USHA-MIB: View SNMP OID List / Download MIB

VENDOR: INGRASYS


 Home MIB: USHA-MIB
Download as:   

Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 ingrasys 1.3.6.1.4.1.2468
           product 1.3.6.1.4.1.2468.1
               upsAgent 1.3.6.1.4.1.2468.1.2
                   ushap 1.3.6.1.4.1.2468.1.2.1
                       upsObjectGroup 1.3.6.1.4.1.2468.1.2.1.1
                           upsIdentGroup 1.3.6.1.4.1.2468.1.2.1.1.1
                               upsIdentGroupManufacturer 1.3.6.1.4.1.2468.1.2.1.1.1.1 displaystring read-only
The name of the UPS manufacturer.
                               upsIdentGroupModel 1.3.6.1.4.1.2468.1.2.1.1.1.2 displaystring read-only
The UPS Model designation.
                               upsIdentGroupUPSFirmwareVersion 1.3.6.1.4.1.2468.1.2.1.1.1.3 displaystring read-only
The UPS firmware/software version(s). This variable may or may not have the same value as upsIdentGroupAgentSoftwareVersion in some implementations.
                               upsIdentGroupAgentSoftwareVersion 1.3.6.1.4.1.2468.1.2.1.1.1.4 displaystring read-only
The USHA software/firmware version. This variable may or may not have the same value as upsIdentGroupUPSSoftwareVersion in some implementations.
                               upsIdentGroupName 1.3.6.1.4.1.2468.1.2.1.1.1.5 displaystring read-write
A string identifying the UPS. This object should be set by the administrator.
                               upsIdentGroupAttachedDevices 1.3.6.1.4.1.2468.1.2.1.1.1.6 displaystring read-write
A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.
                               upsIdentGroupUpsSerialNumber 1.3.6.1.4.1.2468.1.2.1.1.1.7 displaystring read-only
The UPS serial no.
                           upsBatteryGroup 1.3.6.1.4.1.2468.1.2.1.1.2
                               upsBatteryGroupStatus 1.3.6.1.4.1.2468.1.2.1.1.2.1 integer read-only
The indication of the status in the UPS system's batteries. Enumeration: 'unknown': 1, 'batteryDepleted': 4, 'batteryFailure': 6, 'batteryNormal': 2, 'batteryLow': 3, 'batteryDischarging': 5.
                               upsBatteryGroupSecondsOnBattery 1.3.6.1.4.1.2468.1.2.1.1.2.2 integer read-only
If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. 0 shall be returned if the unit is not on battery power.
                               upsBatteryGroupEstimatedMinutesRemaining 1.3.6.1.4.1.2468.1.2.1.1.2.3 integer read-only
An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.
                               upsBatteryGroupEstimatedChargeRemaining 1.3.6.1.4.1.2468.1.2.1.1.2.4 integer read-only
An estimate of the battery charge remaining expressed as a percent of full charge.
                               upsBatteryGroupVoltage 1.3.6.1.4.1.2468.1.2.1.1.2.5 integer read-only
The magnitude of the present battery voltage in 0.1 Volt DC.
                               upsBatteryGroupMandatory 1.3.6.1.4.1.2468.1.2.1.1.2.6 integer read-only
The present battery mandatory.
                               upsBatteryGroupTemperature 1.3.6.1.4.1.2468.1.2.1.1.2.7 integer read-only
The ambient temperature at or near the UPS Battery casing.
                           upsInputGroup 1.3.6.1.4.1.2468.1.2.1.1.3
                               upsInputGroupLineBads 1.3.6.1.4.1.2468.1.2.1.1.3.1 counter read-only
A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance.
                               upsInputGroupNumLines 1.3.6.1.4.1.2468.1.2.1.1.3.2 integer read-only
The number of input lines utilized in this device. This variable indicates the number of rows in the input table.
                               upsInputGroupTable 1.3.6.1.4.1.2468.1.2.1.1.3.3 no-access
A list of input table entries. The number of entries is given by the value of upsInputGroupNumLines.
                                   upsInputGroupEntry 1.3.6.1.4.1.2468.1.2.1.1.3.3.1 no-access
An entry containing information applicable to a particular input line.
                                       upsInputGroupLineIndex 1.3.6.1.4.1.2468.1.2.1.1.3.3.1.1 positiveinteger read-only
The index of UpsInputGroupEntry.
                                       upsInputGroupFrequency 1.3.6.1.4.1.2468.1.2.1.1.3.3.1.2 nonnegativeinteger read-only
The present input frequency.
                                       upsInputGroupVoltage 1.3.6.1.4.1.2468.1.2.1.1.3.3.1.3 nonnegativeinteger read-only
The input utility line voltage in 0.1 volts.
                                       upsInputGroupCurrent 1.3.6.1.4.1.2468.1.2.1.1.3.3.1.4 nonnegativeinteger read-only
The magnitude of the present input current in 0.1 A.
                                       upsInputGroupTruePower 1.3.6.1.4.1.2468.1.2.1.1.3.3.1.5 nonnegativeinteger read-only
The magnitude of the present input true power.
                                       upsInputGroupVoltageMax 1.3.6.1.4.1.2468.1.2.1.1.3.3.1.6 nonnegativeinteger read-only
The maximum utility line voltage in 0.1 VAC for last 1 minute.
                                       upsInputGroupVoltageMin 1.3.6.1.4.1.2468.1.2.1.1.3.3.1.7 nonnegativeinteger read-only
The minimum utility line voltage in 0.1 VAC for last 1 minute.
                           upsOutputGroup 1.3.6.1.4.1.2468.1.2.1.1.4
                               upsOutputGroupSource 1.3.6.1.4.1.2468.1.2.1.1.4.1 integer read-only
The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker. Enumeration: 'none': 2, 'normal': 3, 'battery': 5, 'reducer': 7, 'other': 1, 'bypass': 4, 'booster': 6.
                               upsOutputGroupFrequency 1.3.6.1.4.1.2468.1.2.1.1.4.2 integer read-only
The current output frequency of the UPS system in 0.1 of HZ.
                               upsOutputGroupNumLines 1.3.6.1.4.1.2468.1.2.1.1.4.3 integer read-only
The number of output lines utilized in this device. This variable indicates the number of rows in the output table.
                               upsOutputGroupTable 1.3.6.1.4.1.2468.1.2.1.1.4.4 no-access
A list of output table entries. The number of entries is given by the value of upsOutputGroupNumLines.
                                   upsOutputGroupEntry 1.3.6.1.4.1.2468.1.2.1.1.4.4.1 no-access
An entry containing information applicable to a particular output line.
                                       upsOutputGroupLineIndex 1.3.6.1.4.1.2468.1.2.1.1.4.4.1.1 positiveinteger read-only
The output line identifier.
                                       upsOutputGroupVoltage 1.3.6.1.4.1.2468.1.2.1.1.4.4.1.2 nonnegativeinteger read-only
The output voltage of the UPS system in 0.1 volts.
                                       upsOutputGroupCurrent 1.3.6.1.4.1.2468.1.2.1.1.4.4.1.3 nonnegativeinteger read-only
The output current of the UPS system in 0.1 Amps.
                                       upsOutputGroupPower 1.3.6.1.4.1.2468.1.2.1.1.4.4.1.4 nonnegativeinteger read-only
The present output true power.
                                       upsOutputGroupPercentLoad 1.3.6.1.4.1.2468.1.2.1.1.4.4.1.5 integer read-only
The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.
                           upsBypassGroup 1.3.6.1.4.1.2468.1.2.1.1.5
                               upsBypassGroupFrequency 1.3.6.1.4.1.2468.1.2.1.1.5.1 integer read-only
The present bypass frequency.
                               upsBypassGroupNumLines 1.3.6.1.4.1.2468.1.2.1.1.5.2 integer read-only
The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.
                               upsBypassGroupTable 1.3.6.1.4.1.2468.1.2.1.1.5.3 no-access
A list of bypass table entries. The number of entries is given by the value of upsBypassGroupNumLines.
                                   upsBypassGroupEntry 1.3.6.1.4.1.2468.1.2.1.1.5.3.1 no-access
An entry containing information applicable to a particular bypass input.
                                       upsBypassGroupLineIndex 1.3.6.1.4.1.2468.1.2.1.1.5.3.1.1 positiveinteger read-only
The bypass line identifier.
                                       upsBypassGroupVoltage 1.3.6.1.4.1.2468.1.2.1.1.5.3.1.2 nonnegativeinteger read-only
The present bypass voltage.
                                       upsBypassGroupCurrent 1.3.6.1.4.1.2468.1.2.1.1.5.3.1.3 nonnegativeinteger read-only
The present bypass current.
                                       upsBypassGroupPower 1.3.6.1.4.1.2468.1.2.1.1.5.3.1.4 nonnegativeinteger read-only
The present true power conveyed by the bypass.
                           upsTestGroup 1.3.6.1.4.1.2468.1.2.1.1.6
                               upsTestBatteryTestSettingTime 1.3.6.1.4.1.2468.1.2.1.1.6.1 integer read-write
The object specify the test time for battery test.
                               upsBatteryTest 1.3.6.1.4.1.2468.1.2.1.1.6.2 integer read-write
This object specify the battery test type and initiate battery test. If battTestWithTime selected, the test time is refer to upsTestBatteryTestTime. Enumeration: 'none': 1, 'battTestUntilLow': 3, 'battTestWithTime': 4, 'battTestCancelTest': 5, 'battTest10sec': 2, 'battTestClearInfo': 6.
                               upsTestBatteryTestResult 1.3.6.1.4.1.2468.1.2.1.1.6.3 integer read-only
The results of the current or last UPS diagnostics test performed. The values for donePassed(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results. Enumeration: 'noTestsInitiated': 6, 'donePassed': 1, 'doneError': 3, 'doneWarning': 2, 'aborted': 4, 'inProgress': 5.
                               upsTestBatteryTestStartTime 1.3.6.1.4.1.2468.1.2.1.1.6.4 displaystring read-only
The value of the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestBatteryTestResult is noTestsInitiated(6), upsTestStartTime has the value 01/01/1970 00:00:00.
                               upsTestBatteryTestElapsedTime 1.3.6.1.4.1.2468.1.2.1.1.6.5 displaystring read-only
The amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestElapsedTime has the value 00:00:00.00.
                               upsBatteryTestScheduleTable 1.3.6.1.4.1.2468.1.2.1.1.6.6 no-access
Table which describes the schedule for automatically battery test.
                                   upsBatteryTestScheduleEntry 1.3.6.1.4.1.2468.1.2.1.1.6.6.1 no-access
                                       upsBatteryTestScheduleIndex 1.3.6.1.4.1.2468.1.2.1.1.6.6.1.1 integer read-only
The index of battery test scheduled.
                                       upsBatteryTestScheduleDay 1.3.6.1.4.1.2468.1.2.1.1.6.6.1.2 integer read-write
The weekday on which the UPS should start battery test. Enumeration: 'none': 9, 'monday': 2, 'tuesday': 3, 'friday': 6, 'wednesday': 4, 'thursday': 5, 'sunday': 1, 'specialDay': 8, 'saturday': 7.
                                       upsBatteryTestScheduleTime 1.3.6.1.4.1.2468.1.2.1.1.6.6.1.3 displaystring read-write
The time that the battery test will be initiated in hh:mm format.
                                       upsBatteryTestScheduleType 1.3.6.1.4.1.2468.1.2.1.1.6.6.1.4 integer read-write
The type of battery test. Enumeration: 'battTestWithTime': 4, 'none': 1, 'battTestUntilLow': 3, 'battTest10sec': 2.
                                       upsBatteryTestScheduleTestWithTime 1.3.6.1.4.1.2468.1.2.1.1.6.6.1.5 integer read-only
The battTestWithTime of battery test is supported or not. Enumeration: 'notSupported': 2, 'supported': 1.
                                       upsBatteryTestScheduleSpecialDay 1.3.6.1.4.1.2468.1.2.1.1.6.6.1.6 displaystring read-write
The special day that the battery test will be initiated in dd/mm/yyyy format.
                           upsControlGroup 1.3.6.1.4.1.2468.1.2.1.1.7
                               upsControlUpsShutdownDelay 1.3.6.1.4.1.2468.1.2.1.1.7.1 integer read-write
The delay in seconds the UPS remains on after being told to turn off.
                               upsControlUpsSleepTime 1.3.6.1.4.1.2468.1.2.1.1.7.2 integer read-write
The time in minutes for the UPS to go to sleep when instructed. When in sleep mode, the UPS will not provide output power regardless of the input line state. Once the specified time has elapsed, output power will be restored. This is a configuration setting. The UPS will not go to sleep until told to do so by the manager from a management station. Any input value is allowed, however the UPS only recognizes 0 - 9999 minutes in one minute increments. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.
                               upsControlUpsOnOffControl 1.3.6.1.4.1.2468.1.2.1.1.7.3 integer read-write
Setting this variable to control UPS output status. turnUpsOff(1) will set UPS turn off output after upsControlUpsShutdownDelay period expired. putUpsToSleep(2) will set UPS turn off output after upsControlUpsShutdownDelay period expired, UPS output will stay off with the period defined by upsControlUpsSleepTime, then turn output on. turnOnUpsOrCancelShutdown(3) can used to turn on UPS output, or cancel any shutdown process. Enumeration: 'putUpsToSleep': 2, 'turnUpsOff': 1, 'none': 4, 'turnOnUpsOrCancelShutdown': 3.
                               upsControlShutdownParametersTable 1.3.6.1.4.1.2468.1.2.1.1.7.4 no-access
Table which describes the parametes for shutdown process when shutdown event occurs
                                   upsControlShutdownParametersEntry 1.3.6.1.4.1.2468.1.2.1.1.7.4.1 no-access
                                       upsControlEvent 1.3.6.1.4.1.2468.1.2.1.1.7.4.1.1 integer read-only
The shutdown event identification Enumeration: 'specialDaySchedule': 6, 'emdAlarm2': 9, 'emdAlarm1': 8, 'upsOverload': 3, 'weeklySchedule': 5, 'upsOverTempeature': 4, 'emdTemperatureOverThreshold': 7, 'batteryLow': 2, 'acFail': 1.
                                       upsControlEventStatus 1.3.6.1.4.1.2468.1.2.1.1.7.4.1.2 integer read-write
Status of the corresponding shutdown Event. When set to disable(), shutdown process will not start when corresponding event occured. Enumeration: 'upsTurnOff': 4, 'clientShutdown': 3, 'disable': 1, 'warning': 2.
                                       upsControlDelay 1.3.6.1.4.1.2468.1.2.1.1.7.4.1.3 integer read-write
The Delay after the occurance of the curresponding shutdown event that USHA should issue shutdown request to connected clients. For WeeklyScheduledShutdown and SpecialScheduledShutdown, this is the time before the configured Shutdowntime when USHA will start sending the warning message to the connected clients. The value is in units of minutes.
                                       upsControlFirstWarning 1.3.6.1.4.1.2468.1.2.1.1.7.4.1.4 integer read-write
The delay after the occurance of the curresponding shutdown event that the USHA will start sending the warning message to the connected clients. The value is in units of seconds
                                       upsControlWarningInterval 1.3.6.1.4.1.2468.1.2.1.1.7.4.1.5 integer read-write
The frequency of sending warning messages to the connected clients when the curresponding shutdown event occurs. The value is in units of seconds.
                               upsControlWeeklyScheduleTable 1.3.6.1.4.1.2468.1.2.1.1.7.5 no-access
The table to schedule shutting down the ups by weekly.
                                   upsControlWeeklyScheduleEntry 1.3.6.1.4.1.2468.1.2.1.1.7.5.1 no-access
The entries for each day.
                                       upsControlWeeklyIndex 1.3.6.1.4.1.2468.1.2.1.1.7.5.1.1 integer read-only
The index of scheduled events.
                                       upsControlWeeklyShutdownDay 1.3.6.1.4.1.2468.1.2.1.1.7.5.1.2 integer read-write
The weekday on which the UPS should shut down. Enumeration: 'none': 8, 'monday': 2, 'tuesday': 3, 'friday': 6, 'wednesday': 4, 'thursday': 5, 'sunday': 1, 'saturday': 7.
                                       upsControlWeeklyShutdownTime 1.3.6.1.4.1.2468.1.2.1.1.7.5.1.3 displaystring read-write
The time that the process of shutting down the UPS will be initiated in hh:mm format.
                                       upsControlWeeklyRestartDay 1.3.6.1.4.1.2468.1.2.1.1.7.5.1.4 integer read-write
The weekday on which the UPS should restart Enumeration: 'none': 8, 'monday': 2, 'tuesday': 3, 'friday': 6, 'wednesday': 4, 'thursday': 5, 'sunday': 1, 'saturday': 7.
                                       upsControlWeeklyRestartTime 1.3.6.1.4.1.2468.1.2.1.1.7.5.1.5 displaystring read-write
The time the UPS will restart in hh:mm format.
                               upsControlSpecialScheduleTable 1.3.6.1.4.1.2468.1.2.1.1.7.6 no-access
The table to schedule shutting down the ups.
                                   upsControlSpecialScheduleEntry 1.3.6.1.4.1.2468.1.2.1.1.7.6.1 no-access
The entries for each day.
                                       upsControlSpecialIndex 1.3.6.1.4.1.2468.1.2.1.1.7.6.1.1 integer read-only
The index of scheduled events.
                                       upsControlSpecialShutdownDay 1.3.6.1.4.1.2468.1.2.1.1.7.6.1.2 displaystring read-write
The date on which the UPS should shut down in dd/mm/yyyy format.
                                       upsControlSpecialShutdownTime 1.3.6.1.4.1.2468.1.2.1.1.7.6.1.3 displaystring read-write
The time that the process of shutting down the UPS will be initiated in hh:mm format
                                       upsControlSpecialRestartDay 1.3.6.1.4.1.2468.1.2.1.1.7.6.1.4 displaystring read-write
The date on which the UPS should restart in dd/mm/yyyy format
                                       upsControlSpecialRestartTime 1.3.6.1.4.1.2468.1.2.1.1.7.6.1.5 displaystring read-write
The time the UPS will restart in hh:mm format.
                           upsConfigGroup 1.3.6.1.4.1.2468.1.2.1.1.8
                               upsConfigGroupInputVoltage 1.3.6.1.4.1.2468.1.2.1.1.8.1 integer read-only
The magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.
                               upsConfigGroupInputFreq 1.3.6.1.4.1.2468.1.2.1.1.8.2 integer read-only
The nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.
                               upsConfigGroupOutputVoltage 1.3.6.1.4.1.2468.1.2.1.1.8.3 integer read-only
The magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.
                               upsConfigGroupOutputFreq 1.3.6.1.4.1.2468.1.2.1.1.8.4 integer read-only
The nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.
                               upsConfigGroupOutputVA 1.3.6.1.4.1.2468.1.2.1.1.8.5 nonnegativeinteger read-only
The magnitude of the nominal Volt-Amp rating.
                               upsConfigGroupOutputPower 1.3.6.1.4.1.2468.1.2.1.1.8.6 nonnegativeinteger read-only
The magnitude of the nominal true power rating.
                               upsConfigGroupOverTemperatureSetPoint 1.3.6.1.4.1.2468.1.2.1.1.8.7 nonnegativeinteger read-write
The maximum temperature allowed before the UPS operation temperature is too high.
                               upsConfigGroupOverLoadSetPoint 1.3.6.1.4.1.2468.1.2.1.1.8.8 nonnegativeinteger read-write
The maximum output load allowed before the load is too high for UPS operation.
                           upsClients 1.3.6.1.4.1.2468.1.2.1.1.9
                               upsClientsConnectedNum 1.3.6.1.4.1.2468.1.2.1.1.9.1 nonnegativeinteger read-only
The count of clients which have resgistered for UPS shutdown control.
                               upsDevicesTable 1.3.6.1.4.1.2468.1.2.1.1.9.2 no-access
The devices powered by UPS and registered to USHA
                                   upsDevicesEntry 1.3.6.1.4.1.2468.1.2.1.1.9.2.1 no-access
The devices protected by USHA
                                       indexOfDevice 1.3.6.1.4.1.2468.1.2.1.1.9.2.1.1 nonnegativeinteger read-only
The index of the device that is plugged into the UPS.
                                       addrOfDevice 1.3.6.1.4.1.2468.1.2.1.1.9.2.1.2 ipaddress read-only
The ip address of the device.
                                       nameOfDevice 1.3.6.1.4.1.2468.1.2.1.1.9.2.1.3 displaystring read-only
The name/description of the device plugged into the UPS.
                                       timeOfConnection 1.3.6.1.4.1.2468.1.2.1.1.9.2.1.4 displaystring read-only
The device registered to USHA
                                       timeOfConnectionTime 1.3.6.1.4.1.2468.1.2.1.1.9.2.1.5 displaystring read-only
The device registered time to USHA.
                                       timeOfConnectionTimeout 1.3.6.1.4.1.2468.1.2.1.1.9.2.1.6 integer read-only
The device timeout counter. Unit: 10 seconds
                           agentConfig 1.3.6.1.4.1.2468.1.2.1.1.10
                                 agentConfigIpaddress 1.3.6.1.4.1.2468.1.2.1.1.10.1 ipaddress read-write
The ip address that NMS can identify the managed device
                                 agentConfigGateway 1.3.6.1.4.1.2468.1.2.1.1.10.2 ipaddress read-write
The default gateway that allow device managed through routers
                                 agentConfigSubnetMask 1.3.6.1.4.1.2468.1.2.1.1.10.3 ipaddress read-write
Internet address subnet mask
                                 agentConfigDate 1.3.6.1.4.1.2468.1.2.1.1.10.4 displaystring read-write
The date in agent, format is (dd/mm/yyyy)
                                 agentConfigTime 1.3.6.1.4.1.2468.1.2.1.1.10.5 displaystring read-write
The time in agent, format is (hh:mm:ss)
                                 agentConfigPrimaryTimeServer 1.3.6.1.4.1.2468.1.2.1.1.10.6 ipaddress read-write
The primary time server is responsible for sending the correct time to the agent.
                                 agentConfigSecondaryTimeServer 1.3.6.1.4.1.2468.1.2.1.1.10.7 ipaddress read-write
The secondary time server is responsible for sending the correct time to the agent.
                                 agentConfigHistoryLogFrequency 1.3.6.1.4.1.2468.1.2.1.1.10.8 integer read-write
The frequency of the updation of the history log. The value is in seconds
                                 agentConfigExtHistoryLogFrequency 1.3.6.1.4.1.2468.1.2.1.1.10.9 integer read-write
The ups parameters are sampled at the rate governed by the mconfigHistroyLogFrequency. These sampled values are further conslidated over period of time which is determined by this object.
                                 agentConfigPollRate 1.3.6.1.4.1.2468.1.2.1.1.10.10 integer read-write
The frequency that proxy agent polls the connected UPS in JBUS protocol. (unit : second)
                                 agentConfigBaudRate 1.3.6.1.4.1.2468.1.2.1.1.10.11 integer read-only
The serial port communication speed. only 9600 allowed
                                 agentConfigDhcpStatue 1.3.6.1.4.1.2468.1.2.1.1.10.12 integer read-write
Enable or disable DHCP/BootP capability Enumeration: 'disabled': 2, 'enabled': 1.
                                 agentConfigTelnetStatue 1.3.6.1.4.1.2468.1.2.1.1.10.13 integer read-write
Enable or disable telnet access Enumeration: 'disabled': 2, 'enabled': 1.
                                 agentConfigTftpStatue 1.3.6.1.4.1.2468.1.2.1.1.10.14 integer read-write
Enable or disable network upgrade capability Enumeration: 'disabled': 2, 'enabled': 1.
                                 agentConfigResetToDefault 1.3.6.1.4.1.2468.1.2.1.1.10.15 integer read-write
Reset all parameters of USHA to default value Enumeration: 'reset': 1, 'nothing': 2.
                                 agentConfigRestart 1.3.6.1.4.1.2468.1.2.1.1.10.16 integer read-write
Restart USHA Enumeration: 'nothing': 2, 'restart': 1.
                                 agentConfigClearAgentLog 1.3.6.1.4.1.2468.1.2.1.1.10.17 integer read-write
Clear agent log data Enumeration: 'nothing': 2, 'clear': 1.
                                 agentConfigClearEventLog 1.3.6.1.4.1.2468.1.2.1.1.10.18 integer read-write
Clear event log data Enumeration: 'nothing': 2, 'clear': 1.
                                 agentConfigClearExtHistoryLog 1.3.6.1.4.1.2468.1.2.1.1.10.19 integer read-write
Clear extented history log data Enumeration: 'nothing': 2, 'clear': 1.
                                 agentConfigClearHistoryLog 1.3.6.1.4.1.2468.1.2.1.1.10.20 integer read-write
Clear history log data Enumeration: 'nothing': 2, 'clear': 1.
                                 agentConfigTrapRetryCount 1.3.6.1.4.1.2468.1.2.1.1.10.21 integer read-write
The count of repeat traps to send to NMS before trap acknowledge received.
                                 agentConfigTrapRetryTime 1.3.6.1.4.1.2468.1.2.1.1.10.22 integer read-write
The time between retry traps sned to NMS.
                                 agentConfigTrapAckSignature 1.3.6.1.4.1.2468.1.2.1.1.10.23 integer read-write
The signature of trap acknowledge.
                                 agentConfigMibVersion 1.3.6.1.4.1.2468.1.2.1.1.10.24 integer read-only
The version of MIB spec.
                                 agentConfigTrapsReceiversTable 1.3.6.1.4.1.2468.1.2.1.1.10.25 no-access
A list of managers to send traps to. The number of entries is given by the value of agentConfigNumTrapReceivers
                                       agentConfigTrapsReceiversEntry 1.3.6.1.4.1.2468.1.2.1.1.10.25.1 no-access
The managers to send traps to.
                                           trapsIndex 1.3.6.1.4.1.2468.1.2.1.1.10.25.1.1 integer read-only
The index to a trap receiver entry.
                                           trapsReceiverAddr 1.3.6.1.4.1.2468.1.2.1.1.10.25.1.2 ipaddress read-write
The IP address of the manager to send a trap to.
                                           receiverCommunityString 1.3.6.1.4.1.2468.1.2.1.1.10.25.1.3 displaystring read-write
The community name to use in the trap when sent to the manager.
                                           receiverNmsType 1.3.6.1.4.1.2468.1.2.1.1.10.25.1.4 integer read-write
The trap group that NMS desired. Enumeration: 'none': 1, 'rfc1628-trap': 2, 'usha-trap': 3.
                                           receiverSeverityLevel 1.3.6.1.4.1.2468.1.2.1.1.10.25.1.5 integer read-write
The severity level of traps to be received by this manager. Enumeration: 'severe': 3, 'warning': 2, 'informational': 1.
                                           receiverDescription 1.3.6.1.4.1.2468.1.2.1.1.10.25.1.6 displaystring read-write
Description of trap receivers
                                 agentConfigAccessControlTable 1.3.6.1.4.1.2468.1.2.1.1.10.26 no-access
A list of managers which can access USHA with private community string.
                                       agentConfigAccessControlEntry 1.3.6.1.4.1.2468.1.2.1.1.10.26.1 no-access
The managers.
                                           accessIndex 1.3.6.1.4.1.2468.1.2.1.1.10.26.1.1 integer read-only
The index to a access control entry.
                                           accessControlAddr 1.3.6.1.4.1.2468.1.2.1.1.10.26.1.2 ipaddress read-write
The IP address of the manager to access USHA
                                           accessCommunityString 1.3.6.1.4.1.2468.1.2.1.1.10.26.1.3 displaystring read-write
The community name to use in the manager when access USHA
                                           accessControlMode 1.3.6.1.4.1.2468.1.2.1.1.10.26.1.4 integer read-write
Access type, only read/Write access type can change parameter of USHA Enumeration: 'readWrite': 2, 'readOnly': 1, 'notAccess': 3.
                                 agentConfigDefaultLanguage 1.3.6.1.4.1.2468.1.2.1.1.10.27 integer read-write
The default languauge for browser, when set to auto(1) USHA will send page in the language depends on the request language of browser. Enumeration: 'auto': 1, 'simplifiedChinese': 4, 'traditionalChinese': 3, 'english': 2.
                           emdStatus 1.3.6.1.4.1.2468.1.2.1.1.11
                                 emdSatatusEmdType 1.3.6.1.4.1.2468.1.2.1.1.11.1 integer read-only
The type of EMD plugged into the port. Enumeration: 'disabled': 2, 'unknown': 1, 'emdHT': 3, 'emdT': 4.
                                 emdSatatusTemperature 1.3.6.1.4.1.2468.1.2.1.1.11.2 integer read-only
The measurement of EMD temperature, in 0.1 degree
                                 emdSatatusHumidity 1.3.6.1.4.1.2468.1.2.1.1.11.3 integer read-only
The measurement of EMD humidity, in 0.1 degree
                                 emdSatatusAlarm1 1.3.6.1.4.1.2468.1.2.1.1.11.4 integer read-only
The EMD alarm-1 status Enumeration: 'disabled': 2, 'active': 3, 'inactive': 4, 'unknow': 1.
                                 emdSatatusAlarm2 1.3.6.1.4.1.2468.1.2.1.1.11.5 integer read-only
The EMD alarm-2 status Enumeration: 'disabled': 2, 'active': 3, 'inactive': 4, 'unknow': 1.
                           emdConfig 1.3.6.1.4.1.2468.1.2.1.1.12
                                 usahEmdConfigEmdConfig 1.3.6.1.4.1.2468.1.2.1.1.12.1 integer read-write
Enable or disable to detect presence of EMD Enumeration: 'disabled': 1, 'auto': 2.
                                 emdConfigEmdName 1.3.6.1.4.1.2468.1.2.1.1.12.2 displaystring read-write
Description of EMD
                                 emdConfigTemperature 1.3.6.1.4.1.2468.1.2.1.1.12.3
                                     emdConfigTempName 1.3.6.1.4.1.2468.1.2.1.1.12.3.1 displaystring read-write
Description of EMD temperature sensor
                                     emdConfigTempHighSetPoint 1.3.6.1.4.1.2468.1.2.1.1.12.3.2 integer read-write
The set point for high temperature warning, in degrees
                                     emdConfigTempHighStatus 1.3.6.1.4.1.2468.1.2.1.1.12.3.3 integer read-write
To enable/disable high set point check with emd temperature. Enumeration: 'disabled': 2, 'enabled': 1.
                                     emdConfigTempLowSetPoint 1.3.6.1.4.1.2468.1.2.1.1.12.3.4 integer read-write
The set point for low temperature warning, in degrees
                                     emdConfigTempLowStatus 1.3.6.1.4.1.2468.1.2.1.1.12.3.5 integer read-write
To enable/disable low set point check with emd temperature. Enumeration: 'disabled': 2, 'enabled': 1.
                                     emdConfigTempOffset 1.3.6.1.4.1.2468.1.2.1.1.12.3.6 integer read-write
The offset to calibrate temperature of EMD, in degrees
                                 emdConfigHumidity 1.3.6.1.4.1.2468.1.2.1.1.12.4
                                     emdConfigHumidityName 1.3.6.1.4.1.2468.1.2.1.1.12.4.1 displaystring read-write
Description of EMD humidity sensor
                                     emdConfigHumidityHighSetPoint 1.3.6.1.4.1.2468.1.2.1.1.12.4.2 integer read-write
The set point for high humidity warning, in %
                                     emdConfigHumidityLowStatus 1.3.6.1.4.1.2468.1.2.1.1.12.4.3 integer read-write
To enable/disable high set point check with emd humidity. Enumeration: 'disabled': 2, 'enabled': 1.
                                     emdConfigHumidityLowSetPoint 1.3.6.1.4.1.2468.1.2.1.1.12.4.4 integer read-write
The set point for low humidity warning, in %
                                     emdConfigHumidityHighStatus 1.3.6.1.4.1.2468.1.2.1.1.12.4.5 integer read-write
To enable/disable low set point check with emd humidity. Enumeration: 'disabled': 2, 'enabled': 1.
                                     emdConfigHumidityOffset 1.3.6.1.4.1.2468.1.2.1.1.12.4.6 integer read-write
The offset to calibrate humidity of EMD, in %
                                 emdConfigAlarm1 1.3.6.1.4.1.2468.1.2.1.1.12.5
                                     emdConfigAlarm1Name 1.3.6.1.4.1.2468.1.2.1.1.12.5.1 displaystring read-write
Description of EMD alarm-1
                                     emdConfigAlarm1Type 1.3.6.1.4.1.2468.1.2.1.1.12.5.2 integer read-write
The alarm-1 operation type Enumeration: 'disabled': 1, 'normalClose': 3, 'nomralOpen': 2.
                                 emdConfigAlarm2 1.3.6.1.4.1.2468.1.2.1.1.12.6
                                     emdConfigAlarm2Name 1.3.6.1.4.1.2468.1.2.1.1.12.6.1 displaystring read-write
Description of EMD alarm-2
                                     emdConfigAlarm2Type 1.3.6.1.4.1.2468.1.2.1.1.12.6.2 integer read-write
The alarm-1 operation type Enumeration: 'disabled': 1, 'normalClose': 3, 'nomralOpen': 2.
                       upsTrapGroup 1.3.6.1.4.1.2468.1.2.1.2
                             ushaPowerRestored 1.3.6.1.4.1.2468.1.2.1.20.1
INFORMATION: Utility power has been restore.
                             ushaPowerFail 1.3.6.1.4.1.2468.1.2.1.20.2
WARNING: Utility power not available.
                             ushaReturnFromLowBattery 1.3.6.1.4.1.2468.1.2.1.20.3
INFORMATION: The UPS has return from a low battery condition.
                             ushaLowBattery 1.3.6.1.4.1.2468.1.2.1.20.4
SEVERE: The UPS batteries are low and will soon be exhausted.
                             ushaUpsOk 1.3.6.1.4.1.2468.1.2.1.20.5
INFORMATION: The ups is working fine.
                             ushaUpsFailed 1.3.6.1.4.1.2468.1.2.1.20.6
SEVERE: The ups is not working fine.
                             ushaUpsNotOnBattery 1.3.6.1.4.1.2468.1.2.1.20.7
INFORMATION: The UPS is not on battery power.
                             ushaUpsOnBattery 1.3.6.1.4.1.2468.1.2.1.20.8
WARNING: The UPS has switched to battery backup power.
                             ushaTestOver 1.3.6.1.4.1.2468.1.2.1.20.9
INFORMATION: The testing of UPS is completed.
                             ushaTestInProgress 1.3.6.1.4.1.2468.1.2.1.20.10
INFORMATION: The testing is going on ups.
                             ushaBypassOn 1.3.6.1.4.1.2468.1.2.1.20.11
INFORMATION: The UPS has enabled bypass.
                             ushaUpsOnline 1.3.6.1.4.1.2468.1.2.1.20.12
INFORMATION: The UPS is not on Bypass and return to normal status.
                             ushaCommunicationLost 1.3.6.1.4.1.2468.1.2.1.20.13
SEVERE: Communication to the UPS has been lost.
                             ushaCommunicationEstablished 1.3.6.1.4.1.2468.1.2.1.20.14
INFORMATION: Communication with the UPS has been established.
                             ushaUpsGoingDown 1.3.6.1.4.1.2468.1.2.1.20.15
WARNING: The ups has been given shutdown command.
                             ushaUpsTurnedOff 1.3.6.1.4.1.2468.1.2.1.20.16
INFORMATION: UPS turn off.
                             ushaUpsSleeping 1.3.6.1.4.1.2468.1.2.1.20.17
INFORMATION: UPS has entered sleep mode.
                             ushaUpsWokeUp 1.3.6.1.4.1.2468.1.2.1.20.18
INFORMATION: The UPS woke up from sleep mode.
                             ushaUpsRebooted 1.3.6.1.4.1.2468.1.2.1.20.19
INFORMATION: The UPS is reboot.
                             ushaUpsShutdownCancelled 1.3.6.1.4.1.2468.1.2.1.20.20
INFORMATION: The UPS shutdown process had been cancelled.
                             ushaUpsNotOverTemperature 1.3.6.1.4.1.2468.1.2.1.20.21
INFORMATION: The UPS internal temperature return to normal.
                             ushaUpsOverTemperature 1.3.6.1.4.1.2468.1.2.1.20.22
SEVERE: The UPS temperature is too high.
                             ushaUpsNotOverLoad 1.3.6.1.4.1.2468.1.2.1.20.23
INFORMATION: The UPS load return from overload.
                             ushaUpsOverLoad 1.3.6.1.4.1.2468.1.2.1.20.24
SEVERE: The UPS is overload.
                             ushaUpsModuleInserted 1.3.6.1.4.1.2468.1.2.1.20.25
WARNING: UPS Battery Module plug-in.
                             ushaUpsModuleRemoved 1.3.6.1.4.1.2468.1.2.1.20.26
WARNING: UPS Battery Module unplug.
                             emdTemperatureNotHigh 1.3.6.1.4.1.2468.1.2.1.20.27
INFORMATION: EMD Temperature not over high Set point.
                             emdTemperatureTooHigh 1.3.6.1.4.1.2468.1.2.1.20.28
WARNING: EMD Temperature over high Set point.
                             emdTemperatureNotLow 1.3.6.1.4.1.2468.1.2.1.20.29
INFORMATION: EMD Temperature not under low Set point.
                             emdTemperatureTooLow 1.3.6.1.4.1.2468.1.2.1.20.30
WARNING: EMD Temperature under low Set point.
                             emdHumidityNotHigh 1.3.6.1.4.1.2468.1.2.1.20.31
INFORMATION: EMD Humidity not over high Set point.
                             emdHumidityTooHigh 1.3.6.1.4.1.2468.1.2.1.20.32
WARNING: EMD Humidity over high Set point.
                             emdHumidityNotLow 1.3.6.1.4.1.2468.1.2.1.20.33
INFORMATION: EMD Humidity not under low Set point.
                             emdHumidityTooLow 1.3.6.1.4.1.2468.1.2.1.20.34
WARNING: EMD Humidity under low Set point.
                             emdAlarm1Normal 1.3.6.1.4.1.2468.1.2.1.20.35
INFORMATION: EMD Alarm-1 not active.
                             emdAlarm1Active 1.3.6.1.4.1.2468.1.2.1.20.36
WARNING: EMD Alarm-1 activated.
                             emdAlarm2Normal 1.3.6.1.4.1.2468.1.2.1.20.37
INFORMATION: EMD Alarm-2 not active.
                             emdAlarm2Active 1.3.6.1.4.1.2468.1.2.1.20.38
WARNING: EMD Alarm-2 activated.
                             ushaUpsInternalwarning 1.3.6.1.4.1.2468.1.2.1.20.39
WARNING: Internal warning.
                             ushaUpsReturnFromInternalwarning 1.3.6.1.4.1.2468.1.2.1.20.40
INFORMATION: Return from Internal warning.
                             ushaUpsEPOActive 1.3.6.1.4.1.2468.1.2.1.20.41
WARNING: EPO Active.
                             ushaUpsReturnFromEPOActive 1.3.6.1.4.1.2468.1.2.1.20.42
INFORMATION: Return from EPO Active.
                             ushaUpsModuleUnlock 1.3.6.1.4.1.2468.1.2.1.20.43
WARNING: Module Unlock.
                             ushaUpsReturnFromModuleUnlock 1.3.6.1.4.1.2468.1.2.1.20.44
INFORMATION: Return from Module Unlock.
                             ushaUpsMain1Neutralloss 1.3.6.1.4.1.2468.1.2.1.20.45
WARNING: Main 1 Neutral loss.
                             ushaUpsReturnFromMain1Neutralloss 1.3.6.1.4.1.2468.1.2.1.20.46
INFORMATION: Return from Main 1 Neutral loss.
                             ushaUpsMain1phaseerror 1.3.6.1.4.1.2468.1.2.1.20.47
WARNING: Main 1 phase error.
                             ushaUpsReturnFromMain1phaseerror 1.3.6.1.4.1.2468.1.2.1.20.48
INFORMATION: Return from Main 1 phase error.
                             ushaUpsSitefault 1.3.6.1.4.1.2468.1.2.1.20.49
WARNING: Site fault.
                             ushaUpsReturnFromSitefault 1.3.6.1.4.1.2468.1.2.1.20.50
INFORMATION: Return from Site fault.
                             ushaUpsBypassAbnormal 1.3.6.1.4.1.2468.1.2.1.20.51
WARNING: Bypass Abnormal.
                             ushaUpsReturnFromBypassAbnormal 1.3.6.1.4.1.2468.1.2.1.20.52
INFORMATION: Return from Bypass Abnormal.
                             ushaUpsBypassPhaseError 1.3.6.1.4.1.2468.1.2.1.20.53
WARNING: Bypass Phase Error.
                             ushaUpsReturnFromBypassPhaseError 1.3.6.1.4.1.2468.1.2.1.20.54
INFORMATION: Return from Bypass Phase Error.
                             ushaUpsBatteryOpen 1.3.6.1.4.1.2468.1.2.1.20.55
WARNING: Battery Open.
                             ushaUpsReturnFromBatteryOpen 1.3.6.1.4.1.2468.1.2.1.20.56
INFORMATION: Return from Battery Open.
                             ushaUpsBatteryOverCharge 1.3.6.1.4.1.2468.1.2.1.20.57
WARNING: Battery Over Charge.
                             ushaUpsReturnFromBatteryOverCharge 1.3.6.1.4.1.2468.1.2.1.20.58
INFORMATION: Return from Battery Over Charge.
                             ushaUpsBatteryReverse 1.3.6.1.4.1.2468.1.2.1.20.59
WARNING: Battery Reverse.
                             ushaUpsReturnFromBatteryReverse 1.3.6.1.4.1.2468.1.2.1.20.60
INFORMATION: Return from Battery Reverse.
                             ushaUpsOverloadforewarning 1.3.6.1.4.1.2468.1.2.1.20.61
WARNING: Overload forewarning.
                             ushaUpsReturnFromOverloadforewarning 1.3.6.1.4.1.2468.1.2.1.20.62
INFORMATION: Return from Overload forewarning.
                             ushaUpsOverloadWarning 1.3.6.1.4.1.2468.1.2.1.20.63
WARNING: Overload Warning.
                             ushaUpsReturnFromOverloadWarning 1.3.6.1.4.1.2468.1.2.1.20.64
INFORMATION: Return from Overload Warning.
                             ushaUpsFanLock 1.3.6.1.4.1.2468.1.2.1.20.65
WARNING: Fan Lock.
                             ushaUpsReturnFromFanLock 1.3.6.1.4.1.2468.1.2.1.20.66
INFORMATION: Return from Fan Lock.
                             ushaUpsMaintaincoverisopen 1.3.6.1.4.1.2468.1.2.1.20.67
WARNING: Maintain cover is open.
                             ushaUpsReturnFromMaintaincoverisopen 1.3.6.1.4.1.2468.1.2.1.20.68
INFORMATION: Return from Maintain cover is open.
                             ushaUpsChargerfault 1.3.6.1.4.1.2468.1.2.1.20.69
WARNING: Charger fault.
                             ushaUpsReturnFromChargerfault 1.3.6.1.4.1.2468.1.2.1.20.70
INFORMATION: Return from Charger fault.
                             ushaUpsModulelocationerror 1.3.6.1.4.1.2468.1.2.1.20.71
WARNING: Module location error.
                             ushaUpsReturnFromModulelocationerror 1.3.6.1.4.1.2468.1.2.1.20.72
INFORMATION: Return from Module location error.
                             ushaUpsTurnonabnormal 1.3.6.1.4.1.2468.1.2.1.20.73
WARNING: Turn on abnormal.
                             ushaUpsReturnFromTurnonabnormal 1.3.6.1.4.1.2468.1.2.1.20.74
INFORMATION: Return from Turn on abnormal.
                             ushaUpsRedundancyloss 1.3.6.1.4.1.2468.1.2.1.20.75
WARNING: Redundancy loss.
                             ushaUpsReturnFromRedundancyloss 1.3.6.1.4.1.2468.1.2.1.20.76
INFORMATION: Return from Redundancy loss.
                             ushaUpsHotSwapActived 1.3.6.1.4.1.2468.1.2.1.20.77
WARNING: Hot Swap Actived.
                             ushaUpsReturnFromHotSwapActived 1.3.6.1.4.1.2468.1.2.1.20.78
INFORMATION: Return from Hot Swap Actived.
                             ushaUpsBatteryInform 1.3.6.1.4.1.2468.1.2.1.20.79
WARNING: Battery Inform.
                             ushaUpsReturnFromBatteryInform 1.3.6.1.4.1.2468.1.2.1.20.80
INFORMATION: Return from Battery Inform.
                             ushaUpsInspectionInform 1.3.6.1.4.1.2468.1.2.1.20.81
WARNING: Inspection Inform.
                             ushaUpsReturnFromInspectionInform 1.3.6.1.4.1.2468.1.2.1.20.82
INFORMATION: Return from Inspection Inform.
                             ushaUpsGuaranteeInform 1.3.6.1.4.1.2468.1.2.1.20.83
WARNING: Guarantee Inform.
                             ushaUpsReturnFromGuaranteeInform 1.3.6.1.4.1.2468.1.2.1.20.84
INFORMATION: Return from Guarantee Inform.
                             ushaUpsTemperatureLow 1.3.6.1.4.1.2468.1.2.1.20.85
WARNING: Temperature Low.
                             ushaUpsReturnFromTemperatureLow 1.3.6.1.4.1.2468.1.2.1.20.86
INFORMATION: Return from Temperature Low.
                             ushaUpsTemperatureHigh 1.3.6.1.4.1.2468.1.2.1.20.87
WARNING: Temperature High.
                             ushaUpsReturnFromTemperatureHigh 1.3.6.1.4.1.2468.1.2.1.20.88
INFORMATION: Return from Temperature High.
                             ushaUpsBatteryOverTemperature 1.3.6.1.4.1.2468.1.2.1.20.89
WARNING: Battery Over Temperature.
                             ushaUpsReturnFromBatteryOverTemperature 1.3.6.1.4.1.2468.1.2.1.20.90
INFORMATION: Return from Battery Over Temperature.
                             ushaUpsFanMaintainInform 1.3.6.1.4.1.2468.1.2.1.20.91
WARNING: Fan Maintain Inform.
                             ushaUpsReturnFromFanMaintainInform 1.3.6.1.4.1.2468.1.2.1.20.92
INFORMATION: Return from Fan Maintain Inform.
                             ushaUpsBusCapacitanceMaintainInform 1.3.6.1.4.1.2468.1.2.1.20.93
WARNING: Bus Capacitance Maintain Inform.
                             ushaUpsReturnFromBusCapacitanceMaintainInform 1.3.6.1.4.1.2468.1.2.1.20.94
INFORMATION: Return from Bus Capacitance Maintain Inform.
                             ushaUpsSystemOverCapacity 1.3.6.1.4.1.2468.1.2.1.20.95
WARNING: System Over Capacity.
                             ushaUpsReturnFromSystemOverCapacity 1.3.6.1.4.1.2468.1.2.1.20.96
INFORMATION: Return from System Over Capacity.