XPPC-MIB: View SNMP OID List / Download MIB

VENDOR: PHOENIXTEC POWER CO.


 Home MIB: XPPC-MIB
Download as:   

Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 ppc 1.3.6.1.4.1.935
         products 1.3.6.1.4.1.935.1
             hardware 1.3.6.1.4.1.935.1.1
                 ups 1.3.6.1.4.1.935.1.1.1
                     upsIdentp 1.3.6.1.4.1.935.1.1.1.1
                         upsBaseIdent 1.3.6.1.4.1.935.1.1.1.1.1
                             upsBaseIdentModel 1.3.6.1.4.1.935.1.1.1.1.1.1 displaystring read-only
The UPS model name (e.g. 'Intelligent 8000E 900VA').
                             upsBaseIdentUpsName 1.3.6.1.4.1.935.1.1.1.1.1.2 displaystring read-write
An 8 byte ID string identifying the UPS. This object can be set by the administrator.
                         upsSmartIdent 1.3.6.1.4.1.935.1.1.1.1.2
                             upsSmartIdentFirmwareRevision 1.3.6.1.4.1.935.1.1.1.1.2.1 displaystring read-only
The firmware revision of the UPS system.
                             upsSmartIdentDateOfManufacture 1.3.6.1.4.1.935.1.1.1.1.2.2 displaystring read-only
The date when the UPS was manufactured in mm/dd/yy format.
                             upsSmartIdentUpsSerialNumber 1.3.6.1.4.1.935.1.1.1.1.2.3 displaystring read-only
An 8-character string identifying the serial number of the UPS internal microprocessor. This number is set at the factory. NOTE: This number does NOT correspond to the serial number on the rear of the UPS.
                             upsSmartIdentAgentFirmwareRevision 1.3.6.1.4.1.935.1.1.1.1.2.4 displaystring read-only
The firmware revision of the UPS SNMP Proxy agent.
                     upsBatteryp 1.3.6.1.4.1.935.1.1.1.2
                         upsBaseBattery 1.3.6.1.4.1.935.1.1.1.2.1
                             upsBaseBatteryStatus 1.3.6.1.4.1.935.1.1.1.2.1.1 integer read-only
The status of the UPS batteries. A batteryLow(3) value indicates the UPS will be unable to sustain the current load, and its services will be lost if power is not restored. The amount of run time in reserve at the time of low battery can be configured by the upsSmartConfigLowBatteryRunTime. Enumeration: 'unknown': 1, 'batteryNormal': 2, 'batteryLow': 3.
                             upsBaseBatteryTimeOnBattery 1.3.6.1.4.1.935.1.1.1.2.1.2 integer read-only
The elapsed time in seconds since the UPS has switched to battery power.
                             upsBaseBatteryLastReplaceDate 1.3.6.1.4.1.935.1.1.1.2.1.3 displaystring read-write
The date when the UPS system's batteries were last replaced in mm/dd/yy format. For UPS models, this value is originally set in the factory. When the UPS batteries are replaced, this value should be reset by the administrator.
                         upsSmartBattery 1.3.6.1.4.1.935.1.1.1.2.2
                             upsSmartBatteryCapacity 1.3.6.1.4.1.935.1.1.1.2.2.1 integer read-only
The remaining battery capacity expressed in percent of full capacity.
                             upsSmartBatteryVoltage 1.3.6.1.4.1.935.1.1.1.2.2.2 integer read-only
The current battery voltage expressed in 1/10 VDC.
                             upsSmartBatteryTemperature 1.3.6.1.4.1.935.1.1.1.2.2.3 integer read-only
The current internal UPS temperature expressed in tenths of a Celsius degree.
                             upsSmartBatteryRunTimeRemaining 1.3.6.1.4.1.935.1.1.1.2.2.4 integer read-only
The UPS battery run time remaining before battery exhaustion, in seconds.
                             upsSmartBatteryReplaceIndicator 1.3.6.1.4.1.935.1.1.1.2.2.5 integer read-only
Indicates whether the UPS batteries need replacing. Enumeration: 'batteryNeedsReplacing': 2, 'noBatteryNeedsReplacing': 1.
                             upsSmartBatteryFullChargeVoltage 1.3.6.1.4.1.935.1.1.1.2.2.6 integer read-only
The fully charged battery voltage of the battery system used in the UPS, expressed in tenths of a volt.
                             upsSmartBatteryCurrent 1.3.6.1.4.1.935.1.1.1.2.2.7 integer read-only
The current battery current expressed in percent of maximum current.
                     upsInputp 1.3.6.1.4.1.935.1.1.1.3
                         upsBaseInput 1.3.6.1.4.1.935.1.1.1.3.1
                             upsBaseInputPhase 1.3.6.1.4.1.935.1.1.1.3.1.1 integer read-only
The current AC input phase.
                         upsSmartInput 1.3.6.1.4.1.935.1.1.1.3.2
                             upsSmartInputLineVoltage 1.3.6.1.4.1.935.1.1.1.3.2.1 integer read-only
The current utility line voltage in 1/10 VAC.
                             upsSmartInputMaxLineVoltage 1.3.6.1.4.1.935.1.1.1.3.2.2 integer read-only
The maximum utility line voltage in 1/10 VAC over the previous 1 minute period.
                             upsSmartInputMinLineVoltage 1.3.6.1.4.1.935.1.1.1.3.2.3 integer read-only
The minimum utility line voltage in 1/10 VAC over the previous 1 minute period.
                             upsSmartInputFrequency 1.3.6.1.4.1.935.1.1.1.3.2.4 integer read-only
The current input frequency to the UPS system in 1/10 Hz.
                             upsSmartInputLineFailCause 1.3.6.1.4.1.935.1.1.1.3.2.5 integer read-only
The reason for the occurrence of the last transfer to UPS battery power. The variable is set to noTransfer(1) if there is no transfer yet. The variable is set to highLineVoltage(2) if the transfer to battery is caused by an over voltage greater than the high transfer voltage. The variable is set to brownout(3) if the duration of the outage is greater than five seconds and the line voltage is between 40 percent of the rated output voltage and the low transfer voltage. The variable is set to blackout(4) if the duration of the outage is greater than five seconds and the line voltage is between 40 percent of the rated output voltage and ground. The variable is set to smallMomentarySag(5) if the duration of the outage is less than five seconds and the line voltage is between 40 percent of the rated output voltage and the low transfer voltage. The variable is set to deepMomentarySag(6) if the duration of the outage is less than five seconds and the line voltage is between 40 percent of the rated output voltage and ground. Enumeration: 'highLineVoltage': 2, 'largeMomentarySpike': 8, 'brownout': 3, 'noTransfer': 1, 'deepMomentarySag': 6, 'smallMomentarySag': 5, 'smallMomentarySpike': 7, 'blackout': 4.
                     upsOutputp 1.3.6.1.4.1.935.1.1.1.4
                         upsBaseOutput 1.3.6.1.4.1.935.1.1.1.4.1
                             upsBaseOutputStatus 1.3.6.1.4.1.935.1.1.1.4.1.1 integer read-only
The current state of the UPS. If the UPS is unable to determine the state of the UPS this variable is set to unknown(1). Enumeration: 'onBypass': 6, 'onBoost': 4, 'standBy': 8, 'unknown': 1, 'rebooting': 7, 'sleeping': 5, 'onBuck': 9, 'onLine': 2, 'onBattery': 3.
                             upsBaseOutputPhase 1.3.6.1.4.1.935.1.1.1.4.1.2 integer read-only
The current output phase.
                         upsSmartOutput 1.3.6.1.4.1.935.1.1.1.4.2
                             upsSmartOutputVoltage 1.3.6.1.4.1.935.1.1.1.4.2.1 integer read-only
The output voltage of the UPS system in 1/10 VAC.
                             upsSmartOutputFrequency 1.3.6.1.4.1.935.1.1.1.4.2.2 integer read-only
The current output frequency of the UPS system in 1/10 Hz.
                             upsSmartOutputLoad 1.3.6.1.4.1.935.1.1.1.4.2.3 integer read-only
The current UPS load expressed in percent of rated capacity.
                     upsConfigp 1.3.6.1.4.1.935.1.1.1.5
                         upsBaseConfig 1.3.6.1.4.1.935.1.1.1.5.1
                             upsBaseConfigNumDevices 1.3.6.1.4.1.935.1.1.1.5.1.1 integer read-only
The number of devices that are plugged into the UPS.
                             upsBaseConfigDeviceTable 1.3.6.1.4.1.935.1.1.1.5.1.2 no-access
A list of devices that are plugged into the UPS. The number of entries is given by the value of upsBaseConfigNumDevices.
                                 upsBaseConfigDeviceEntry 1.3.6.1.4.1.935.1.1.1.5.1.2.1 no-access
The devices plugged in to the UPS.
                                     indexOfDevice 1.3.6.1.4.1.935.1.1.1.5.1.2.1.1 integer read-only
The index of the device that is plugged into the UPS.
                                     nameOfDevice 1.3.6.1.4.1.935.1.1.1.5.1.2.1.2 displaystring read-write
The name/description of the device plugged into the UPS.
                                     vaRatingOfDevice 1.3.6.1.4.1.935.1.1.1.5.1.2.1.3 integer read-write
The volt-amp rating of the device plugged into the UPS.
                                     deviceAccept 1.3.6.1.4.1.935.1.1.1.5.1.2.1.4 integer read-write
An entry is added if yes, the entry is deleted if no. Enumeration: 'yes': 1, 'no': 2.
                         upsSmartConfig 1.3.6.1.4.1.935.1.1.1.5.2
                             upsSmartConfigRatedOutputVoltage 1.3.6.1.4.1.935.1.1.1.5.2.1 integer read-write
The nominal output voltage from the UPS in 1/10 VAC. Possible values are 1000, 1200, 2080, 2200, 2250, 2300 and 2400. NOTE: Only units that are 2200, 2250, 2300 and 2400 can be changed. Allowable values are 2200, 2250, 2300 and 2400. For these adjustable units, if a value other than a supported value is provided in a set request, the UPS interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used.
                             upsSmartConfigHighTransferVolt 1.3.6.1.4.1.935.1.1.1.5.2.2 integer read-write
The maximum line voltage in 1/10 VAC allowed before the UPS system transfers to battery backup. Allowed value depend on the UPS used: 120 Volt units allow settings of 1290, 1320, 1350, 1380. 100 Volt units allow settings of 1080, 1100, 1120, 1140. 230 Volt units allow settings of 2530, 2640, 2710, 2800. 208 Volt units allow settings of 2240, 2290, 2340, 2390. If a value other than a supported value is provided in a set request, the UPS interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used.
                             upsSmartConfigLowTransferVolt 1.3.6.1.4.1.935.1.1.1.5.2.3 integer read-write
The minimum line voltage in 1/10 VAC allowed before the UPS system transfers to battery backup. Allowable values depend on the UPS used: 120 Volt units allow settings of 970, 1000, 1030, 1060. 100 Volt units allow settings of 810, 830, 850, 870. 230 Volt units allow settings of 1880, 1960, 2040, 2080. 208 Volt units allow settings of 1680, 1720, 1770, 1820. If a value other than a supported value is provided in a set request, the UPS interprets it as a the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.
                             upsSmartConfigAlarm 1.3.6.1.4.1.935.1.1.1.5.2.4 integer read-write
A flag indicating how the UPS should handle audible line fail alarms. Enumeration: 'timed': 1, 'atLowBattery': 2, 'never': 3.
                             upsSmartConfigAlarmTimer 1.3.6.1.4.1.935.1.1.1.5.2.5 integer read-write
The time in seconds after initial line failure at which the UPS begins emitting audible alarms (beeping). This timer is observerd only if the value of extControlAlarm is timed(2). Allowed values are 0 or 30 seconds. If a value other than a supported value is provided in a set request, the UPS interprets it as a the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used.
                             upsSmartConfigMinReturnCapacity 1.3.6.1.4.1.935.1.1.1.5.2.6 integer read-write
The minimum battery capacity as a percent of full capacity required before the UPS will return from a low battery shutdown condition. In other words, the UPS will not re-energize the output until the battery capacity is equal to this value. Allowed values are 0, 10, 25, or 90 percent. If a value other than a supported value is provided in a set request, the UPS interprets it as a the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.
                             upsSmartConfigSensitivity 1.3.6.1.4.1.935.1.1.1.5.2.7 integer read-write
The sensitivity of the UPS to utility line abnormalities or noises. Enumeration: 'high': 4, 'auto': 1, 'medium': 3, 'low': 2.
                             upsSmartConfigLowBatteryRunTime 1.3.6.1.4.1.935.1.1.1.5.2.8 integer read-write
The desired run time in seconds once the low battery condition is reached. Allowed values are 120, 300, 420, or 600 seconds. During this time the UPS will produce a constant warning tone which can not be disabled. If a value other than a supported value is provided in a set request, the UPS interprets it as a the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.
                             upsSmartConfigReturnDelay 1.3.6.1.4.1.935.1.1.1.5.2.9 integer read-write
The delay in seconds after utility line power returns before the UPS will turn on. This value is also used when the UPS comes out of a reboot and before the UPS wakes up from 'sleep' mode. Allowed values are 0, 60, 180 and 300 seconds. If a value other than a supported value is provided in a set request, the UPS interprets it as a the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.
                             upsSmartConfigShutoffDelay 1.3.6.1.4.1.935.1.1.1.5.2.10 integer read-write
The delay in seconds the UPS remains on after being told to turn off. Allowed values are 12, 18, 24, 30, 36, 42, 48, 54, 60, 120, 180, 240, 300, 360, 420, 480, 540, and 600 seconds. If a value other than a supported value is provided in a set request, the UPS interprets it as next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.
                             upsSmartConfigUpsSleepTime 1.3.6.1.4.1.935.1.1.1.5.2.11 integer read-write
The time in minutes for the UPS to go to 'sleep' when instructed. When in sleep mode, the UPS will not provide output power regardless of the input line state. Once the specified time has elapsed, output power will be restored. This is a configuration setting. The UPS will not go to sleep until told to do so by the manager from a management station. Any input value is allowed, however the UPS only recognizes 0 - 9999 minutes in one minute increments. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.
                             upsSmartConfigSetEEPROMDefaults 1.3.6.1.4.1.935.1.1.1.5.2.12 integer read-write
WRITE: Resets the UPS EEPROM variables to default values. READ: returns 0 Enumeration: 'noSetEEPROMDefaults': 1, 'setEEPROMDefaults': 2.
                     upsControlp 1.3.6.1.4.1.935.1.1.1.6
                         upsBaseControl 1.3.6.1.4.1.935.1.1.1.6.1
                             upsBaseControlConserveBattery 1.3.6.1.4.1.935.1.1.1.6.1.1 integer read-write
Setting this variable to turnUpsOffToConserveBattery(2) causes a UPS on battery to be put into 'sleep' mode immediately. The (10) means suspending time(10 minutes) before turn off UPS. UPS will turn back on when utility power is restored. Attempting to turn off a UPS that is not on battery will result in a badValue error. Setting this value to noTurnOffUps(1) has no effect. The value noTurnOffUps(1) will always be returned when the variable is read. Enumeration: 'turnUpsOffToConserveBatteryDelay': 3, 'noTurnOffUps': 1, 'turnUpsOffToConserveBattery': 2.
                         upsSmartControl 1.3.6.1.4.1.935.1.1.1.6.2
                             upsSmartControlUpsOff 1.3.6.1.4.1.935.1.1.1.6.2.1 integer read-write
Setting this variable to turnUpsOff(2) causes the UPS to shut off. When in this state, the UPS will not provide output power regardless of the input line state. The on/off switch on the UPS must be toggled for the UPS to return to operation. Setting this value to noTurnUpsOff(1) has no effect. The value noTurnUpsOff(1) will always be returned when the variable is read. Enumeration: 'turnUpsOff': 2, 'noTurnUpsOff': 1.
                             upsSmartControlRebootUps 1.3.6.1.4.1.935.1.1.1.6.2.2 integer read-write
Setting this variable to rebootUps(2) causes the UPS to shut off and turn back on. Setting this value to noRebootUps(1) has no effect. The value noRebootUps(1) will always be returned when the variable is read. Enumeration: 'rebootUps': 2, 'noRebootUps': 1.
                             upsSmartControlUpsSleep 1.3.6.1.4.1.935.1.1.1.6.2.3 integer read-write
Setting this variable to putUpsToSleep(2) causes the UPS to go to sleep for the time specified by upsSmartConfigUpsSleepTime. When in sleep mode, the UPS will not provide output power regardless of the input line state. Once the specified time has elapsed, output power will be restored. Setting this value to noPutUpsToSleep(1) has no effect. The value noPutUpsToSleep(1) will always be returned when the variable is read. Enumeration: 'putUpsToSleep': 2, 'noPutUpsToSleep': 1.
                             upsSmartControlSimulatePowerFail 1.3.6.1.4.1.935.1.1.1.6.2.4 integer read-write
Setting this variable to simulatePowerFailure(2) causes the UPS switch to battery power. Setting this value to noSimulatePowerFailure(1) has no effect. The value noSimulatePowerFailure(1) will always be returned when the variable is read. Enumeration: 'noSimulatePowerFailure': 1, 'simulatePowerFailure': 2.
                             upsSmartControlFlashAndBeep 1.3.6.1.4.1.935.1.1.1.6.2.5 integer read-write
UPS to identify itself by lighting all indicators and beeping. Setting this variable to FlashAndBeep(2) causes the UPS lights all panel indicators and beeps. Setting this value to noFlashAndBeep(1) has no effect. The value noFlashAndBeep(1) will always be returned when the variable is read. Enumeration: 'flashAndBeep': 2, 'noFlashAndBeep': 1.
                             upsSmartControlTurnOnUpsLoad 1.3.6.1.4.1.935.1.1.1.6.2.6 integer read-write
Setting this variable to upsSmartControlTurnOnUpsLoad(2) causes the UPS switch back to utility power if utility power is present. Setting this value to noUpsSmartControlTurnOnUpsLoad(1) has no effect. The value noUpsSmartControlTurnOnUpsLoad(1) will always be returned when the variable is read. Enumeration: 'upsSmartControlTurnOnUpsLoad': 2, 'noUpsSmartControlTurnOnUpsLoad': 1.
                     upsTestp 1.3.6.1.4.1.935.1.1.1.7
                         upsBaseTest 1.3.6.1.4.1.935.1.1.1.7.1
                         upsSmartTest 1.3.6.1.4.1.935.1.1.1.7.2
                             upsSmartTestDiagnosticSchedule 1.3.6.1.4.1.935.1.1.1.7.2.1 integer read-write
The UPS system's automatic battery test schedule. Enumeration: 'unknown': 1, 'biweekly': 2, 'never': 4, 'weekly': 3.
                             upsSmartTestDiagnostics 1.3.6.1.4.1.935.1.1.1.7.2.2 integer read-write
Setting this variable to testDiagnostics(2) causes the UPS to perform a diagnostic self test. Setting this value to noTestDiagnostics(1) has no effect. The value noTestDiagnostics(1) will always be returned when the variable is read. Enumeration: 'noTestDiagnostics': 1, 'testDiagnostics': 2.
                             upsSmartTestDiagnosticsResults 1.3.6.1.4.1.935.1.1.1.7.2.3 integer read-only
The results of the last UPS diagnostics test performed. Enumeration: 'failed': 2, 'testInProgress': 4, 'ok': 1, 'invalidTest': 3.
                             upsSmartTestLastDiagnosticsDate 1.3.6.1.4.1.935.1.1.1.7.2.4 displaystring read-only
The date the last UPS diagnostics test was performed in mm/dd/yy format.
                             upsSmartTestIndicators 1.3.6.1.4.1.935.1.1.1.7.2.5 integer read-write
Setting this variable to testIndicators(2) causes the UPS to perform a front panel indicator (lights) test. Setting this value to noTestIndicators(1) has no effect. The value noTestIndicators(1) will always be returned when the variable is read. Enumeration: 'testIndicators': 2, 'noTestIndicators': 1.
                             upsSmartTestRuntimeCalibration 1.3.6.1.4.1.935.1.1.1.7.2.6 integer read-write
Setting this variable to performCalibration(2) causes the UPS to discharge to calibrate the UPS. The test will only start if the battery capacity is 100 percent. The test runs until capacity is less than 25 percent. Setting this variable to cancelCurrentCalibration(3) after setting performCalibration(2) will cancel the current discharge. Setting this variable to noPerformCalibration(1) will have no effect. The value noPerformCalibration(1) will always be returned when the variable is read. The result of the calibration will be saved in upsSmartTestCalibrationResult. Enumeration: 'noPerformCalibration': 1, 'cancelCurrentCalibration': 3, 'performCalibration': 2.
                             upsSmartTestCalibrationResults 1.3.6.1.4.1.935.1.1.1.7.2.7 integer read-only
The results of the last runtime calibration. Value ok(1) means a successful runtime calibration. Value invalidTest(2) indicates last calibration did not take place since the battery capacity was below 100 percent. Value calibrationInProgress(3) means a calibration is occurring now. Enumeration: 'calibrationInProgress': 3, 'ok': 1, 'invalidTest': 2.
                             upsSmartTestCalibrationDate 1.3.6.1.4.1.935.1.1.1.7.2.8 displaystring read-only
The date the last UPS runtime calibration was performed in mm/dd/yy format.
                     upsThreePhase 1.3.6.1.4.1.935.1.1.1.8
                         upsThreePhaseBatteryGrp 1.3.6.1.4.1.935.1.1.1.8.1
                             upsThreePhaseBatteryVoltage 1.3.6.1.4.1.935.1.1.1.8.1.1 integer read-only
Battery Voltage
                             upsThreePhaseBatteryCapacityPercentage 1.3.6.1.4.1.935.1.1.1.8.1.2 integer read-only
Battery Capacity Percentage
                             upsThreePhaseBatteryTimeRemain 1.3.6.1.4.1.935.1.1.1.8.1.3 integer read-only
Battery Time Remain (unit is Minute)
                             upsThreePhaseBatteryCurrent 1.3.6.1.4.1.935.1.1.1.8.1.4 integer read-only
Battery Electric Current
                             upsThreePhaseBatteryTemperature 1.3.6.1.4.1.935.1.1.1.8.1.5 integer read-only
Battery Temperature
                         upsThreePhaseInputGrp 1.3.6.1.4.1.935.1.1.1.8.2
                             upsThreePhaseInputFrequency 1.3.6.1.4.1.935.1.1.1.8.2.1 integer read-only
Input Frequency
                             upsThreePhaseInputVoltageR 1.3.6.1.4.1.935.1.1.1.8.2.2 integer read-only
Input VoltageR
                             upsThreePhaseInputVoltageS 1.3.6.1.4.1.935.1.1.1.8.2.3 integer read-only
Input VoltageS
                             upsThreePhaseInputVoltageT 1.3.6.1.4.1.935.1.1.1.8.2.4 integer read-only
Input VoltageT
                         upsThreePhaseOutputGrp 1.3.6.1.4.1.935.1.1.1.8.3
                             upsThreePhaseOutputFrequency 1.3.6.1.4.1.935.1.1.1.8.3.1 integer read-only
Output Frequency
                             upsThreePhaseOutputVoltageR 1.3.6.1.4.1.935.1.1.1.8.3.2 integer read-only
Output VoltageR
                             upsThreePhaseOutputVoltageS 1.3.6.1.4.1.935.1.1.1.8.3.3 integer read-only
Output VoltageS
                             upsThreePhaseOutputVoltageT 1.3.6.1.4.1.935.1.1.1.8.3.4 integer read-only
Output VoltageT
                             upsThreePhaseOutputLoadPercentageR 1.3.6.1.4.1.935.1.1.1.8.3.5 integer read-only
Load PercentageR
                             upsThreePhaseOutputLoadPercentageS 1.3.6.1.4.1.935.1.1.1.8.3.6 integer read-only
Load PercentageS
                             upsThreePhaseOutputLoadPercentageT 1.3.6.1.4.1.935.1.1.1.8.3.7 integer read-only
Load PercentageT
                         upsThreePhaseBypassGrp 1.3.6.1.4.1.935.1.1.1.8.4
                             upsThreePhaseBypassSourceFrequency 1.3.6.1.4.1.935.1.1.1.8.4.1 integer read-only
Bypass Frequency
                             upsThreePhaseBypssSourceVoltageR 1.3.6.1.4.1.935.1.1.1.8.4.2 integer read-only
Bypass VoltageR
                             upsThreePhaseBypssSourceVoltageS 1.3.6.1.4.1.935.1.1.1.8.4.3 integer read-only
Bypass VoltageS
                             upsThreePhaseBypssSourceVoltageT 1.3.6.1.4.1.935.1.1.1.8.4.4 integer read-only
Bypass VoltageT
                         upsThreePhaseDCandRectifierStatusGrp 1.3.6.1.4.1.935.1.1.1.8.5
                             upsThreePhaseDCandRectifierStatusRecRotError 1.3.6.1.4.1.935.1.1.1.8.5.1 integer read-only
Rectifier Rotation Error Enumeration: 'yes': 14, 'no': 16.
                             upsThreePhaseDCandRectifierStatusLowBatteryShutdown 1.3.6.1.4.1.935.1.1.1.8.5.2 integer read-only
Low Battery Shutdown Enumeration: 'yes': 14, 'no': 16.
                             upsThreePhaseDCandRectifierStatusLowBattery 1.3.6.1.4.1.935.1.1.1.8.5.3 integer read-only
Low Battery Enumeration: 'yes': 14, 'no': 16.
                             upsThreePhaseDCandRectifierStatusInAndOut 1.3.6.1.4.1.935.1.1.1.8.5.4 integer read-only
In And Put Enumeration: 'threeInOneOut': 2, 'threeInThreeOut': 3.
                             upsThreePhaseDCandRectifierStatusBatteryStatus 1.3.6.1.4.1.935.1.1.1.8.5.5 integer read-only
Back Status Enumeration: 'acnormal': 5, 'backup': 4.
                             upsThreePhaseDCandRectifierStatusChargeStatus 1.3.6.1.4.1.935.1.1.1.8.5.6 integer read-only
Charge Status Enumeration: 'float': 7, 'boost': 6, 'no': 16.
                             upsThreePhaseDCandRectifierStatusRecOperating 1.3.6.1.4.1.935.1.1.1.8.5.7 integer read-only
Rectifier Operating Enumeration: 'yes': 14, 'no': 16.
                         upsThreePhaseUPSStatusGrp 1.3.6.1.4.1.935.1.1.1.8.6
                             upsThreePhaseUPSStatusBypassFreqFail 1.3.6.1.4.1.935.1.1.1.8.6.1 integer read-only
Bypass Status Enumeration: 'yes': 14, 'no': 16.
                             upsThreePhaseUPSStatusManualBypassBreaker 1.3.6.1.4.1.935.1.1.1.8.6.2 integer read-only
Breaker Status Enumeration: 'close': 8, 'open': 9.
                             upsThreePhaseUPSStatusACStatus 1.3.6.1.4.1.935.1.1.1.8.6.3 integer read-only
AC Status Enumeration: 'abnormal': 11, 'normal': 10.
                             upsThreePhaseUPSStaticSwitchMode 1.3.6.1.4.1.935.1.1.1.8.6.4 integer read-only
Switch Mode Enumeration: 'invermode': 12, 'bypassmode': 13.
                             upsThreePhaseUPSStatusInverterOperating 1.3.6.1.4.1.935.1.1.1.8.6.5 integer read-only
Operating Enumeration: 'yes': 14, 'no': 16.
                         upsThreePhaseFaultStatusGrp 1.3.6.1.4.1.935.1.1.1.8.7
                             upsThreePhaseFaultStatusEmergencyStop 1.3.6.1.4.1.935.1.1.1.8.7.1 integer read-only
Emergency Stop Enumeration: 'yes': 14, 'no': 16.
                             upsThreePhaseFaultStatusHighDCShutdown 1.3.6.1.4.1.935.1.1.1.8.7.2 integer read-only
High DC Shutdown Enumeration: 'yes': 14, 'no': 16.
                             upsThreePhaseFaultStatusBypassBreaker 1.3.6.1.4.1.935.1.1.1.8.7.3 integer read-only
Bypass Breaker Enumeration: 'yes': 14, 'no': 16.
                             upsThreePhaseFaultStatusOverLoad 1.3.6.1.4.1.935.1.1.1.8.7.4 integer read-only
Over Load Enumeration: 'yes': 14, 'no': 16.
                             upsThreePhaseFaultStatusInverterOutputFail 1.3.6.1.4.1.935.1.1.1.8.7.5 integer read-only
Output Fail Enumeration: 'yes': 14, 'no': 16.
                             upsThreePhaseFaultStatusOverTemperature 1.3.6.1.4.1.935.1.1.1.8.7.6 integer read-only
Over Temperature Enumeration: 'yes': 14, 'no': 16.
                             upsThreePhaseFaultStatusShortCircuit 1.3.6.1.4.1.935.1.1.1.8.7.7 integer read-only
Short Circuit Enumeration: 'yes': 14, 'no': 16.
                         upsThreePhaseRatingGrp 1.3.6.1.4.1.935.1.1.1.8.8
                             upsThreePhaseRatingRectifierVoltage 1.3.6.1.4.1.935.1.1.1.8.8.1 displaystring read-only
Rectifier Voltage
                             upsThreePhaseRatingRectifierFrequency 1.3.6.1.4.1.935.1.1.1.8.8.2 integer read-only
Rectifier Frequency
                             upsThreePhaseRatingBypassVoltage 1.3.6.1.4.1.935.1.1.1.8.8.3 displaystring read-only
Bypass Voltage
                             upsThreePhaseRatingBypassFrequency 1.3.6.1.4.1.935.1.1.1.8.8.4 integer read-only
Bypass Frequency
                             upsThreePhaseRatingOutputVoltage 1.3.6.1.4.1.935.1.1.1.8.8.5 displaystring read-only
Output Voltage
                             upsThreePhaseRatingOutputFrequency 1.3.6.1.4.1.935.1.1.1.8.8.6 integer read-only
Output Frequency
                             upsThreePhaseRatingBatteryVoltage 1.3.6.1.4.1.935.1.1.1.8.8.7 integer read-only
Battery Voltage
                             upsThreePhaseRatingPower 1.3.6.1.4.1.935.1.1.1.8.8.8 displaystring read-only
Power Rating
                     upsEnvironment 1.3.6.1.4.1.935.1.1.1.9
                         upsEnvStatus 1.3.6.1.4.1.935.1.1.1.9.1
                             upsEnvTemperature 1.3.6.1.4.1.935.1.1.1.9.1.1 integer read-only
The ambient environment temperature.
                             upsEnvHumidity 1.3.6.1.4.1.935.1.1.1.9.1.2 integer read-only
The environment humidity.
                             upsEnvWater 1.3.6.1.4.1.935.1.1.1.9.1.3 integer read-only
Water status Enumeration: 'abnormal': 2, 'normal': 1.
                             upsEnvSmoke 1.3.6.1.4.1.935.1.1.1.9.1.4 integer read-only
Smoke status Enumeration: 'abnormal': 2, 'normal': 1.
                             upsEnvSecurity1 1.3.6.1.4.1.935.1.1.1.9.1.5 integer read-only
Security status Enumeration: 'abnormal': 2, 'normal': 1.
                             upsEnvSecurity2 1.3.6.1.4.1.935.1.1.1.9.1.6 integer read-only
Security status Enumeration: 'abnormal': 2, 'normal': 1.
                             upsEnvSecurity3 1.3.6.1.4.1.935.1.1.1.9.1.7 integer read-only
Security status Enumeration: 'abnormal': 2, 'normal': 1.
                             upsEnvSecurity4 1.3.6.1.4.1.935.1.1.1.9.1.8 integer read-only
Security status Enumeration: 'abnormal': 2, 'normal': 1.
                             upsEnvSecurity5 1.3.6.1.4.1.935.1.1.1.9.1.9 integer read-only
Security status Enumeration: 'abnormal': 2, 'normal': 1.
                             upsEnvSecurity6 1.3.6.1.4.1.935.1.1.1.9.1.10 integer read-only
Security status Enumeration: 'abnormal': 2, 'normal': 1.
                             upsEnvSecurity7 1.3.6.1.4.1.935.1.1.1.9.1.11 integer read-only
Security status Enumeration: 'abnormal': 2, 'normal': 1.
                         upsEnvSetting 1.3.6.1.4.1.935.1.1.1.9.2
                             upsEnvOverTemperature 1.3.6.1.4.1.935.1.1.1.9.2.1 integer read-write
Alarm dupsAlarmOverTemperature on when the environment temperature over the value.
                             upsEnvUnderTemperature 1.3.6.1.4.1.935.1.1.1.9.2.2 integer read-write
Alarm dupsAlarmUnderTemperature on when the environment temperature below the value.
                             upsEnvOverHumidity 1.3.6.1.4.1.935.1.1.1.9.2.3 integer read-write
Alarm dupsAlarmOverHumidity on when the environment humidity over the value.
                             upsEnvUnderHumidity 1.3.6.1.4.1.935.1.1.1.9.2.4 integer read-write
Alarm dupsAlarmUnderHumidity on when the environment humidity below the value.
         ppcmgmt 1.3.6.1.4.1.935.2
             mconfig 1.3.6.1.4.1.935.2.1
                 mconfigTrapsReceiversNum 1.3.6.1.4.1.935.2.1.1 integer read-only
The number of managers to send traps to.
                 mconfigTrapsReceiversTable 1.3.6.1.4.1.935.2.1.2 no-access
A list of managers to send traps to. The number of entries is given by the value of mconfigNumTrapReceivers
                     mconfigTrapsReceiversEntry 1.3.6.1.4.1.935.2.1.2.1 no-access
The managers to send traps to.
                         trapsIndex 1.3.6.1.4.1.935.2.1.2.1.1 integer read-only
The index to a trap receiver entry.
                         trapsReceiverAddr 1.3.6.1.4.1.935.2.1.2.1.2 ipaddress read-write
The IP address of the manager to send a trap to.
                         receiverCommunityString 1.3.6.1.4.1.935.2.1.2.1.3 displaystring read-write
The community name to use in the trap when sent to the manager.
                         severityLevel 1.3.6.1.4.1.935.2.1.2.1.4 integer read-write
The severity threshold of traps to send to the manager. traps are labeled in severity as informational(1), warning(2), severe(3). Only traps of equal or greater severity than this value are sent to the manager. Enumeration: 'information': 1, 'severe': 3, 'warning': 2.
                         receiverAccept 1.3.6.1.4.1.935.2.1.2.1.5 integer read-write
An entry will become active if yes, and will be deleted if no. Enumeration: 'yes': 1, 'no': 2.
           communicationLost 1.3.6.1.4.1.9350.1
SEVERE: Communication to the UPS has been lost. Steps to reestablish communication are in progress.
           upsOverLoad 1.3.6.1.4.1.9350.2
SEVERE: The UPS has sensed a load greater than 100 percent of its rated capacity.
           upsDiagnosticsFailed 1.3.6.1.4.1.9350.3
SEVERE: The UPS failed its internal diagnostic self-test.
           upsDischarged 1.3.6.1.4.1.9350.4
SEVERE: The UPS just started a runtime calibration discharge. The UPS batteries are being discharged.
           upsOnBattery 1.3.6.1.4.1.9350.5
WARNING: The UPS has switched to battery backup power.
           boostOn 1.3.6.1.4.1.9350.6
WARNING: The UPS has enabled Boost.
           lowBattery 1.3.6.1.4.1.9350.7
SEVERE: The UPS batteries are low and will soon be exhausted. If utility power is not restored the UPS will put itself to 'sleep' and immediately cut power to the load.
           communicationEstablished 1.3.6.1.4.1.9350.8
INFORMATION: Communication with the UPS has been established.
           powerRestored 1.3.6.1.4.1.9350.9
INFORMATION: Utility power has been restored.
           upsDiagnosticsPassed 1.3.6.1.4.1.9350.10
INFORMATION: The UPS passed its internal self-test.
           returnFromLowBattery 1.3.6.1.4.1.9350.11
INFORMATION: The UPS has returned from a low battery condition.
           upsTurnedOff 1.3.6.1.4.1.9350.12
WARNING: The UPS has been turned 'off' by the management station.
           upsSleeping 1.3.6.1.4.1.9350.13
WARNING: The UPS is entering 'sleep' mode. Power to the load will be cut off.
           upsWokeUp 1.3.6.1.4.1.9350.14
INFORMATION: The UPS woke up from 'sleep' mode. Power to the load has been restored.
           upsRebootStarted 1.3.6.1.4.1.9350.15
WARNING: The UPS has started its reboot sequence. After the specified delay the UPS will perform a reboot.
           envOverTemperature 1.3.6.1.4.1.9350.16
WARNING: The environment temperature exceed the normal value.
           envTemperatureNormal 1.3.6.1.4.1.9350.17
INFORMATION: The environment temperature is normal.
           envOverHumidity 1.3.6.1.4.1.9350.18
WARNING: The environment humidity exceed the normal value.
           envHumidityNormal 1.3.6.1.4.1.9350.19
INFORMATION: The environment humidity is normal.
           envSmokeAbnormal 1.3.6.1.4.1.9350.20
WARNING: Smoke is abnormal.
           envWaterAbnormal 1.3.6.1.4.1.9350.21
WARNING: Water is abnormal.
           envSecurityAbnormal 1.3.6.1.4.1.9350.22
WARNING: Security is abnormal.
           envWaterNormal 1.3.6.1.4.1.9350.24
INFORMATION: Water is normal.
           envGasAbnormal 1.3.6.1.4.1.9350.26
WARNING: Gas Alarm
           upsTemp 1.3.6.1.4.1.9350.27
WARNING: UPS Temperature Overrun
           upsLoadNormal 1.3.6.1.4.1.9350.28
WARNING: UPS Load Normal
           upsTempNormal 1.3.6.1.4.1.9350.29
WARNING: UPS temperature Normal
           envUnderTemperature 1.3.6.1.4.1.9350.30
WARNING: The environment temperature below the normal value.
           envUnderHumidity 1.3.6.1.4.1.9350.31
WARNING: The environment humidity below the normal value.
           upsBypass 1.3.6.1.4.1.9350.32
WARNING: The UPS is entering 'bypass' mode.
           envSecurity1 1.3.6.1.4.1.9350.33
WARNING: Security1 Alarm.
           envSecurity2 1.3.6.1.4.1.9350.34
WARNING: Security2 Alarm.
           envSecurity3 1.3.6.1.4.1.9350.35
WARNING: Security3 Alarm.
           envSecurity4 1.3.6.1.4.1.9350.36
WARNING: Security4 Alarm.
           envSecurity5 1.3.6.1.4.1.9350.37
WARNING: Security5 Alarm.
           envSecurity6 1.3.6.1.4.1.9350.38
WARNING: Security6 Alarm.
           envSecurity7 1.3.6.1.4.1.9350.39
WARNING: Security7 Alarm.
           upsRecroterror 1.3.6.1.4.1.9350.47
WARNING: Rectifier Rotation Error
           upsBypassFreFail 1.3.6.1.4.1.9350.48
WARNING: Bypass Frequency Fail
           upsBypassacnormal 1.3.6.1.4.1.9350.49
WARNING: Bypass AC Normal
           upsBypassacabnormal 1.3.6.1.4.1.9350.50
WARNING: Bypass AC Abnormal
           upsTest 1.3.6.1.4.1.9350.51
WARNING: UPS Test
           upsScheduleShutdown 1.3.6.1.4.1.9350.52
WARNING: UPS Schedule Shutdown
           upsBypassReturn 1.3.6.1.4.1.9350.53
The UPS return from Bypass Mode
           upsShortCircuitShutdown 1.3.6.1.4.1.9350.54
The UPS Short Circuit Shutdown
           upsInverterOutputFailShutdown 1.3.6.1.4.1.9350.55
The UPS Inverter Output Fail Shutdown
           upsBypassBreadkerOnShutdown 1.3.6.1.4.1.9350.56
The UPS Manual Bypass Breaker on Shutdown
           upsHighDCShutdown 1.3.6.1.4.1.9350.57
The UPS High DC Shutdown
           upsEmergencyStop 1.3.6.1.4.1.9350.58
The UPS Emergency Stop
           upsInverterMode 1.3.6.1.4.1.9350.59
The UPS Static Switch in Inverter Mode
           upsBypassMode 1.3.6.1.4.1.9350.60
The UPS Static Switch in Bypass Mode
           upsOverTemperatureShutdown 1.3.6.1.4.1.9350.61
The UPS Over Temperature Shutdown
           upsOverLoadShutdown 1.3.6.1.4.1.9350.62
The UPS Overload Shutdown
           upsCapacityUnderrun 1.3.6.1.4.1.9350.63
The UPS Capacity Underrun
           upsCapacityNormal 1.3.6.1.4.1.9350.64
The UPS Capacity Normal
           upsLowBatteryShutdown 1.3.6.1.4.1.9350.67
The UPS Low Battery Shutdown
           buckOn 1.3.6.1.4.1.9350.68
WARNING: The UPS has enabled Buck.
           returnFromBuck 1.3.6.1.4.1.9350.69
WARNING: The UPS has return from Buck.
           returnFromBoost 1.3.6.1.4.1.9350.70
WARNING: The UPS has return from Boost.