for the first AmpDetect is unplugged or malfunctioning.
                               netBotz_prd_bot_amp1_sensor_replugged 1.3.6.1.4.1.5528.30.100.60.7
NetBotz Amp 1 Sensor Replugged Trap. The sensor for the first AmpDetect was unplugged, but has been reconnected.
                               netBotz_prd_bot_amp2_low_trap 1.3.6.1.4.1.5528.30.100.70.1
NetBotz Amp2 Low Trap. This trap indicates that the lower limit for the second amp detect has been exceeded.
                               netBotz_prd_bot_amp2_high_trap 1.3.6.1.4.1.5528.30.100.70.2
NetBotz Amp2 High Trap. This trap indicates that the upper limit for the second amp detect has been exceeded.
                               netBotz_prd_bot_amp2_trap_clear 1.3.6.1.4.1.5528.30.100.70.3
NetBotz Amp2 Cleared Trap. The trap has been cleared because the second amp detect value has returned to acceptable limits.
                               netBotz_prd_bot_amp2_sensor_unplugged 1.3.6.1.4.1.5528.30.100.70.6
NetBotz Amp 2 Sensor Unplugged Trap. The sensor for the second AmpDetect is unplugged or malfunctioning.
                               netBotz_prd_bot_amp2_sensor_replugged 1.3.6.1.4.1.5528.30.100.70.7
NetBotz Amp 2 Sensor Replugged Trap. The sensor for the second AmpDetect was unplugged, but has been reconnected.
                               netBotz_prd_bot_amp3_low_trap 1.3.6.1.4.1.5528.30.100.80.1
NetBotz Amp3 Low Trap. This trap indicates that the lower limit for the third amp detect has been exceeded.
                               netBotz_prd_bot_amp3_high_trap 1.3.6.1.4.1.5528.30.100.80.2
NetBotz Amp3 High Trap. This trap indicates that the upper limit for the third amp detect has been exceeded.
                               netBotz_prd_bot_amp3_trap_clear 1.3.6.1.4.1.5528.30.100.80.3
NetBotz Amp3 Cleared Trap. The trap has been cleared because the third amp detect value has returned to acceptable limits.
                               netBotz_prd_bot_amp3_sensor_unplugged 1.3.6.1.4.1.5528.30.100.80.6
NetBotz Amp 3 Sensor Unplugged Trap. The sensor for the third AmpDetect is unplugged or malfunctioning.
                               netBotz_prd_bot_amp3_sensor_replugged 1.3.6.1.4.1.5528.30.100.80.7
NetBotz Amp 3 Sensor Replugged Trap. The sensor for the third AmpDetect was unplugged, but has been reconnected.
                               netBotz_prd_bot_amp4_low_trap 1.3.6.1.4.1.5528.30.100.90.1
NetBotz Amp4 Low Trap. This trap indicates that the lower limit for the fourth amp detect has been exceeded.
                               netBotz_prd_bot_amp4_high_trap 1.3.6.1.4.1.5528.30.100.90.2
NetBotz Amp4 High Trap. This trap indicates that the upper limit for the fourth amp detect has been exceeded.
                               netBotz_prd_bot_amp4_trap_clear 1.3.6.1.4.1.5528.30.100.90.3
NetBotz Amp4 Cleared Trap. The trap has been cleared because the fourth amp detect value has returned to acceptable limits.
                               netBotz_prd_bot_amp4_sensor_unplugged 1.3.6.1.4.1.5528.30.100.90.6
NetBotz Amp 4 Sensor Unplugged Trap. The sensor for the fourth AmpDetect is unplugged or malfunctioning.
                               netBotz_prd_bot_amp4_sensor_replugged 1.3.6.1.4.1.5528.30.100.90.7
NetBotz Amp 4 Sensor Replugged Trap. The sensor for the fourth AmpDetect was unplugged, but has been reconnected.
                                 netBotz_prd_bot_amp_total_low_trap 1.3.6.1.4.1.5528.30.100.100.1
NetBotz Total Amps Low Trap. This trap indicates that the lower limit for the total amperage has been exceeded.
                                 netBotz_prd_bot_amp_total_high_trap 1.3.6.1.4.1.5528.30.100.100.2
NetBotz Total Amps High Trap. This trap indicates that the upper limit for the total amperage has been exceeded.
                                 netBotz_prd_bot_amp_total_trap_clear 1.3.6.1.4.1.5528.30.100.100.3
NetBotz Total Amps Cleared Trap. The trap has been cleared because the total amperage value has returned to acceptable limits.
                                 netBotz_prd_bot_ext_temp1_low_trap 1.3.6.1.4.1.5528.30.100.110.1
NetBotz External Temperature 1 Low Trap. This trap indicates that the lower limit for external temperature probe on port 1 has been exceeded.
                                 netBotz_prd_bot_ext_temp1_high_trap 1.3.6.1.4.1.5528.30.100.110.2
NetBotz External Temperature 1 High Trap. This trap indicates that the upper limit for external temperature probe on port 1 has been exceeded.
                                 netBotz_prd_bot_ext_temp1_trap_clear 1.3.6.1.4.1.5528.30.100.110.3
NetBotz External Temperature 1 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 1 has returned to acceptable limits.
                                 netBotz_prd_bot_ext_temp1_sensor_unplugged 1.3.6.1.4.1.5528.30.100.110.6
NetBotz External Temperature 1 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
                                 netBotz_prd_bot_ext_temp1_sensor_replugged 1.3.6.1.4.1.5528.30.100.110.7
NetBotz External Temperature 1 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
                                 netBotz_prd_bot_ext_temp2_low_trap 1.3.6.1.4.1.5528.30.100.120.1
NetBotz External Temperature 2 Low Trap. This trap indicates that the lower limit for external temperature probe on port 2 has been exceeded.
                                 netBotz_prd_bot_ext_temp2_high_trap 1.3.6.1.4.1.5528.30.100.120.2
NetBotz External Temperature 2 High Trap. This trap indicates that the upper limit for external temperature probe on port 2 has been exceeded.
                                 netBotz_prd_bot_ext_temp2_trap_clear 1.3.6.1.4.1.5528.30.100.120.3
NetBotz External Temperature 2 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 2 has returned to acceptable limits.
                                 netBotz_prd_bot_ext_temp2_sensor_unplugged 1.3.6.1.4.1.5528.30.100.120.6
NetBotz External Temperature 2 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
                                 netBotz_prd_bot_ext_temp2_sensor_replugged 1.3.6.1.4.1.5528.30.100.120.7
NetBotz External Temperature 2 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
                                 netBotz_prd_bot_ext_temp3_low_trap 1.3.6.1.4.1.5528.30.100.130.1
NetBotz External Temperature 3 Low Trap. This trap indicates that the lower limit for external temperature probe on port 3 has been exceeded.
                                 netBotz_prd_bot_ext_temp3_high_trap 1.3.6.1.4.1.5528.30.100.130.2
NetBotz External Temperature 3 High Trap. This trap indicates that the upper limit for external temperature probe on port 3 has been exceeded.
                                 netBotz_prd_bot_ext_temp3_trap_clear 1.3.6.1.4.1.5528.30.100.130.3
NetBotz External Temperature 3 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 3 has returned to acceptable limits.
                                 netBotz_prd_bot_ext_temp3_sensor_unplugged 1.3.6.1.4.1.5528.30.100.130.6
NetBotz External Temperature 3 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
                                 netBotz_prd_bot_ext_temp3_sensor_replugged 1.3.6.1.4.1.5528.30.100.130.7
NetBotz External Temperature 3 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
                                 netBotz_prd_bot_ext_temp4_low_trap 1.3.6.1.4.1.5528.30.100.140.1
NetBotz External Temperature 4 Low Trap. This trap indicates that the lower limit for external temperature probe on port 4 has been exceeded.
                                 netBotz_prd_bot_ext_temp4_high_trap 1.3.6.1.4.1.5528.30.100.140.2
NetBotz External Temperature 4 High Trap. This trap indicates that the upper limit for external temperature probe on port 4 has been exceeded.
                                 netBotz_prd_bot_ext_temp4_trap_clear 1.3.6.1.4.1.5528.30.100.140.3
NetBotz External Temperature 4 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 4 has returned to acceptable limits.
                                 netBotz_prd_bot_ext_temp4_sensor_unplugged 1.3.6.1.4.1.5528.30.100.140.6
NetBotz External Temperature 4 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
                                 netBotz_prd_bot_ext_temp4_sensor_replugged 1.3.6.1.4.1.5528.30.100.140.7
NetBotz External Temperature 4 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
                                 netBotz_prd_bot_ext_dry1_triggered_trap 1.3.6.1.4.1.5528.30.100.150.2
NetBotz External Dry Contact 1 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext1 matches the alarm value.
                                 netBotz_prd_bot_ext_dry1_trap_clear 1.3.6.1.4.1.5528.30.100.150.3
NetBotz External Dry Contact 1 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext1 no longer matches the alarm value.
                                 netBotz_prd_bot_ext_dry2_triggered_trap 1.3.6.1.4.1.5528.30.100.160.2
NetBotz External Dry Contact 2 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext2 matches the alarm value.
                                 netBotz_prd_bot_ext_dry2_trap_clear 1.3.6.1.4.1.5528.30.100.160.3
NetBotz External Dry Contact 2 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext2 no longer matches the alarm value.
                                 netBotz_prd_bot_ext_dry3_triggered_trap 1.3.6.1.4.1.5528.30.100.170.2
NetBotz External Dry Contact 3 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext3 matches the alarm value.
                                 netBotz_prd_bot_ext_dry3_trap_clear 1.3.6.1.4.1.5528.30.100.170.3
NetBotz External Dry Contact 3 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext3 no longer matches the alarm value.
                                 netBotz_prd_bot_ext_dry4_triggered_trap 1.3.6.1.4.1.5528.30.100.180.2
NetBotz External Dry Contact 4 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext4 matches the alarm value.
                                 netBotz_prd_bot_ext_dry4_trap_clear 1.3.6.1.4.1.5528.30.100.180.3
NetBotz External Dry Contact 4 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext4 no longer matches the alarm value.
                                 netBotz_prd_bot_amp5_low_trap 1.3.6.1.4.1.5528.30.100.190.1
NetBotz Amp 5 Low Trap. This trap indicates that the lower limit for the fifth amp detect has been exceeded.
                                 netBotz_prd_bot_amp5_high_trap 1.3.6.1.4.1.5528.30.100.190.2
NetBotz Amp 5 High Trap. This trap indicates that the upper limit for the fifth amp detect has been exceeded.
                                 netBotz_prd_bot_amp5_trap_clear 1.3.6.1.4.1.5528.30.100.190.3
NetBotz Amp 5 Cleared Trap. The trap has been cleared because the fifth amp detect value has returned to acceptable limits.
                                 netBotz_prd_bot_amp5_sensor_unplugged 1.3.6.1.4.1.5528.30.100.190.6
NetBotz Amp 5 Sensor Unplugged Trap. The sensor for the fifth AmpDetect is unplugged or malfunctioning.
                                 netBotz_prd_bot_amp5_sensor_replugged 1.3.6.1.4.1.5528.30.100.190.7
NetBotz Amp 5 Sensor Replugged Trap. The sensor for the fifth AmpDetect was unplugged, but has been reconnected.
                                 netBotz_prd_bot_amp6_low_trap 1.3.6.1.4.1.5528.30.100.200.1
NetBotz Amp 6 Low Trap. This trap indicates that the lower limit for the sixth amp detect has been exceeded.
                                 netBotz_prd_bot_amp6_high_trap 1.3.6.1.4.1.5528.30.100.200.2
NetBotz Amp 6 High Trap. This trap indicates that the upper limit for the sixth amp detect has been exceeded.
                                 netBotz_prd_bot_amp6_trap_clear 1.3.6.1.4.1.5528.30.100.200.3
NetBotz Amp 6 Cleared Trap. The trap has been cleared because the sixth amp detect value has returned to acceptable limits.
                                 netBotz_prd_bot_amp6_sensor_unplugged 1.3.6.1.4.1.5528.30.100.200.6
NetBotz Amp 6 Sensor Unplugged Trap. The sensor for the sixth AmpDetect is unplugged or malfunctioning.
                                 netBotz_prd_bot_amp6_sensor_replugged 1.3.6.1.4.1.5528.30.100.200.7
NetBotz Amp 6 Sensor Replugged Trap. The sensor for the sixth AmpDetect was unplugged, but has been reconnected.
                                 netBotz_prd_bot_amp7_low_trap 1.3.6.1.4.1.5528.30.100.210.1
NetBotz Amp 7 Low Trap. This trap indicates that the lower limit for the seventh amp detect has been exceeded.
                                 netBotz_prd_bot_amp7_high_trap 1.3.6.1.4.1.5528.30.100.210.2
NetBotz Amp 7 High Trap. This trap indicates that the upper limit for the seventh amp detect has been exceeded.
                                 netBotz_prd_bot_amp7_trap_clear 1.3.6.1.4.1.5528.30.100.210.3
NetBotz Amp 7 Cleared Trap. The trap has been cleared because the seventh amp detect value has returned to acceptable limits.
                                 netBotz_prd_bot_amp7_sensor_unplugged 1.3.6.1.4.1.5528.30.100.210.6
NetBotz Amp 7 Sensor Unplugged Trap. The sensor for the seventh AmpDetect is unplugged or malfunctioning.
                                 netBotz_prd_bot_amp7_sensor_replugged 1.3.6.1.4.1.5528.30.100.210.7
NetBotz Amp 7 Sensor Replugged Trap. The sensor for the seventh AmpDetect was unplugged, but has been reconnected.
                                 netBotz_prd_bot_ext_temp5_low_trap 1.3.6.1.4.1.5528.30.100.220.1
NetBotz External Temperature 5 Low Trap. This trap indicates that the lower limit for external temperature probe on port 5 has been exceeded.
                                 netBotz_prd_bot_ext_temp5_high_trap 1.3.6.1.4.1.5528.30.100.220.2
NetBotz External Temperature 5 High Trap. This trap indicates that the upper limit for external temperature probe on port 5 has been exceeded.
                                 netBotz_prd_bot_ext_temp5_trap_clear 1.3.6.1.4.1.5528.30.100.220.3
NetBotz External Temperature 5 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 5 has returned to acceptable limits.
                                 netBotz_prd_bot_ext_temp5_sensor_unplugged 1.3.6.1.4.1.5528.30.100.220.6
NetBotz External Temperature 5 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
                                 netBotz_prd_bot_ext_temp5_sensor_replugged 1.3.6.1.4.1.5528.30.100.220.7
NetBotz External Temperature 5 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
                                 netBotz_prd_bot_ext_temp6_low_trap 1.3.6.1.4.1.5528.30.100.230.1
NetBotz External Temperature 6 Low Trap. This trap indicates that the lower limit for external temperature probe on port 6 has been exceeded.
                                 netBotz_prd_bot_ext_temp6_high_trap 1.3.6.1.4.1.5528.30.100.230.2
NetBotz External Temperature 6 High Trap. This trap indicates that the upper limit for external temperature probe on port 6 has been exceeded.
                                 netBotz_prd_bot_ext_temp6_trap_clear 1.3.6.1.4.1.5528.30.100.230.3
NetBotz External Temperature 6 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 6 has returned to acceptable limits.
                                 netBotz_prd_bot_ext_temp6_sensor_unplugged 1.3.6.1.4.1.5528.30.100.230.6
NetBotz External Temperature 6 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
                                 netBotz_prd_bot_ext_temp6_sensor_replugged 1.3.6.1.4.1.5528.30.100.230.7
NetBotz External Temperature 6 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
                                 netBotz_prd_bot_ext_temp7_low_trap 1.3.6.1.4.1.5528.30.100.240.1
NetBotz External Temperature 7 Low Trap. This trap indicates that the lower limit for external temperature probe on port 7 has been exceeded.
                                 netBotz_prd_bot_ext_temp7_high_trap 1.3.6.1.4.1.5528.30.100.240.2
NetBotz External Temperature 7 High Trap. This trap indicates that the upper limit for external temperature probe on port 7 has been exceeded.
                                 netBotz_prd_bot_ext_temp7_trap_clear 1.3.6.1.4.1.5528.30.100.240.3
NetBotz External Temperature 7 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 7 has returned to acceptable limits.
                                 netBotz_prd_bot_ext_temp7_sensor_unplugged 1.3.6.1.4.1.5528.30.100.240.6
NetBotz External Temperature 7 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
                                 netBotz_prd_bot_ext_temp7_sensor_replugged 1.3.6.1.4.1.5528.30.100.240.7
NetBotz External Temperature 7 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
                                 netBotz_prd_bot_ext_dry5_triggered_trap 1.3.6.1.4.1.5528.30.100.250.2
NetBotz External Dry Contact 5 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext5 matches the alarm value.
                                 netBotz_prd_bot_ext_dry5_trap_clear 1.3.6.1.4.1.5528.30.100.250.3
NetBotz External Dry Contact 5 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext5 no longer matches the alarm value.
                                 netBotz_prd_bot_ext_dry6_triggered_trap 1.3.6.1.4.1.5528.30.100.260.2
NetBotz External Dry Contact 6 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext6 matches the alarm value.
                                 netBotz_prd_bot_ext_dry6_trap_clear 1.3.6.1.4.1.5528.30.100.260.3
NetBotz External Dry Contact 6 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext6 no longer matches the alarm value.
                                 netBotz_prd_bot_ext_dry7_triggered_trap 1.3.6.1.4.1.5528.30.100.270.2
NetBotz External Dry Contact 7 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext7 matches the alarm value.
                                 netBotz_prd_bot_ext_dry7_trap_clear 1.3.6.1.4.1.5528.30.100.270.3
NetBotz External Dry Contact 7 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext7 no longer matches the alarm value.
                                 netBotz_prd_bot_camera_motion_trap_tripped 1.3.6.1.4.1.5528.30.100.280.2
NetBotz Camera Motion Sensor Tripped Trap. This trap indicates that the camera motion sensor has been triggered (motion has been detected).
                                 netBotz_prd_bot_camera_motion_trap_clear 1.3.6.1.4.1.5528.30.100.280.3
NetBotz Camera Motion Cleared Trap. The trap has been cleared because the camera motion sensor has returned to normal (no longer is detecting motion).
                                 netBotz_prd_bot_ext_humi1_low_trap 1.3.6.1.4.1.5528.30.100.290.1
NetBotz External Humidity 1 Low Trap. This trap indicates that the lower limit for external humidity probe on port 1 has been exceeded.
                                 netBotz_prd_bot_ext_humi1_high_trap 1.3.6.1.4.1.5528.30.100.290.2
NetBotz External Humidity 1 High Trap. This trap indicates that the upper limit for external humidity probe on port 1 has been exceeded.
                                 netBotz_prd_bot_ext_humi1_trap_clear 1.3.6.1.4.1.5528.30.100.290.3
NetBotz External Humidity 1 Cleared Trap. The trap has been cleared because the humidity value for the humidity probe on port 1 has returned to acceptable limits.
                                 netBotz_prd_bot_ext_humi1_sensor_unplugged 1.3.6.1.4.1.5528.30.100.290.6
NetBotz External Humidity 1 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
                                 netBotz_prd_bot_ext_humi1_sensor_replugged 1.3.6.1.4.1.5528.30.100.290.7
NetBotz External Humidity 1 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
                                 netBotz_prd_bot_ext_humi2_low_trap 1.3.6.1.4.1.5528.30.100.300.1
NetBotz External Humidity 2 Low Trap. This trap indicates that the lower limit for external humidity probe on port 2 has been exceeded.
                                 netBotz_prd_bot_ext_humi2_high_trap 1.3.6.1.4.1.5528.30.100.300.2
NetBotz External Humidity 2 High Trap. This trap indicates that the upper limit for external humidity probe on port 2 has been exceeded.
                                 netBotz_prd_bot_ext_humi2_trap_clear 1.3.6.1.4.1.5528.30.100.300.3
NetBotz External Humidity 2 Cleared Trap. The trap has been cleared because the humidity value for the humidity probe on port 2 has returned to acceptable limits.
                                 netBotz_prd_bot_ext_humi2_sensor_unplugged 1.3.6.1.4.1.5528.30.100.300.6
NetBotz External Humidity 2 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
                                 netBotz_prd_bot_ext_humi2_sensor_replugged 1.3.6.1.4.1.5528.30.100.300.7
NetBotz External Humidity 2 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
                                 netBotz_prd_bot_ext_humi3_low_trap 1.3.6.1.4.1.5528.30.100.310.1
NetBotz External Humidity 3 Low Trap. This trap indicates that the lower limit for external humidity probe on port 3 has been exceeded.
                                 netBotz_prd_bot_ext_humi3_high_trap 1.3.6.1.4.1.5528.30.100.310.2
NetBotz External Humidity 3 High Trap. This trap indicates that the upper limit for external humidity probe on port 3 has been exceeded.
                                 netBotz_prd_bot_ext_humi3_trap_clear 1.3.6.1.4.1.5528.30.100.310.3
NetBotz External Humidity 3 Cleared Trap. The trap has been cleared because the humidity value for the humidity probe on port 3 has returned to acceptable limits.
                                 netBotz_prd_bot_ext_humi3_sensor_unplugged 1.3.6.1.4.1.5528.30.100.310.6
NetBotz External Humidity 3 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
                                 netBotz_prd_bot_ext_humi3_sensor_replugged 1.3.6.1.4.1.5528.30.100.310.7
NetBotz External Humidity 3 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
                                 netBotz_prd_bot_ext_humi4_low_trap 1.3.6.1.4.1.5528.30.100.320.1
NetBotz External Humidity 4 Low Trap. This trap indicates that the lower limit for external humidity probe on port 4 has been exceeded.
                                 netBotz_prd_bot_ext_humi4_high_trap 1.3.6.1.4.1.5528.30.100.320.2
NetBotz External Humidity 4 High Trap. This trap indicates that the upper limit for external humidity probe on port 4 has been exceeded.
                                 netBotz_prd_bot_ext_humi4_trap_clear 1.3.6.1.4.1.5528.30.100.320.3
NetBotz External Humidity 4 Cleared Trap. The trap has been cleared because the humidity value for the humidity probe on port 4 has returned to acceptable limits.
                                 netBotz_prd_bot_ext_humi4_sensor_unplugged 1.3.6.1.4.1.5528.30.100.320.6
NetBotz External Humidity 4 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
                                 netBotz_prd_bot_ext_humi4_sensor_replugged 1.3.6.1.4.1.5528.30.100.320.7
NetBotz External Humidity 4 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
                                 netBotz_prd_bot_ext_humi5_low_trap 1.3.6.1.4.1.5528.30.100.330.1
NetBotz External Humidity 5 Low Trap. This trap indicates that the lower limit for external humidity probe on port 5 has been exceeded.
                                 netBotz_prd_bot_ext_humi5_high_trap 1.3.6.1.4.1.5528.30.100.330.2
NetBotz External Humidity 5 High Trap. This trap indicates that the upper limit for external humidity probe on port 5 has been exceeded.
                                 netBotz_prd_bot_ext_humi5_trap_clear 1.3.6.1.4.1.5528.30.100.330.3
NetBotz External Humidity 5 Cleared Trap. The trap has been cleared because the humidity value for the humidity probe on port 5 has returned to acceptable limits.
                                 netBotz_prd_bot_ext_humi5_sensor_unplugged 1.3.6.1.4.1.5528.30.100.330.6
NetBotz External Humidity 5 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
                                 netBotz_prd_bot_ext_humi5_sensor_replugged 1.3.6.1.4.1.5528.30.100.330.7
NetBotz External Humidity 5 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
                                 netBotz_prd_bot_ext_humi6_low_trap 1.3.6.1.4.1.5528.30.100.340.1
NetBotz External Humidity 6 Low Trap. This trap indicates that the lower limit for external humidity probe on port 6 has been exceeded.
                                 netBotz_prd_bot_ext_humi6_high_trap 1.3.6.1.4.1.5528.30.100.340.2
NetBotz External Humidity 6 High Trap. This trap indicates that the upper limit for external humidity probe on port 6 has been exceeded.
                                 netBotz_prd_bot_ext_humi6_trap_clear 1.3.6.1.4.1.5528.30.100.340.3
NetBotz External Humidity 6 Cleared Trap. The trap has been cleared because the humidity value for the humidity probe on port 6 has returned to acceptable limits.
                                 netBotz_prd_bot_ext_humi6_sensor_unplugged 1.3.6.1.4.1.5528.30.100.340.6
NetBotz External Humidity 6 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
                                 netBotz_prd_bot_ext_humi6_sensor_replugged 1.3.6.1.4.1.5528.30.100.340.7
NetBotz External Humidity 6 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
                                 netBotz_prd_bot_ext_humi7_low_trap 1.3.6.1.4.1.5528.30.100.350.1
NetBotz External Humidity 7 Low Trap. This trap indicates that the lower limit for external humidity probe on port 7 has been exceeded.
                                 netBotz_prd_bot_ext_humi7_high_trap 1.3.6.1.4.1.5528.30.100.350.2
NetBotz External Humidity 7 High Trap. This trap indicates that the upper limit for external humidity probe on port 7 has been exceeded.
                                 netBotz_prd_bot_ext_humi7_trap_clear 1.3.6.1.4.1.5528.30.100.350.3
NetBotz External Humidity 7 Cleared Trap. The trap has been cleared because the humidity value for the humidity probe on port 7 has returned to acceptable limits.
                                 netBotz_prd_bot_ext_humi7_sensor_unplugged 1.3.6.1.4.1.5528.30.100.350.6
NetBotz External Humidity 7 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
                                 netBotz_prd_bot_ext_humi7_sensor_replugged 1.3.6.1.4.1.5528.30.100.350.7
NetBotz External Humidity 7 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
                 netBotz_prd_WallBotz_300 1.3.6.1.4.1.5528.30.1000
                 netBotz_prd_RackBotz_300 1.3.6.1.4.1.5528.30.1001
                 netBotz_prd_RackBotz_300U 1.3.6.1.4.1.5528.30.1002
                 netBotz_prd_WallBotz_400 1.3.6.1.4.1.5528.30.1003
                 netBotz_prd_RackBotz_400 1.3.6.1.4.1.5528.30.1004
                 netBotz_prd_RackBotz_303 1.3.6.1.4.1.5528.30.1006
                 netBotz_prd_WallBotz_310 1.3.6.1.4.1.5528.30.1007
                 netBotz_prd_RackBotz_310 1.3.6.1.4.1.5528.30.1008
                 netBotz_prd_WallBotz_300B 1.3.6.1.4.1.5528.30.1009
                 netBotz_prd_WallBotz_300C 1.3.6.1.4.1.5528.30.1100
                 netBotz_prd_RackBotz_300C 1.3.6.1.4.1.5528.30.1101
                 netBotz_prd_RackBotz_300UC 1.3.6.1.4.1.5528.30.1102
                 netBotz_prd_WallBotz_400C 1.3.6.1.4.1.5528.30.1103
                 netBotz_prd_RackBotz_400C 1.3.6.1.4.1.5528.30.1104
                 netBotz_prd_RackBotz_303C 1.3.6.1.4.1.5528.30.1106
                 netBotz_prd_WallBotz_310C 1.3.6.1.4.1.5528.30.1107
                 netBotz_prd_RackBotz_310C 1.3.6.1.4.1.5528.30.1108
                 netBotz_prd_WallBotz_300BC 1.3.6.1.4.1.5528.30.1109
                 netBotz_prd_WallBotz_300E 1.3.6.1.4.1.5528.30.1200
                 netBotz_prd_RackBotz_300E 1.3.6.1.4.1.5528.30.1201
                 netBotz_prd_RackBotz_300UE 1.3.6.1.4.1.5528.30.1202
                 netBotz_prd_WallBotz_400E 1.3.6.1.4.1.5528.30.1203
                 netBotz_prd_RackBotz_400E 1.3.6.1.4.1.5528.30.1204
                 netBotz_prd_RackBotz_303E 1.3.6.1.4.1.5528.30.1206
                 netBotz_prd_WallBotz_310E 1.3.6.1.4.1.5528.30.1207
                 netBotz_prd_RackBotz_310E 1.3.6.1.4.1.5528.30.1208
                 netBotz_prd_WallBotz_300BE 1.3.6.1.4.1.5528.30.1209
           expPortTable 1.3.6.1.4.1.5528.31 no-access
A list of expansion port entries.
                 expPortEntry 1.3.6.1.4.1.5528.31.1 no-access
An expansion port entry for a single port
                     expPort_module_id 1.3.6.1.4.1.5528.31.1.1 displaystring read-write
The module ID of the sensor module installed. Blank string indicates that no module is installed.
                     expPort_module_type 1.3.6.1.4.1.5528.31.1.2 displaystring read-write
The type of sensor module installed. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor.
                     expPort_label 1.3.6.1.4.1.5528.31.1.3 displaystring read-write
The label for the expansion port. Ports default to the label 'Extn', for port n.
                     expPort_amps 1.3.6.1.4.1.5528.31.1.20 integer read-only
The reading of the amperage probe, in milliamps.
                     expPort_total_amp_seconds 1.3.6.1.4.1.5528.31.1.21 integer read-only
The accumulated total of amp-seconds on the AmpDetect.
                     expPort_total_amp_seconds_since_time 1.3.6.1.4.1.5528.31.1.22 integer read-write
The UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect. Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time.
                     expPort_amps_enabled 1.3.6.1.4.1.5528.31.1.23 integer read-write
Amperage probe alarm enabled(1) or disabled(0).
                     expPort_amps_min 1.3.6.1.4.1.5528.31.1.24 integer read-write
The amperage probe minimum, from 0 to 30000 milliamps.
                     expPort_amps_max 1.3.6.1.4.1.5528.31.1.25 integer read-write
The amperage probe maximum, from 0 to 30000 milliamps.
                     expPort_amps_uV_per_10mA 1.3.6.1.4.1.5528.31.1.26 integer read-write
The scaling factor used for the amperage probe to convert microvolts measured from the Amp Detect into 10s of milliamps of current. Needs to be set based on the type of Amp Detect module installed.
                     expPort_amps_max_range 1.3.6.1.4.1.5528.31.1.27 integer read-write
The maximum RMS milliamps measureable by the AmpDetect.
                     expPort_ext_temp 1.3.6.1.4.1.5528.31.1.40 integer read-only
The reading of the external temperature probe, in degrees F or degrees C (depends on netBotz-ismetric).
                     expPort_ext_temp_enabled 1.3.6.1.4.1.5528.31.1.41 integer read-write
External temperature probe alarm enabled(1) or disabled(0).
                     expPort_ext_temp_min 1.3.6.1.4.1.5528.31.1.42 integer read-write
The external temperature probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).
                     expPort_ext_temp_max 1.3.6.1.4.1.5528.31.1.43 integer read-write
The external temperature probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).
                     expPort_ext_temp_uV_per_degreeC 1.3.6.1.4.1.5528.31.1.44 integer read-write
The scaling factor used for the external temperature probe to convert microvolts measured from the temperature sensor into degrees C. Needs to be set based on the type of temperature sensor module installed.
                     expPort_ext_temp_uV_at_0_degreeC 1.3.6.1.4.1.5528.31.1.45 integer read-write
The offset used for the external temperature probe of microvolts measured from the temperature sensor at zero degrees C. Needs to be set based on the type of temperature sensor module installed.
                     expPort_ext_temp_min_range 1.3.6.1.4.1.5528.31.1.46 integer read-write
The minimum temperature measureable by the temperature sensor, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installed.
                     expPort_ext_temp_max_range 1.3.6.1.4.1.5528.31.1.47 integer read-write
The maximum temperature measureable by the temperature sensor, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installed.
                     expPort_ext_dry 1.3.6.1.4.1.5528.31.1.60 integer read-only
The current value of the external dry contact sensor: 0=Open, 1=Closed, -1=N/A
                     expPort_ext_dry_alarm_value 1.3.6.1.4.1.5528.31.1.61 integer read-write
The value to generate alarms on for the external dry contact sensor: 0=Open, 1=Closed
                     expPort_ext_dry_enabled 1.3.6.1.4.1.5528.31.1.62 integer read-write
External dry contact sensor alarm enabled(1) or disabled(0).
                     expPort_ext_dry_label 1.3.6.1.4.1.5528.31.1.63 displaystring read-write
The sensor name/label for the dry contact sensor
                     expPort_ext_dry_open_label 1.3.6.1.4.1.5528.31.1.64 displaystring read-write
The sensor name/label for the open(0) state for the dry contact sensor
                     expPort_ext_dry_closed_label 1.3.6.1.4.1.5528.31.1.65 displaystring read-write
The sensor name/label for the closed(0) state for the dry contact sensor
                     expPort_ext_dry_open_to_close_millis 1.3.6.1.4.1.5528.31.1.66 integer read-write
The minimum number of milliseconds that the dry contact sensor must read closed before the state is changed from open to closed.
                     expPort_ext_dry_close_to_open_millis 1.3.6.1.4.1.5528.31.1.67 integer read-write
The minimum number of milliseconds that the dry contact sensor must read openbefore the state is changed from closed to open.
                     expPort_ext_dry_response 1.3.6.1.4.1.5528.31.1.68 displaystring read-write
The type of alert response for the dry contact sensor: ALERT=e-mail with no pictures, CAMERA=e-mail with pictures from camera.
                     expPort_ext_humi 1.3.6.1.4.1.5528.31.1.80 integer read-only
The reading of the external humidity probe, in percent.
                     expPort_ext_humi_enabled 1.3.6.1.4.1.5528.31.1.81 integer read-write
External humidity probe alarm enabled(1) or disabled(0).
                     expPort_ext_humi_min 1.3.6.1.4.1.5528.31.1.82 integer read-write
The external humidity probe minimum, in percent.
                     expPort_ext_humi_max 1.3.6.1.4.1.5528.31.1.83 integer read-write
The external humidity probe maximum, in percent.
                     expPort_ext_humi_uV_per_percent 1.3.6.1.4.1.5528.31.1.84 integer read-write
The scaling factor used for the external humidity probe to convert microvolts measured from the humidity sensor into percent. Needs to be set based on the type of humidity sensor module installed.
                     expPort_ext_humi_uV_at_0_percent 1.3.6.1.4.1.5528.31.1.85 integer read-write
The offset used for the external humidity probe of microvolts measured from the humidity sensor at zero percent. Needs to be set based on the type of humidity sensor module installed.
                     expPort_ext_humi_min_range 1.3.6.1.4.1.5528.31.1.86 integer read-write
The minimum humidity measureable by the humidity sensor, in percent. Needs to be set based on the type of humidity sensor module installed.
                     expPort_ext_humi_max_range 1.3.6.1.4.1.5528.31.1.87 integer read-write
The maximum humidity measureable by the humidity sensor, in percent. Needs to be set based on the type of humidity sensor module installed.
           netBotz_metric 1.3.6.1.4.1.5528.32
                 netBotz_metric_onboard 1.3.6.1.4.1.5528.32.10
                       netBotz_metric_onboard_model 1.3.6.1.4.1.5528.32.10.1 displaystring read-only
The model description of the appliance.
                       netBotz_metric_onboard_temp 1.3.6.1.4.1.5528.32.10.2 integer read-only
The reading of the built-in temperature probe, in tenths of a degree C.
                       netBotz_metric_onboard_humidity 1.3.6.1.4.1.5528.32.10.3 integer read-only
The reading of the built-in humidity probe, in percent.
                       netBotz_metric_onboard_airflow 1.3.6.1.4.1.5528.32.10.4 integer read-only
The reading of the built-in airflow probe, in meters/minute.
                       netBotz_metric_onboard_audio 1.3.6.1.4.1.5528.32.10.5 integer read-only
The reading of the built-in audio alarm probe on/off.
                       netBotz_metric_onboard_doorajar 1.3.6.1.4.1.5528.32.10.6 integer read-only
The reading of the door switch probe open(1) or closed(0).
                       netBotz_metric_onboard_temp_min 1.3.6.1.4.1.5528.32.10.7 integer read-only
The temperature probe minimum, from 1 to 50 degrees C in tenths of a degree C.
                       netBotz_metric_onboard_temp_max 1.3.6.1.4.1.5528.32.10.8 integer read-only
The temperature probe maximum, from 1 to 50 degrees C in tenths of a degree C.
                       netBotz_metric_onboard_humidity_min 1.3.6.1.4.1.5528.32.10.9 integer read-only
The humidity probe minimum, from 10 to 90 percent.
                       netBotz_metric_onboard_humidity_max 1.3.6.1.4.1.5528.32.10.10 integer read-only
The humidity probe maximum, from 10 to 90 percent.
                       netBotz_metric_onboard_airflow_mins 1.3.6.1.4.1.5528.32.10.11 integer read-only
Minutes without airflow before alarm set.
                       netBotz_metric_onboard_audio_secs 1.3.6.1.4.1.5528.32.10.12 integer read-only
Seconds of alarm audio before alarm set.
                       netBotz_metric_onboard_switch_state 1.3.6.1.4.1.5528.32.10.13 integer read-only
Switch state setting. The state controls which condition of the door switch indicates an alarm. If set to 0, alarm is set when the switch is closed. If set to 1, alarm is set when the switch is open.
                       netBotz_metric_onboard_audio_level 1.3.6.1.4.1.5528.32.10.14 integer read-only
Audio level setting, this is the relative audio level, from 0-11, above which an alarm will be sent.
                       netBotz_metric_onboard_airflow_level 1.3.6.1.4.1.5528.32.10.15 integer read-only
Airflow alert level. This is the level, in meters per second, below which an alarm will be sent.
                       netBotz_metric_onboard_cam_motion 1.3.6.1.4.1.5528.32.10.16 integer read-only
The current motion reading for the camera motion sensor (0=none, 1=motion detected, -1=not licensed).
                       netBotz_metric_onboard_cam_motion_sensitivity 1.3.6.1.4.1.5528.32.10.17 integer read-only
Camera motion sensor sensitivity: 1=max, 15=min, 0=disabled.
           netBotz_snmp 1.3.6.1.4.1.5528.40
                 netBotz_snmp_traptarget 1.3.6.1.4.1.5528.40.1 ipaddress read-write
Target of traps from the NetBotz device. This field contains the IP address where NetBotz traps are to be sent.
                 netBotz_snmp_community 1.3.6.1.4.1.5528.40.2 displaystring read-write
The read/write community of the NetBotz device.
                 netBotz_snmp_timeout 1.3.6.1.4.1.5528.40.3 integer read-write
SNMP Timeout period.
                 netBotz_snmp_retries 1.3.6.1.4.1.5528.40.4 integer read-write
SNMP Retry count.
                 netBotz_userid_1 1.3.6.1.4.1.5528.40.5 displaystring read-write
The userID of the supervisor account (write-only).
                 netBotz_password_1 1.3.6.1.4.1.5528.40.6 displaystring read-write
The password of the supervisor account (write-only).
                 netBotz_userid_2 1.3.6.1.4.1.5528.40.7 displaystring read-write
The userID of the full read access account (write-only).
                 netBotz_password_2 1.3.6.1.4.1.5528.40.8 displaystring read-write
The password of the full read access account (write-only).
                 netBotz_userid_3 1.3.6.1.4.1.5528.40.9 displaystring read-write
The userID of the minimum read access account (write-only).
                 netBotz_password_3 1.3.6.1.4.1.5528.40.10 displaystring read-write
The password of the minimum read access account (write-only).
                 netBotz_snmp_traptarget2 1.3.6.1.4.1.5528.40.11 ipaddress read-write
Second target of traps from the NetBotz device. This field contains an additional IP address where NetBotz traps are to be sent.
                 netBotz_snmp_read_community 1.3.6.1.4.1.5528.40.12 displaystring read-write
The read-only community of the NetBotz device.
           netBotz_device 1.3.6.1.4.1.5528.50
                 netBotz_dev_host 1.3.6.1.4.1.5528.50.1 displaystring read-write
NetBotz device's host name.
                 netBotz_dev_domain 1.3.6.1.4.1.5528.50.2 displaystring read-write
NetBotz device's default DNS domain.
                 netBotz_dev_ip 1.3.6.1.4.1.5528.50.3 ipaddress read-write
NetBotz device's IP address.
                 netBotz_dev_netmask 1.3.6.1.4.1.5528.50.4 ipaddress read-write
NetBotz device's netmask.
                 netBotz_dev_gateway 1.3.6.1.4.1.5528.50.5 ipaddress read-write
NetBotz device's default gateway/router. 0.0.0.0 if not defined.
                 netBotz_dev_primarydns 1.3.6.1.4.1.5528.50.6 ipaddress read-write
Primary Domain Name Server. 0.0.0.0 if not defined.
                 netBotz_dev_secondarydns 1.3.6.1.4.1.5528.50.7 ipaddress read-write
Secondary Domain Name Server. 0.0.0.0 if not defined.
                 netBotz_dev_smtp 1.3.6.1.4.1.5528.50.8 displaystring read-write
SMTP server address. This is the mail server used for sending alert e-mails.
                 netBotz_dev_smtpport 1.3.6.1.4.1.5528.50.9 integer read-write
SMTP port. Port number of SMTP server used for sending alert e-mails.
                 netBotz_dev_popport 1.3.6.1.4.1.5528.50.10 integer read-write
POP port. Currently, not used.
                 netBotz_dev_loglevel 1.3.6.1.4.1.5528.50.11 integer read-write
This field contains the log level of the NetBotz device. Log messages will be filtered, so that only same or lower-level messages will be passed. The default log level is 5, for warnings and lower levels. The log levels are the following: 1 - emergency 2 - alert 3 - critical 4 - error 5 - warning 6 - notice 7 - info 8 - trace
                 netBotz_dev_primaryemail 1.3.6.1.4.1.5528.50.14 displaystring read-write
The primary email addresses for alerts and messages (list separated by commas for multiple addresses).
                 netBotz_dev_secondaryemail 1.3.6.1.4.1.5528.50.15 displaystring read-write
The secondary email address for alerts and messages (list separated by commas for multiple addresses).
                 netBotz_dev_serialno 1.3.6.1.4.1.5528.50.17 displaystring read-only
The serial number of the NetBotz device.
                 netBotz_dev_pop 1.3.6.1.4.1.5528.50.18 displaystring read-write
POP server name. Currently, not used.
                 netBotz_dev_version 1.3.6.1.4.1.5528.50.19 displaystring read-only
The current NetBotz device firmware version.
                 netBotz_dev_registered 1.3.6.1.4.1.5528.50.20 integer read-only
Indicates if the device has been registered with NetBotz, Inc. 1=registered, 0=not registered.
                 netBotz_default_applet 1.3.6.1.4.1.5528.50.21 integer read-write
Setting to control if default web page should launch applet by default(1) or the HTML status page(0).
                 netBotz_guibar_color 1.3.6.1.4.1.5528.50.22 integer read-write
Setting for color of GUI bar (RGB). Value = 0xRRGGBB.
                 netBotz_locale 1.3.6.1.4.1.5528.50.23 displaystring read-write
The locale ID of the NetBotz device. Format is ISO 639 language (lower case), an underscore, and ISO 3166 country (upper case). Some locales are just the ISO 639 language code.
                 netBotz_timezone 1.3.6.1.4.1.5528.50.24 displaystring read-write
The timezone ID of the NetBotz device.
                 netBotz_24hourpreferred 1.3.6.1.4.1.5528.50.25 integer read-write
Indicates if 24-hour(1) versus 12-hour(0) time format is preferred.
                 netBotz_utc_clock 1.3.6.1.4.1.5528.50.26 integer read-write
Current time of clock on NetBotz device, in UTC seconds (seconds since 1/1/1970 12:00am GMT).
                 netBotz_ismetric 1.3.6.1.4.1.5528.50.27 integer read-only
Units are metric (1) or U.S. (0). Applies to temperature and airflow rate.
                 netBotz_alert_url 1.3.6.1.4.1.5528.50.28 displaystring read-write
The URL, if defined, to which non-picture alerts are HTTP POSTed
                 netBotz_picture_alert_url 1.3.6.1.4.1.5528.50.29 displaystring read-write
The URL, if defined, to which picture alerts are HTTP POSTed, using multipart/form-data encoding.
                 netBotz_sensor_data_url 1.3.6.1.4.1.5528.50.30 displaystring read-write
The URL, if defined, to which sensor data is periodically HTTP POSTed.
                 netBotz_alert_url_logon 1.3.6.1.4.1.5528.50.31 displaystring read-write
The user ID and password, if defined, used for POSTing non-picture alerts. Field is write-only, and formatted /
                 netBotz_picture_alert_url_logon 1.3.6.1.4.1.5528.50.32 displaystring read-write
The user ID and password, if defined, used for POSTing picture alerts. Field is write-only, and formatted /
                 netBotz_sensor_data_url_logon 1.3.6.1.4.1.5528.50.33 displaystring read-write
The user ID and password, if defined, used for POSTing sensor data. Field is write-only, and formatted /
                 netBotz_sensor_data_url_period 1.3.6.1.4.1.5528.50.34 integer read-write
Default number of minutes between periodic sensor data HTTP POSTs.
                 netBotz_sensor_data_url_flags 1.3.6.1.4.1.5528.50.35 integer read-write
Option flags for data POSTs of sensor data. Bit 0=1 if current picture should be included. Bits 1-31 are reserved.
                 netBotz_dev_backup_smtp 1.3.6.1.4.1.5528.50.36 displaystring read-write
Backup SMTP server address. This is the backup mail server used for sending alert e-mails.
                 netBotz_dev_tertiarydns 1.3.6.1.4.1.5528.50.37 ipaddress read-write
Tertiary Domain Name Server. 0.0.0.0 if not defined.
                 netBotz_dev_ntp_server 1.3.6.1.4.1.5528.50.38 displaystring read-write
NTP (Network Time Protocol) Server configured for appliance.
                 netBotz_dev_ntp_period 1.3.6.1.4.1.5528.50.39 integer read-write
Hours between automatic refreshes of the appliance clock using the NTP server.
                 netBotz_dev_socks_server 1.3.6.1.4.1.5528.50.40 displaystring read-write
Socks V4 or V5 proxy server configured for appliance.
                 netBotz_dev_socks_portnum 1.3.6.1.4.1.5528.50.41 integer read-write
Port number of Socks Proxy.
                 netBotz_dev_socks_user_id 1.3.6.1.4.1.5528.50.42 displaystring read-write
User ID for Socks V4 or V5 proxy server configured for appliance.
                 netBotz_dev_socks_password 1.3.6.1.4.1.5528.50.43 displaystring read-write
Password for Socks V4 or V5 proxy server configured for appliance.
                 netBotz_alert_ftp_site 1.3.6.1.4.1.5528.50.44 displaystring read-write
The hostname or dotted-decimal IP address of the FTP server to deliver alerts to
                 netBotz_alert_ftp_path 1.3.6.1.4.1.5528.50.45 displaystring read-write
The directory on the FTP server to store alerts in.
                 netBotz_alert_ftp_filename 1.3.6.1.4.1.5528.50.46 displaystring read-write
The base filename for the files on the FTP server to store alerts in.
                 netBotz_alert_ftp_logon 1.3.6.1.4.1.5528.50.47 displaystring read-write
The user-id and password on the FTP server to store alerts in. Field is write-only, and formatted /
                 netBotz_sensor_ftp_site 1.3.6.1.4.1.5528.50.48 displaystring read-write
The hostname or dotted-decimal IP address of the FTP server to deliver periodic sensor reports to
                 netBotz_sensor_ftp_path 1.3.6.1.4.1.5528.50.49 displaystring read-write
The directory on the FTP server to store periodic sensor reports in.
                 netBotz_sensor_ftp_filename 1.3.6.1.4.1.5528.50.50 displaystring read-write
The base filename for the files on the FTP server to store periodic sensor reports in.
                 netBotz_sensor_ftp_logon 1.3.6.1.4.1.5528.50.51 displaystring read-write
The user-id and password on the FTP server to store sensor reports in. Field is write-only, and formatted /
                 netBotz_sensor_ftp_period 1.3.6.1.4.1.5528.50.52 integer read-write
The period, in minutes, between delivery of sensor data reports.
                 netBotz_use_syslog 1.3.6.1.4.1.5528.50.53 integer read-write
Enable syslog
                 netBotz_syslog_address 1.3.6.1.4.1.5528.50.54 displaystring read-write
Host address to use for syslogging
                 netBotz_syslog_facility 1.3.6.1.4.1.5528.50.55 integer read-write
Syslog facility code
                 netBotz_color_balance 1.3.6.1.4.1.5528.50.56 displaystring read-write
Color balance for color camera. AUTO=automatic, FLUOR=fluorescent, DAY=daylight, INCAND=incandescent, x/y=Custom (scale red by x/64, scale blue by y/64)
           netBotz_addonapp 1.3.6.1.4.1.5528.60
                 device_crawlers_trap_target_index 1.3.6.1.4.1.5528.60.2
                 branch_checker_trap_target_index 1.3.6.1.4.1.5528.60.3
                 vendor_netBotz 1.3.6.1.4.1.5528.60.5528
                           device_crawlers_trap 1.3.6.1.4.1.5528.60.5528.2
                           branch_checker_trap 1.3.6.1.4.1.5528.60.5528.3
                                 netBotz_device_crawlers_value_low_alert_trap 1.3.6.1.4.1.5528.60.5528.20.1
NetBotz Device Crawlers Value Low Trap. This trap indicates that the lower limit on a monitored value has been exceeded.
                                 netBotz_device_crawlers_value_high_alert_trap 1.3.6.1.4.1.5528.60.5528.20.2
NetBotz Device Crawlers Value High Trap. This trap indicates that the upper limit on a monitored value has been exceeded.
                                 netBotz_device_crawlers_clear_alert_trap 1.3.6.1.4.1.5528.60.5528.20.3
NetBotz Device Crawlers Clear Trap. This trap indicates that the previous alert condition has been cleared.
                                 netBotz_device_crawlers_offline_alert_trap 1.3.6.1.4.1.5528.60.5528.20.4
NetBotz Device Crawlers Offline Trap. This trap indicates that a monitored target could not be contacted.
                                 netBotz_device_crawlers_online_alert_trap 1.3.6.1.4.1.5528.60.5528.20.5
NetBotz Device Crawlers Online Trap. This trap indicates that a monitored target that previously could not be contacted has now been contacted successfully.
                                 netBotz_device_crawlers_ifopstatus_alert_trap 1.3.6.1.4.1.5528.60.5528.20.8
NetBotz Device Crawlers Interface Operational Status Trap. This trap indicates that one or more of a monitored target's network interfaces operational status is not equal to the desired status.
                                 netBotz_branch_checker_clear_alert_trap 1.3.6.1.4.1.5528.60.5528.30.3
NetBotz Branch Checker Clear Trap. This trap indicates that the previous alert condition has been cleared.
                                 netBotz_branch_checker_offline_alert_trap 1.3.6.1.4.1.5528.60.5528.30.4
NetBotz Branch Checker Offline Trap. This trap indicates that a monitored target could not be contacted.
                                 netBotz_branch_checker_online_alert_trap 1.3.6.1.4.1.5528.60.5528.30.5
NetBotz Branch Checker Online Trap. This trap indicates that a monitored target that previously could not be contacted has now been contacted successfully.
                                 netBotz_branch_checker_target_error_trap 1.3.6.1.4.1.5528.60.5528.30.12
NetBotz Branch Target Error Trap. This trap indicates that a monitored target could be contacted, but not withing the timeout period specified.
           netBotz_addonapp_trap 1.3.6.1.4.1.5528.61
                 device_crawlers_trap_attrib 1.3.6.1.4.1.5528.61.2
                     device_crawlers_trap_index 1.3.6.1.4.1.5528.61.2.20 integer read-only
The ID of the device crawler which sent the last trap.
                     device_crawlers_trap_address 1.3.6.1.4.1.5528.61.2.21 ipaddress read-only
The IP address of the appliance actually creating the last trap.
                     device_crawlers_trap_oid 1.3.6.1.4.1.5528.61.2.22 object identifier read-only
The object id of the attribute on the device crawlers target device which is the concern of the last trap. The second to last element indicates the index of the source of the problem (1=ICMP Ping, 2=SNMP Agent Status, 256-10239=Network Interfaces 1-9984, 10240 and above, indicates Advanced crawlers data). The last element is the decimal representation of the IP address of the source of the problem.
                     device_crawlers_trap_botoid 1.3.6.1.4.1.5528.61.2.23 object identifier read-only
The object id of the device crawlers attribute on the NetBotz device which is the concern of the last trap.
                     device_crawlers_trap_value 1.3.6.1.4.1.5528.61.2.24 integer read-only
The integer value of the device crawlers attribute associated with the last trap.
                     device_crawlers_trap_stringvalue 1.3.6.1.4.1.5528.61.2.25 displaystring read-only
The string representation of the value of the device crawlers attribute associated with the last trap.
                     device_crawlers_trap_date 1.3.6.1.4.1.5528.61.2.26 integer read-only
The date and time of a specific device crawlers trap. This field contains the number of seconds elapsed since midnight (00:00:00), January 1, 1970
                     device_crawlers_trap_attrib_index 1.3.6.1.4.1.5528.61.2.27 integer read-only
The identification number of the device crawlers attribute in error
                     device_crawlers_crawlers_trap_desc 1.3.6.1.4.1.5528.61.2.28 displaystring read-only
Description of the Device Crawlers Trap Attribute
                 branch_checker_trap_attrib 1.3.6.1.4.1.5528.61.3
                     branch_checker_trap_index 1.3.6.1.4.1.5528.61.3.20 integer read-only
The ID of the branch checker which sent the last trap.
                     branch_checker_trap_address 1.3.6.1.4.1.5528.61.3.21 ipaddress read-only
The IP address of the appliance actually creating the last trap.
                     branch_checker_trap_oid 1.3.6.1.4.1.5528.61.3.22 object identifier read-only
The object id of the attribute on the branch checker target device which is the concern of the last trap The second to last element is the index of the source of the problem (256-260=SMTP Server, 1024-1026=DNS Server, 1536-1538=Web Server, 2048-2052=Generic Server). The last element is the decimal representation of the IP address of the source of the problem.
                     branch_checker_trap_botoid 1.3.6.1.4.1.5528.61.3.23 object identifier read-only
The object id of the branch checker attribute on the NetBotz device which is the concern of the last trap. The second to last element is the index of the source of the problem (256-260=SMTP Server, 1024-1026=DNS Server, 1536-1538=Web Server, 2048-2052=Generic Server). The last element is the decimal representation of the IP address of the source of the problem.
                     branch_checker_trap_value 1.3.6.1.4.1.5528.61.3.24 integer read-only
The integer value of the branch checker attribute associated with the last trap.
                     branch_checker_trap_stringvalue 1.3.6.1.4.1.5528.61.3.25 displaystring read-only
The string representation of the value of the branch checker attribute associated with the last trap.
                     branch_checker_trap_date 1.3.6.1.4.1.5528.61.3.26 integer read-only
The date and time of a specific branch checker trap. This field contains the number of seconds elapsed since midnight (00:00:00), January 1, 1970
                     branch_checker_trap_attrib_index 1.3.6.1.4.1.5528.61.3.27 integer read-only
The identification number of the branch checker attribute in error
                     branch_checker_trap_desc 1.3.6.1.4.1.5528.61.3.28 displaystring read-only
Description of the Branch Checker Trap Attribute