Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 lightcom 1.3.6.1.4.1.25728
             netPing 1.3.6.1.4.1.25728.253
MIB for NetPing remote sensing and control
             npReboot 1.3.6.1.4.1.25728.911
                     npSoftReboot 1.3.6.1.4.1.25728.911.1 integer read-write
Write 1 to reboot device after current operations completition
                     npResetStack 1.3.6.1.4.1.25728.911.2 integer read-write
Write 1 to re-initialize network stack
                     npForcedReboot 1.3.6.1.4.1.25728.911.3 integer read-write
Write 1 to immediate forced reboot
             npIo 1.3.6.1.4.1.25728.8900
                       npIoTable 1.3.6.1.4.1.25728.8900.1 no-access
Digital Input/output Table
                           npIoEntry 1.3.6.1.4.1.25728.8900.1.1 no-access
Digital Input/output Table Row
                               npIoLineN 1.3.6.1.4.1.25728.8900.1.1.1 integer read-only
Number of IO line, from 1 to max supported
                               npIoLevelIn 1.3.6.1.4.1.25728.8900.1.1.2 integer read-only
Input level, 0 or 1
                               npIoLevelOut 1.3.6.1.4.1.25728.8900.1.1.3 integer read-write
Output level, 0 or 1. Write -1 to flip output. Enumeration: 'high': 1, 'flip': -1, 'low': 0.
                               npIoMemo 1.3.6.1.4.1.25728.8900.1.1.6 displaystring read-only
IO line memo
                               npIoPulseCounter 1.3.6.1.4.1.25728.8900.1.1.9 counter32 read-write
Pulse Counter (counts positive fronts) Write 0 to reset.
                               npIoSinglePulseDuration 1.3.6.1.4.1.25728.8900.1.1.12 integer read-write
Set duration of single pulse on IO output line, 100ms to 25500ms, min. step is 100ms
                               npIoSinglePulseStart 1.3.6.1.4.1.25728.8900.1.1.13 integer read-write
Write 1 to start single pulse on IO output. Output will be inverted for time, specified by npIoSinglePulseDuration
                       npIoTraps 1.3.6.1.4.1.25728.8900.2
                           npIoTrapPrefix 1.3.6.1.4.1.25728.8900.2.0
                               npIoTrap 1.3.6.1.4.1.25728.8900.2.0.1
Input state of IO line is changed
                           npIoTrapLineN 1.3.6.1.4.1.25728.8900.2.1 integer read-only
Trap data, Number of IO line
                           npIoTrapLevelIn 1.3.6.1.4.1.25728.8900.2.2 integer read-only
Trap data, new Input level, 0 or 1
                           npIoTrapMemo 1.3.6.1.4.1.25728.8900.2.6 displaystring read-only
Trap data, IO line memo
                           npIoTrapLevelIn1 1.3.6.1.4.1.25728.8900.2.21 integer read-only
Trap data, current Input level Line 1, value 0 or 1
                           npIoTrapLevelIn2 1.3.6.1.4.1.25728.8900.2.22 integer read-only
Trap data, current Input level Line 2, value 0 or 1
                           npIoTrapLevelIn3 1.3.6.1.4.1.25728.8900.2.23 integer read-only
Trap data, current Input level Line 3, value 0 or 1
                           npIoTrapLevelIn4 1.3.6.1.4.1.25728.8900.2.24 integer read-only
Trap data, current Input level Line 4, value 0 or 1
             npElecMeter 1.3.6.1.4.1.25728.9700
                       npElecTable 1.3.6.1.4.1.25728.9700.1 no-access
Electricity Meter Table
                           npElecEntry 1.3.6.1.4.1.25728.9700.1.1 no-access
Electricity Meter Table Table Row
                               npElecIndex 1.3.6.1.4.1.25728.9700.1.1.1 integer read-only
Number of elec.meter, associated with IO line
                               npElecPulsesPerKwh 1.3.6.1.4.1.25728.9700.1.1.2 integer read-write
Pulses on IO line input per 1 kWh of consumed energy
                               npElecPower 1.3.6.1.4.1.25728.9700.1.1.3 gauge32 read-only
Power, Watts, based on pulse rate/interval, 5 minute average
                               npElecEnergy 1.3.6.1.4.1.25728.9700.1.1.4 counter32 read-write
Energy counter, kWh, based on pulse count
                               npElecEnergy100 1.3.6.1.4.1.25728.9700.1.1.5 counter32 read-write
Energy counter, kWh*100, based on pulse count