Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 inverterSystem 1.3.6.1.4.1.7309.5.3.3
This MIB provides a flat list of data points available from the Cordex HP controller to present information of one Inverter System.
     invTotalAcOutputPowerVa 1.3.6.1.4.1.7309.5.3.3.1 scalednumber read-only
The total output power summed from all the phases (VA).
     invSysAverageLoadingOfInstalledPowerVa 1.3.6.1.4.1.7309.5.3.3.2 scalednumber read-only
The average output loading of all phases (% VA).
     invSysAverageDcInputToOutputPowerRatio 1.3.6.1.4.1.7309.5.3.3.3 scalednumber read-only
The percentage of the output that is taken from the DC input (%).
     invSysSystemMode 1.3.6.1.4.1.7309.5.3.3.4 scalednumber read-only
The mode of the system. See manual for decoding the number.
     invSysPhase1OutputPowerVa 1.3.6.1.4.1.7309.5.3.3.5 scalednumber read-only
The total output power from the phase 1 (VA).
     invSysPhase2OutputPowerVa 1.3.6.1.4.1.7309.5.3.3.6 scalednumber read-only
The total output power from phase 2 (VA).
     invSysPhase3OutputPowerVa 1.3.6.1.4.1.7309.5.3.3.7 scalednumber read-only
The total output power from the phase 3 (VA).
     invSysAverageOutputVoltageMeasured 1.3.6.1.4.1.7309.5.3.3.8 scalednumber read-only
The average output voltage of all the phases (V).
     invSysEnabledDisconnects 1.3.6.1.4.1.7309.5.3.3.9 scalednumber read-only
The number of disconnects that are enabled.
     invSysActivatedDisconnects 1.3.6.1.4.1.7309.5.3.3.10 scalednumber read-only
The number of disconnects that are active.
     invSysTotalDCInputCurrent 1.3.6.1.4.1.7309.5.3.3.11 scalednumber read-only
Total DC input current for the inverter system (A).
     invSysAverageDcInputVoltage 1.3.6.1.4.1.7309.5.3.3.12 scalednumber read-only
Average DC input voltage reading for the inverter system (V).
     invSysTotalDcInputPower 1.3.6.1.4.1.7309.5.3.3.13 scalednumber read-only
Total DC input power reading for the inverter system (W).
     invSysSystemOnBypass 1.3.6.1.4.1.7309.5.3.3.14 scalednumber read-only
True when the bypass switch is on. The AC input from the grid is fed to the AC load directly.
     invSysTotalAcInputPowerVa 1.3.6.1.4.1.7309.5.3.3.18 scalednumber read-only
Total AC input power reading of the Inverter System (VA).
     phaseGroup 1.3.6.1.4.1.7309.5.3.3.80
           invSysAcPhaseCount 1.3.6.1.4.1.7309.5.3.3.80.1 integer32 read-only
           invSysAcPhaseTable 1.3.6.1.4.1.7309.5.3.3.80.2 no-access
               invSysAcPhaseEntry 1.3.6.1.4.1.7309.5.3.3.80.2.1 no-access
                   invSysAcPhaseAcOutputPowerVa 1.3.6.1.4.1.7309.5.3.3.80.2.1.1 scalednumber read-only
The power of the AC output (VA).
                   invSysAcPhaseOutputVoltageMeasured 1.3.6.1.4.1.7309.5.3.3.80.2.1.2 scalednumber read-only
The output voltage of the phase or inverter (V).
                   invSysAcPhaseOutputCurrent 1.3.6.1.4.1.7309.5.3.3.80.2.1.3 scalednumber read-only
The output current of the phase or inverter (A).
                   invSysAcPhaseFrequency 1.3.6.1.4.1.7309.5.3.3.80.2.1.4 scalednumber read-only
Frequency to which the inverters will lock (Hz).
                   invSysAcPhaseLoadingOfInstalledPowerVa 1.3.6.1.4.1.7309.5.3.3.80.2.1.5 scalednumber read-only
The ratio of output load to installed power (%VA).
                   invSysAcPhaseNumberOfModulesOn 1.3.6.1.4.1.7309.5.3.3.80.2.1.6 scalednumber read-only
The number of inverters that are On and can deliver power.
                   invSysAcPhaseLoadingOfInstalledPowerWatts 1.3.6.1.4.1.7309.5.3.3.80.2.1.7 scalednumber read-only
The ratio of output load to installed power (% W).
                   invSysAcPhaseDcInputToOutputPowerRatioMeasured 1.3.6.1.4.1.7309.5.3.3.80.2.1.8 scalednumber read-only
The measured percentage of DC input power to output power(%). Under light or no load this value will not computed accurately.
                   invSysAcPhaseAcInputPowerWatts 1.3.6.1.4.1.7309.5.3.3.80.2.1.9 scalednumber read-only
The power drawn by the AC input (W).
                   invSysAcPhaseAcInputPowerVa 1.3.6.1.4.1.7309.5.3.3.80.2.1.10 scalednumber read-only
The power drawn by the AC input (VA).
                   invSysAcPhaseAcOutputPowerWatts 1.3.6.1.4.1.7309.5.3.3.80.2.1.11 scalednumber read-only
The power of the AC output (W).
                   invSysAcPhaseDCInputPowerWatts 1.3.6.1.4.1.7309.5.3.3.80.2.1.12 scalednumber read-only
The power drawn by the DC input (W).
                   invSysAcPhaseNumberOfRedundantModulesMeasured 1.3.6.1.4.1.7309.5.3.3.80.2.1.13 scalednumber read-only
Number of inverters currently unneeded by the load.
                   invSysAcPhaseNumberOfModulesDetected 1.3.6.1.4.1.7309.5.3.3.80.2.1.14 scalednumber read-only
The number of inverters assigned to this phase that the T2S has detected.
                   invSysAcPhaseNumberOfModulesOff 1.3.6.1.4.1.7309.5.3.3.80.2.1.15 scalednumber read-only
The number of inverters that are manually turned off.
                   invSysAcPhaseNumberOfModulesFailed 1.3.6.1.4.1.7309.5.3.3.80.2.1.16 scalednumber read-only
The number of inverters that have failed and cannot deliver power.
     acInputGroup 1.3.6.1.4.1.7309.5.3.3.81
           invSysAcInputCount 1.3.6.1.4.1.7309.5.3.3.81.1 integer32 read-only
           invSysAcInputTable 1.3.6.1.4.1.7309.5.3.3.81.2 no-access
               invSysAcInputEntry 1.3.6.1.4.1.7309.5.3.3.81.2.1 no-access
                   invSysAcInputInputVoltage 1.3.6.1.4.1.7309.5.3.3.81.2.1.1 scalednumber read-only
The input voltage of the inverter or group (V).
                   invSysAcInputInputCurrent 1.3.6.1.4.1.7309.5.3.3.81.2.1.2 scalednumber read-only
The input current of the inverter or group (A).
                   invSysAcInputFrequency 1.3.6.1.4.1.7309.5.3.3.81.2.1.3 scalednumber read-only
The frequency of the input voltage and current of the inverter or group (Hz).
                   invSysAcInputAcInputPowerVa 1.3.6.1.4.1.7309.5.3.3.81.2.1.4 scalednumber read-only
The power drawn by the AC input (VA).
                   invSysAcInputNumberOfModulesOn 1.3.6.1.4.1.7309.5.3.3.81.2.1.5 scalednumber read-only
The number of inverters that are On and can deliver power.
                   invSysAcInputAcInputPowerWatts 1.3.6.1.4.1.7309.5.3.3.81.2.1.6 scalednumber read-only
The power drawn by the AC input (W).
                   invSysAcInputNumberOfModulesDetected 1.3.6.1.4.1.7309.5.3.3.81.2.1.7 scalednumber read-only
The number of inverters assigned to this phase that the T2S has detected.
                   invSysAcInputNumberOfModulesOff 1.3.6.1.4.1.7309.5.3.3.81.2.1.8 scalednumber read-only
The number of inverters that are manually turned off.
                   invSysAcInputNumberOfModulesFailed 1.3.6.1.4.1.7309.5.3.3.81.2.1.9 scalednumber read-only
The number of inverters that have failed and cannot deliver power.
     dcInputGroup 1.3.6.1.4.1.7309.5.3.3.82
           invSysDcInputCount 1.3.6.1.4.1.7309.5.3.3.82.1 integer32 read-only
           invSysDcInputTable 1.3.6.1.4.1.7309.5.3.3.82.2 no-access
               invSysDcInputEntry 1.3.6.1.4.1.7309.5.3.3.82.2.1 no-access
                   invSysDcInputInputVoltage 1.3.6.1.4.1.7309.5.3.3.82.2.1.1 scalednumber read-only
The input voltage of the inverter or group (V).
                   invSysDcInputInputCurrent 1.3.6.1.4.1.7309.5.3.3.82.2.1.2 scalednumber read-only
The input current of the inverter or group (A).
                   invSysDcInputDcInputPowerWatts 1.3.6.1.4.1.7309.5.3.3.82.2.1.3 scalednumber read-only
The power drawn by the DC input (W).
                   invSysDcInputNumberOfModulesOn 1.3.6.1.4.1.7309.5.3.3.82.2.1.4 scalednumber read-only
The number of inverters that are On and can deliver power.
                   invSysDcInputNumberOfModulesOff 1.3.6.1.4.1.7309.5.3.3.82.2.1.5 scalednumber read-only
The number of inverters that are manually turned off.
                   invSysDcInputNumberOfModulesFailed 1.3.6.1.4.1.7309.5.3.3.82.2.1.6 scalednumber read-only
The number of inverters that have failed and cannot deliver power.
                   invSysDcInputNumberOfModulesDetected 1.3.6.1.4.1.7309.5.3.3.82.2.1.7 scalednumber read-only
The number of inverters assigned to this phase that the T2S has detected.