CPQUPS-MIB: View SNMP OID List / Download MIB

VENDOR: COMPAQ


 Home MIB: CPQUPS-MIB
Download as:   

Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 cpqUps 1.3.6.1.4.1.232.12
       cpqUpsMibRev 1.3.6.1.4.1.232.12.1
           cpqUpsMibRevMajor 1.3.6.1.4.1.232.12.1.1 integer read-only
The Major Revision level of the MIB. A change in the major revision level represents a major change in the architecture of the MIB. A change in the major revision level may indicate a significant change in the information supported and/or the meaning of the supported information, correct interpretation of data may require a MIB document with the same major revision level.
           cpqUpsMibRevMinor 1.3.6.1.4.1.232.12.1.2 integer read-only
The Minor Revision level of the MIB. A change in the minor revision level may represent some minor additional support, no changes to any pre-existing information has occurred.
           cpqUpsMibCondition 1.3.6.1.4.1.232.12.1.3 integer read-only
The overall condition. This object represents the overall status of the UPS system represented by this MIB. Enumeration: 'failed': 4, 'degraded': 3, 'other': 1, 'ok': 2.
       cpqUpsComponent 1.3.6.1.4.1.232.12.2
           cpqUpsInterface 1.3.6.1.4.1.232.12.2.1
               cpqUpsOsCommon 1.3.6.1.4.1.232.12.2.1.4
                   cpqUpsOsCommonPollFreq 1.3.6.1.4.1.232.12.2.1.4.1 integer read-write
The Insight Agent's polling frequency. The frequency, in seconds, at which the Insight Agent requests information from the device driver. A frequency of zero (0) indicates that the Insight Agent retrieves the information upon request of a management station, it does not poll the device driver at a specific interval. If the poll frequency is zero (0) all attempts to write to this object will fail. If the poll frequency is non-zero, setting this value will change the polling frequency of the Insight Agent. Setting the poll frequency to zero (0) will always fail, an agent may also choose to fail any request to change the poll frequency to a value that would severely impact system performance.
                   cpqUpsOsCommonModuleTable 1.3.6.1.4.1.232.12.2.1.4.2 no-access
A table of software modules/ that provide an interface to the device this MIB describes.
                       cpqUpsOsCommonModuleEntry 1.3.6.1.4.1.232.12.2.1.4.2.1 no-access
A description of a software module that provides an interface to the device this MIB describes.
                           cpqUpsOsCommonModuleIndex 1.3.6.1.4.1.232.12.2.1.4.2.1.1 integer read-only
A unique index for this module description.
                           cpqUpsOsCommonModuleName 1.3.6.1.4.1.232.12.2.1.4.2.1.2 displaystring read-only
The module name.
                           cpqUpsOsCommonModuleVersion 1.3.6.1.4.1.232.12.2.1.4.2.1.3 displaystring read-only
The module version in XX.YY format. Where XX is the major version number and YY is the minor version number. This field will be a null (size 0) string if the agent cannot provide the module version.
                           cpqUpsOsCommonModuleDate 1.3.6.1.4.1.232.12.2.1.4.2.1.4 octet string read-only
The module date. field octets contents range ===== ====== ======= ===== 1 1-2 year 0..65536 2 3 month 1..12 3 4 day 1..31 4 5 hour 0..23 5 6 minute 0..59 6 7 second 0..60 (use 60 for leap-second) This field will be set to year = 0 if the agent cannot provide the module date. The hour, minute, and second field will be set to zero (0) if they are not relevant. The year field is set with the most significant octet first.
                           cpqUpsOsCommonModulePurpose 1.3.6.1.4.1.232.12.2.1.4.2.1.5 displaystring read-only
The purpose of the module described in this entry.
           cpqUpsBasic 1.3.6.1.4.1.232.12.2.2
               cpqUpsLineStatus 1.3.6.1.4.1.232.12.2.2.1 integer read-only
The status of the AC line input to the UPS. Enumeration: 'failed': 4, 'other': 1, 'ok': 2.
               cpqUpsName 1.3.6.1.4.1.232.12.2.2.2 displaystring read-only
The UPS name (type).
               cpqUpsEstimatedBatteryLife 1.3.6.1.4.1.232.12.2.2.3 integer read-only
The estimated time, in minutes, of battery power available. The value will be negative one (-1) if the agent is unable to determine this information. A UPS may not provide this information when AC power is available.
               cpqUpsAutoShutdownDelay 1.3.6.1.4.1.232.12.2.2.4 integer read-write
The number of minutes of battery power remaining before the UPS driver will begin a graceful shutdown of the OS. A value of -1 indicates that no automatic shutdown will occur.
               cpqUpsLaunchCommand 1.3.6.1.4.1.232.12.2.2.5 octet string read-only
Application to launch for UPS support.
               cpqUpsAlarm 1.3.6.1.4.1.232.12.2.2.6 displaystring read-only
This variable contains the UPS alarm text.
           cpqUpsFamily 1.3.6.1.4.1.232.12.2.3
               cpqUpsMemberTable 1.3.6.1.4.1.232.12.2.3.1 no-access
A table of entries that describes the family of rack-mounted servers that a single UPS supports.
                   cpqUpsMemberEntry 1.3.6.1.4.1.232.12.2.3.1.1 no-access
A table of entries that describes the family of rack-mounted servers that a single UPS supports.
                       cpqUpsMemberIndex 1.3.6.1.4.1.232.12.2.3.1.1.1 integer read-write
A unique index for this module description.
                       cpqUpsMemberName 1.3.6.1.4.1.232.12.2.3.1.1.2 displaystring read-write
The name or address of one of the individual servers that is served by the rack-mounted UPS. Set cpqUpsMemberName to 0 to delete this row.
                       cpqUpsMemberCommunityStr 1.3.6.1.4.1.232.12.2.3.1.1.3 displaystring read-write
The Community string for this individual server.
               cpqUpsAddMemberName 1.3.6.1.4.1.232.12.2.3.2 displaystring read-write
To add a row to the cpqUpsMemberTable, this variable must be set, followed immediately by the set of the cpqUpsAddMemberCommunityStr. Sets must occur in this order, or else a new row will not be added to the table.
               cpqUpsAddMemberCommunityStr 1.3.6.1.4.1.232.12.2.3.3 displaystring read-write
To add a row to the cpqUpsMemberTable, the cpqUpsAddMemberName must be set, followed immediately by a set of this variable. Sets must occur in this order, or else a new row will not be added to the cpqUpsMemberTable.
   cpqUpsLineFailed 1.3.6.1.4.1.2320.12001
AC Line power failure. The UPS reports that the AC line power has failed.
   cpqUpsLineOk 1.3.6.1.4.1.2320.12002
AC line power ok. The UPS reports that the AC line power has returned.
   cpqUpsShutdown 1.3.6.1.4.1.2320.12003
UPS initiating graceful server shutdown. The UPS software is initiating a graceful server shutdown. Every attempt to preserve the state of the file system will be made. The server shutdown will be initiated due to a power anomaly.
   cpqUpsConfirmation 1.3.6.1.4.1.2320.12004
Server now operational after power down. This server has previously been shutdown due to a power anomaly and has just become operational again.
   cpqUpsBatteryLow 1.3.6.1.4.1.2320.12005
UPS Battery Low. The server will soon lose power.
   cpqUps2LineFailed 1.3.6.1.4.1.2320.12006
AC Line power failure. The UPS reports that the AC line power has failed.
   cpqUps2LineOk 1.3.6.1.4.1.2320.12007
AC line power ok. The UPS reports that the AC line power has returned.
   cpqUps2Shutdown 1.3.6.1.4.1.2320.12008
UPS initiating graceful server shutdown. The UPS software is initiating a graceful server shutdown. Every attempt to preserve the state of the file system will be made. The server shutdown will be initiated due to a power anomaly.
   cpqUps2Confirmation 1.3.6.1.4.1.2320.12009
Server now operational after power down. This server has previously been shutdown due to a power anomaly and has just become operational again.
   cpqUps2BatteryLow 1.3.6.1.4.1.2320.12010
UPS Battery Low. The server will soon lose power.
   cpqUpsOverload 1.3.6.1.4.1.2320.12011
The UPS has entered an overload condition. A failure may occur unless the overload is corrected.
   cpqUpsPendingBatteryFailure 1.3.6.1.4.1.2320.12012
The UPS battery is about to fail. Replace as soon as possible.
   cpqUpsGenericCritical 1.3.6.1.4.1.2320.12013
Generic UPS critical alarm.
   cpqUpsGenericInfo 1.3.6.1.4.1.2320.12014
Generic UPS informational alarm.