KELVIN-pCOWeb-Chiller-MIB: View SNMP OID List / Download MIB

VENDOR: CAREL


 Home MIB: KELVIN-pCOWeb-Chiller-MIB
Download as:   

Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 carel 1.3.6.1.4.1.9839
           systm 1.3.6.1.4.1.9839.1
               agentRelease 1.3.6.1.4.1.9839.1.1 integer32 read-only
Release of the Agent.
               agentCode 1.3.6.1.4.1.9839.1.2 integer32 read-only
Code of the Agent. 2=pCOWeb.
           instruments 1.3.6.1.4.1.9839.2
               pCOWebInfo 1.3.6.1.4.1.9839.2.0
                   pCOStatusgroup 1.3.6.1.4.1.9839.2.0.10
                         pCOId1_Status 1.3.6.1.4.1.9839.2.0.10.1 integer32 read-only
Status of pCOId1. 0=Offline, 1=Init, 2=Online
                   pCOErrorsNumbergroup 1.3.6.1.4.1.9839.2.0.11
                         pCOId1_ErrorsNumber 1.3.6.1.4.1.9839.2.0.11.1 integer32 read-only
Number of Communication Errors from pCOId1 to pCOWeb.
               kelvin_pCOWebMIB_Chiller 1.3.6.1.4.1.9839.2.1
This is the MIB module for the kelvin-pCOWeb-Chiller device.
                   digitalObjects 1.3.6.1.4.1.9839.2.1.1
                       al_pa1 1.3.6.1.4.1.9839.2.1.1.1 integer32 read-only
High pressure switch 1 alarm
                       al_pa2 1.3.6.1.4.1.9839.2.1.1.2 integer32 read-only
High pressure switch 2 alarm
                       al_pb1 1.3.6.1.4.1.9839.2.1.1.3 integer32 read-only
Low pressure switch 1 alarm
                       al_pb2 1.3.6.1.4.1.9839.2.1.1.4 integer32 read-only
Low pressure switch 2 alarm
                       al_le 1.3.6.1.4.1.9839.2.1.1.6 integer32 read-only
Water level alarm
                       al_idrofrigo_fl1 1.3.6.1.4.1.9839.2.1.1.8 integer32 read-only
Flow switch alarm
                       static_press_alarm 1.3.6.1.4.1.9839.2.1.1.9 integer32 read-only
Water static pressure alarm
                       w_static_press_alarm 1.3.6.1.4.1.9839.2.1.1.10 integer32 read-only
Water static pressure warning
                       flow_value_alarm 1.3.6.1.4.1.9839.2.1.1.11 integer32 read-only
Flow rate alarm
                       al_q_comp1 1.3.6.1.4.1.9839.2.1.1.12 integer32 read-only
Overload compressor 1 circuit 1 alarm
                       al_q_comp2 1.3.6.1.4.1.9839.2.1.1.13 integer32 read-only
Overload compressor 2 circuit 1 alarm
                       al_q_comp3 1.3.6.1.4.1.9839.2.1.1.14 integer32 read-only
Overload compressor 3 circuit 1 alarm
                       al_q_comp4 1.3.6.1.4.1.9839.2.1.1.15 integer32 read-only
Overload compressor 1 circuit 2 alarm
                       al_q_comp5 1.3.6.1.4.1.9839.2.1.1.16 integer32 read-only
Overload compressor 2 circuit 2 alarm
                       al_q_comp6 1.3.6.1.4.1.9839.2.1.1.17 integer32 read-only
Overload compressor 3 circuit 2 alarm
                       al_q_fan_1 1.3.6.1.4.1.9839.2.1.1.18 integer32 read-only
Overload fans circuit 1
                       al_q_fan_2 1.3.6.1.4.1.9839.2.1.1.19 integer32 read-only
Overload fans circuit 2
                       al_q_fan11 1.3.6.1.4.1.9839.2.1.1.20 integer32 read-only
Overload fan 1 circuit 1 alarm
                       al_q_fan12 1.3.6.1.4.1.9839.2.1.1.21 integer32 read-only
Overload fan 2 circuit 1 alarm
                       al_q_fan13 1.3.6.1.4.1.9839.2.1.1.22 integer32 read-only
Overload fan 3 circuit 1 alarm
                       al_q_fan14 1.3.6.1.4.1.9839.2.1.1.23 integer32 read-only
Overload fan 4 circuit 1 alarm
                       al_q_fan21 1.3.6.1.4.1.9839.2.1.1.24 integer32 read-only
Overload fan 1 circuit 2 alarm
                       al_q_fan22 1.3.6.1.4.1.9839.2.1.1.25 integer32 read-only
Overload fan 2 circuit 2 alarm
                       al_q_fan_23 1.3.6.1.4.1.9839.2.1.1.26 integer32 read-only
Overload fan 3 circuit 2 alarm
                       al_q_fan24 1.3.6.1.4.1.9839.2.1.1.27 integer32 read-only
Overload fan 4 circuit 2 alarm
                       al_idrofrigo_pump1 1.3.6.1.4.1.9839.2.1.1.28 integer32 read-only
Overload pump 1 alarm
                       al_idrofrigo_pump2 1.3.6.1.4.1.9839.2.1.1.29 integer32 read-only
Overload pump 2 alarm
                       al_phase_cont 1.3.6.1.4.1.9839.2.1.1.30 integer32 read-only
Wrong phase rotation alarm
                       al_door_sw 1.3.6.1.4.1.9839.2.1.1.31 integer32 read-only
Back Door open alarm
                       compressor_FlowRate 1.3.6.1.4.1.9839.2.1.1.32 integer32 read-write
Compressor FlowRate Management
                       setpoint_inv_pumps 1.3.6.1.4.1.9839.2.1.1.33 integer32 read-write
Setpoint Type for Inverter pumps
                       enable_pumps_redundance 1.3.6.1.4.1.9839.2.1.1.34 integer32 read-write
Enable Pumps redundance
                       enable_chiller_redundance 1.3.6.1.4.1.9839.2.1.1.35 integer32 read-write
Enable Chiller redundance
                       status_in_alarm 1.3.6.1.4.1.9839.2.1.1.36 integer32 read-write
Status in alarm
                       compressor_recovery 1.3.6.1.4.1.9839.2.1.1.37 integer32 read-write
Compressor Recovery
                       enable_thermal_redundance 1.3.6.1.4.1.9839.2.1.1.38 integer32 read-write
Enable Thermal redundance
                       enable_multi_pumps_function 1.3.6.1.4.1.9839.2.1.1.39 integer32 read-write
Enable multi-pumps function
                       enable_pumps_offline 1.3.6.1.4.1.9839.2.1.1.40 integer32 read-write
Enable function pumps-Offline
                       enable_3way_valve 1.3.6.1.4.1.9839.2.1.1.41 integer32 read-write
Enable 3way valve
                       enable_speed_up_FCM 1.3.6.1.4.1.9839.2.1.1.42 integer32 read-write
Enable speed-up FCM
                       enable_soft_start_FCM 1.3.6.1.4.1.9839.2.1.1.43 integer32 read-write
Enable soft-start FCM
                       enable_freecooling 1.3.6.1.4.1.9839.2.1.1.44 integer32 read-write
Enable Freecooling
                       enable_rot_FIFO_FC 1.3.6.1.4.1.9839.2.1.1.45 integer32 read-write
Enable rotation FIFO Freecooling
                       enable_HT_function 1.3.6.1.4.1.9839.2.1.1.46 integer32 read-write
Enable HT-function
                       enable_PID_Fc_valve 1.3.6.1.4.1.9839.2.1.1.47 integer32 read-write
Enable PID-regulation for Freecooling valve
                       enable_Fc_Thermal_Exclusion 1.3.6.1.4.1.9839.2.1.1.48 integer32 read-write
Enable Freecooling Thermal Exclusion
                       manual_Reset_Ext_Drycooler_Alarm 1.3.6.1.4.1.9839.2.1.1.49 integer32 read-write
Manual Reset External Dry-cooler Alarm
                       enable_static_press_Alarm 1.3.6.1.4.1.9839.2.1.1.50 integer32 read-write
Enable static pressure Alarm
                       manual_reset_static_press_Alarm 1.3.6.1.4.1.9839.2.1.1.51 integer32 read-write
Manual reset static pressure Alarm
                       enable_static_press_Warning 1.3.6.1.4.1.9839.2.1.1.52 integer32 read-write
Enable static pressure Warning
                       manual_reset_static_press_Warning 1.3.6.1.4.1.9839.2.1.1.53 integer32 read-write
Manual reset static pressure Warning
                       enable_diff_press_Alarm 1.3.6.1.4.1.9839.2.1.1.54 integer32 read-write
Enable differential pressure Alarm
                       manual_reset_diff_press_Alarm 1.3.6.1.4.1.9839.2.1.1.55 integer32 read-write
Manual reset differential pressure Alarm
                       enable_pressure_recovery 1.3.6.1.4.1.9839.2.1.1.56 integer32 read-write
Enable pressure recovery
                       enable_Flow_Rate_Alarm 1.3.6.1.4.1.9839.2.1.1.57 integer32 read-write
Enable Flow-Rate Alarm
                       manual_reset_Flow_Rate_Alarm 1.3.6.1.4.1.9839.2.1.1.58 integer32 read-write
Manual reset Flow-Rate Alarm
                       enable_Flow_Rate_recovery 1.3.6.1.4.1.9839.2.1.1.59 integer32 read-write
Enable Flow-Rate recovery
                       enable_pCOWeb 1.3.6.1.4.1.9839.2.1.1.60 integer32 read-write
Enable pCOWeb
                       fc_single_chiller 1.3.6.1.4.1.9839.2.1.1.61 integer32 read-write
Freecooling single chiller function
                       al_idrofrigo_pump_c_1 1.3.6.1.4.1.9839.2.1.1.75 integer32 read-only
Condensation pump 1 breaker switch alarm
                       al_idrofrigo_pump_c_2 1.3.6.1.4.1.9839.2.1.1.76 integer32 read-only
Condensation pump 2 breaker switch alarm
                       al_idrofrigo_fl_C 1.3.6.1.4.1.9839.2.1.1.80 integer32 read-only
Condensation flow switch alarm
                       c11_on 1.3.6.1.4.1.9839.2.1.1.100 integer32 read-only
Compressor 1 circuit 1 ON
                       c12_on 1.3.6.1.4.1.9839.2.1.1.101 integer32 read-only
Compressor 2 circuit 1 ON
                       c13_on 1.3.6.1.4.1.9839.2.1.1.102 integer32 read-only
Compressor 3 circuit 1 ON
                       c21_on 1.3.6.1.4.1.9839.2.1.1.103 integer32 read-only
Compressor 1 circuit 2 ON
                       c22_on 1.3.6.1.4.1.9839.2.1.1.104 integer32 read-only
Compressor 2 circuit 2 ON
                       c23_on 1.3.6.1.4.1.9839.2.1.1.105 integer32 read-only
Compressor 3 circuit 2 ON
                       pump1_on 1.3.6.1.4.1.9839.2.1.1.106 integer32 read-only
Pump 1 ON
                       pump2_on 1.3.6.1.4.1.9839.2.1.1.107 integer32 read-only
Pump 2 ON
                       on_fan_gr1 1.3.6.1.4.1.9839.2.1.1.108 integer32 read-only
Fans group 1 ON
                       on_fan_gr2 1.3.6.1.4.1.9839.2.1.1.109 integer32 read-only
Fans group 2 ON
                       fc_on 1.3.6.1.4.1.9839.2.1.1.110 integer32 read-only
Freecooling or external dry-cooler 1 ON
                       en_on_off_rem 1.3.6.1.4.1.9839.2.1.1.130 integer32 read-write
Remote on-off
                       unit_on 1.3.6.1.4.1.9839.2.1.1.131 integer32 read-write
Chiller ON
                       disch_alarm_scw_1 1.3.6.1.4.1.9839.2.1.1.148 integer32 read-only
Discharge screw compressor 1 alarm
                       disch_alarm_scw_2 1.3.6.1.4.1.9839.2.1.1.149 integer32 read-only
Discharge screw compressor 2 alarm
                       al_probe_inlet 1.3.6.1.4.1.9839.2.1.1.150 integer32 read-only
Inlet probe alarm (broken or disconnected)
                       al_probe_amb 1.3.6.1.4.1.9839.2.1.1.151 integer32 read-only
Ambient probe alarm (broken or disconnected)
                       al_frigo_fl1 1.3.6.1.4.1.9839.2.1.1.152 integer32 read-only
Flow switch alarm (cooling alarm)
                       al_idro_pump1 1.3.6.1.4.1.9839.2.1.1.153 integer32 read-only
Pump 1 hydraulic alarm
                       al_idro_pump2 1.3.6.1.4.1.9839.2.1.1.154 integer32 read-only
Pump 2 hydraulic alarm
                       al_idro_fl1 1.3.6.1.4.1.9839.2.1.1.155 integer32 read-only
Flow switch alarm (hydraulic alarm)
                       al_warning_fl1 1.3.6.1.4.1.9839.2.1.1.156 integer32 read-only
Flow switch alarm (warning alarm)
                       al_hi_water_temp 1.3.6.1.4.1.9839.2.1.1.157 integer32 read-only
High Temperature alarm
                       al_lo_water_temp 1.3.6.1.4.1.9839.2.1.1.158 integer32 read-only
Low Temperature alarm
                       al_ta_probe1 1.3.6.1.4.1.9839.2.1.1.159 integer32 read-only
Antifreeze/evaporator probe 1 alarm
                       al_hi_press 1.3.6.1.4.1.9839.2.1.1.160 integer32 read-only
High condensation pressure alarm
                       al_lo_press 1.3.6.1.4.1.9839.2.1.1.161 integer32 read-only
Low condensation pressure alarm
                       al_probe_evap_1 1.3.6.1.4.1.9839.2.1.1.162 integer32 read-only
Antifreeze/evaporator probe 1 alarm (broken or disconnected)
                       al_probe_evap_2 1.3.6.1.4.1.9839.2.1.1.163 integer32 read-only
Antifreeze/evaporator probe 2 alarm (broken or disconnected)
                       al_hi_press_1 1.3.6.1.4.1.9839.2.1.1.164 integer32 read-only
High condensation pressure 1 alarm
                       al_hi_press_2 1.3.6.1.4.1.9839.2.1.1.165 integer32 read-only
High condensation pressure 2 alarm
                       al_lo_press_1 1.3.6.1.4.1.9839.2.1.1.166 integer32 read-only
Low condensation pressure 1 alarm
                       al_lo_press_2 1.3.6.1.4.1.9839.2.1.1.167 integer32 read-only
Low condensation pressure 2 alarm
                       al_probe_tank 1.3.6.1.4.1.9839.2.1.1.168 integer32 read-only
Tank/Out probe alarm (broken or disconnected)
                       off_line_1 1.3.6.1.4.1.9839.2.1.1.169 integer32 read-only
Chiller 1 offline
                       off_line_2 1.3.6.1.4.1.9839.2.1.1.170 integer32 read-only
Chiller 2 offline
                       off_line_3 1.3.6.1.4.1.9839.2.1.1.171 integer32 read-only
Chiller 3 offline
                       off_line_4 1.3.6.1.4.1.9839.2.1.1.172 integer32 read-only
Chiller 4 offline
                       off_line_5 1.3.6.1.4.1.9839.2.1.1.173 integer32 read-only
Chiller 5 offline
                       off_line_6 1.3.6.1.4.1.9839.2.1.1.174 integer32 read-only
Chiller 6 offline
                       off_line_7 1.3.6.1.4.1.9839.2.1.1.175 integer32 read-only
Chiller 7 offline
                       off_line_8 1.3.6.1.4.1.9839.2.1.1.176 integer32 read-only
Chiller 8 offline
                       al_ta_probe2 1.3.6.1.4.1.9839.2.1.1.177 integer32 read-only
Antifreeze/evaporator probe 2 alarm
                       al_sms 1.3.6.1.4.1.9839.2.1.1.178 integer32 read-only
SMS alarm
                       al_modem 1.3.6.1.4.1.9839.2.1.1.179 integer32 read-only
Modem alarm
                       sms_coda_alarm 1.3.6.1.4.1.9839.2.1.1.180 integer32 read-only
SMS coda alarm
                       al_probe_fc 1.3.6.1.4.1.9839.2.1.1.181 integer32 read-only
Freecooling probe alarm (broken or disconnected)
                       al_maint_pw1 1.3.6.1.4.1.9839.2.1.1.182 integer32 read-only
Maintenance pump 1 alarm)
                       al_maint_pw2 1.3.6.1.4.1.9839.2.1.1.183 integer32 read-only
Maintenance pump 2 alarm)
                       al_hi_temp_rid 1.3.6.1.4.1.9839.2.1.1.184 integer32 read-only
High temperature alarm (redundance)
                       al_q_fc_sep 1.3.6.1.4.1.9839.2.1.1.185 integer32 read-only
DryCooler breaker switch alarm
                       al_p_wat2 1.3.6.1.4.1.9839.2.1.1.186 integer32 read-only
Water pressure 2 alarm
                       al_p_wat1 1.3.6.1.4.1.9839.2.1.1.187 integer32 read-only
Water pressure 1 alarm
                       al_foult_flow_p1 1.3.6.1.4.1.9839.2.1.1.188 integer32 read-only
Pump 1 flow alarm
                       al_foult_flow_p2 1.3.6.1.4.1.9839.2.1.1.189 integer32 read-only
Pump 2 flow alarm
                       al_foult_fl1_p1 1.3.6.1.4.1.9839.2.1.1.190 integer32 read-only
Pump 1 flow-switch alarm
                       al_foult_fl1_p2 1.3.6.1.4.1.9839.2.1.1.191 integer32 read-only
Pump 2 flow-switch alarm
                       al_warning_le 1.3.6.1.4.1.9839.2.1.1.192 integer32 read-only
Water level warning
                       al_frigo_fl_C 1.3.6.1.4.1.9839.2.1.1.193 integer32 read-only
Flow switch condensation alarm (cooling alarm)
                       al_idro_pump_c_1 1.3.6.1.4.1.9839.2.1.1.194 integer32 read-only
Pump 1 condensation hydraulic alarm
                       al_idro_pump_c_2 1.3.6.1.4.1.9839.2.1.1.195 integer32 read-only
Pump 2 condensation hydraulic alarm
                       al_idro_fl_C 1.3.6.1.4.1.9839.2.1.1.196 integer32 read-only
Flow switch condensation alarm (hydraulic alarm)
                       al_warning_fl_C 1.3.6.1.4.1.9839.2.1.1.197 integer32 read-only
Flow switch condensation alarm (warning alarm)
                       al_foul_fl_C_p1 1.3.6.1.4.1.9839.2.1.1.198 integer32 read-only
Pump 1 condensation flow-switch alarm
                       al_foul_fl_C_p2 1.3.6.1.4.1.9839.2.1.1.199 integer32 read-only
Pump 2 condensation flow-switch alarm
                   analogObjects 1.3.6.1.4.1.9839.2.1.2
                       setpoint_antifreeze1 1.3.6.1.4.1.9839.2.1.2.1 integer32 read-write
Setpoint Antifreeze 1
                       setpoint_antifreeze2 1.3.6.1.4.1.9839.2.1.2.2 integer32 read-write
Setpoint Antifreeze 2
                       setpoint_Compensation 1.3.6.1.4.1.9839.2.1.2.3 integer32 read-write
Setpoint Compensation
                       hysteresis_Compensation 1.3.6.1.4.1.9839.2.1.2.4 integer32 read-write
Hysteresis Compensation
                       max_Compensation 1.3.6.1.4.1.9839.2.1.2.5 integer32 read-write
Max. Compensation
                       setpoint_Differential 1.3.6.1.4.1.9839.2.1.2.6 integer32 read-write
Setpoint Differential
                       high_Limit 1.3.6.1.4.1.9839.2.1.2.7 integer32 read-write
High Limit
                       low_Limit 1.3.6.1.4.1.9839.2.1.2.8 integer32 read-write
Low Limit
                       max_Setpoint_Differential 1.3.6.1.4.1.9839.2.1.2.9 integer32 read-write
Max. Setpoint Differential
                       min_Setpoint_Differential 1.3.6.1.4.1.9839.2.1.2.10 integer32 read-write
Min. Setpoint Differential
                       setpoint_ASB_Inverter_pumps 1.3.6.1.4.1.9839.2.1.2.11 integer32 read-write
Setpoint ASB Inverter pumps
                       setpoint_DIFF_Inverter_pumps 1.3.6.1.4.1.9839.2.1.2.12 integer32 read-write
Setpoint DIFF Inverter pumps
                       pressure_Out 1.3.6.1.4.1.9839.2.1.2.13 integer32 read-only
Pressure Out
                       proportional_Band_Inverter_Pumps_PID 1.3.6.1.4.1.9839.2.1.2.14 integer32 read-write
Proportional Band Inverter Pumps PID
                       integral_Time_Inverter_Pumps_PID 1.3.6.1.4.1.9839.2.1.2.15 integer32 read-write
Integral Time Inverter Pumps PID
                       derivative_Time_Inverter_Pumps_PID 1.3.6.1.4.1.9839.2.1.2.16 integer32 read-write
Derivative Time Inverter Pumps PID
                       hysteresis_Thermal_redundance 1.3.6.1.4.1.9839.2.1.2.17 integer32 read-write
Hysteresis Thermal redundance
                       min_Opening_3Way_Valve_Hydraulic 1.3.6.1.4.1.9839.2.1.2.18 integer32 read-write
Min. Opening 3Way Valve Hydraulic
                       max_Opening_3Way_Valve_Hydraulic 1.3.6.1.4.1.9839.2.1.2.19 integer32 read-write
Max. Opening 3Way Valve Hydraulic
                       proportional_Band_3Way_Valve_Hydrauli_PID 1.3.6.1.4.1.9839.2.1.2.20 integer32 read-write
Proportional Band 3Way Valve Hydraulic PID
                       setpoint_FCM 1.3.6.1.4.1.9839.2.1.2.21 integer32 read-write
Setpoint FCM
                       hysteresis_FCM 1.3.6.1.4.1.9839.2.1.2.22 integer32 read-write
Hysteresis FCM
                       max_Out_Speed_FCM 1.3.6.1.4.1.9839.2.1.2.23 integer32 read-write
Max. Out Speed FCM
                       min_Out_Speed_FCM 1.3.6.1.4.1.9839.2.1.2.24 integer32 read-write
Min. Out Speed FCM
                       hysteresis_Cut_off_FCM 1.3.6.1.4.1.9839.2.1.2.25 integer32 read-write
Hysteresis Cut-off FCM
                       max_Pressure_Alarm_FCM 1.3.6.1.4.1.9839.2.1.2.26 integer32 read-write
Max. Pressure Alarm FCM
                       hysteresis_Max_Pressure_Alarm_FCM 1.3.6.1.4.1.9839.2.1.2.27 integer32 read-write
Hysteresis Max.Pressure Alarm FCM
                       max_Out_FCM 1.3.6.1.4.1.9839.2.1.2.28 integer32 read-write
Max. Out FCM
                       min_Pressure_Alarm_FCM 1.3.6.1.4.1.9839.2.1.2.29 integer32 read-write
Min. Pressure Alarm FCM
                       hysteresis_Min_Pressure_Alarm_FCM 1.3.6.1.4.1.9839.2.1.2.30 integer32 read-write
Hysteresis Min.Pressure Alarm FCM
                       min_Out_FCM 1.3.6.1.4.1.9839.2.1.2.31 integer32 read-write
Min. Out FCM
                       delta_Freecooling 1.3.6.1.4.1.9839.2.1.2.32 integer32 read-write
Delta Freecooling
                       hysteresis_Freecooling 1.3.6.1.4.1.9839.2.1.2.33 integer32 read-write
Hysteresis Freecooling
                       proportional_Band_Freecooling_PID 1.3.6.1.4.1.9839.2.1.2.34 integer32 read-write
Proportional Band Freecooling PID
                       offset_Freecooling_PID 1.3.6.1.4.1.9839.2.1.2.35 integer32 read-write
Offset Freecooling PID
                       temperature_Overlap_Freecooling 1.3.6.1.4.1.9839.2.1.2.36 integer32 read-write
Temperature Overlap Freecooling
                       min_out_freecooling 1.3.6.1.4.1.9839.2.1.2.37 integer32 read-write
Min. out freecooling
                       neutral_zone_K_costant 1.3.6.1.4.1.9839.2.1.2.38 integer32 read-write
Neutral zone K costant
                       neutral_zone_V_variable 1.3.6.1.4.1.9839.2.1.2.39 integer32 read-write
Neutral zone V variable
                       proportional_Band_freecooling_Valve_PID 1.3.6.1.4.1.9839.2.1.2.40 integer32 read-write
Proportional Band freecooling Valve PID
                       offset_Freecooling_Valve_PID 1.3.6.1.4.1.9839.2.1.2.41 integer32 read-write
Offset Freecooling Valve PID
                       temperature_A_B 1.3.6.1.4.1.9839.2.1.2.42 integer32 read-only
Temperature A-B
                       delta_Thermal_Excusion_Freecoling 1.3.6.1.4.1.9839.2.1.2.43 integer32 read-write
Delta Thermal Excusion Freecoling
                       hysteresis_Thermal_Excusion_Freecoling 1.3.6.1.4.1.9839.2.1.2.44 integer32 read-write
hysteresis Thermal Excusion Freecoling
                       alarm_Setpoint_Static_Pressure_Hydraulic_circuit 1.3.6.1.4.1.9839.2.1.2.45 integer32 read-write
Alarm Setpoint Static Pressure Hydraulic circuit
                       warnig_Setpoint_Static_Pressure_Hydraulic_circuit 1.3.6.1.4.1.9839.2.1.2.46 integer32 read-write
Warnig Setpoint Static Pressure Hydraulic circuit
                       alarm_Setpoint_Differential_Pressure_Hydraulic_circuit 1.3.6.1.4.1.9839.2.1.2.47 integer32 read-write
Alarm Setpoint Differential Pressure Hydraulic circuit
                       alarm_Setpoint_Flow_Rate_Hydraulic_circuit 1.3.6.1.4.1.9839.2.1.2.48 integer32 read-write
Alarm Setpoint Flow-Rate Hydraulic circuit
                       tempertaure_Cut_off_FCM 1.3.6.1.4.1.9839.2.1.2.50 integer32 read-write
Tempertaure Cut-off FCM
                       set_effective 1.3.6.1.4.1.9839.2.1.2.59 integer32 read-only
Set-effective
                       set_fc 1.3.6.1.4.1.9839.2.1.2.60 integer32 read-only
Freecooling or drycooler Set-point
                       setpoint_a_us 1.3.6.1.4.1.9839.2.1.2.61 integer32 read-write
Set-point MAIN
                       max_setpoint 1.3.6.1.4.1.9839.2.1.2.62 integer32 read-write
Max.setpoint
                       min_setpoint 1.3.6.1.4.1.9839.2.1.2.63 integer32 read-write
Min.setpoint
                       diff 1.3.6.1.4.1.9839.2.1.2.64 integer32 read-write
differential
                       max_diff 1.3.6.1.4.1.9839.2.1.2.65 integer32 read-write
Max. differential
                       min_diff 1.3.6.1.4.1.9839.2.1.2.66 integer32 read-write
Min.Differential
                       fcs_out 1.3.6.1.4.1.9839.2.1.2.67 integer32 read-only
Fans speed controller output %
                       water_temp 1.3.6.1.4.1.9839.2.1.2.70 integer32 read-only
Tank - Process water temperature
                       temp_inlet 1.3.6.1.4.1.9839.2.1.2.71 integer32 read-only
Water inlet temperature
                       temp_outlet 1.3.6.1.4.1.9839.2.1.2.72 integer32 read-only
Water outlet temperature
                       flow_value 1.3.6.1.4.1.9839.2.1.2.73 integer32 read-only
Flow rate value
                       amp_value 1.3.6.1.4.1.9839.2.1.2.74 integer32 read-only
Current cunsumption
                       ta_probe_temp_1 1.3.6.1.4.1.9839.2.1.2.75 integer32 read-only
Antifreeze 1 temperature monitoring
                       ta_probe_temp_2 1.3.6.1.4.1.9839.2.1.2.76 integer32 read-only
Antifreeze 2 temperature monitoring
                       pressione1 1.3.6.1.4.1.9839.2.1.2.77 integer32 read-only
Condensation pressure circuit 1
                       pressione2 1.3.6.1.4.1.9839.2.1.2.78 integer32 read-only
Condensation pressure circuit 2
                       pump_sp_press 1.3.6.1.4.1.9839.2.1.2.79 integer32 read-only
Pump discharge pressure
                       p_wat2 1.3.6.1.4.1.9839.2.1.2.80 integer32 read-only
Pump suction or static pressure
                       temp_amb 1.3.6.1.4.1.9839.2.1.2.81 integer32 read-only
Ambient temperature
                       temp_fc 1.3.6.1.4.1.9839.2.1.2.82 integer32 read-only
Inlet - freecooling temperature
                       pp1 1.3.6.1.4.1.9839.2.1.2.90 integer32 read-only
Pump 1 speed
                       pp2 1.3.6.1.4.1.9839.2.1.2.91 integer32 read-only
Pump 2 speed
                       cooling_capacity 1.3.6.1.4.1.9839.2.1.2.100 integer32 read-only
Cooling Capacity
                       freecooling_capacity 1.3.6.1.4.1.9839.2.1.2.101 integer32 read-only
FreeCooling Capacity
                       total_capacity 1.3.6.1.4.1.9839.2.1.2.102 integer32 read-only
TotalCooling Capacity
                   integerObjects 1.3.6.1.4.1.9839.2.1.3
                       ip_Address1 1.3.6.1.4.1.9839.2.1.3.6 integer32 read-only
IP Address 1 (XXX.xxx.xxx.xxx)
                       ip_Address2 1.3.6.1.4.1.9839.2.1.3.7 integer32 read-only
IP Address 2 (xxx.XXX.xxx.xxx)
                       ip_Address3 1.3.6.1.4.1.9839.2.1.3.8 integer32 read-only
IP Address 3 (xxx.xxx.XXX.xxx)
                       ip_Address4 1.3.6.1.4.1.9839.2.1.3.9 integer32 read-only
IP Address 4 (xxx.xxx.xxx.XXX)
                       netMask 1.3.6.1.4.1.9839.2.1.3.10 integer32 read-only
NetMask 8-16-24-32
                       gateway1 1.3.6.1.4.1.9839.2.1.3.11 integer32 read-only
Gateway 1 (XXX.xxx.xxx.xxx)
                       gateway2 1.3.6.1.4.1.9839.2.1.3.12 integer32 read-only
Gateway 2 (xxx.XXX.xxx.xxx)
                       gateway3 1.3.6.1.4.1.9839.2.1.3.13 integer32 read-only
Gateway 3 (xxx.xxx.XXX.xxx)
                       gateway4 1.3.6.1.4.1.9839.2.1.3.14 integer32 read-only
Gateway 4 (xxx.xxx.xxx.XXX)
                       dns1_1 1.3.6.1.4.1.9839.2.1.3.15 integer32 read-only
DNS (1) 1 (XXX.xxx.xxx.xxx)
                       dns1_2 1.3.6.1.4.1.9839.2.1.3.16 integer32 read-only
DNS (1) 2 (xxx.XXX.xxx.xxx)
                       dns1_3 1.3.6.1.4.1.9839.2.1.3.17 integer32 read-only
DNS (1) 3 (xxx.xxx.XXX.xxx)
                       dns1_4 1.3.6.1.4.1.9839.2.1.3.18 integer32 read-only
DNS (1) 4 (xxx.xxx.xxx.XXX)
                       dns2_1 1.3.6.1.4.1.9839.2.1.3.19 integer32 read-only
DNS (2) 1 (XXX.xxx.xxx.xxx)
                       dns2_2 1.3.6.1.4.1.9839.2.1.3.20 integer32 read-only
DNS (2) 2 (xxx.XXX.xxx.xxx)
                       dns2_3 1.3.6.1.4.1.9839.2.1.3.21 integer32 read-only
DNS (2) 3 (xxx.xxx.XXX.xxx)
                       dns2_4 1.3.6.1.4.1.9839.2.1.3.22 integer32 read-only
DNS (2) 4 (xxx.xxx.xxx.XXX)
                       ip_Address1_Out 1.3.6.1.4.1.9839.2.1.3.26 integer32 read-only
IP Address Out 1 (XXX.xxx.xxx.xxx)
                       ip_Address2_Out 1.3.6.1.4.1.9839.2.1.3.27 integer32 read-only
IP Address Out 2 (xxx.XXX.xxx.xxx)
                       ip_Address3_Out 1.3.6.1.4.1.9839.2.1.3.28 integer32 read-only
IP Address Out 3 (xxx.xxx.XXX.xxx)
                       ip_Address4_Out 1.3.6.1.4.1.9839.2.1.3.29 integer32 read-only
IP Address Out 4 (xxx.xxx.xxx.XXX)
                       starting_delay_Second_Pump 1.3.6.1.4.1.9839.2.1.3.30 integer32 read-write
Starting delay Second Pump
                       starting_delay_btw_Pump_Compressor 1.3.6.1.4.1.9839.2.1.3.31 integer32 read-write
Starting delay btw Pump - Compressor
                       overlap_time_Pumps 1.3.6.1.4.1.9839.2.1.3.32 integer32 read-write
Overlap time Pumps
                       working_time_Pumps 1.3.6.1.4.1.9839.2.1.3.33 integer32 read-write
Working time Pumps
                       running_time_Chillers 1.3.6.1.4.1.9839.2.1.3.34 integer32 read-write
Running time Chillers
                       overlap_time_Chillers 1.3.6.1.4.1.9839.2.1.3.35 integer32 read-write
Overlap time Chillers
                       n_chillers_Max 1.3.6.1.4.1.9839.2.1.3.36 integer32 read-write
N chillers Max
                       n_chillers_ON 1.3.6.1.4.1.9839.2.1.3.37 integer32 read-write
N chillers ON
                       n_pumps_ON 1.3.6.1.4.1.9839.2.1.3.38 integer32 read-write
N pumps ON
                       time_Enable_Pumps_Chiller_Offline 1.3.6.1.4.1.9839.2.1.3.39 integer32 read-write
Time Enable Pumps - Chiller Offline
                       time_Running_Pumps_Chiller_Offline 1.3.6.1.4.1.9839.2.1.3.40 integer32 read-write
Time Running Pumps - Chiller Offline
                       integral_Time_3Way_Valve_Hydraulic_PID 1.3.6.1.4.1.9839.2.1.3.41 integer32 read-write
Integral Time 3Way Valve Hydraulic (PID)
                       derivative_Time_3Way_Valve_Hydraulic_PID 1.3.6.1.4.1.9839.2.1.3.42 integer32 read-write
Derivative Time 3Way Valve Hydraulic (PID)
                       output_Address_3Way_Valve_Hydraulic 1.3.6.1.4.1.9839.2.1.3.43 integer32 read-write
Output Address 3Way Valve Hydraulic
                       time_Speed_Up_FCM 1.3.6.1.4.1.9839.2.1.3.44 integer32 read-write
Time Speed-Up (FCM)
                       time_Soft_Start_FCM 1.3.6.1.4.1.9839.2.1.3.45 integer32 read-write
Time Soft-Start (FCM)
                       delay_Freecooling 1.3.6.1.4.1.9839.2.1.3.47 integer32 read-write
Delay Freecooling
                       integral_Time_Freeccoling_PID 1.3.6.1.4.1.9839.2.1.3.48 integer32 read-write
Integral Time Freeccoling (PID)
                       derivative_Time_Freeccoling_PID 1.3.6.1.4.1.9839.2.1.3.49 integer32 read-write
Derivative Time Freeccoling (PID)
                       time_Min_On_Freecooling_Chiller_timing 1.3.6.1.4.1.9839.2.1.3.50 integer32 read-write
Time Min. On (Freecooling - Chiller timing)
                       time_Min_Off_Freecooling_Chiller_timing 1.3.6.1.4.1.9839.2.1.3.51 integer32 read-write
Time Min. Off (Freecooling - Chiller timing)
                       time_Min_Different_Freecooling_Chiller_timing 1.3.6.1.4.1.9839.2.1.3.52 integer32 read-write
Time Min. Different (Freecooling - Chiller timing)
                       time_Min_Same_Freecooling_Chiller_timing 1.3.6.1.4.1.9839.2.1.3.53 integer32 read-write
Time Min. Same (Freecooling - Chiller timing)
                       integral_Time_Freeccoling_Valve_PID 1.3.6.1.4.1.9839.2.1.3.54 integer32 read-write
Integral Time Freeccoling Valve (PID)
                       derivative_Time_Freeccoling_Valve_PID 1.3.6.1.4.1.9839.2.1.3.55 integer32 read-write
Derivative Time Freeccoling Valve (PID)
                       output_Address_Valve_Freecooling 1.3.6.1.4.1.9839.2.1.3.56 integer32 read-write
Output Address Valve Freecooling
                       delay_Freecooling_Thermal_Exclusion 1.3.6.1.4.1.9839.2.1.3.57 integer32 read-write
Delay Freecoolimg Thermal Exclusion
                       n_of_alarm_External_Dry_Cooler 1.3.6.1.4.1.9839.2.1.3.58 integer32 read-write
N of alarm (External Dry-Cooler)
                       delay_Alarm_Static_Pressure 1.3.6.1.4.1.9839.2.1.3.59 integer32 read-write
Delay Alarm (Static Pressure)
                       n_of_Alarm_Static_Pressure 1.3.6.1.4.1.9839.2.1.3.60 integer32 read-write
N of Alarm (Static Pressure)
                       delay_Warning_Static_Pressure 1.3.6.1.4.1.9839.2.1.3.61 integer32 read-write
Delay Warning (Static Pressure)
                       n_of_Warning_Static_Pressure 1.3.6.1.4.1.9839.2.1.3.62 integer32 read-write
N of Warning (Static Pressure)
                       n_of_Alarm_Differential_Pressure 1.3.6.1.4.1.9839.2.1.3.63 integer32 read-write
N of Alarm (Differential Pressure)
                       priming_Time_Hydraulic_Pressure 1.3.6.1.4.1.9839.2.1.3.64 integer32 read-write
Priming Time (Hydraulic Pressure)
                       delay_priming_Time_Hydraulic_Pressure 1.3.6.1.4.1.9839.2.1.3.65 integer32 read-write
Delay Priming Time (Hydraulic Pressure)
                       output_Address_Alarm_Static_Pressure 1.3.6.1.4.1.9839.2.1.3.66 integer32 read-write
Output Address Alarm (Static Pressure)
                       n_of_Alarm_Flow_Rate 1.3.6.1.4.1.9839.2.1.3.67 integer32 read-write
N of Alarm (Flow Rate)
                       priming_Time_Flow_Rate 1.3.6.1.4.1.9839.2.1.3.68 integer32 read-write
Priming Time (Flow Rate)
                       delay_priming_Time_Flow_Rate 1.3.6.1.4.1.9839.2.1.3.69 integer32 read-write
Delay Priming Time (Flow Rate)
                       bms_address_IDENT 1.3.6.1.4.1.9839.2.1.3.70 integer32 read-only
BMS address (IDENT)
                       chiller_name0 1.3.6.1.4.1.9839.2.1.3.99 integer32 read-only
Chiller Model - Article Number - 0
                       chiller_name1 1.3.6.1.4.1.9839.2.1.3.100 integer32 read-only
Chiller Model - Article Number - 1
                       current_day 1.3.6.1.4.1.9839.2.1.3.123 integer32 read-only
Current Day
                       current_month 1.3.6.1.4.1.9839.2.1.3.124 integer32 read-only
Current Month
                       current_year 1.3.6.1.4.1.9839.2.1.3.125 integer32 read-only
Current Year
                       current_hour 1.3.6.1.4.1.9839.2.1.3.126 integer32 read-only
Current Hour
                       current_minute 1.3.6.1.4.1.9839.2.1.3.127 integer32 read-only
Current Minute
                       chiller_mode_operation 1.3.6.1.4.1.9839.2.1.3.150 integer32 read-only
Chiller mode operation
                   trapObjects 1.3.6.1.4.1.9839.2.1.100
                           high_pressure_switch_1_alarm 1.3.6.1.4.1.9839.2.1.100.1
High pressure switch 1 alarm
                           high_pressure_switch_2_alarm 1.3.6.1.4.1.9839.2.1.100.2
High pressure switch 2 alarm
                           low_pressure_switch_1_alarm 1.3.6.1.4.1.9839.2.1.100.3
Low pressure switch 1 alarm
                           low_pressure_switch_2_alarm 1.3.6.1.4.1.9839.2.1.100.4
Low pressure switch 2 alarm
                           water_level_alarm 1.3.6.1.4.1.9839.2.1.100.6
Water level alarm
                           flow_switch_alarm 1.3.6.1.4.1.9839.2.1.100.8
Flow switch alarm
                           water_static_pressure_alarm 1.3.6.1.4.1.9839.2.1.100.9
Water static pressure alarm
                           water_static_pressure_warning 1.3.6.1.4.1.9839.2.1.100.10
Water static pressure warning
                           flow_rate_alarm 1.3.6.1.4.1.9839.2.1.100.11
Flow rate alarm
                           overload_compressor1_circuit1_alarm 1.3.6.1.4.1.9839.2.1.100.12
Overload compressor 1 circuit 1 alarm
                           overload_compressor2_circuit1_alarm 1.3.6.1.4.1.9839.2.1.100.13
Overload compressor 2 circuit 1 alarm
                           overload_compressor3_circuit1_alarm 1.3.6.1.4.1.9839.2.1.100.14
Overload compressor 3 circuit 1 alarm
                           overload_compressor1_circuit2_alarm 1.3.6.1.4.1.9839.2.1.100.15
Overload compressor 1 circuit 2 alarm
                           overload_compressor2_circuit2_alarm 1.3.6.1.4.1.9839.2.1.100.16
Overload compressor 2 circuit 2 alarm
                           overload_compressor3_circuit2_alarm 1.3.6.1.4.1.9839.2.1.100.17
Overload compressor 3 circuit 2 alarm
                           overload_fans_circuit1 1.3.6.1.4.1.9839.2.1.100.18
Overload fans circuit 1
                           overload_fans_circuit2 1.3.6.1.4.1.9839.2.1.100.19
Overload fans circuit 2
                           overload_fan1_circuit1_alarm 1.3.6.1.4.1.9839.2.1.100.20
Overload fan 1 circuit 1 alarm
                           overload_fan2_circuit1_alarm 1.3.6.1.4.1.9839.2.1.100.21
Overload fan 2 circuit 1 alarm
                           overload_fan3_circuit1_alarm 1.3.6.1.4.1.9839.2.1.100.22
Overload fan 3 circuit 1 alarm
                           overload_fan4_circuit1_alarm 1.3.6.1.4.1.9839.2.1.100.23
Overload fan 4 circuit 1 alarm
                           overload_fan1_circuit_2_alarm 1.3.6.1.4.1.9839.2.1.100.24
Overload fan 1 circuit 2 alarm
                           overload_fan2_circuit2_alarm 1.3.6.1.4.1.9839.2.1.100.25
Overload fan 2 circuit 2 alarm
                           overload_fan3_circuit2_alarm 1.3.6.1.4.1.9839.2.1.100.26
Overload fan 3 circuit 2 alarm
                           overload_fan4_circuit2_alarm 1.3.6.1.4.1.9839.2.1.100.27
Overload fan 4 circuit 2 alarm
                           overload_pump1_alarm 1.3.6.1.4.1.9839.2.1.100.28
Overload pump 1 alarm
                           overload_pump2_alarm 1.3.6.1.4.1.9839.2.1.100.29
Overload pump 2 alarm
                           wrong_phase_rotation_alarm 1.3.6.1.4.1.9839.2.1.100.30
Wrong phase rotation alarm
                           back_Door_open_alarm 1.3.6.1.4.1.9839.2.1.100.31
Back Door open alarm
                           alarm_idrofrigo_pump_c_1 1.3.6.1.4.1.9839.2.1.100.75
Condensation pump 1 breaker switch alarm
                           alarm_idrofrigo_pump_c_2 1.3.6.1.4.1.9839.2.1.100.76
Condensation pump 2 breaker switch alarm
                           alarm_idrofrigo_fl_C 1.3.6.1.4.1.9839.2.1.100.80
Condensation flow switch alarm
                           remote_on_off 1.3.6.1.4.1.9839.2.1.100.130
Remote on-off
                           chiller_ON_OFF 1.3.6.1.4.1.9839.2.1.100.131
Chiller ON/OFF
                           alarm_disch_scw_1 1.3.6.1.4.1.9839.2.1.100.148
Discharge screw compressor 1 alarm
                           alarm_disch_scw_2 1.3.6.1.4.1.9839.2.1.100.149
Discharge screw compressor 2 alarm
                           alarm_probe_inlet 1.3.6.1.4.1.9839.2.1.100.150
Inlet probe alarm (broken or disconnected)
                           alarm_probe_amb 1.3.6.1.4.1.9839.2.1.100.151
Ambient probe alarm (broken or disconnected)
                           alarm_frigo_fl1 1.3.6.1.4.1.9839.2.1.100.152
Flow switch alarm (cooling alarm)
                           alarm_idro_pump1 1.3.6.1.4.1.9839.2.1.100.153
Pump 1 hydraulic alarm
                           alarm_idro_pump2 1.3.6.1.4.1.9839.2.1.100.154
Pump 2 hydraulic alarm
                           alarm_idro_fl1 1.3.6.1.4.1.9839.2.1.100.155
Flow switch alarm (hydraulic alarm)
                           alarm_warning_fl1 1.3.6.1.4.1.9839.2.1.100.156
Flow switch alarm (warning alarm)
                           alarm_hi_water_temp 1.3.6.1.4.1.9839.2.1.100.157
High Temperature alarm
                           alarm_lo_water_temp 1.3.6.1.4.1.9839.2.1.100.158
Low Temperature alarm
                           alarm_ta_probe1 1.3.6.1.4.1.9839.2.1.100.159
Antifreeze/evaporator probe 1 alarm
                           alarm_hi_press 1.3.6.1.4.1.9839.2.1.100.160
High condensation pressure alarm
                           alarm_lo_press 1.3.6.1.4.1.9839.2.1.100.161
Low condensation pressure alarm
                           alarm_probe_evap_1 1.3.6.1.4.1.9839.2.1.100.162
Antifreeze/evaporator probe 1 alarm (broken or disconnected)
                           alarm_probe_evap_2 1.3.6.1.4.1.9839.2.1.100.163
Antifreeze/evaporator probe 2 alarm (broken or disconnected)
                           alarm_hi_press_1 1.3.6.1.4.1.9839.2.1.100.164
High condensation pressure 1 alarm
                           alarm_hi_press_2 1.3.6.1.4.1.9839.2.1.100.165
High condensation pressure 2 alarm
                           alarm_lo_press_1 1.3.6.1.4.1.9839.2.1.100.166
Low condensation pressure 1 alarm
                           alarm_lo_press_2 1.3.6.1.4.1.9839.2.1.100.167
Low condensation pressure 2 alarm
                           alarm_probe_tank 1.3.6.1.4.1.9839.2.1.100.168
Tank/Out probe alarm (broken or disconnected)
                           alarm_off_line_1 1.3.6.1.4.1.9839.2.1.100.169
Chiller 1 offline
                           alarm_off_line_2 1.3.6.1.4.1.9839.2.1.100.170
Chiller 2 offline
                           alarm_off_line_3 1.3.6.1.4.1.9839.2.1.100.171
Chiller 3 offline
                           alarm_off_line_4 1.3.6.1.4.1.9839.2.1.100.172
Chiller 4 offline
                           alarm_off_line_5 1.3.6.1.4.1.9839.2.1.100.173
Chiller 5 offline
                           alarm_off_line_6 1.3.6.1.4.1.9839.2.1.100.174
Chiller 6 offline
                           alarm_off_line_7 1.3.6.1.4.1.9839.2.1.100.175
Chiller 7 offline
                           alarm_off_line_8 1.3.6.1.4.1.9839.2.1.100.176
Chiller 8 offline
                           alarm_ta_probe2 1.3.6.1.4.1.9839.2.1.100.177
Antifreeze/evaporator probe 2 alarm
                           alarm_sms 1.3.6.1.4.1.9839.2.1.100.178
SMS alarm
                           alarm_modem 1.3.6.1.4.1.9839.2.1.100.179
Modem alarm
                           alarm_sms_coda 1.3.6.1.4.1.9839.2.1.100.180
SMS coda alarm
                           alarm_probe_fc 1.3.6.1.4.1.9839.2.1.100.181
Freecooling probe alarm (broken or disconnected)
                           alarm_maint_pw1 1.3.6.1.4.1.9839.2.1.100.182
Maintenance pump 1 alarm)
                           alarm_maint_pw2 1.3.6.1.4.1.9839.2.1.100.183
Maintenance pump 2 alarm)
                           alarm_hi_temp_rid 1.3.6.1.4.1.9839.2.1.100.184
High temperature alarm (redundance)
                           alarm_q_fc_sep 1.3.6.1.4.1.9839.2.1.100.185
DryCooler breaker switch alarm
                           alarm_p_wat2 1.3.6.1.4.1.9839.2.1.100.186
Water pressure 2 alarm
                           alarm_p_wat1 1.3.6.1.4.1.9839.2.1.100.187
Water pressure 1 alarm
                           alarm_foult_flow_p1 1.3.6.1.4.1.9839.2.1.100.188
Pump 1 flow alarm
                           alarm_foult_flow_p2 1.3.6.1.4.1.9839.2.1.100.189
Pump 2 flow alarm
                           alarm_foult_fl1_p1 1.3.6.1.4.1.9839.2.1.100.190
Pump 1 flow-switch alarm
                           alarm_foult_fl1_p2 1.3.6.1.4.1.9839.2.1.100.191
Pump 2 flow-switch alarm
                           alarm_warning_le 1.3.6.1.4.1.9839.2.1.100.192
Water level warning
                           alarm_frigo_fl_C 1.3.6.1.4.1.9839.2.1.100.193
Flow switch condensation alarm (cooling alarm)
                           alarm_idro_pump_c_1 1.3.6.1.4.1.9839.2.1.100.194
Pump 1 condensation hydraulic alarm
                           alarm_idro_pump_c_2 1.3.6.1.4.1.9839.2.1.100.195
Pump 2 condensation hydraulic alarm
                           alarm_idro_fl_C 1.3.6.1.4.1.9839.2.1.100.196
Flow switch condensation alarm (hydraulic alarm)
                           alarm_warning_fl_C 1.3.6.1.4.1.9839.2.1.100.197
Flow switch condensation alarm (warning alarm)
                           alarm_foul_fl_C_p1 1.3.6.1.4.1.9839.2.1.100.198
Pump 1 condensation flow-switch alarm
                           alarm_foul_fl_C_p2 1.3.6.1.4.1.9839.2.1.100.199
Pump 2 condensation flow-switch alarm