WebGraph-OLD-Thermo-Hygrometer-US-MIB: View SNMP OID List / Download MIB

VENDOR: WIESEMANN N THEIS


 Home MIB: WebGraph-OLD-Thermo-Hygrometer-US-MIB
Download as:   

Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 wut 1.3.6.1.4.1.5040
           wtComServer 1.3.6.1.4.1.5040.1
               wtWebio 1.3.6.1.4.1.5040.1.2
                   wtWebGraphThermHygro 1.3.6.1.4.1.5040.1.2.9
                       wtWebGraphThermHygroTemp 1.3.6.1.4.1.5040.1.2.9.1
                           wtWebGraphThermHygroSensors 1.3.6.1.4.1.5040.1.2.9.1.1 integer read-only
Number of sensors
                           wtWebGraphThermHygroSensorTable 1.3.6.1.4.1.5040.1.2.9.1.2 no-access
List of sensors.
                               wtWebGraphThermHygroSensorEntry 1.3.6.1.4.1.5040.1.2.9.1.2.1 no-access
List of sensor numbers.
                                   wtWebGraphThermHygroSensorNo 1.3.6.1.4.1.5040.1.2.9.1.2.1.1 integer read-only
Sensor number.
                           wtWebGraphThermHygroTempValueTable 1.3.6.1.4.1.5040.1.2.9.1.3 no-access
List of measurement values corresponding to the channel numbers.
                               wtWebGraphThermHygroTempValueEntry 1.3.6.1.4.1.5040.1.2.9.1.3.1 no-access
Measurement values of the sensors.
                                   wtWebGraphThermHygroTempValue 1.3.6.1.4.1.5040.1.2.9.1.3.1.1 octet string read-only
Measurement value of the sensor, ASCII, 5 characters in length.
                           wtWebGraphThermHygroBinaryTempValueTable 1.3.6.1.4.1.5040.1.2.9.1.4 no-access
List of binary measurement values corresponding to the channel numbers.
                               wtWebGraphThermHygroBinaryTempValueEntry 1.3.6.1.4.1.5040.1.2.9.1.4.1 no-access
Binary measurement values of the sensors.
                                   wtWebGraphThermHygroBinaryTempValue 1.3.6.1.4.1.5040.1.2.9.1.4.1.1 integer read-only
Binary measurement value of the sensor in 1/10 degrees Celsius or 1/10 per cent, signed number, 0x4FFF6 indicates an invalid measured value.
                       wtWebGraphThermHygroSessCntrl 1.3.6.1.4.1.5040.1.2.9.2
                           wtWebGraphThermHygroSessCntrlPassword 1.3.6.1.4.1.5040.1.2.9.2.1 octet string read-write
Entering this password opens a session which is ended by writing a 1 to wtWebGraphThermHygroSessCntrlLogout. When read this variable provides a string of length zero.
                           wtWebGraphThermHygroSessCntrlConfigMode 1.3.6.1.4.1.5040.1.2.9.2.2 integer read-only
When the device is in SNMP configuration mode, the value 1 is returned, otherwise 0. If the read value is 0 even though the password was written, the device is already in config mode and the variables can only be read. Enumeration: 'wtWebGraphThermHygroSessCntrl-NoSession': 0, 'wtWebGraphThermHygroSessCntrl-Session': 1.
                           wtWebGraphThermHygroSessCntrlLogout 1.3.6.1.4.1.5040.1.2.9.2.3 integer read-write
If the device is in configuration mode and the session was opened by this SNMP Manager, writing a 1 to this variable will end the session and all parameters are stored. Writing a 2 discards all entries again. When read this variable provides the value 0.
                           wtWebGraphThermHygroSessCntrlAdminPassword 1.3.6.1.4.1.5040.1.2.9.2.4 octet string read-write
This password protects access to the variables with administrator rights. It can only be changed by the administrator. If no password was assigned, the valid password is public.
                           wtWebGraphThermHygroSessCntrlConfigPassword 1.3.6.1.4.1.5040.1.2.9.2.5 octet string read-write
This password protects access to the variables with configurator rights. It can be changed by the administrator and by the configurator. If no password was assigned, the valid password is public. When read this variable provides a null-pointer.
                       wtWebGraphThermHygroConfig 1.3.6.1.4.1.5040.1.2.9.3
                           wtWebGraphThermHygroDevice 1.3.6.1.4.1.5040.1.2.9.3.1
                               wtWebGraphThermHygroText 1.3.6.1.4.1.5040.1.2.9.3.1.1
                                   wtWebGraphThermHygroDeviceName 1.3.6.1.4.1.5040.1.2.9.3.1.1.1 octet string read-write
Name of the Webio, which is user definable.
                                   wtWebGraphThermHygroDeviceText 1.3.6.1.4.1.5040.1.2.9.3.1.1.2 octet string read-write
Description of the Webio, which is user definable.
                                   wtWebGraphThermHygroDeviceLocation 1.3.6.1.4.1.5040.1.2.9.3.1.1.3 octet string read-write
Description of the location of the Webio, which is user definable.
                                   wtWebGraphThermHygroDeviceContact 1.3.6.1.4.1.5040.1.2.9.3.1.1.4 octet string read-write
Contact address of the system operator of the Webio, which is user definable.
                               wtWebGraphThermHygroTimeDate 1.3.6.1.4.1.5040.1.2.9.3.1.2
                                   wtWebGraphThermHygroTimeZone 1.3.6.1.4.1.5040.1.2.9.3.1.2.1
                                       wtWebGraphThermHygroTzOffsetHrs 1.3.6.1.4.1.5040.1.2.9.3.1.2.1.1 integer read-write
Offset hours for the time zone (winter time) with respect to UTC.
                                       wtWebGraphThermHygroTzOffsetMin 1.3.6.1.4.1.5040.1.2.9.3.1.2.1.2 integer read-write
Offset minutes for the time zone (winter time) with respect to UTC.
                                       wtWebGraphThermHygroTzEnable 1.3.6.1.4.1.5040.1.2.9.3.1.2.1.3 octet string read-write
Binary coded conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Apply Timezone
                                       wtWebGraphThermHygroStTzOffsetHrs 1.3.6.1.4.1.5040.1.2.9.3.1.2.1.4 integer read-write
Offset hours of the time zone (summer time) with respect to UTC.
                                       wtWebGraphThermHygroStTzOffsetMin 1.3.6.1.4.1.5040.1.2.9.3.1.2.1.5 integer read-write
Offset minutes of the time zone (summer time) with respect to UTC.
                                       wtWebGraphThermHygroStTzEnable 1.3.6.1.4.1.5040.1.2.9.3.1.2.1.6 octet string read-write
Binary coded conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Apply Summertime
                                       wtWebGraphThermHygroStTzStartMonth 1.3.6.1.4.1.5040.1.2.9.3.1.2.1.7 integer read-write
Month in which the change is made from winter time to summer time. Enumeration: 'wtWebGraphThermHygroStartMonth-February': 2, 'wtWebGraphThermHygroStartMonth-January': 1, 'wtWebGraphThermHygroStartMonth-November': 11, 'wtWebGraphThermHygroStartMonth-June': 6, 'wtWebGraphThermHygroStartMonth-December': 12, 'wtWebGraphThermHygroStartMonth-April': 4, 'wtWebGraphThermHygroStartMonth-July': 7, 'wtWebGraphThermHygroStartMonth-September': 9, 'wtWebGraphThermHygroStartMonth-August': 8, 'wtWebGraphThermHygroStartMonth-October': 10, 'wtWebGraphThermHygroStartMonth-March': 3, 'wtWebGraphThermHygroStartMonth-May': 5.
                                       wtWebGraphThermHygroStTzStartMode 1.3.6.1.4.1.5040.1.2.9.3.1.2.1.8 integer read-write
Mode of the day of the week for which the change is made from winter time to summer time. Enumeration: 'wtWebGraphThermHygroStartMode-last': 5, 'wtWebGraphThermHygroStartMode-third': 3, 'wtWebGraphThermHygroStartMode-first': 1, 'wtWebGraphThermHygroStartMode-fourth': 4, 'wtWebGraphThermHygroStartMode-second': 2.
                                       wtWebGraphThermHygroStTzStartWday 1.3.6.1.4.1.5040.1.2.9.3.1.2.1.9 integer read-write
Day of the week on which the change is made from winter time to summer time Enumeration: 'wtWebGraphThermHygroStartWday-Thursday': 4, 'wtWebGraphThermHygroStartWday-Wednesday': 5, 'wtWebGraphThermHygroStartWday-Monday': 2, 'wtWebGraphThermHygroStartWday-Tuesday': 3, 'wtWebGraphThermHygroStartWday-Friday': 6, 'wtWebGraphThermHygroStartWday-Sunday': 1, 'wtWebGraphThermHygroStartWday-Saturday': 7.
                                       wtWebGraphThermHygroStTzStartHrs 1.3.6.1.4.1.5040.1.2.9.3.1.2.1.10 integer read-write
Hour in which the time zone is changed from winter to summer time with respect to UTC.
                                       wtWebGraphThermHygroStTzStartMin 1.3.6.1.4.1.5040.1.2.9.3.1.2.1.11 integer read-write
Minute in which the time zone is changed from winter to summer time with respect to UTC.
                                       wtWebGraphThermHygroStTzStopMonth 1.3.6.1.4.1.5040.1.2.9.3.1.2.1.12 integer read-write
Month in which the change is made from summer time to winter time. Enumeration: 'wtWebGraphThermHygroStopMonth-May': 5, 'wtWebGraphThermHygroStopMonth-February': 2, 'wtWebGraphThermHygroStopMonth-October': 10, 'wtWebGraphThermHygroStopMonth-January': 1, 'wtWebGraphThermHygroStopMonth-September': 9, 'wtWebGraphThermHygroStopMonth-December': 12, 'wtWebGraphThermHygroStopMonth-August': 8, 'wtWebGraphThermHygroStopMonth-November': 11, 'wtWebGraphThermHygroStopMonth-March': 3, 'wtWebGraphThermHygroStopMonth-June': 6, 'wtWebGraphThermHygroStopMonth-July': 7, 'wtWebGraphThermHygroStopMonth-April': 4.
                                       wtWebGraphThermHygroStTzStopMode 1.3.6.1.4.1.5040.1.2.9.3.1.2.1.13 integer read-write
Mode of the week day on which the change is made from summer time to winter time. Enumeration: 'wtWebGraphThermHygroStopMode-fourth': 4, 'wtWebGraphThermHygroStopMode-last': 5, 'wtWebGraphThermHygroStopMode-second': 2, 'wtWebGraphThermHygroStopMode-first': 1, 'wtWebGraphThermHygroStopMode-third': 3.
                                       wtWebGraphThermHygroStTzStopWday 1.3.6.1.4.1.5040.1.2.9.3.1.2.1.14 integer read-write
Day of the week on which the change is made from summer time to winter time. Enumeration: 'wtWebGraphThermHygroStopWday-Tuesday': 3, 'wtWebGraphThermHygroStopWday-Friday': 6, 'wtWebGraphThermHygroStopWday-Sunday': 1, 'wtWebGraphThermHygroStopWday-Thursday': 4, 'wtWebGraphThermHygroStopWday-Saturday': 7, 'wtWebGraphThermHygroStopWday-Wednesday': 5, 'wtWebGraphThermHygroStopWday-Monday': 2.
                                       wtWebGraphThermHygroStTzStopHrs 1.3.6.1.4.1.5040.1.2.9.3.1.2.1.15 integer read-write
Hour at which the time zone is changed from summer to winter time with respect to UTC.
                                       wtWebGraphThermHygroStTzStopMin 1.3.6.1.4.1.5040.1.2.9.3.1.2.1.16 integer read-write
Minute at which the time zone is changed from summer to winter time with respect to UTC.
                                   wtWebGraphThermHygroTimeServer 1.3.6.1.4.1.5040.1.2.9.3.1.2.2
                                       wtWebGraphThermHygroTimeServer1 1.3.6.1.4.1.5040.1.2.9.3.1.2.2.1 octet string read-write
IP address or name of the 1st time server in ASCII
                                       wtWebGraphThermHygroTimeServer2 1.3.6.1.4.1.5040.1.2.9.3.1.2.2.2 octet string read-write
IP address or name of the 2nd time server in ASCII
                                       wtWebGraphThermHygroTsEnable 1.3.6.1.4.1.5040.1.2.9.3.1.2.2.3 octet string read-write
Binary coded conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Apply Time Server
                                       wtWebGraphThermHygroTsSyncTime 1.3.6.1.4.1.5040.1.2.9.3.1.2.2.4 integer read-write
Daily synchronisation time with the time server (hour: 0-23).
                                   wtWebGraphThermHygroDeviceClock 1.3.6.1.4.1.5040.1.2.9.3.1.2.3
                                       wtWebGraphThermHygroClockHrs 1.3.6.1.4.1.5040.1.2.9.3.1.2.3.1 integer read-write
Clock hours taking into account the time zone settings.
                                       wtWebGraphThermHygroClockMin 1.3.6.1.4.1.5040.1.2.9.3.1.2.3.2 integer read-write
Clock minutes taking into account the time zone settings.
                                       wtWebGraphThermHygroClockDay 1.3.6.1.4.1.5040.1.2.9.3.1.2.3.3 integer read-write
Date: Day of the month, taking into account the time zone settings.
                                       wtWebGraphThermHygroClockMonth 1.3.6.1.4.1.5040.1.2.9.3.1.2.3.4 integer read-write
Date: Month, taking into account the time zone settings. Enumeration: 'wtWebGraphThermHygroClockMonth-October': 10, 'wtWebGraphThermHygroClockMonth-February': 2, 'wtWebGraphThermHygroClockMonth-May': 5, 'wtWebGraphThermHygroClockMonth-November': 11, 'wtWebGraphThermHygroClockMonth-March': 3, 'wtWebGraphThermHygroClockMonth-April': 4, 'wtWebGraphThermHygroClockMonth-January': 1, 'wtWebGraphThermHygroClockMonth-July': 7, 'wtWebGraphThermHygroClockMonth-June': 6, 'wtWebGraphThermHygroClockMonth-August': 8, 'wtWebGraphThermHygroClockMonth-September': 9, 'wtWebGraphThermHygroClockMonth-December': 12.
                                       wtWebGraphThermHygroClockYear 1.3.6.1.4.1.5040.1.2.9.3.1.2.3.5 integer read-write
Date: Year, taking into account the time zone settings.
                               wtWebGraphThermHygroBasic 1.3.6.1.4.1.5040.1.2.9.3.1.3
                                   wtWebGraphThermHygroNetwork 1.3.6.1.4.1.5040.1.2.9.3.1.3.1
                                       wtWebGraphThermHygroIpAddress 1.3.6.1.4.1.5040.1.2.9.3.1.3.1.1 ipaddress read-write
IP address of the Webio
                                       wtWebGraphThermHygroSubnetMask 1.3.6.1.4.1.5040.1.2.9.3.1.3.1.2 ipaddress read-write
Subnet mask of the Webio
                                       wtWebGraphThermHygroGateway 1.3.6.1.4.1.5040.1.2.9.3.1.3.1.3 ipaddress read-write
Gateway of the Webio
                                       wtWebGraphThermHygroDnsServer1 1.3.6.1.4.1.5040.1.2.9.3.1.3.1.4 octet string read-write
IP address of the 1st DNS server in ASCII
                                       wtWebGraphThermHygroDnsServer2 1.3.6.1.4.1.5040.1.2.9.3.1.3.1.5 octet string read-write
IP address of the 2nd DNS server in ASCII
                                       wtWebGraphThermHygroAddConfig 1.3.6.1.4.1.5040.1.2.9.3.1.3.1.6 octet string read-write
Additional configuration (1=ON): Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: BOOTP disable
                                   wtWebGraphThermHygroHTTP 1.3.6.1.4.1.5040.1.2.9.3.1.3.2
                                       wtWebGraphThermHygroStartup 1.3.6.1.4.1.5040.1.2.9.3.1.3.2.1 octet string read-write
Binary coded start page: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1: Index.htm Bit 2: Home.htm Bit 3: User.htm Only one page may be selected at a time.
                                       wtWebGraphThermHygroGetHeaderEnable 1.3.6.1.4.1.5040.1.2.9.3.1.3.2.2 octet string read-write
If this bit is set, every answer of a short form GET question will be lead by the IP-address and name of the device: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : GET Header enable
                                       wtWebGraphThermHygroHttpPort 1.3.6.1.4.1.5040.1.2.9.3.1.3.2.3 integer read-write
Definition of the standard HTML port (Default: 80).
                                   wtWebGraphThermHygroMail 1.3.6.1.4.1.5040.1.2.9.3.1.3.3
                                       wtWebGraphThermHygroMailAdName 1.3.6.1.4.1.5040.1.2.9.3.1.3.3.1 octet string read-write
Device name for mail administration.
                                       wtWebGraphThermHygroMailReply 1.3.6.1.4.1.5040.1.2.9.3.1.3.3.2 octet string read-write
Reply address for the mail server.
                                       wtWebGraphThermHygroMailServer 1.3.6.1.4.1.5040.1.2.9.3.1.3.3.3 octet string read-write
Name or IP address of the mail server.
                                       wtWebioAn1MailEnable 1.3.6.1.4.1.5040.1.2.9.3.1.3.3.4 octet string read-write
Set this bit to enable the sending of mails: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Mail enable
                                       wtWebGraphThermHygroMailAuthentication 1.3.6.1.4.1.5040.1.2.9.3.1.3.3.5 octet string read-write
Selection of the authentication modi: The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : POP3 before SMTP Bit 1 : ESMTP, authentication Bit 0 : SMTP, no authentication
                                       wtWebGraphThermHygroMailAuthUser 1.3.6.1.4.1.5040.1.2.9.3.1.3.3.6 octet string read-write
Name of the user to be authenticated.
                                       wtWebGraphThermHygroMailAuthPassword 1.3.6.1.4.1.5040.1.2.9.3.1.3.3.7 octet string read-write
Authentication password.
                                       wtWebGraphThermHygroMailPop3Server 1.3.6.1.4.1.5040.1.2.9.3.1.3.3.8 octet string read-write
Name or Ip-address of the POP3 Servers.
                                   wtWebGraphThermHygroSNMP 1.3.6.1.4.1.5040.1.2.9.3.1.3.4
                                       wtWebGraphThermHygroSnmpCommunityStringRead 1.3.6.1.4.1.5040.1.2.9.3.1.3.4.1 octet string read-write
Community string read only
                                       wtWebGraphThermHygroSnmpCommunityStringReadWrite 1.3.6.1.4.1.5040.1.2.9.3.1.3.4.2 octet string read-write
Community string read / write
                                       wtWebGraphThermHygroSystemTrapManagerIP 1.3.6.1.4.1.5040.1.2.9.3.1.3.4.3 octet string read-write
Name or IP address of the TCP server which accepts the system trap.
                                       wtWebGraphThermHygroSystemTrapEnable 1.3.6.1.4.1.5040.1.2.9.3.1.3.4.4 octet string read-write
Binary coded trigger conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: ColdStart Bit 1: WarmStart Bit 2-7: unused
                                       wtWebGraphThermHygroSnmpEnable 1.3.6.1.4.1.5040.1.2.9.3.1.3.4.5 octet string read-write
Set bit 0 to enable SNMP. If disabled, the device did not respond to any SNMP requests. Bit 1 decided wether the community string of read operations is compared with the system password or not: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : SNMP enable
                                       wtWebGraphThermHygroSnmpCommunityStringTrap 1.3.6.1.4.1.5040.1.2.9.3.1.3.4.6 octet string read-write
Community string send within traps.
                                   wtWebGraphThermHygroUDP 1.3.6.1.4.1.5040.1.2.9.3.1.3.5
                                       wtWebGraphThermHygroUdpPort 1.3.6.1.4.1.5040.1.2.9.3.1.3.5.1 integer read-write
Udp port to which the Udp queries ( short form GET requests) can be sent. This port number must be unique within the device.
                                       wtWebGraphThermHygroUdpEnable 1.3.6.1.4.1.5040.1.2.9.3.1.3.5.2 octet string read-write
Set this bit to enable UDP support: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : UDP enable
                                   wtWebGraphThermHygroSyslog 1.3.6.1.4.1.5040.1.2.9.3.1.3.6
                                       wtWebGraphThermHygroSyslogServerIP 1.3.6.1.4.1.5040.1.2.9.3.1.3.6.1 octet string read-write
Name or IP address of the Syslog server, which accepts the Syslog messgaes.
                                       wtWebGraphThermHygroSyslogServerPort 1.3.6.1.4.1.5040.1.2.9.3.1.3.6.2 integer read-write
Portnumber of the Syslog servers, default 514.
                                       wtWebGraphThermHygroSyslogSystemMessagesEnable 1.3.6.1.4.1.5040.1.2.9.3.1.3.6.3 octet string read-write
Binary coded trigger conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: ColdStart Bit 1: WarmStart Bit 2: Diag Messages Bit 3-7: unused
                                       wtWebGraphThermHygroSyslogEnable 1.3.6.1.4.1.5040.1.2.9.3.1.3.6.4 octet string read-write
Set bit 0to enable Syslog: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Syslog enable
                                   wtWebGraphThermHygroFTP 1.3.6.1.4.1.5040.1.2.9.3.1.3.7
                                       wtWebGraphThermHygroFTPServerIP 1.3.6.1.4.1.5040.1.2.9.3.1.3.7.1 octet string read-write
Name or IP address of the FTP server, which accepts the FTP messages.
                                       wtWebGraphThermHygroFTPServerControlPort 1.3.6.1.4.1.5040.1.2.9.3.1.3.7.2 integer read-write
Portnumber of the control port of the FTP server, default 21.
                                       wtWebGraphThermHygroFTPUserName 1.3.6.1.4.1.5040.1.2.9.3.1.3.7.3 octet string read-write
FTP Loggin: user name.
                                       wtWebGraphThermHygroFTPPassword 1.3.6.1.4.1.5040.1.2.9.3.1.3.7.4 octet string read-write
FTP Loggin: user password.
                                       wtWebGraphThermHygroFTPAccount 1.3.6.1.4.1.5040.1.2.9.3.1.3.7.5 octet string read-write
FTP Loggin: name of account.
                                       wtWebGraphThermHygroFTPOption 1.3.6.1.4.1.5040.1.2.9.3.1.3.7.6 octet string read-write
Bit 0 switches the FTP Server in Passiv-Mode, the Client controls the data connection on its own: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : PASV enable
                                       wtWebGraphThermHygroFTPEnable 1.3.6.1.4.1.5040.1.2.9.3.1.3.7.7 octet string read-write
Set Bit 0 to enable FTP: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : FTP enable
                               wtWebGraphThermHygroDatalogger 1.3.6.1.4.1.5040.1.2.9.3.1.4
                                   wtWebGraphThermHygroLoggerTimebase 1.3.6.1.4.1.5040.1.2.9.3.1.4.1 integer read-write
Time base of the data logger Enumeration: 'wtWebGraphThermHygroDatalogger-1Min': 1, 'wtWebGraphThermHygroDatalogger-60Min': 4, 'wtWebGraphThermHygroDatalogger-5Min': 2, 'wtWebGraphThermHygroDatalogger-15Min': 3.
                                   wtWebGraphThermHygroLoggerSensorSel 1.3.6.1.4.1.5040.1.2.9.3.1.4.2 octet string read-write
Binary coded trigger conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Sensor 1 Bit 1: Sensor 2 Bit 2-7: unused
                                   wtWebGraphThermHygroDisplaySensorSel 1.3.6.1.4.1.5040.1.2.9.3.1.4.3 octet string read-write
Binary coded sensor selection: only selected sensors will be shown in the graphical presentation: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Sensor 1 Bit 1: Sensor 2 Bit 2-7: unused
                                   wtWebGraphThermHygroSensorColorTable 1.3.6.1.4.1.5040.1.2.9.3.1.4.4 no-access
List of sensor colors for the praphical presentation.
                                       wtWebGraphThermHygroSensorColorEntry 1.3.6.1.4.1.5040.1.2.9.3.1.4.4.1 no-access
Index numbers of the sensors.
                                           wtWebGraphThermHygroSensorColor 1.3.6.1.4.1.5040.1.2.9.3.1.4.4.1.1 octet string read-write
Color of the sensors at the praphical presention.
                                   wtWebGraphThermHygroAutoScaleEnable 1.3.6.1.4.1.5040.1.2.9.3.1.4.5 octet string read-write
If bit 0 is set, vertical auto scale is enabled: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Auto Scale enable
                                   wtWebGraphThermHygroVerticalUpperLimit 1.3.6.1.4.1.5040.1.2.9.3.1.4.6 octet string read-write
This value defines the maximum temperature shown in the graphical presentation, if no auto scaling is selected. Temperature in degrees with maximum 2 decimal places.
                                   wtWebGraphThermHygroVerticalLowerLimit 1.3.6.1.4.1.5040.1.2.9.3.1.4.7 octet string read-write
This value defines the minimum temperature shown in the graphical presentation, if no auto scaling is selected. Temperature in degrees with maximum 2 decimal places.
                                   wtWebGraphThermHygroHorizontalZoom 1.3.6.1.4.1.5040.1.2.9.3.1.4.8 integer read-write
Defines the default zoom stage, if no auto scaling is selected. Enumeration: 'wtWebGraphThermHygroZoom-25days': 6, 'wtWebGraphThermHygroZoom-75min': 2, 'wtWebGraphThermHygroZoom-5hrs': 3, 'wtWebGraphThermHygroZoom-25min': 1, 'wtWebGraphThermHygroZoom-30hrs': 4, 'wtWebGraphThermHygroZoom-5days': 5.
                               wtWebGraphThermHygroAlarm 1.3.6.1.4.1.5040.1.2.9.3.1.5
                                   wtWebGraphThermHygroAlarmCount 1.3.6.1.4.1.5040.1.2.9.3.1.5.1 integer read-only
Number of independent alarms.
                                   wtWebGraphThermHygroAlarmIfTable 1.3.6.1.4.1.5040.1.2.9.3.1.5.2 no-access
List of alarm indices.
                                       wtWebGraphThermHygroAlarmIfEntry 1.3.6.1.4.1.5040.1.2.9.3.1.5.2.1 no-access
Numbers of the alarms.
                                           wtWebGraphThermHygroAlarmNo 1.3.6.1.4.1.5040.1.2.9.3.1.5.2.1.1 integer read-only
Alarm number.
                                   wtWebGraphThermHygroAlarmTable 1.3.6.1.4.1.5040.1.2.9.3.1.5.3 no-access
List of settings depending on the alarm number.
                                       wtWebGraphThermHygroAlarmEntry 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1 no-access
Alarm parameters of the individual alarms.
                                           wtWebGraphThermHygroAlarmTrigger 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.1 octet string read-write
Binary coded trigger conditions: Octet 1: unused Octet 2: unused Octet 3: Bit 0: Timer Bit 1: ColdStart Bit 2: WarmStart Octet 4: Bit 0: Sensor 1 Bit 1: Sensor 2 Bit 2-7: unused
                                           wtWebGraphThermHygroAlarmMin 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.2 octet string read-write
Minimum temperature in degrees with maximum 2 decimal places.
                                           wtWebGraphThermHygroAlarmMax 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.3 octet string read-write
Maximum temperature in degrees with maximum 2 decimal places.
                                           wtWebGraphThermHygroAlarmHysteresis 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.4 octet string read-write
Temperature changes of this size clears the alarm state (MAX-hyst, MIN+hyst.) , in degrees with maximum 2 decimal places.
                                           wtWebGraphThermHygroAlarmDelay 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.5 octet string read-write
Alarm will be delayed by setting this time while stable alarm condition occur (time in minutes).
                                           wtWebGraphThermHygroAlarmInterval 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.6 octet string read-write
Send interval for alarm messages.
                                           wtWebGraphThermHygroAlarmEnable 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.7 octet string read-write
Binary coded alarm enable: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Mail Enable Bit 1: SNMP Trap enable Bit 2: TCP Client enable
                                           wtWebGraphThermHygroAlarmEMailAddr 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.8 octet string read-write
E-Mail address for sending the alarm mail to.
                                           wtWebGraphThermHygroAlarmMailSubject 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.9 octet string read-write
Subject line for alarm mail.
                                           wtWebGraphThermHygroAlarmMailText 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.10 octet string read-write
Alarm mail text: provides the current temperature; n = 1..8. provides the current time.
                                           wtWebGraphThermHygroAlarmManagerIP 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.11 octet string read-write
Name or IP address of the SNMP Manager which accepts the trap.
                                           wtWebGraphThermHygroAlarmTrapText 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.12 octet string read-write
This text is sent in the trap body.
                                           wtWebGraphThermHygroAlarmMailOptions 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.13 octet string read-write
Binary coded options: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Attach Thermo.csv Enable Bit 1 : CSV-Data_since_last_report Bit 2-7: unused
                                           wtWebGraphThermHygroAlarmTcpIpAddr 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.14 octet string read-write
Name or IP address of the TCP server which accepts the trap.
                                           wtWebGraphThermHygroAlarmTcpPort 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.15 integer read-write
Port number of the TCP server which accepts the trap.
                                           wtWebGraphThermHygroAlarmTcpText 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.16 octet string read-write
This text is sent in the TCP trap body.
                                           wtWebGraphThermHygroAlarmClearMailSubject 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.17 octet string read-write
Subject line for alarm clear mail.
                                           wtWebGraphThermHygroAlarmClearMailText 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.18 octet string read-write
Alarm clear mail text: provides the current temperature; n = 1..8. provides the current time.
                                           wtWebGraphThermHygroAlarmClearTrapText 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.19 octet string read-write
This text is sent in the trap body.
                                           wtWebGraphThermHygroAlarmClearTcpText 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.20 octet string read-write
This text is sent in the TCP trap body.
                                           wtWebGraphThermHygroAlarmDeltaTemp 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.21 octet string read-write
Maximum rate of change degrees/min with maximum 2 decimal places. Compared with the average of a period of 5 minutes.
                                           wtWebGraphThermHygroAlarmRHMin 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.22 octet string read-write
Minimum rel. Humidity in percent with maximum 2 decimal places.
                                           wtWebGraphThermHygroAlarmRHMax 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.23 octet string read-write
Maximum rel.Humidity in percent with maximum 2 decimal places.
                                           wtWebGraphThermHygroAlarmRHHysteresis 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.24 octet string read-write
Hysterese rel. Humidity in percent with maximum 2 decimal places.
                                           wtWebGraphThermHygroAlarmAHMin 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.25 octet string read-write
Minimum abs. Humidity in g/(m*m*m) with maximum 2 decimal places.
                                           wtWebGraphThermHygroAlarmAHMax 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.26 octet string read-write
Maximum abs. Humidity in g/(m*m*m) with maximum 2 decimal places.
                                           wtWebGraphThermHygroAlarmSyslogIpAddr 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.27 ipaddress read-write
IP address of the syslog server to which the Webio device should send syslog messages.
                                           wtWebGraphThermHygroAlarmSyslogPort 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.28 integer read-write
Port number of the syslog server to which the Webio device should send syslog messages.
                                           wtWebGraphThermHygroAlarmSyslogText 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.29 octet string read-write
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164. This text appears in the following syslog message body.
                                           wtWebGraphThermHygroAlarmSyslogClearText 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.30 octet string read-write
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164. This text appears in the following syslog message body.
                                           wtWebGraphThermHygroAlarmFtpDataPort 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.31 octet string read-write
Local data port: 1..65535 or AUTO: the next free port will be assigned.
                                           wtWebGraphThermHygroAlarmFtpFileName 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.32 octet string read-write
Name of the file including path informations.
                                           wtWebGraphThermHygroAlarmFtpText 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.33 octet string read-write
Message text to store on the FTP server.
                                           wtWebGraphThermHygroAlarmFtpClearText 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.34 octet string read-write
Alarm clear message to store on the FTP server.
                                           wtWebGraphThermHygroAlarmFtpOptions 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.35 octet string read-write
Binary coded options, select only one option at the same time: STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STORE Bit 1 : APPEND Bit 2-7: unused
                                           wtWebGraphThermHygroAlarmTimerCron 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.36 octet string read-write
This entry contains 5 space or tab seperated text fields for time trigger definition. Each field must match with the actual time to trigger a message, weekday and day of month are interpreted separatley. 1: Minutes Range 0-59 2. Hours Range 0-23, 0 is midnight 3: Day of month Range 1-31 4: Month Range 1-12 5: Weekday Range 0-6, 0 is sunday Syntax for every field: - an asterix (*) enables every possible setting of a field - single numbers seperated by commas - a partition within the allowed range (1-5) - step size within an partition of the allowed range (0-59/2: every second minute).
                           wtWebGraphThermHygroPorts 1.3.6.1.4.1.5040.1.2.9.3.2
                               wtWebGraphThermHygroPortTable 1.3.6.1.4.1.5040.1.2.9.3.2.1 no-access
List of settings depending on the sensor number.
                                   wtWebGraphThermHygroPortEntry 1.3.6.1.4.1.5040.1.2.9.3.2.1.1 no-access
Sensor parameters for the individual sensors.
                                       wtWebGraphThermHygroPortName 1.3.6.1.4.1.5040.1.2.9.3.2.1.1.1 octet string read-write
Name of the sensor.
                                       wtWebGraphThermHygroPortText 1.3.6.1.4.1.5040.1.2.9.3.2.1.1.2 octet string read-write
Description of the sensor.
                                       wtWebGraphThermHygroPortOffset1 1.3.6.1.4.1.5040.1.2.9.3.2.1.1.3 octet string read-write
Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 1.
                                       wtWebGraphThermHygroPortTemperature1 1.3.6.1.4.1.5040.1.2.9.3.2.1.1.4 octet string read-write
Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places.
                                       wtWebGraphThermHygroPortOffset2 1.3.6.1.4.1.5040.1.2.9.3.2.1.1.5 octet string read-write
Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 2.
                                       wtWebGraphThermHygroPortTemperature2 1.3.6.1.4.1.5040.1.2.9.3.2.1.1.6 octet string read-write
Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places.
                                       wtWebGraphThermHygroPortComment 1.3.6.1.4.1.5040.1.2.9.3.2.1.1.7 octet string read-write
Offset calibration: informations of date, name of operator, reference devices.
                                       wtWebGraphThermHygroPortSensorSelect 1.3.6.1.4.1.5040.1.2.9.3.2.1.1.8 octet string read-write
Binary coded options for sensor 1: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : PT100 Bit 1 : PT1000 (default) Bit 2-7: unused Binary coded options for sensor 2: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : W&T Sensor rel. humidity (default) Bit 1 : Skalar 0-2.5V Bit 2 : Disconnect Bit 3-7: unused
                           wtWebGraphThermHygroManufact 1.3.6.1.4.1.5040.1.2.9.3.3
                               wtWebGraphThermHygroMfName 1.3.6.1.4.1.5040.1.2.9.3.3.1 octet string read-write
Manufacturer company name
                               wtWebGraphThermHygroMfAddr 1.3.6.1.4.1.5040.1.2.9.3.3.2 octet string read-write
Manufacturer address.
                               wtWebGraphThermHygroMfHotline 1.3.6.1.4.1.5040.1.2.9.3.3.3 octet string read-write
Manufacturer hotline.
                               wtWebGraphThermHygroMfInternet 1.3.6.1.4.1.5040.1.2.9.3.3.4 octet string read-write
Manufacturer Internet address.
                               wtWebGraphThermHygroMfDeviceTyp 1.3.6.1.4.1.5040.1.2.9.3.3.5 octet string read-write
Manufacturer device name (model number).
                               wtWebGraphThermHygroMfOrderNo 1.3.6.1.4.1.5040.1.2.9.3.3.6 octet string read-write
Manufacturer part number.
                       wtWebGraphThermHygroDiag 1.3.6.1.4.1.5040.1.2.9.4
                           wtWebGraphThermHygroDiagErrorCount 1.3.6.1.4.1.5040.1.2.9.4.1 integer read-only
Number of entries in the error memory.
                           wtWebGraphThermHygroDiagBinaryError 1.3.6.1.4.1.5040.1.2.9.4.2 octet string read-only
Error causes coded bit-by-bit.
                           wtWebGraphThermHygroDiagErrorIndex 1.3.6.1.4.1.5040.1.2.9.4.3 integer read-write
The value of this variable is used as an index to read an error massege from wtWebGraphThermHygroDiagErrorMessage. Errors are numbered from 1 to wtWebGraphThermHygroDiagErrorCount. Writing a valid value into this variable, making the appropriate message readable from wtWebGraphThermHygroDiagErrorMessage.
                           wtWebGraphThermHygroDiagErrorMessage 1.3.6.1.4.1.5040.1.2.9.4.4 octet string read-only
Using wtWebGraphThermHygroDiagErrorIndex as an index, the appropriate message is available.
                           wtWebGraphThermHygroDiagErrorClear 1.3.6.1.4.1.5040.1.2.9.4.5 integer read-write
Writing 1 into this variable clears all diagnosis messages.
                         wtWebGraphThermHygroAlert1 1.3.6.1.4.1.5040.1.2.90.31
This SNMP trap is generated when Alarm 1 was triggered, SNMP trap enable is set and SNMP is enabled.
                         wtWebGraphThermHygroAlert2 1.3.6.1.4.1.5040.1.2.90.32
This SNMP trap is generated when Alarm 2 was triggered, SNMP trap enable is set and SNMP is enabled.
                         wtWebGraphThermHygroAlert3 1.3.6.1.4.1.5040.1.2.90.33
This SNMP trap is generated when Alarm 3 was triggered, SNMP trap enable is set and SNMP is enabled.
                         wtWebGraphThermHygroAlert4 1.3.6.1.4.1.5040.1.2.90.34
This SNMP trap is generated when Alarm 4 was triggered, SNMP trap enable is set and SNMP is enabled.
                         wtWebGraphThermHygroAlert5 1.3.6.1.4.1.5040.1.2.90.35
This SNMP trap is generated when Alarm 5 was triggered, SNMP trap enable is set and SNMP is enabled.
                         wtWebGraphThermHygroAlert6 1.3.6.1.4.1.5040.1.2.90.36
This SNMP trap is generated when Alarm 6 was triggered, SNMP trap enable is set and SNMP is enabled.
                         wtWebGraphThermHygroAlert7 1.3.6.1.4.1.5040.1.2.90.37
This SNMP trap is generated when Alarm 7 was triggered, SNMP trap enable is set and SNMP is enabled.
                         wtWebGraphThermHygroAlert8 1.3.6.1.4.1.5040.1.2.90.38
This SNMP trap is generated when Alarm 8 was triggered, SNMP trap enable is set and SNMP is enabled.
                         wtWebGraphThermHygroAlert9 1.3.6.1.4.1.5040.1.2.90.91
This SNMP trap is generated when Alarm 1 was cleared, SNMP trap enable is set and SNMP is enabled.
                         wtWebGraphThermHygroAlert10 1.3.6.1.4.1.5040.1.2.90.92
This SNMP trap is generated when Alarm 2 was cleared, SNMP trap enable is set and SNMP is enabled.
                         wtWebGraphThermHygroAlert11 1.3.6.1.4.1.5040.1.2.90.93
This SNMP trap is generated when Alarm 3 was cleared, SNMP trap enable is set and SNMP is enabled.
                         wtWebGraphThermHygroAlert12 1.3.6.1.4.1.5040.1.2.90.94
This SNMP trap is generated when Alarm 4 was cleared, SNMP trap enable is set and SNMP is enabled.
                         wtWebGraphThermHygroAlert13 1.3.6.1.4.1.5040.1.2.90.95
This SNMP trap is generated when Alarm 5 was cleared, SNMP trap enable is set and SNMP is enabled.
                         wtWebGraphThermHygroAlert14 1.3.6.1.4.1.5040.1.2.90.96
This SNMP trap is generated when Alarm 6 was cleared, SNMP trap enable is set and SNMP is enabled.
                         wtWebGraphThermHygroAlert15 1.3.6.1.4.1.5040.1.2.90.97
This SNMP trap is generated when Alarm 7 was cleared, SNMP trap enable is set and SNMP is enabled.
                         wtWebGraphThermHygroAlert16 1.3.6.1.4.1.5040.1.2.90.98
This SNMP trap is generated when Alarm 8 was cleared, SNMP trap enable is set and SNMP is enabled.
                         wtWebGraphThermHygroAlertDiag 1.3.6.1.4.1.5040.1.2.90.110
This SNMP trap is generated when a diagnosis/error message was triggered, SNMP trap enable is set and SNMP is enabled.