VEC-MIBv5-5: View SNMP OID List / Download MIB
VENDOR: RELTEC CORPORATION
Home | MIB: VEC-MIBv5-5 | |||
---|---|---|---|---|
Download as: |
Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
|
|||
Object Name | OID | Type | Access | Info |
emersonESNA | 1.3.6.1.4.1.885 | |||
vecMIB | 1.3.6.1.4.1.885.1 |
Emerson Energy Systems North America(ESNA) VEC MIB. revision 5.5 |
||
vec | 1.3.6.1.4.1.885.3 | |||
vecInformation | 1.3.6.1.4.1.885.3.1 | |||
vecFirmwareVersion | 1.3.6.1.4.1.885.3.1.1 | displaystring | read-only |
VEC System Firmware Version. |
vecMessageStats | 1.3.6.1.4.1.885.3.1.2 | |||
vecMessageRequests | 1.3.6.1.4.1.885.3.1.2.1 | integer | read-only |
Total number of message requests. |
vecMessageTransmissions | 1.3.6.1.4.1.885.3.1.2.2 | integer | read-only |
Total number of messages transmitted. |
vecMessageNoResponses | 1.3.6.1.4.1.885.3.1.2.3 | integer | read-only |
Total number of no responses. |
vecMessageBadCRCs | 1.3.6.1.4.1.885.3.1.2.4 | integer | read-only |
Total number of bad CRC checks. |
vecMessageLinkErrors | 1.3.6.1.4.1.885.3.1.2.5 | integer | read-only |
Total number of link errors. |
vecMessagePartialResponses | 1.3.6.1.4.1.885.3.1.2.6 | integer | read-only |
Total number of partial responses received. |
vecMessageWrongPackets | 1.3.6.1.4.1.885.3.1.2.7 | integer | read-only |
Total number of wrong packet numbers detected. |
vecMessageErrorReplies | 1.3.6.1.4.1.885.3.1.2.8 | integer | read-only |
Total number of error responses received. |
psStatus | 1.3.6.1.4.1.885.3.2 | |||
psMeasurement | 1.3.6.1.4.1.885.3.2.1 | |||
psSystemVoltage | 1.3.6.1.4.1.885.3.2.1.1 | displaystring | read-only |
System Voltage. |
psSystemCurrent | 1.3.6.1.4.1.885.3.2.1.2 | integer | read-only |
System Current. |
psSubsystemVoltage | 1.3.6.1.4.1.885.3.2.1.3 | displaystring | read-only |
Sub System Voltage. |
psSubsystemCurrent | 1.3.6.1.4.1.885.3.2.1.4 | integer | read-only |
Sub System Current. |
psSenseVoltage | 1.3.6.1.4.1.885.3.2.1.5 | displaystring | read-only |
Sense Voltage. |
psPCUTotalCurrent | 1.3.6.1.4.1.885.3.2.1.6 | displaystring | read-only |
Total PCU Current. |
psBatteryCurrent | 1.3.6.1.4.1.885.3.2.1.7 | displaystring | read-only |
Total Battery Current. |
psBatteryReserveHours | 1.3.6.1.4.1.885.3.2.1.8 | displaystring | read-only |
Battery Reserve Time. |
psTemperatureTable | 1.3.6.1.4.1.885.3.2.2 | no-access |
Temperature Measurement Table. |
|
1.3.6.1.4.1.885.3.2.2.1 | no-access |
Temperature Measurement Table Entry. |
||
psTemperatureIndex | 1.3.6.1.4.1.885.3.2.2.1.1 | integer | read-only |
Temperature Probe Number |
psTemperatureMeasurement | 1.3.6.1.4.1.885.3.2.2.1.2 | displaystring | read-only |
Temperature Value In Centigrade. |
psLVDTable | 1.3.6.1.4.1.885.3.2.3 | no-access |
Low Voltage Disconnect Table. |
|
1.3.6.1.4.1.885.3.2.3.1 | no-access |
Low Voltage Disconnect Table Entry. |
||
psLVDIndex | 1.3.6.1.4.1.885.3.2.3.1.1 | integer | read-only |
LVD Number |
psLVDCircuitA | 1.3.6.1.4.1.885.3.2.3.1.2 | displaystring | read-only |
LVD Circuit A Disconnect Voltage |
psLVDCircuitB | 1.3.6.1.4.1.885.3.2.3.1.3 | displaystring | read-only |
LVD Circuit B Disconnect Voltage |
psDistributionTable | 1.3.6.1.4.1.885.3.2.4 | no-access |
Shunt Pod Table |
|
1.3.6.1.4.1.885.3.2.4.1 | no-access |
Shunt Pod Table Entry. |
||
psShuntIndex | 1.3.6.1.4.1.885.3.2.4.1.1 | integer | read-only |
Shunt Pod Number. |
psShuntCurrent | 1.3.6.1.4.1.885.3.2.4.1.2 | displaystring | read-only |
Shunt POD Current. |
psPCUTable | 1.3.6.1.4.1.885.3.2.5 | no-access |
PCU Table. |
|
1.3.6.1.4.1.885.3.2.5.1 | no-access |
PCU Table Entry. |
||
psPCUIndex | 1.3.6.1.4.1.885.3.2.5.1.1 | integer | read-only |
PCU Number. |
psPCUFail | 1.3.6.1.4.1.885.3.2.5.1.2 | integer | read-only |
PCU Fail Alarm Enumeration: 'true': 1, 'false': 0. |
psPCUCurrent | 1.3.6.1.4.1.885.3.2.5.1.3 | integer | read-only |
PCU Current |
psPCUFerroGateway | 1.3.6.1.4.1.885.3.2.5.1.4 | integer | read-only |
PCU is a Ferro Gateway Rectifier. Enumeration: 'true': 1, 'false': 0. |
psTraps | 1.3.6.1.4.1.885.3.3 | |||
psAlarmsGeneral1 | 1.3.6.1.4.1.885.3.3.1 | |||
psEmergencyStop | 1.3.6.1.4.1.885.3.3.1.1 |
Emergency Stop Alarm. |
||
psAlarmVeryLowVoltage | 1.3.6.1.4.1.885.3.3.1.2 |
50 Percent Battery On Discharge Alarm. |
||
psAlarmLowVoltage | 1.3.6.1.4.1.885.3.3.1.3 |
Battery On Discharge Alarm. |
||
psAlarmSystemHighVoltage1 | 1.3.6.1.4.1.885.3.3.1.4 |
High Voltage 1 Alarm. |
||
psAlarmSystemHighVoltage2 | 1.3.6.1.4.1.885.3.3.1.5 |
High Voltage 2 Alarm. |
||
psAlarmSubsystemLowVoltage | 1.3.6.1.4.1.885.3.3.1.6 |
Subsystem Low Voltage Alarm. |
||
psAlarmSubsystemHighVoltage | 1.3.6.1.4.1.885.3.3.1.7 |
Subsystem High Voltage Alarm. |
||
psAlarmSystemFuse | 1.3.6.1.4.1.885.3.3.1.8 |
System Fuse Alarm. |
||
psAlarmSubsystemFuse | 1.3.6.1.4.1.885.3.3.1.9 |
Subsystem Fuse Alarm. |
||
psAlarmAllACOff | 1.3.6.1.4.1.885.3.3.1.10 |
All AC Off Alarm. |
||
psAlarmSystemOverCurrent | 1.3.6.1.4.1.885.3.3.1.11 |
System Over Current Alarm. |
||
psAlarmSubsystemOverCurrent | 1.3.6.1.4.1.885.3.3.1.12 |
Subsystem Over Current Alarm. |
||
psAlarmLVDsAreInhibited | 1.3.6.1.4.1.885.3.3.1.13 |
LVDs Are Inhibited Alarm. |
||
psAlarmTestEqualizeMode | 1.3.6.1.4.1.885.3.3.1.14 |
Test/Equalize Mode Active. |
||
psAlarmMinor | 1.3.6.1.4.1.885.3.3.1.15 |
System Minor Alarm. |
||
psAlarmMajor | 1.3.6.1.4.1.885.3.3.1.16 |
System Major Alarm. |
||
psAlarmSenseVoltageFuse | 1.3.6.1.4.1.885.3.3.1.17 |
Sense Voltage Fuse Alarm. |
||
psAlarmSystemVoltageFuse | 1.3.6.1.4.1.885.3.3.1.18 |
System Voltage Fuse Alarm. |
||
psAlarmNoSystemVoltage | 1.3.6.1.4.1.885.3.3.1.19 |
No System Voltage Alarm. |
||
psAlarmNoSubsystemVoltage | 1.3.6.1.4.1.885.3.3.1.20 |
No Subsystem Voltage Alarm. |
||
psAlarmNoSenseVoltage | 1.3.6.1.4.1.885.3.3.1.21 |
No Sense Voltage Alarm. |
||
psAlarmDisplayNoReply | 1.3.6.1.4.1.885.3.3.1.22 |
Display Communications Alarm. |
||
psAlarmSubsystemMajor | 1.3.6.1.4.1.885.3.3.1.23 |
Subsystem Major Alarm. |
||
psAlarmSubsystemMinor | 1.3.6.1.4.1.885.3.3.1.24 |
Subsystem Minor Alarm. |
||
psAlarmHighACLine | 1.3.6.1.4.1.885.3.3.1.25 |
High AC Line Alarm. |
||
psAlarmSenseVoltageError | 1.3.6.1.4.1.885.3.3.1.26 |
Sense Voltage Error Alarm. |
||
psAlarmsGeneral2 | 1.3.6.1.4.1.885.3.3.2 | |||
psTestEqualizeHardwareInput | 1.3.6.1.4.1.885.3.3.2.1 |
The MCA Test Equalize Hardware Input Active. |
||
psPCUFailMajor | 1.3.6.1.4.1.885.3.3.2.2 |
PCU Fail Major Alarm. |
||
psPCUFailMinor | 1.3.6.1.4.1.885.3.3.2.3 |
PCU Fail Minor Alarm. |
||
psLVDAlarmMajor | 1.3.6.1.4.1.885.3.3.2.4 |
LVD Major Alarm. |
||
psLVDAlarmMinor | 1.3.6.1.4.1.885.3.3.2.5 |
LVD Minor Alarm. |
||
psPCULoadShare | 1.3.6.1.4.1.885.3.3.2.6 |
PCU Load Share Alarm. |
||
psACFailMajor | 1.3.6.1.4.1.885.3.3.2.7 |
AC Fail Major Alarm. |
||
psACFailMinor | 1.3.6.1.4.1.885.3.3.2.8 |
AC Fail Minor Alarm. |
||
psMCACommFail | 1.3.6.1.4.1.885.3.3.2.9 |
MCA Communications Failure Alarm. |
||
psHVSActive | 1.3.6.1.4.1.885.3.3.2.10 |
High Voltage Shutdown Active. |
||
psRemoteHVSActive | 1.3.6.1.4.1.885.3.3.2.11 |
Remote High Voltage Shutdown Active. |
||
psRemoteEstopActive | 1.3.6.1.4.1.885.3.3.2.12 |
Remote Emergency Stop Active. |
||
psAlarmsBattery | 1.3.6.1.4.1.885.3.3.3 | |||
psAlarmBatteryChargeOverCurrent | 1.3.6.1.4.1.885.3.3.3.1 |
Battery Charge Over Current Alarm. |
||
psBatteryCurrentLimitInhibited | 1.3.6.1.4.1.885.3.3.3.2 |
Battery Current Limit Inhibited Alarm. |
||
psAlarmBatteryPoorHealth | 1.3.6.1.4.1.885.3.3.3.3 |
Battery Poor Health Alarm. |
||
psAlarmBatteryReserveLow | 1.3.6.1.4.1.885.3.3.3.4 |
Battery Reserve Low Alarm. |
||
psPCUSummaryTypeTraps | 1.3.6.1.4.1.885.3.3.4 | |||
psPCUSummaryTraps | 1.3.6.1.4.1.885.3.3.4.1 | |||
psAlarmPCUSummary | 1.3.6.1.4.1.885.3.3.4.1.2 |
PCU Alarm Active. |
||
psPCUNodeTypeTraps | 1.3.6.1.4.1.885.3.3.5 | |||
psPCUTraps | 1.3.6.1.4.1.885.3.3.5.1 | |||
psAlarmPCUId | 1.3.6.1.4.1.885.3.3.5.1.1 | integer | read-only |
PCU Number. |
psAlarmPCUHighACLine | 1.3.6.1.4.1.885.3.3.5.1.2 |
PCU High AC Line Alarm. |
||
psAlarmPCUControllerFailure | 1.3.6.1.4.1.885.3.3.5.1.3 |
PCU Controller Failure Alarm. |
||
psAlarmPCUFanSlowOrStopped | 1.3.6.1.4.1.885.3.3.5.1.4 |
PCU Fan Slow Or Stopped Alarm. |
||
psAlarmPCUTurnedOffByMca | 1.3.6.1.4.1.885.3.3.5.1.5 |
PCU Turned Off By MCA. |
||
psAlarmPCUCircuitBreakerOff | 1.3.6.1.4.1.885.3.3.5.1.6 |
PCU Circuit Breaker Off Alarm. |
||
psAlarmPCUDCorACConvertFail | 1.3.6.1.4.1.885.3.3.5.1.7 |
PCU Converter Fail Alarm. |
||
psAlarmPCUThermalAlarmorCurrentLimit | 1.3.6.1.4.1.885.3.3.5.1.8 |
PCU Thermal Current Limit Alarm. |
||
psAlarmPCUEmergencyStop | 1.3.6.1.4.1.885.3.3.5.1.9 |
PCU Emergency Stop Alarm. |
||
psAlarmPCUInputSwitchOff | 1.3.6.1.4.1.885.3.3.5.1.10 |
PCU Input Switch Off Alarm. |
||
psAlarmPCUHighVoltageShutdown | 1.3.6.1.4.1.885.3.3.5.1.11 |
PCU High Voltage Shutdown Alarm. |
||
psAlarmPCUACInputIsOffOrLow | 1.3.6.1.4.1.885.3.3.5.1.12 |
PCU AC Input Is Off Or Low Alarm. |
||
psAlarmPCUCommunicationFailureWithMCA | 1.3.6.1.4.1.885.3.3.5.1.13 |
PCU Communication Failure Alarm. |
||
psAlarmPCUSenseLeadOpen | 1.3.6.1.4.1.885.3.3.5.1.14 |
PCU Sense Lead Open Alarm. |
||
psShuntTypeTraps | 1.3.6.1.4.1.885.3.3.6 | |||
psShuntTraps | 1.3.6.1.4.1.885.3.3.6.1 | |||
psAlarmShuntId | 1.3.6.1.4.1.885.3.3.6.1.1 | integer | read-only |
Shunt POD Number. |
psAlarmShuntType | 1.3.6.1.4.1.885.3.3.6.1.2 |
Shunt POD Type Alarm. |
||
psAlarmShuntNoReply | 1.3.6.1.4.1.885.3.3.6.1.3 |
Shunt POD Communications Alarm. |
||
psLVDTypeTraps | 1.3.6.1.4.1.885.3.3.7 | |||
psLVDTraps | 1.3.6.1.4.1.885.3.3.7.1 | |||
psAlarmLVDId | 1.3.6.1.4.1.885.3.3.7.1.1 | integer | read-only |
The Analog LVD Number |
psAlarmLVDDisconnectedA | 1.3.6.1.4.1.885.3.3.7.1.2 |
LVD Circuit A Disconnected Alarm. |
||
psAlarmLVDNoReplyA | 1.3.6.1.4.1.885.3.3.7.1.3 |
LVD Circuit A Communications Alarm. |
||
psAlarmLVDBoardFailA | 1.3.6.1.4.1.885.3.3.7.1.4 |
LVD Board Circuit A Fail Alarm. |
||
psAlarmLVDDisconnectedB | 1.3.6.1.4.1.885.3.3.7.1.5 |
LVD Circuit B Disconnected Alarm. |
||
psAlarmLVDNoReplyB | 1.3.6.1.4.1.885.3.3.7.1.6 |
LVD Circuit B No Communications Alarm. |
||
psAlarmLVDBoardFailB | 1.3.6.1.4.1.885.3.3.7.1.7 |
LVD Board Circuit B Fail Alarm. |
||
psTemperatureTypeTraps | 1.3.6.1.4.1.885.3.3.8 | |||
psTemperatureTraps | 1.3.6.1.4.1.885.3.3.8.1 | |||
psAlarmTemperatureId | 1.3.6.1.4.1.885.3.3.8.1.1 | integer | read-only |
Temperature Probe Number. |
psAlarmTemperatureHigh | 1.3.6.1.4.1.885.3.3.8.1.2 |
Temperature High Alarm. |
||
psAlarmTemperatureLow | 1.3.6.1.4.1.885.3.3.8.1.3 |
Temperature Low Alarm. |
||
psAlarmTemperatureNoReply | 1.3.6.1.4.1.885.3.3.8.1.4 |
Temperature Communications Alarm. |
||
psSysInfoTypeTraps | 1.3.6.1.4.1.885.3.3.9 | |||
psSysInfoTraps | 1.3.6.1.4.1.885.3.3.9.1 | |||
psAlarmSysInfoError1 | 1.3.6.1.4.1.885.3.3.9.1.1 |
SysInfo Error 1. |
||
psAlarmSysInfoError2 | 1.3.6.1.4.1.885.3.3.9.1.2 |
SysInfo Error 2. |
||
psAlarmSysInfoString1 | 1.3.6.1.4.1.885.3.3.9.1.3 |
SysInfo String 1. |
||
psAlarmSysInfoString2 | 1.3.6.1.4.1.885.3.3.9.1.4 |
SysInfo String 2. |
||
psAlarmSysInfoString3 | 1.3.6.1.4.1.885.3.3.9.1.5 |
SysInfo String 3. |
||
psAlarmSysInfoString4 | 1.3.6.1.4.1.885.3.3.9.1.6 |
SysInfo String 4. |
||
psAlarmSysInfoString5 | 1.3.6.1.4.1.885.3.3.9.1.7 |
SysInfo String 5. |
||
psAlarmSysInfoString6 | 1.3.6.1.4.1.885.3.3.9.1.8 |
SysInfo String 6. |
||
psAlarmSysInfoString7 | 1.3.6.1.4.1.885.3.3.9.1.9 |
SysInfo String 7. |
||
psAlarmSysInfoString8 | 1.3.6.1.4.1.885.3.3.9.1.10 |
SysInfo String 8. |
||
psAlarmSysInfoString9 | 1.3.6.1.4.1.885.3.3.9.1.11 |
SysInfo String 9. |
||
psAlarmSysInfoString10 | 1.3.6.1.4.1.885.3.3.9.1.12 |
SysInfo String 10. |