Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 carel 1.3.6.1.4.1.9839
           systm 1.3.6.1.4.1.9839.1
               agentRelease 1.3.6.1.4.1.9839.1.1 integer32 read-only
Release of the Agent.
               agentCode 1.3.6.1.4.1.9839.1.2 integer32 read-only
Code of the Agent. 2=pCOWeb.
           instruments 1.3.6.1.4.1.9839.2
               pCOWebInfo 1.3.6.1.4.1.9839.2.0
                   pCOStatusgroup 1.3.6.1.4.1.9839.2.0.10
                         pCOId1_Status 1.3.6.1.4.1.9839.2.0.10.1 integer32 read-only
Status of pCOId1. 0=Offline, 1=Init, 2=Online
                   pCOErrorsNumbergroup 1.3.6.1.4.1.9839.2.0.11
                         pCOId1_ErrorsNumber 1.3.6.1.4.1.9839.2.0.11.1 integer32 read-only
Number of Communication Errors from pCOId1 to pCOWeb.
               dap4_alMIB 1.3.6.1.4.1.9839.2.1
This is the MIB module for the dap4_al device.
                   digitalObjects 1.3.6.1.4.1.9839.2.1.1
                       dehum_on 1.3.6.1.4.1.9839.2.1.1.1 integer32 read-only
Dehumidify mode is running
                       hum_on 1.3.6.1.4.1.9839.2.1.1.2 integer32 read-only
Humidifier is running
                       engy_on 1.3.6.1.4.1.9839.2.1.1.3 integer32 read-only
Energy saver is running
                       cool_inhibit 1.3.6.1.4.1.9839.2.1.1.4 integer32 read-only
Cooling inhibit from Zone Master
                       heat_held 1.3.6.1.4.1.9839.2.1.1.5 integer32 read-only
Heat inhibited due to alarm condition
                       humidifier_inhibit 1.3.6.1.4.1.9839.2.1.1.6 integer32 read-only
Humidifier stopped due to alarm
                       dehum_inhibit 1.3.6.1.4.1.9839.2.1.1.7 integer32 read-only
Dehum is inhibited
                       rht_during_dehum 1.3.6.1.4.1.9839.2.1.1.8 integer32 read-only
reheat during dehum
                       floor_wtr_alm 1.3.6.1.4.1.9839.2.1.1.9 integer32 read-only
Water under floor alarm
                       air_flow_alm 1.3.6.1.4.1.9839.2.1.1.10 integer32 read-only
No air flow alarm
                       filter_alm 1.3.6.1.4.1.9839.2.1.1.11 integer32 read-only
Dirty filter from digital input
                       humidifier_alm 1.3.6.1.4.1.9839.2.1.1.12 integer32 read-only
Alarm from humidifier digital input
                       firestat_alm 1.3.6.1.4.1.9839.2.1.1.13 integer32 read-only
Temperature of return air above firestat alarm set point
                       shortcycle_alm 1.3.6.1.4.1.9839.2.1.1.14 integer32 read-only
One or more comps has short cycled
                       humidity_fail 1.3.6.1.4.1.9839.2.1.1.15 integer32 read-only
Sensor is out of range
                       ret_air_fail 1.3.6.1.4.1.9839.2.1.1.16 integer32 read-only
Sensor is out of range
                       maint_alm 1.3.6.1.4.1.9839.2.1.1.17 integer32 read-only
Maintenance Schedule Due alarm
                       c1_hp_alm 1.3.6.1.4.1.9839.2.1.1.18 integer32 read-only
High pressure alarm
                       c1_lp_alm 1.3.6.1.4.1.9839.2.1.1.19 integer32 read-only
Low pressure alarm
                       c2_hp_alm 1.3.6.1.4.1.9839.2.1.1.20 integer32 read-only
High pressure alarm
                       c2_lp_alm 1.3.6.1.4.1.9839.2.1.1.21 integer32 read-only
Low pressure alarm
                       smoke_alm 1.3.6.1.4.1.9839.2.1.1.22 integer32 read-only
Smoke detected from digital input
                       wtr_flow_alm 1.3.6.1.4.1.9839.2.1.1.23 integer32 read-only
No water flow alarm
                       disch_air_fail 1.3.6.1.4.1.9839.2.1.1.24 integer32 read-only
Sensor is out of range
                       ra_tmp_hi_alm 1.3.6.1.4.1.9839.2.1.1.25 integer32 read-only
Temperature of return air above alarm set point
                       ra_tmp_lo_alm 1.3.6.1.4.1.9839.2.1.1.26 integer32 read-only
Temperature of return air below alarm set point
                       hum_hi_alm 1.3.6.1.4.1.9839.2.1.1.27 integer32 read-only
Humidity above alarm set point
                       hum_lo_alm 1.3.6.1.4.1.9839.2.1.1.28 integer32 read-only
Humidity below alarm set point
                       fan_overload 1.3.6.1.4.1.9839.2.1.1.29 integer32 read-only
Fan overload
                       stdby_pump_on 1.3.6.1.4.1.9839.2.1.1.30 integer32 read-only
Standby pump on: Check primary pump -Optional alarm. Pump failure input signal required
                       cust_msg_sw1 1.3.6.1.4.1.9839.2.1.1.31 integer32 read-only
Custom alarm #1 -Optional alarm. External alarm input required. Factory programmed custom message required
                       cust_msg_sw2 1.3.6.1.4.1.9839.2.1.1.32 integer32 read-only
Custom alarm #2 -Optional alarm. External alarm input required. Factory programmed custom message required
                       cust_msg_sw3 1.3.6.1.4.1.9839.2.1.1.33 integer32 read-only
Custom alarm #3 -Optional alarm. External alarm input required. Factory programmed custom message required
                       cust_msg_sw4 1.3.6.1.4.1.9839.2.1.1.34 integer32 read-only
Custom alarm #4 -Optional alarm. External alarm input required. Factory programmed custom message required
                       humsw_inhibit 1.3.6.1.4.1.9839.2.1.1.35 integer32 read-only
Humidifier stopped due to custom alarm switch
                       heat_inhibit 1.3.6.1.4.1.9839.2.1.1.36 integer32 read-only
Heat inhibited due to custom switch alarm condition
                       rht_hum_inhibit 1.3.6.1.4.1.9839.2.1.1.37 integer32 read-only
Reheat and humidification inhibited from operation
                       disch_tmp_lo_alm 1.3.6.1.4.1.9839.2.1.1.38 integer32 read-only
Temperature of discharge air below alarm set point
                       override_alm 1.3.6.1.4.1.9839.2.1.1.39 integer32 read-only
Manual override: Check bypass switches - Standard alarm. Manual override switch is on
                       condensation_alm 1.3.6.1.4.1.9839.2.1.1.40 integer32 read-only
High condensation from digital input
                       unit_in_standby 1.3.6.1.4.1.9839.2.1.1.41 integer32 read-only
Unit in standby, all functions held off - Optional alarm. Control input signal required Factory setting required
                       cw_sns_fail 1.3.6.1.4.1.9839.2.1.1.42 integer32 read-only
Sensor is out of range
                       humsw_chk_cyl 1.3.6.1.4.1.9839.2.1.1.43 integer32 read-only
Humidifier stopped due to custom alarm switch
                       bms_cooling_inhibit 1.3.6.1.4.1.9839.2.1.1.44 integer32 read-write
Cooling operation inhibited by BMS
                       bms_heat_inhibit 1.3.6.1.4.1.9839.2.1.1.45 integer32 read-write
Heat inhibited due to bms
                       bms_humidifier_inhibit 1.3.6.1.4.1.9839.2.1.1.46 integer32 read-write
Humidifier operation inhibited by BMS
                       bms_dehum_inhibit 1.3.6.1.4.1.9839.2.1.1.47 integer32 read-write
Dehumidify mode inhibited by bms
                       fan_inhibit_bms 1.3.6.1.4.1.9839.2.1.1.48 integer32 read-write
Inhibit fan by bms
                       hum_expect 1.3.6.1.4.1.9839.2.1.1.49 integer32 read-only
Reduces control humidity cycling
                       usashr_f_c 1.3.6.1.4.1.9839.2.1.1.50 integer32 read-write
Temperature Mode 0=_C 1=_F
                       lead_comp 1.3.6.1.4.1.9839.2.1.1.52 integer32 read-only
Lead compressor select 0= C1, 1= C2
                       wtrvlv_dir 1.3.6.1.4.1.9839.2.1.1.53 integer32 read-only
Water valve direct or reverse acting
                       ups_on_alm 1.3.6.1.4.1.9839.2.1.1.54 integer32 read-only
Alarm: UPS power on: Check main power -Optional alarm. External alarm input required
                       pwrup_alm 1.3.6.1.4.1.9839.2.1.1.55 integer32 read-only
Loss of power requires manual reset of alarm
                       seetag_cust_alm1 1.3.6.1.4.1.9839.2.1.1.56 integer32 read-only
Local alarm #1: See tag inside door =Optional alarm. External alarm input required
                       seetag_cust_alm2 1.3.6.1.4.1.9839.2.1.1.57 integer32 read-only
Local alarm #2: See tag inside door =Optional alarm. External alarm input required
                       seetag_cust_alm3 1.3.6.1.4.1.9839.2.1.1.58 integer32 read-only
Local alarm #3: See tag inside door =Optional alarm. External alarm input required
                       seetag_cust_alm4 1.3.6.1.4.1.9839.2.1.1.59 integer32 read-only
Local alarm #4: See tag inside door =Optional alarm. External alarm input required
                       shortcycle_alm_en 1.3.6.1.4.1.9839.2.1.1.60 integer32 read-only
Enable short cycle alarm of the compressors
                       superv_off 1.3.6.1.4.1.9839.2.1.1.61 integer32 read-only
Supervisor (BMS) On-Off. Show the state OFFbyBMS in main mask (1: Off; 0: On
                       bms_heartbeat 1.3.6.1.4.1.9839.2.1.1.62 integer32 read-only
Bms heartbeat - pCO looks for update every 10 minutes
                   analogObjects 1.3.6.1.4.1.9839.2.1.2
                       ret_air_tmp 1.3.6.1.4.1.9839.2.1.2.1 integer32 read-only
Temperature of return air
                       minmax_24hr_retair_maximum 1.3.6.1.4.1.9839.2.1.2.2 integer32 read-only
Maximum Return air temp in last 24hrs
                       minmax_24hr_retair_minumum 1.3.6.1.4.1.9839.2.1.2.3 integer32 read-only
Minimum Return air temp in last 24hrs
                       temp_setpoint 1.3.6.1.4.1.9839.2.1.2.4 integer32 read-write
Temperature setpoint
                       temp_deadband 1.3.6.1.4.1.9839.2.1.2.5 integer32 read-write
Amount from setpoint before a comp is staged on
                       humidity_ain_offs 1.3.6.1.4.1.9839.2.1.2.6 integer32 read-only
Humidity Sensor Calibration
                       return_ain_offs 1.3.6.1.4.1.9839.2.1.2.7 integer32 read-only
Return Temperature Sensor Calibration
                       cw_tmp 1.3.6.1.4.1.9839.2.1.2.8 integer32 read-only
Temperature of chilled water
                       disch_air_tmp 1.3.6.1.4.1.9839.2.1.2.9 integer32 read-only
Temperature of discharge air
                       discharge_ain_offs 1.3.6.1.4.1.9839.2.1.2.10 integer32 read-only
Discharge Temperature Sensor Calibration - Optional discharge air temperature sensor required (B9)
                       cw_ain_offs 1.3.6.1.4.1.9839.2.1.2.11 integer32 read-only
Chilled Water Temperature Sensor Calibration - Optional chilled water temperature sensor required (B10)
                       engsaver_setpoint 1.3.6.1.4.1.9839.2.1.2.12 integer32 read-write
Temperature setpoint where chilled water will is requested
                       opt1_analog 1.3.6.1.4.1.9839.2.1.2.13 integer32 read-only
Value of the analog input
                       opt2_analog 1.3.6.1.4.1.9839.2.1.2.14 integer32 read-only
Value of the analog input
                       opt3_analog 1.3.6.1.4.1.9839.2.1.2.15 integer32 read-only
Value of the analog input
                       opt4_analog 1.3.6.1.4.1.9839.2.1.2.16 integer32 read-only
Value of the analog input
                       opt_sns_1_y1 1.3.6.1.4.1.9839.2.1.2.17 integer32 read-only
Analog Sensor 1 Minimum Value
                       opt_sns_1_y2 1.3.6.1.4.1.9839.2.1.2.18 integer32 read-only
Analog Sensor 1 Maximum Value
                       opt_sns_1_ain_offs 1.3.6.1.4.1.9839.2.1.2.19 integer32 read-only
Analog Sensor 1 Calibration
                       opt_sns_2_y1 1.3.6.1.4.1.9839.2.1.2.20 integer32 read-only
Analog Sensor 2 Minimum Value
                       opt_sns_2_y2 1.3.6.1.4.1.9839.2.1.2.21 integer32 read-only
Analog Sensor 2 Maximum Value
                       opt_sns_2_ain_offs 1.3.6.1.4.1.9839.2.1.2.22 integer32 read-only
Analog Sensor 2 Calibration
                       opt_sns_3_y1 1.3.6.1.4.1.9839.2.1.2.23 integer32 read-only
Analog Sensor 3 Minimum Value
                       opt_sns_3_y2 1.3.6.1.4.1.9839.2.1.2.24 integer32 read-only
Analog Sensor 3 Maximum Value
                       opt_sns_3_ain_offs 1.3.6.1.4.1.9839.2.1.2.25 integer32 read-only
Analog Sensor 3 Calibration
                       opt_sns_4_y1 1.3.6.1.4.1.9839.2.1.2.26 integer32 read-only
Analog Sensor 4 Minimum Value
                       opt_sns_4_y2 1.3.6.1.4.1.9839.2.1.2.27 integer32 read-only
Analog Sensor 4 Maximum Value
                       opt_sns_4_ain_offs 1.3.6.1.4.1.9839.2.1.2.28 integer32 read-only
Analog Sensor 4 Calibration
                   integerObjects 1.3.6.1.4.1.9839.2.1.3
                       disch_air_lo_sp 1.3.6.1.4.1.9839.2.1.3.1 integer32 read-write
Lower Limit alarm of discharge air temp
                       humidity_dis 1.3.6.1.4.1.9839.2.1.3.2 integer32 read-only
Relative humidity displayed as xx%
                       stages_on 1.3.6.1.4.1.9839.2.1.3.3 integer32 read-only
Cooling Stages On, DX only
                       heaters_on 1.3.6.1.4.1.9839.2.1.3.4 integer32 read-only
Number of heat stages running
                       minmax_24hr_hum_maximum 1.3.6.1.4.1.9839.2.1.3.5 integer32 read-only
Maximum humidity in last 24hrs
                       minmax_24hr_hum_minumum 1.3.6.1.4.1.9839.2.1.3.6 integer32 read-only
Minimum humidity in last 24hrs
                       comp_duty 1.3.6.1.4.1.9839.2.1.3.7 integer32 read-only
Cooling Utilization Over Last Hour -Percentage of cooling is used in the last hour of operation; this point applies to DX unit.
                       heat_duty 1.3.6.1.4.1.9839.2.1.3.8 integer32 read-only
Heating Utilization Over Last Hour -Percentage of heating is used in the last hour of operation
                       hum_duty 1.3.6.1.4.1.9839.2.1.3.9 integer32 read-only
Humidifier Utilization Over Last Hour -Percentage of humidifier is used in the last hour of operation
                       c1_hours_h 1.3.6.1.4.1.9839.2.1.3.10 integer32 read-only
Compressor 1 Runtime -This point applies to DX unit with one compressor -high
                       c1_hours_l 1.3.6.1.4.1.9839.2.1.3.11 integer32 read-only
Compressor 1 Runtime -This point applies to DX unit with one compressor -low
                       c2_hours_h 1.3.6.1.4.1.9839.2.1.3.12 integer32 read-only
Compressor 2 Runtime -This point applies to DX unit with dual compressor - high
                       c2_hours_l 1.3.6.1.4.1.9839.2.1.3.13 integer32 read-only
Compressor 2 Runtime -This point applies to DX unit with dual compressor - low
                       ht1_hours_h 1.3.6.1.4.1.9839.2.1.3.14 integer32 read-only
Heater 1 Runtime - high
                       ht1_hours_l 1.3.6.1.4.1.9839.2.1.3.15 integer32 read-only
Heater 1 Runtime - low
                       current_second 1.3.6.1.4.1.9839.2.1.3.16 integer32 read-only
Current second
                       current_minute 1.3.6.1.4.1.9839.2.1.3.17 integer32 read-only
Current minute
                       current_hour 1.3.6.1.4.1.9839.2.1.3.18 integer32 read-only
Current hour
                       current_day 1.3.6.1.4.1.9839.2.1.3.19 integer32 read-only
Current day
                       current_month 1.3.6.1.4.1.9839.2.1.3.20 integer32 read-only
Current month
                       current_year 1.3.6.1.4.1.9839.2.1.3.21 integer32 read-only
Current year
                       firestat_sp 1.3.6.1.4.1.9839.2.1.3.22 integer32 read-write
Alarm settting of return air temp to determine there is a fire
                       hum_hi_sp 1.3.6.1.4.1.9839.2.1.3.23 integer32 read-write
Humidity upper limit alarm
                       ret_air_hi_sp 1.3.6.1.4.1.9839.2.1.3.24 integer32 read-write
Upper limit alarm of return air temp
                       hum_lo_sp 1.3.6.1.4.1.9839.2.1.3.25 integer32 read-write
Humidity lower limit alarm
                       ret_air_lo_sp 1.3.6.1.4.1.9839.2.1.3.26 integer32 read-write
Lower limit alarm of return air temp
                       hum_deadband 1.3.6.1.4.1.9839.2.1.3.27 integer32 read-write
amount hum must change from setpoint before acting
                       hum_setpoint 1.3.6.1.4.1.9839.2.1.3.28 integer32 read-write
humidity setpoint
                       start_dly 1.3.6.1.4.1.9839.2.1.3.29 integer32 read-write
Time before the system starts up
                       alm1_del 1.3.6.1.4.1.9839.2.1.3.30 integer32 read-only
Optional Alarm 1 Delay
                       alm2_del 1.3.6.1.4.1.9839.2.1.3.31 integer32 read-only
Optional Alarm 2 Delay
                       alm3_del 1.3.6.1.4.1.9839.2.1.3.32 integer32 read-only
Optional Alarm 3 Delay
                       alarm1_txt 1.3.6.1.4.1.9839.2.1.3.33 integer32 read-only
Message on optional alarm screen, some also add function
                       alarm2_txt 1.3.6.1.4.1.9839.2.1.3.34 integer32 read-only
Message on optional alarm screen, some also add function
                       alarm3_txt 1.3.6.1.4.1.9839.2.1.3.35 integer32 read-only
Message on optional alarm screen, some also add function
                       alarm4_txt 1.3.6.1.4.1.9839.2.1.3.36 integer32 read-only
Message on optional alarm screen, some also add function
                       comp_sel 1.3.6.1.4.1.9839.2.1.3.37 integer32 read-only
Comps 0=none, 1=one, 2=one+UL, 3=two, 4=two+UL, 5=Four/two circuit
                       dehum_mode 1.3.6.1.4.1.9839.2.1.3.38 integer32 read-only
0=none, 1= comp limited, 2=twocomp limited, 3= comp unlimited, 4=twocomp unlimited
                       reheat_sel 1.3.6.1.4.1.9839.2.1.3.39 integer32 read-only
Number of heat stages
                       hum_sel 1.3.6.1.4.1.9839.2.1.3.40 integer32 read-only
0=none, 1=comp mod, 2=comp non, 3= comf mod, 4= conf non mod
                       alm_contact_msg 1.3.6.1.4.1.9839.2.1.3.41 integer32 read-only
Text displayed on all alarm screens
                       powerup_sel 1.3.6.1.4.1.9839.2.1.3.42 integer32 read-only
0= start wo/alarm, 1= start w/alarm, 2= requires reset of alarm
                       buzzer_select 1.3.6.1.4.1.9839.2.1.3.43 integer32 read-only
0=None, 1=short beeps, 2=long beep, 3=Constant
                       cw_disp 1.3.6.1.4.1.9839.2.1.3.44 integer32 read-only
% of 10volts of analog output #1
                       wtrvlv_duty 1.3.6.1.4.1.9839.2.1.3.45 integer32 read-only
Chilled Water Utilization Over Last Hour - This applies to Chilled water or Energy saver units.
                       hum_hours_h 1.3.6.1.4.1.9839.2.1.3.46 integer32 read-only
Humidifier Runtime - high
                       hum_hours_l 1.3.6.1.4.1.9839.2.1.3.47 integer32 read-only
Humidifier Runtime - low
                       blower_hours_h 1.3.6.1.4.1.9839.2.1.3.48 integer32 read-only
Blower Runtime - high
                       blower_hours_l 1.3.6.1.4.1.9839.2.1.3.49 integer32 read-only
Blower Runtime - low
                       alm4_del 1.3.6.1.4.1.9839.2.1.3.50 integer32 read-only
Optional Alarm 4 Delay
                       assist_sel 1.3.6.1.4.1.9839.2.1.3.51 integer32 read-only
0= no comp assist, 1=one comp assist, 2= two comp assist, 3... 4...
                       wtrvlv_sel 1.3.6.1.4.1.9839.2.1.3.52 integer32 read-only
Water valve type 0=none, 1=chill, 2=Engy, 3=Aux chill, 4=Disc Reg
                       wtrvlv_volts_sel 1.3.6.1.4.1.9839.2.1.3.53 integer32 read-only
Water valve voltage 0= 0-10, 1=2-10, 2=7-10, 3=6-9, 4=4-7
                       hum_volts 1.3.6.1.4.1.9839.2.1.3.54 integer32 read-only
% of 10volts of analog output #2
                       dehum_hours_h 1.3.6.1.4.1.9839.2.1.3.55 integer32 read-only
Dehumidifier Runtime - High
                       dehum_hours_l 1.3.6.1.4.1.9839.2.1.3.56 integer32 read-only
Dehumidifier Runtime - Low
                       autoflush_dly 1.3.6.1.4.1.9839.2.1.3.58 integer32 read-only
Time between drain cycles 0=12hr, 1=24hr, 2=48hr, 3=96hr, 4=None
                       y4_out 1.3.6.1.4.1.9839.2.1.3.59 integer32 read-only
Value sent to optional analog output#1
                       y5_out 1.3.6.1.4.1.9839.2.1.3.60 integer32 read-only
Value sent to optional analog output#2
                       air_flow 1.3.6.1.4.1.9839.2.1.3.61 integer32 read-only
Current Fan Airflow - Based on calculated Pressure Diff formula
                       opt_snsr1_name 1.3.6.1.4.1.9839.2.1.3.62 integer32 read-only
Name of the sensor
                       opt_sns_1_ain_type 1.3.6.1.4.1.9839.2.1.3.63 integer32 read-only
Analog Sensor 1 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170}
                       opt_snsr2_name 1.3.6.1.4.1.9839.2.1.3.64 integer32 read-only
Name of the sensor
                       opt_sns_2_ain_type 1.3.6.1.4.1.9839.2.1.3.65 integer32 read-only
Analog Sensor 2 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170}
                       opt_snsr3_name 1.3.6.1.4.1.9839.2.1.3.66 integer32 read-only
Name of the sensor
                       opt_sns_3_ain_type 1.3.6.1.4.1.9839.2.1.3.67 integer32 read-only
Analog Sensor 3 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170}
                       opt_snsr4_name 1.3.6.1.4.1.9839.2.1.3.68 integer32 read-only
Name of the sensor
                       opt_sns_4_ain_type 1.3.6.1.4.1.9839.2.1.3.69 integer32 read-only
Analog Sensor 4 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170}
                       cw_fan_speed_bms 1.3.6.1.4.1.9839.2.1.3.70 integer32 read-write
CW Fan speed (%) sent via BMS
                       dx_fan_speed_bms 1.3.6.1.4.1.9839.2.1.3.71 integer32 read-write
DX Fan speed (%) sent via BMS
                       fan_speed_max 1.3.6.1.4.1.9839.2.1.3.72 integer32 read-write
Maximum Fan speed (% of output) modulation.
                       fan_speed_min 1.3.6.1.4.1.9839.2.1.3.73 integer32 read-write
Minimum Fan speed (% of output) modulation from pressure.
                       fan_pr_sp 1.3.6.1.4.1.9839.2.1.3.74 integer32 read-write
Fan pressure setpoint (0.01 inches of water)
                       fan_pr_band 1.3.6.1.4.1.9839.2.1.3.75 integer32 read-write
Fan pressure band (0.01 inches of water)
                       fan_af_max 1.3.6.1.4.1.9839.2.1.3.76 integer32 read-write
Maximum air flow limit of setpoint from BMS or valve modulation.
                       fan_af_min 1.3.6.1.4.1.9839.2.1.3.77 integer32 read-write
Minimum air flow limit of setpoint from BMS or valve modulation.
                       fan_kfactor 1.3.6.1.4.1.9839.2.1.3.78 integer32 read-write
Fan K Factor
                       num_fans 1.3.6.1.4.1.9839.2.1.3.79 integer32 read-write
Number of fans installed in this unit
                       ht2_hours_h 1.3.6.1.4.1.9839.2.1.3.81 integer32 read-only
Heater 2 Runtime - high
                       ht2_hours_l 1.3.6.1.4.1.9839.2.1.3.82 integer32 read-only
Heater 2 Runtime - low
                       ht3_hours_h 1.3.6.1.4.1.9839.2.1.3.83 integer32 read-only
Heater 3 Runtime - high
                       ht3_hours_l 1.3.6.1.4.1.9839.2.1.3.84 integer32 read-only
Heater 3 Runtime - low
                       engy_hours_h 1.3.6.1.4.1.9839.2.1.3.85 integer32 read-only
Energy Saver Runtime - This optional point applies to energy saver units only -high
                       engy_hours_l 1.3.6.1.4.1.9839.2.1.3.86 integer32 read-only
Energy Saver Runtime - This optional point applies to energy saver units only - low
                       cw_hours_h 1.3.6.1.4.1.9839.2.1.3.87 integer32 read-only
Chilled Water Runtime - This applies to chilled water units only - high
                       cw_hours_l 1.3.6.1.4.1.9839.2.1.3.88 integer32 read-only
Chilled Water Runtime - This applies to chilled water units only - low
                       c3_hours_h 1.3.6.1.4.1.9839.2.1.3.89 integer32 read-only
Compressor 3 Runtime - This applies when unit has four stages tandem compressors - high
                       c3_hours_l 1.3.6.1.4.1.9839.2.1.3.90 integer32 read-only
Compressor 3 Runtime - This applies when unit has four stages tandem compressors - low
                       c4_hours_l 1.3.6.1.4.1.9839.2.1.3.91 integer32 read-only
Compressor 4 Runtime - This applies when unit has four stages tandem compressors. - high
                       c4_hours_h 1.3.6.1.4.1.9839.2.1.3.92 integer32 read-only
Compressor 4 Runtime - This applies when unit has four stages tandem compressors. - low
                       cond_hours_h 1.3.6.1.4.1.9839.2.1.3.93 integer32 read-only
Condenser Runtime - high
                       cond_hours_l 1.3.6.1.4.1.9839.2.1.3.94 integer32 read-only
Condenser Runtime - low
                       dx_fan_speed 1.3.6.1.4.1.9839.2.1.3.95 integer32 read-only
Fan speed (% of output) when compressor cooling.
                       cw_fan_speed 1.3.6.1.4.1.9839.2.1.3.96 integer32 read-only
Fan speed (% of output) when cold water cooling.
                       fan_af_dx_sp 1.3.6.1.4.1.9839.2.1.3.97 integer32 read-only
Fan air flow setpoint for DX unit (cfm)
                       fan_af_cw_sp 1.3.6.1.4.1.9839.2.1.3.98 integer32 read-only
Fan air flow setpoint for CW unit (cfm)
                       zm_airflow_sp 1.3.6.1.4.1.9839.2.1.3.99 integer32 read-write
Zone Airflow Setpoint kcfm