CAREL-ug40cdz-MIB: View SNMP OID List / Download MIB

VENDOR: CAREL


 Home MIB: CAREL-ug40cdz-MIB
Download as:   

Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 carel 1.3.6.1.4.1.9839
           systm 1.3.6.1.4.1.9839.1
               agentRelease 1.3.6.1.4.1.9839.1.1 integer32 read-only
Release of the Agent.
               agentCode 1.3.6.1.4.1.9839.1.2 integer32 read-only
Code of the Agent. 1=WebGate
           instruments 1.3.6.1.4.1.9839.2
               webGateInfo 1.3.6.1.4.1.9839.2.0
                   agentParameters 1.3.6.1.4.1.9839.2.0.1
                       netSize 1.3.6.1.4.1.9839.2.0.1.1 integer32 read-write
Network size. It corresponds to the number of units connected to the WebGate.
                       baudRate 1.3.6.1.4.1.9839.2.0.1.2 integer32 read-write
Baudrate of the Carel network.
                   unitTypeGroup 1.3.6.1.4.1.9839.2.0.2
                       unit1_Type 1.3.6.1.4.1.9839.2.0.2.1 displaystring read-only
Type of the unit having serial address 1.
                   unitCodeGroup 1.3.6.1.4.1.9839.2.0.3
                       unit1_Code 1.3.6.1.4.1.9839.2.0.3.1 integer32 read-only
Code of the unit having serial address 1.
                   unitSoftwareReleaseGroup 1.3.6.1.4.1.9839.2.0.4
                       unit1_SoftwareRelease 1.3.6.1.4.1.9839.2.0.4.1 integer32 read-only
Software release of the unit having serial address 1.
                   unitMinSoftwareReleaseGroup 1.3.6.1.4.1.9839.2.0.5
                       unit1_MinSoftwareRelease 1.3.6.1.4.1.9839.2.0.5.1 integer32 read-only
Minimum software release of the unit having serial address 1.
                   unitMaxSoftwareReleaseGroup 1.3.6.1.4.1.9839.2.0.6
                       unit1_MaxSoftwareRelease 1.3.6.1.4.1.9839.2.0.6.1 integer32 read-only
Maximum software release of the unit having serial address 1.
                   unitNoAnswerCounterGroup 1.3.6.1.4.1.9839.2.0.7
                       unit1_NoAnswerCounter 1.3.6.1.4.1.9839.2.0.7.1 integer32 read-only
No answer counter of the unit having serial address 1.
                   unitErrorChecksumCounterGroup 1.3.6.1.4.1.9839.2.0.8
                       unit1_ErrorChecksumCounter 1.3.6.1.4.1.9839.2.0.8.1 integer32 read-only
Error checksum counter of the unit having serial address 1.
                   unitTimeoutCounterGroup 1.3.6.1.4.1.9839.2.0.9
                       unit1_TimeoutCounter 1.3.6.1.4.1.9839.2.0.9.1 integer32 read-only
Timeout counter of the unit having serial address 1.
               ug40cdzMIB 1.3.6.1.4.1.9839.2.1
This is the MIB module for the UG40 Close Control Uniflair device.
                   digitalObjects 1.3.6.1.4.1.9839.2.1.1
                       systemOn 1.3.6.1.4.1.9839.2.1.1.1 integer32 read-only
System On (Fan)
                       compressore1 1.3.6.1.4.1.9839.2.1.1.2 integer32 read-only
Compressor 1
                       compressore2 1.3.6.1.4.1.9839.2.1.1.3 integer32 read-only
Compressor 2
                       compressore3 1.3.6.1.4.1.9839.2.1.1.4 integer32 read-only
Compressor 3
                       compressore4 1.3.6.1.4.1.9839.2.1.1.5 integer32 read-only
Compressor 4
                       heating1 1.3.6.1.4.1.9839.2.1.1.6 integer32 read-only
Heating 1
                       heating2 1.3.6.1.4.1.9839.2.1.1.7 integer32 read-only
Heating 2
                       hotGasCoil 1.3.6.1.4.1.9839.2.1.1.9 integer32 read-only
Hot Gas Coil
                       dehumidification 1.3.6.1.4.1.9839.2.1.1.10 integer32 read-only
Dehumidification
                       humidification 1.3.6.1.4.1.9839.2.1.1.11 integer32 read-only
Humidification
                       emerg 1.3.6.1.4.1.9839.2.1.1.12 integer32 read-only
Main Power Loss
                       alarmAccess 1.3.6.1.4.1.9839.2.1.1.20 integer32 read-only
Tampering Alarm
                       alarmRoomHT 1.3.6.1.4.1.9839.2.1.1.21 integer32 read-only
Alarm: Room High Temperature
                       alarmRoomLT 1.3.6.1.4.1.9839.2.1.1.22 integer32 read-only
Alarm: Room Low Temperature
                       alarmRoomHH 1.3.6.1.4.1.9839.2.1.1.23 integer32 read-only
Alarm: Room High Humidity
                       alarmRoomLH 1.3.6.1.4.1.9839.2.1.1.24 integer32 read-only
Alarm: Room Low Humidity
                       alarmRoomEAP 1.3.6.1.4.1.9839.2.1.1.25 integer32 read-only
Room T+H Limits by External Sensors
                       alarmFilter 1.3.6.1.4.1.9839.2.1.1.26 integer32 read-only
Alarm: Clogged Filter
                       alarmFlood 1.3.6.1.4.1.9839.2.1.1.27 integer32 read-only
Alarm: Water Leakage Detected
                       alarmAirFlow 1.3.6.1.4.1.9839.2.1.1.28 integer32 read-only
Alarm: Loss of Air Flow
                       alarmHeater 1.3.6.1.4.1.9839.2.1.1.29 integer32 read-only
Alarm: Heater Overheating
                       alarmHP1 1.3.6.1.4.1.9839.2.1.1.30 integer32 read-only
Alarm: Circuit 1 High Pressure
                       alarmHP2 1.3.6.1.4.1.9839.2.1.1.31 integer32 read-only
Alarm: Circuit 1 High Pressure
                       alarmLP1 1.3.6.1.4.1.9839.2.1.1.32 integer32 read-only
Alarm: Circuit 1 Low Pressure
                       alarmLP2 1.3.6.1.4.1.9839.2.1.1.33 integer32 read-only
Alarm: Circuit 2 Low Pressure
                       alarmEXV1 1.3.6.1.4.1.9839.2.1.1.34 integer32 read-only
Alarm: Circuit 1 Electronic Valve Failure
                       alarmEXV2 1.3.6.1.4.1.9839.2.1.1.35 integer32 read-only
Alarm: Circuit 2 Electronic Valve Failure
                       alarmPSE 1.3.6.1.4.1.9839.2.1.1.36 integer32 read-only
Alarm: Wrong Phase Sequence
                       alarmSmokeFire 1.3.6.1.4.1.9839.2.1.1.37 integer32 read-only
Alarm: SMOKE-FIRE DETECTED
                       alarmLAN 1.3.6.1.4.1.9839.2.1.1.38 integer32 read-only
Interrupted LAN Alarm
                       alarmHUHC 1.3.6.1.4.1.9839.2.1.1.39 integer32 read-only
Alarm: Humidifier High Current
                       alarmHUPL 1.3.6.1.4.1.9839.2.1.1.40 integer32 read-only
Alarm: Humidifier Power Loss
                       alarmHUWL 1.3.6.1.4.1.9839.2.1.1.41 integer32 read-only
Alarm: Humidifier Water Loss
                       alarmCWDHT 1.3.6.1.4.1.9839.2.1.1.42 integer32 read-only
Alarm: CW Temperature too High for Dehumidification
                       alarmCWF 1.3.6.1.4.1.9839.2.1.1.43 integer32 read-only
Alarm: CW Valve Failure or Water Flow too Low
                       alarmCWFF 1.3.6.1.4.1.9839.2.1.1.44 integer32 read-only
Alarm: Loss of Water Flow
                       alarmCWHT 1.3.6.1.4.1.9839.2.1.1.45 integer32 read-only
Alarm: High Chilled Water Temperature
                       alarmRTS 1.3.6.1.4.1.9839.2.1.1.46 integer32 read-only
Alarm: Room Temp. Sensor Failed/Disconnected
                       alarmHWS 1.3.6.1.4.1.9839.2.1.1.47 integer32 read-only
Alarm: Hot Water Temp. Sensor Failed/Disconnected
                       alarmCWS 1.3.6.1.4.1.9839.2.1.1.48 integer32 read-only
Alarm: Chilled Water Temp. Sensor Failed/Disconnected
                       alarmOTS 1.3.6.1.4.1.9839.2.1.1.49 integer32 read-only
Alarm: Outdoor Temperature Sensor Failed/Disconnected
                       alarmDTS 1.3.6.1.4.1.9839.2.1.1.50 integer32 read-only
Alarm: Delivery Air Temp. Sensor Failed/Disconnected
                       alarmRHS 1.3.6.1.4.1.9839.2.1.1.51 integer32 read-only
Alarm: Room Humidity Sensor Failed/Disconnected
                       alarmCWOTS 1.3.6.1.4.1.9839.2.1.1.52 integer32 read-only
Alarm: Chilled Water Outlet T. Sensor Failed/Disconnected
                       alarmC1Hours 1.3.6.1.4.1.9839.2.1.1.53 integer32 read-only
ServiceAlarm: Compressor 1 hour counter threshold
                       alarmC2Hours 1.3.6.1.4.1.9839.2.1.1.54 integer32 read-only
ServiceAlarm: Compressor 2 hour counter threshold
                       alarmC3Hours 1.3.6.1.4.1.9839.2.1.1.55 integer32 read-only
ServiceAlarm: Compressor 3 hour counter threshold
                       alarmC4Hours 1.3.6.1.4.1.9839.2.1.1.56 integer32 read-only
ServiceAlarm: Compressor 4 hour counter threshold
                       alarmFilterHours 1.3.6.1.4.1.9839.2.1.1.57 integer32 read-only
ServiceAlarm: Air Filter hour counter threshold
                       alarmHeat1Hours 1.3.6.1.4.1.9839.2.1.1.58 integer32 read-only
ServiceAlarm: Heater 1 hour counter threshold
                       alarmHeat2Hours 1.3.6.1.4.1.9839.2.1.1.59 integer32 read-only
ServiceAlarm: Heater 1 hour counter threshold
                       alarmHumHours 1.3.6.1.4.1.9839.2.1.1.60 integer32 read-only
ServiceAlarm: Humidifier hour counter threshold
                       alarmUnitHours 1.3.6.1.4.1.9839.2.1.1.61 integer32 read-only
ServiceAlarm: Unit hour counter threshold
                       alarmDI2 1.3.6.1.4.1.9839.2.1.1.62 integer32 read-only
Alarm by Digital Input 2
                       alarmDI4 1.3.6.1.4.1.9839.2.1.1.63 integer32 read-only
Alarm by Digital Input 4
                       alarmDI6 1.3.6.1.4.1.9839.2.1.1.64 integer32 read-only
Alarm by Digital Input 6
                       alarmHum 1.3.6.1.4.1.9839.2.1.1.65 integer32 read-only
Humidifier General Alarm
                       alarmGeneral 1.3.6.1.4.1.9839.2.1.1.66 integer32 read-only
General Alarm
                       alarm2ndLevel 1.3.6.1.4.1.9839.2.1.1.67 integer32 read-only
Standby Unit Switchover Alarm
                       alarmA 1.3.6.1.4.1.9839.2.1.1.68 integer32 read-only
Type A Alarm
                       alarmB 1.3.6.1.4.1.9839.2.1.1.69 integer32 read-only
Type B Alarm
                       alarmC 1.3.6.1.4.1.9839.2.1.1.70 integer32 read-only
Type C Alarm
                       selDXCW 1.3.6.1.4.1.9839.2.1.1.71 integer32 read-write
DX/CW Switch on TC Units
                       selSW 1.3.6.1.4.1.9839.2.1.1.72 integer32 read-write
Summer/Winter Switchover
                       systemOnOff 1.3.6.1.4.1.9839.2.1.1.75 integer32 read-write
System On-Off
                       resetAlarm 1.3.6.1.4.1.9839.2.1.1.76 integer32 read-write
Alarm Reset
                       resetHrsFilt 1.3.6.1.4.1.9839.2.1.1.77 integer32 read-write
Filter Run Hours Reset
                       resetHrC1 1.3.6.1.4.1.9839.2.1.1.78 integer32 read-write
Compressor 1 Run Hours Reset
                       resetHrC2 1.3.6.1.4.1.9839.2.1.1.79 integer32 read-write
Compressor 2 Run Hours Reset
                       resetHrC3 1.3.6.1.4.1.9839.2.1.1.80 integer32 read-write
Compressor 3 Run Hours Reset
                       resetHrC4 1.3.6.1.4.1.9839.2.1.1.81 integer32 read-write
Compressor 4 Run Hours Reset
                       resetStC1 1.3.6.1.4.1.9839.2.1.1.82 integer32 read-write
Compressor 1 Starting Counter Reset
                       resetStC2 1.3.6.1.4.1.9839.2.1.1.83 integer32 read-write
Compressor 2 Starting Counter Reset
                       resetStC3 1.3.6.1.4.1.9839.2.1.1.84 integer32 read-write
Compressor 3 Starting Counter Reset
                       resetStC4 1.3.6.1.4.1.9839.2.1.1.85 integer32 read-write
Compressor 4 Starting Counter Reset
                       resetHrH1 1.3.6.1.4.1.9839.2.1.1.86 integer32 read-write
Heater 1 Run Hours Reset
                       resetHrH2 1.3.6.1.4.1.9839.2.1.1.87 integer32 read-write
Heater 2 Run Hours Reset
                       resetStH1 1.3.6.1.4.1.9839.2.1.1.88 integer32 read-write
Heater 1 Starting Counter Reset
                       resetStH2 1.3.6.1.4.1.9839.2.1.1.89 integer32 read-write
Heater 2 Starting Counter Reset
                       resetHrHU 1.3.6.1.4.1.9839.2.1.1.90 integer32 read-write
Humidifier Run Hours Reset
                       resetStHU 1.3.6.1.4.1.9839.2.1.1.91 integer32 read-write
Humidifier Starting Counter Reset
                       resetHrACU 1.3.6.1.4.1.9839.2.1.1.92 integer32 read-write
Unit Run Hours Reset
                       sleepmode 1.3.6.1.4.1.9839.2.1.1.95 integer32 read-write
Setback Mode (Sleep Mode)
                       smtest 1.3.6.1.4.1.9839.2.1.1.96 integer32 read-write
Sleep Mode Test
                       enablemeanT 1.3.6.1.4.1.9839.2.1.1.97 integer32 read-write
Local/Mean Usage of Values
                   analogObjects 1.3.6.1.4.1.9839.2.1.2
                       roomTemp 1.3.6.1.4.1.9839.2.1.2.1 integer32 read-only
Room Temperature
                       outdoorTemp 1.3.6.1.4.1.9839.2.1.2.2 integer32 read-only
Ambient Temperature
                       deliveryTemp 1.3.6.1.4.1.9839.2.1.2.3 integer32 read-write
Delivery Air Temperature
                       cwTemp 1.3.6.1.4.1.9839.2.1.2.4 integer32 read-only
Chilled Water Temperature
                       hwTemp 1.3.6.1.4.1.9839.2.1.2.5 integer32 read-only
Hot Water Temperature
                       roomRH 1.3.6.1.4.1.9839.2.1.2.6 integer32 read-only
Room Relative Humidity
                       cwoTemp 1.3.6.1.4.1.9839.2.1.2.7 integer32 read-only
Chilled Water Outlet Temperature
                       evapPress1 1.3.6.1.4.1.9839.2.1.2.8 integer32 read-write
Circuit 1 Evaporating Pressure
                       evapPress2 1.3.6.1.4.1.9839.2.1.2.9 integer32 read-write
Circuit 2 Evaporating Pressure
                       suctTemp1 1.3.6.1.4.1.9839.2.1.2.10 integer32 read-only
Circuit 1 Suction Temperature
                       suctTemp2 1.3.6.1.4.1.9839.2.1.2.11 integer32 read-only
Circuit 2 Suction Temperature
                       evapTemp1 1.3.6.1.4.1.9839.2.1.2.12 integer32 read-only
Circuit 1 Evap.Temperature
                       evapTemp2 1.3.6.1.4.1.9839.2.1.2.13 integer32 read-only
Circuit 2 Evap.Temperature
                       ssh1 1.3.6.1.4.1.9839.2.1.2.14 integer32 read-only
Circuit 1 Superheat
                       ssh2 1.3.6.1.4.1.9839.2.1.2.15 integer32 read-only
Circuit 2 Superheat
                       coolRamp 1.3.6.1.4.1.9839.2.1.2.16 integer32 read-only
Cooling Valve Ramp
                       heatRamp 1.3.6.1.4.1.9839.2.1.2.17 integer32 read-only
Heating Valve Ramp
                       fanSpeed 1.3.6.1.4.1.9839.2.1.2.18 integer32 read-only
Evapor. Fan Speed
                       coolSetP 1.3.6.1.4.1.9839.2.1.2.20 integer32 read-write
Cooling Set Point
                       coolDiff 1.3.6.1.4.1.9839.2.1.2.21 integer32 read-write
Cooling Prop.Band
                       cool2SetP 1.3.6.1.4.1.9839.2.1.2.22 integer32 read-write
Cooling 2nd Set Point
                       heatSetP 1.3.6.1.4.1.9839.2.1.2.23 integer32 read-write
Heating Set point
                       heat2SetP 1.3.6.1.4.1.9839.2.1.2.24 integer32 read-write
Heating 2nd Set point
                       heatDiff 1.3.6.1.4.1.9839.2.1.2.25 integer32 read-write
Heating Prop.Band
                       thrsHT 1.3.6.1.4.1.9839.2.1.2.26 integer32 read-write
High Room Temperature Alarm Threshold
                       thrsLT 1.3.6.1.4.1.9839.2.1.2.27 integer32 read-write
Low Room Temperature Alarm Threshold
                       smCoolSetp 1.3.6.1.4.1.9839.2.1.2.28 integer32 read-write
Setback Mode: Cooling Setpoint
                       smHeatSetp 1.3.6.1.4.1.9839.2.1.2.29 integer32 read-write
Setback Mode: Heating Setpoint
                       cwDehumSetp 1.3.6.1.4.1.9839.2.1.2.30 integer32 read-write
CW Setpoint to Start Dehumidification
                       cwHtThrsh 1.3.6.1.4.1.9839.2.1.2.31 integer32 read-write
CW High Temperature Alarm Threshold
                       cwModeSetp 1.3.6.1.4.1.9839.2.1.2.32 integer32 read-write
CW Setpoint to start CW Operating Mode (Only TC Units)
                       radcoolSpES 1.3.6.1.4.1.9839.2.1.2.33 integer32 read-write
Radcooler Setpoint in Energy Saving Mode
                       radcoolSpDX 1.3.6.1.4.1.9839.2.1.2.34 integer32 read-write
Radcooler Setpoint in DX Mode
                       delTempLimit 1.3.6.1.4.1.9839.2.1.2.35 integer32 read-write
Delivery Temperature Low Limit Setpoint
                       dtAutChgMLT 1.3.6.1.4.1.9839.2.1.2.36 integer32 read-write
Delta Temperature for Automatic Mean/Local Changeover
                   integerObjects 1.3.6.1.4.1.9839.2.1.3
                       filterWorkH 1.3.6.1.4.1.9839.2.1.3.1 integer32 read-only
Air Filter Working Houres
                       unitWorkH 1.3.6.1.4.1.9839.2.1.3.2 integer32 read-only
Unit Working Houres
                       compr1WorkH 1.3.6.1.4.1.9839.2.1.3.3 integer32 read-only
Compressor 1 Run Hours
                       compr2WorkH 1.3.6.1.4.1.9839.2.1.3.4 integer32 read-only
Compressor 2 Run Hours
                       compr3WorkH 1.3.6.1.4.1.9839.2.1.3.5 integer32 read-only
Compressor 3 Run Hours
                       compr4WorkH 1.3.6.1.4.1.9839.2.1.3.6 integer32 read-only
Compressor 4 Run Hours
                       heat1WorkH 1.3.6.1.4.1.9839.2.1.3.7 integer32 read-only
Heater 1 Run Hours
                       heat2WorkH 1.3.6.1.4.1.9839.2.1.3.8 integer32 read-only
Heater 2 Run Hours
                       humiWorkH 1.3.6.1.4.1.9839.2.1.3.9 integer32 read-only
Humidifier Run Hours
                       dehumPband 1.3.6.1.4.1.9839.2.1.3.12 integer32 read-write
Dehumidification Prop.Band
                       humidPband 1.3.6.1.4.1.9839.2.1.3.13 integer32 read-write
Humidification Prop.Band
                       hhAlarmThrsh 1.3.6.1.4.1.9839.2.1.3.14 integer32 read-write
High Humidity Alarm Threshold
                       lhAlarmThrsh 1.3.6.1.4.1.9839.2.1.3.15 integer32 read-write
Low Humidity Alarm Threshold
                       dehumSetp 1.3.6.1.4.1.9839.2.1.3.16 integer32 read-write
Dehumidification Setpoint
                       smDehumSetp 1.3.6.1.4.1.9839.2.1.3.17 integer32 read-write
Setback Mode: Dehumidification Setpoint
                       humidSetp 1.3.6.1.4.1.9839.2.1.3.18 integer32 read-write
Humidification Setpoint
                       smHumidSetp 1.3.6.1.4.1.9839.2.1.3.19 integer32 read-write
Setback Mode: Humidification Setpoint
                       pwOnDelay 1.3.6.1.4.1.9839.2.1.3.20 integer32 read-write
Restart Delay
                       regulDelay 1.3.6.1.4.1.9839.2.1.3.21 integer32 read-write
Regulation Start Transitory
                       lowPdelay 1.3.6.1.4.1.9839.2.1.3.22 integer32 read-write
Low Pressure Delay
                       thAlarmdelay 1.3.6.1.4.1.9839.2.1.3.23 integer32 read-write
Temp./Humid.Limits Alarm Delay
                       regExcTime 1.3.6.1.4.1.9839.2.1.3.24 integer32 read-write
Anti-Hunting Constant
                       stdbyTime 1.3.6.1.4.1.9839.2.1.3.25 integer32 read-write
Stand-by Cycle Base Time
                       lanUnit 1.3.6.1.4.1.9839.2.1.3.27 integer32 read-write
Number of LAN Units
                       smCycleTime 1.3.6.1.4.1.9839.2.1.3.28 integer32 read-write
Sleep Mode Testing Cycle Time
                       exv1steps 1.3.6.1.4.1.9839.2.1.3.29 integer32 read-only
Circuit 1 EXV Valve Position
                       exv2steps 1.3.6.1.4.1.9839.2.1.3.30 integer32 read-only
Circuit 2 EXV Valve Position