LHX-MIB: View SNMP OID List / Download MIB

VENDOR: RARITAN COMPUTER


 Home MIB: LHX-MIB
Download as:   

Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 raritan 1.3.6.1.4.1.13742
This MIB describes the SNMP functions of the Schroff Varistar LHX heat exchanger supported by Raritan devices.
             lhxgw 1.3.6.1.4.1.13742.9
                 traps 1.3.6.1.4.1.13742.9.0
                     trapInformation 1.3.6.1.4.1.13742.9.0.0
                         deviceName 1.3.6.1.4.1.13742.9.0.0.1 displaystring no-access
The user-defined name for the Device.
                         deviceInetAddressType 1.3.6.1.4.1.13742.9.0.0.2 inetaddresstype no-access
The type of address format
                         deviceInetIPAddress 1.3.6.1.4.1.13742.9.0.0.3 inetaddress no-access
The current IP address. A value of 0.0.0.0 indicates an error or an unset option.
                         lhxErrorCode 1.3.6.1.4.1.13742.9.0.0.4 displaystring no-access
The LHX error code (F1 - F25, EP).
                         portId 1.3.6.1.4.1.13742.9.0.0.5 integer32 no-access
A unique value for the physical port, the LHX controlller is connected to. Its value ranges between 1 and the value of portCount.
                         probeId 1.3.6.1.4.1.13742.9.0.0.6 displaystring no-access
The physical Sensor ID (F1 - F7).
                         fanId 1.3.6.1.4.1.13742.9.0.0.7 displaystring no-access
The Fan ID (M1 - M6).
                         powerSupplyId 1.3.6.1.4.1.13742.9.0.0.8 displaystring no-access
The Power Supply ID (1, 2).
                         oldSensorState 1.3.6.1.4.1.13742.9.0.0.9 sensorstateenumeration no-access
The old sensor state used in Sensor State Transition traps.
                         sensorTypeId 1.3.6.1.4.1.13742.9.0.0.10 gwsensortypeenumeration no-access
A unique value for the type of sensor.
                         sensorId 1.3.6.1.4.1.13742.9.0.0.11 integer32 no-access
A unique value for each sensor. Its value ranges between 1 and the value of sensorCount.
                         oldOperationalState 1.3.6.1.4.1.13742.9.0.0.12 operationalstateenumeration read-only
The old operational state used in Operational State Transition traps.
                         agentInetPortNumber 1.3.6.1.4.1.13742.9.0.0.13 inetportnumber no-access
The UDP port number used for accessing the SNMP agent on the device. Examples: If the associated device MIB (PX2-MIB, EMD-MIB) has deviceCascadeType set to portForwarding, then master: 50500 slave 1:50501 slave 2: 50502 ...... If cascading mode is not portForwarding and default (Standard) ports are being used, then port: 161
                     lhxSensorFailure 1.3.6.1.4.1.13742.9.0.1
A sensor failure (broken or short circuit) occurred.
                     lhxFanFailure 1.3.6.1.4.1.13742.9.0.2
A fan motor failure occurred.
                     lhxPowerSupplyFailure 1.3.6.1.4.1.13742.9.0.3
A power supply failure occurred.
                     lhxThresholdAirOutlet 1.3.6.1.4.1.13742.9.0.4
The air outlet temperature threshold was crossed.
                     lhxThresholdAirInlet 1.3.6.1.4.1.13742.9.0.5
The air inlet temperature threshold was crossed.
                     lhxThresholdWaterInlet 1.3.6.1.4.1.13742.9.0.6
The water inlet temperature threshold was crossed.
                     lhxDoorOpened 1.3.6.1.4.1.13742.9.0.7
The door was opened.
                     lhxMaximumCoolingRequest 1.3.6.1.4.1.13742.9.0.8
Maximum cooling was requested.
                     lhxEmergencyCooling 1.3.6.1.4.1.13742.9.0.9
Emergency cooling was activated.
                     lhxWaterLeak 1.3.6.1.4.1.13742.9.0.10
Water leakage was detected.
                     lhxThresholdHumidity 1.3.6.1.4.1.13742.9.0.11
The humidity threshold was crossed.
                     lhxExternalWaterCoolingFailure 1.3.6.1.4.1.13742.9.0.12
An external water cooling failure occurred.
                     lhxThresholdWaterOutlet 1.3.6.1.4.1.13742.9.0.13
The water outlet temperature threshold was crossed.
                     lhxParameterDataLoss 1.3.6.1.4.1.13742.9.0.14
Data loss in parameter memory was detected.
                     lhxStBusError 1.3.6.1.4.1.13742.9.0.15
An ST-Bus communication error was detected.
                     lhxCollectiveFault 1.3.6.1.4.1.13742.9.0.16
An error was detected.
                     gwSensorStateChange 1.3.6.1.4.1.13742.9.0.17
Sensor State Change.
                     gwLhxOperationalStateChange 1.3.6.1.4.1.13742.9.0.18
Operational State Change.
                     lhxVoltageLow 1.3.6.1.4.1.13742.9.0.19
The supply voltage of an LHX became low.
                     lhxBaseElectronicsFailure 1.3.6.1.4.1.13742.9.0.20
The base electronics of an LHX controller failed.
                     lhxCondenserPumpFailure 1.3.6.1.4.1.13742.9.0.21
An LHX condenser pump failed.
                 configuration 1.3.6.1.4.1.13742.9.1
                     portCount 1.3.6.1.4.1.13742.9.1.1 integer32 read-only
The number of lhx units supported.
                     sensorCountTable 1.3.6.1.4.1.13742.9.1.2 no-access
A list of lhx sensor count extries.
                         sensorCountEntry 1.3.6.1.4.1.13742.9.1.2.1 no-access
An entry containing the number of lhx sensors of a certain type.
                             sensorCount 1.3.6.1.4.1.13742.9.1.2.1.1 integer32 read-only
The number of sensors.
                     lhx 1.3.6.1.4.1.13742.9.1.3
                         lhxConfigurationTable 1.3.6.1.4.1.13742.9.1.3.1 no-access
A list of lhx controller configuration extries. The number of entries is given by the value of portCount.
                             lhxConfigurationEntry 1.3.6.1.4.1.13742.9.1.3.1.1 no-access
An entry containing parameters for an lhx.
                                 operationalState 1.3.6.1.4.1.13742.9.1.3.1.1.1 operationalstateenumeration read-write
The operational state of the lhx controller. To switch LHX power state while controller is connected, set operationalState to 1 (off) or 2 (on). Switching power state while LHX is disconnected or to 0 (disconnected) is undefined.
                                 setpointVentilators 1.3.6.1.4.1.13742.9.1.3.1.1.2 integer32 read-write
The setpoint of the ventilators.
                                 setpointWaterValve 1.3.6.1.4.1.13742.9.1.3.1.1.3 integer32 read-write
The setpoint of the water valve.
                                 defaultFanSpeed 1.3.6.1.4.1.13742.9.1.3.1.1.4 integer32 read-write
The 'default' fan speed during normal operation in per mill. Default is 80% (= 800).
                                 maximumCoolingState 1.3.6.1.4.1.13742.9.1.3.1.1.5 truthvalue read-write
Indicates whether maximum cooling was requested or not. To request maximum cooling, set maximumCoolingState to 1 (true). Setting maximumCoolingState to 2 (false) is undefined, set alertState to 2 (false) instead.
                                 alertState 1.3.6.1.4.1.13742.9.1.3.1.1.6 truthvalue read-write
Indicates whether LHX controler is in alert state or not. To acknowledge alert status, set alertState to 2 (false). Setting alertState to 1 (true) is undefined.
                                 model 1.3.6.1.4.1.13742.9.1.3.1.1.7 displaystring read-only
The model indentifier of an LHX controller.
                                 fwVersion 1.3.6.1.4.1.13742.9.1.3.1.1.8 displaystring read-only
The firmware version of an LHX controller.
                     gwSensors 1.3.6.1.4.1.13742.9.1.4
                         sensorConfigurationTable 1.3.6.1.4.1.13742.9.1.4.1 no-access
A list of lhx sensor configuration extries. The number of entries is given by the value of portCount.
                             sensorConfigurationEntry 1.3.6.1.4.1.13742.9.1.4.1.1 no-access
An entry containing parameters for an lhx.
                                 portIdx 1.3.6.1.4.1.13742.9.1.4.1.1.1 integer32 no-access
A unique value for each port. Its value ranges between 1 and the value of portCount.
                                 sensorTypeIdx 1.3.6.1.4.1.13742.9.1.4.1.1.2 integer32 no-access
A unique value for the type of sensor.
                                 sensorIdx 1.3.6.1.4.1.13742.9.1.4.1.1.3 integer32 no-access
A unique value for each sensor. Its value ranges between 1 and the value of sensorCount.
                                 sensorLabel 1.3.6.1.4.1.13742.9.1.4.1.1.4 displaystring read-only
The short ID of the sensor (e.g. F1, M2).
                                 sensorUnit 1.3.6.1.4.1.13742.9.1.4.1.1.5 sensorunitsenumeration read-only
The base units. This parameter does not apply to state sensors.
                                 sensorDecimalDigits 1.3.6.1.4.1.13742.9.1.4.1.1.6 unsigned32 read-only
The number of digits displayed to the right of the decimal point. This parameter does not apply to state sensors.
                                 sensorMaximum 1.3.6.1.4.1.13742.9.1.4.1.1.7 integer32 read-only
The largest possible value. The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to state sensors.
                                 sensorMinimum 1.3.6.1.4.1.13742.9.1.4.1.1.8 integer32 read-only
The smallest possible value. The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to state sensors.
                                 sensorHysteresis 1.3.6.1.4.1.13742.9.1.4.1.1.9 unsigned32 read-write
The hysteresis used for deassertions. The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to state sensors.
                                 sensorLowerCriticalThreshold 1.3.6.1.4.1.13742.9.1.4.1.1.10 integer32 read-write
The lower critical threshold. The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to state sensors.
                                 sensorLowerWarningThreshold 1.3.6.1.4.1.13742.9.1.4.1.1.11 integer32 read-write
The lower non-critical (warning) threshold. The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to state sensors.
                                 sensorUpperCriticalThreshold 1.3.6.1.4.1.13742.9.1.4.1.1.12 integer32 read-write
The upper critical threshold. The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to state sensors.
                                 sensorUpperWarningThreshold 1.3.6.1.4.1.13742.9.1.4.1.1.13 integer32 read-write
The upper non-critical (warning) threshold. The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to state sensors.
                                 sensorEnabledThresholds 1.3.6.1.4.1.13742.9.1.4.1.1.14 bits read-write
A bit string which indicates which thresholds are enabled. This parameter does not apply to state sensors. Bits: 'lowerWarning': 1, 'upperCritical': 3, 'upperWarning': 2, 'lowerCritical': 0.
                                 sensorThresholdMaximum 1.3.6.1.4.1.13742.9.1.4.1.1.15 integer32 read-only
The largest possible threshold value. The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to state sensors.
                                 sensorThresholdMinimum 1.3.6.1.4.1.13742.9.1.4.1.1.16 integer32 read-only
The smallest possible threshold value. The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to state sensors.
                                 sensorName 1.3.6.1.4.1.13742.9.1.4.1.1.17 displaystring read-only
The descriptive ID of the sensor (e.g. Fan Speed 1).
                 measurements 1.3.6.1.4.1.13742.9.2
                     sensorMeasurementsTable 1.3.6.1.4.1.13742.9.2.1 no-access
A list of external sensor entries. The number of entries is given by the value of sensorCount for the LHX.
                         sensorMeasurementsEntry 1.3.6.1.4.1.13742.9.2.1.1 no-access
An entry containing measurement objects for an external sensor.
                             measurementsSensorIsAvailable 1.3.6.1.4.1.13742.9.2.1.1.1 truthvalue read-only
Is the sensor available?
                             measurementsSensorState 1.3.6.1.4.1.13742.9.2.1.1.2 sensorstateenumeration read-only
The sensor state.
                             measurementsSensorValue 1.3.6.1.4.1.13742.9.2.1.1.3 integer32 read-only
The sensor reading. This parameter does not apply to state sensors.
                             measurementsSensorTimeStamp 1.3.6.1.4.1.13742.9.2.1.1.4 unsigned32 read-only
The sensor reading timestamp.
                 conformance 1.3.6.1.4.1.13742.9.3
                     compliances 1.3.6.1.4.1.13742.9.3.1
                         complianceRev1 1.3.6.1.4.1.13742.9.3.1.1
The requirements for conformance to the LHX-MIB.
                     groups 1.3.6.1.4.1.13742.9.3.2
                         configurationGroup 1.3.6.1.4.1.13742.9.3.2.1
A collection of objects representing configuration data.
                         measurementsGroup 1.3.6.1.4.1.13742.9.3.2.2
A collection of objects providing the measurement capability of LHX.
                         trapInformationGroup 1.3.6.1.4.1.13742.9.3.2.3
A collection of objects providing information in the traps.
                         trapsGroup 1.3.6.1.4.1.13742.9.3.2.4
A collection of traps.