ALPHA-INVERTER-SYS-MIB: View SNMP OID List / Download MIB
VENDOR: ARGUS TECHNOLOGIES
Home | MIB: ALPHA-INVERTER-SYS-MIB | |||
---|---|---|---|---|
Download as: |
Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
|
|||
Object Name | OID | Type | Access | Info |
inverterSystem | 1.3.6.1.4.1.7309.5.3.3 |
This MIB provides a flat list of data points available from the Cordex HP controller to present information of one Inverter System. |
||
invTotalAcOutputPowerVa | 1.3.6.1.4.1.7309.5.3.3.1 | scalednumber | read-only |
The total output power summed from all the phases (VA). |
invSysAverageLoadingOfInstalledPowerVa | 1.3.6.1.4.1.7309.5.3.3.2 | scalednumber | read-only |
The average output loading of all phases (% VA). |
invSysAverageDcInputToOutputPowerRatio | 1.3.6.1.4.1.7309.5.3.3.3 | scalednumber | read-only |
The percentage of the output that is taken from the DC input (%). |
invSysSystemMode | 1.3.6.1.4.1.7309.5.3.3.4 | scalednumber | read-only |
The mode of the system. See manual for decoding the number. |
invSysPhase1OutputPowerVa | 1.3.6.1.4.1.7309.5.3.3.5 | scalednumber | read-only |
The total output power from the phase 1 (VA). |
invSysPhase2OutputPowerVa | 1.3.6.1.4.1.7309.5.3.3.6 | scalednumber | read-only |
The total output power from phase 2 (VA). |
invSysPhase3OutputPowerVa | 1.3.6.1.4.1.7309.5.3.3.7 | scalednumber | read-only |
The total output power from the phase 3 (VA). |
invSysAverageOutputVoltageMeasured | 1.3.6.1.4.1.7309.5.3.3.8 | scalednumber | read-only |
The average output voltage of all the phases (V). |
invSysEnabledDisconnects | 1.3.6.1.4.1.7309.5.3.3.9 | scalednumber | read-only |
The number of disconnects that are enabled. |
invSysActivatedDisconnects | 1.3.6.1.4.1.7309.5.3.3.10 | scalednumber | read-only |
The number of disconnects that are active. |
invSysTotalDCInputCurrent | 1.3.6.1.4.1.7309.5.3.3.11 | scalednumber | read-only |
Total DC input current for the inverter system (A). |
invSysAverageDcInputVoltage | 1.3.6.1.4.1.7309.5.3.3.12 | scalednumber | read-only |
Average DC input voltage reading for the inverter system (V). |
invSysTotalDcInputPower | 1.3.6.1.4.1.7309.5.3.3.13 | scalednumber | read-only |
Total DC input power reading for the inverter system (W). |
invSysSystemOnBypass | 1.3.6.1.4.1.7309.5.3.3.14 | scalednumber | read-only |
True when the bypass switch is on. The AC input from the grid is fed to the AC load directly. |
invSysTotalAcInputPowerVa | 1.3.6.1.4.1.7309.5.3.3.18 | scalednumber | read-only |
Total AC input power reading of the Inverter System (VA). |
phaseGroup | 1.3.6.1.4.1.7309.5.3.3.80 | |||
invSysAcPhaseCount | 1.3.6.1.4.1.7309.5.3.3.80.1 | integer32 | read-only |
|
invSysAcPhaseTable | 1.3.6.1.4.1.7309.5.3.3.80.2 | no-access |
|
|
1.3.6.1.4.1.7309.5.3.3.80.2.1 | no-access |
|
||
invSysAcPhaseAcOutputPowerVa | 1.3.6.1.4.1.7309.5.3.3.80.2.1.1 | scalednumber | read-only |
The power of the AC output (VA). |
invSysAcPhaseOutputVoltageMeasured | 1.3.6.1.4.1.7309.5.3.3.80.2.1.2 | scalednumber | read-only |
The output voltage of the phase or inverter (V). |
invSysAcPhaseOutputCurrent | 1.3.6.1.4.1.7309.5.3.3.80.2.1.3 | scalednumber | read-only |
The output current of the phase or inverter (A). |
invSysAcPhaseFrequency | 1.3.6.1.4.1.7309.5.3.3.80.2.1.4 | scalednumber | read-only |
Frequency to which the inverters will lock (Hz). |
invSysAcPhaseLoadingOfInstalledPowerVa | 1.3.6.1.4.1.7309.5.3.3.80.2.1.5 | scalednumber | read-only |
The ratio of output load to installed power (%VA). |
invSysAcPhaseNumberOfModulesOn | 1.3.6.1.4.1.7309.5.3.3.80.2.1.6 | scalednumber | read-only |
The number of inverters that are On and can deliver power. |
invSysAcPhaseLoadingOfInstalledPowerWatts | 1.3.6.1.4.1.7309.5.3.3.80.2.1.7 | scalednumber | read-only |
The ratio of output load to installed power (% W). |
invSysAcPhaseDcInputToOutputPowerRatioMeasured | 1.3.6.1.4.1.7309.5.3.3.80.2.1.8 | scalednumber | read-only |
The measured percentage of DC input power to output power(%). Under light or no load this value will not computed accurately. |
invSysAcPhaseAcInputPowerWatts | 1.3.6.1.4.1.7309.5.3.3.80.2.1.9 | scalednumber | read-only |
The power drawn by the AC input (W). |
invSysAcPhaseAcInputPowerVa | 1.3.6.1.4.1.7309.5.3.3.80.2.1.10 | scalednumber | read-only |
The power drawn by the AC input (VA). |
invSysAcPhaseAcOutputPowerWatts | 1.3.6.1.4.1.7309.5.3.3.80.2.1.11 | scalednumber | read-only |
The power of the AC output (W). |
invSysAcPhaseDCInputPowerWatts | 1.3.6.1.4.1.7309.5.3.3.80.2.1.12 | scalednumber | read-only |
The power drawn by the DC input (W). |
invSysAcPhaseNumberOfRedundantModulesMeasured | 1.3.6.1.4.1.7309.5.3.3.80.2.1.13 | scalednumber | read-only |
Number of inverters currently unneeded by the load. |
invSysAcPhaseNumberOfModulesDetected | 1.3.6.1.4.1.7309.5.3.3.80.2.1.14 | scalednumber | read-only |
The number of inverters assigned to this phase that the T2S has detected. |
invSysAcPhaseNumberOfModulesOff | 1.3.6.1.4.1.7309.5.3.3.80.2.1.15 | scalednumber | read-only |
The number of inverters that are manually turned off. |
invSysAcPhaseNumberOfModulesFailed | 1.3.6.1.4.1.7309.5.3.3.80.2.1.16 | scalednumber | read-only |
The number of inverters that have failed and cannot deliver power. |
acInputGroup | 1.3.6.1.4.1.7309.5.3.3.81 | |||
invSysAcInputCount | 1.3.6.1.4.1.7309.5.3.3.81.1 | integer32 | read-only |
|
invSysAcInputTable | 1.3.6.1.4.1.7309.5.3.3.81.2 | no-access |
|
|
1.3.6.1.4.1.7309.5.3.3.81.2.1 | no-access |
|
||
invSysAcInputInputVoltage | 1.3.6.1.4.1.7309.5.3.3.81.2.1.1 | scalednumber | read-only |
The input voltage of the inverter or group (V). |
invSysAcInputInputCurrent | 1.3.6.1.4.1.7309.5.3.3.81.2.1.2 | scalednumber | read-only |
The input current of the inverter or group (A). |
invSysAcInputFrequency | 1.3.6.1.4.1.7309.5.3.3.81.2.1.3 | scalednumber | read-only |
The frequency of the input voltage and current of the inverter or group (Hz). |
invSysAcInputAcInputPowerVa | 1.3.6.1.4.1.7309.5.3.3.81.2.1.4 | scalednumber | read-only |
The power drawn by the AC input (VA). |
invSysAcInputNumberOfModulesOn | 1.3.6.1.4.1.7309.5.3.3.81.2.1.5 | scalednumber | read-only |
The number of inverters that are On and can deliver power. |
invSysAcInputAcInputPowerWatts | 1.3.6.1.4.1.7309.5.3.3.81.2.1.6 | scalednumber | read-only |
The power drawn by the AC input (W). |
invSysAcInputNumberOfModulesDetected | 1.3.6.1.4.1.7309.5.3.3.81.2.1.7 | scalednumber | read-only |
The number of inverters assigned to this phase that the T2S has detected. |
invSysAcInputNumberOfModulesOff | 1.3.6.1.4.1.7309.5.3.3.81.2.1.8 | scalednumber | read-only |
The number of inverters that are manually turned off. |
invSysAcInputNumberOfModulesFailed | 1.3.6.1.4.1.7309.5.3.3.81.2.1.9 | scalednumber | read-only |
The number of inverters that have failed and cannot deliver power. |
dcInputGroup | 1.3.6.1.4.1.7309.5.3.3.82 | |||
invSysDcInputCount | 1.3.6.1.4.1.7309.5.3.3.82.1 | integer32 | read-only |
|
invSysDcInputTable | 1.3.6.1.4.1.7309.5.3.3.82.2 | no-access |
|
|
1.3.6.1.4.1.7309.5.3.3.82.2.1 | no-access |
|
||
invSysDcInputInputVoltage | 1.3.6.1.4.1.7309.5.3.3.82.2.1.1 | scalednumber | read-only |
The input voltage of the inverter or group (V). |
invSysDcInputInputCurrent | 1.3.6.1.4.1.7309.5.3.3.82.2.1.2 | scalednumber | read-only |
The input current of the inverter or group (A). |
invSysDcInputDcInputPowerWatts | 1.3.6.1.4.1.7309.5.3.3.82.2.1.3 | scalednumber | read-only |
The power drawn by the DC input (W). |
invSysDcInputNumberOfModulesOn | 1.3.6.1.4.1.7309.5.3.3.82.2.1.4 | scalednumber | read-only |
The number of inverters that are On and can deliver power. |
invSysDcInputNumberOfModulesOff | 1.3.6.1.4.1.7309.5.3.3.82.2.1.5 | scalednumber | read-only |
The number of inverters that are manually turned off. |
invSysDcInputNumberOfModulesFailed | 1.3.6.1.4.1.7309.5.3.3.82.2.1.6 | scalednumber | read-only |
The number of inverters that have failed and cannot deliver power. |
invSysDcInputNumberOfModulesDetected | 1.3.6.1.4.1.7309.5.3.3.82.2.1.7 | scalednumber | read-only |
The number of inverters assigned to this phase that the T2S has detected. |