UPSMAN: View SNMP OID List / Download MIB
VENDOR: GENEREX SYSTEMS GMBH
Home | MIB: UPSMAN | |||
---|---|---|---|---|
Download as: |
Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
|
|||
Object Name | OID | Type | Access | Info |
upsman | 1.3.6.1.4.1.1356 | |||
ups | 1.3.6.1.4.1.1356.1 | |||
upsIdent | 1.3.6.1.4.1.1356.1.1 | |||
upsIdentModelName | 1.3.6.1.4.1.1356.1.1.1 | displaystring | read-only |
The UPS model name (e.g. 'O1000S'). |
upsIdentUpsIDName | 1.3.6.1.4.1.1356.1.1.2 | displaystring | read-write |
An ID string identifying the UPS. This object can be set by the administrator. |
upsBattery | 1.3.6.1.4.1.1356.1.2 | |||
upsBatteryStatus | 1.3.6.1.4.1.1356.1.2.1 | integer | read-only |
The status of the UPS batteries. A batteryLow(3) value indicates the UPS will be unable to sustain the current load, and its services will be lost if power is not restored. Enumeration: 'unknown': 1, 'batteryNormal': 2, 'batteryLow': 3. |
upsBatteryCapacity | 1.3.6.1.4.1.1356.1.2.2 | integer | read-only |
The remaining battery capacity expressed in percent of full capacity. |
upsBatteryVoltage | 1.3.6.1.4.1.1356.1.2.3 | integer | read-only |
The current battery voltage expressed in VDC. |
upsBatteryTemperature | 1.3.6.1.4.1.1356.1.2.4 | integer | read-only |
The current internal UPS temperature expressed in Celsius. |
upsBatteryRunTimeRemaining | 1.3.6.1.4.1.1356.1.2.5 | integer | read-only |
The UPS battery run time remaining before battery exhaustion, in seconds. |
upsBatteryLifeTimeRemaining | 1.3.6.1.4.1.1356.1.2.6 | integer | read-only |
Forecast of the battery lifetime, replacement recommended in x month. Format: month |
upsInput | 1.3.6.1.4.1.1356.1.3 | |||
upsInputLineVoltage | 1.3.6.1.4.1.1356.1.3.1 | integer | read-only |
The current utility line voltage in VAC. |
upsInputLineFrequence | 1.3.6.1.4.1.1356.1.3.2 | integer | read-only |
The current utility line frequence in Hz. |
upsOutput | 1.3.6.1.4.1.1356.1.4 | |||
upsOutputStatus | 1.3.6.1.4.1.1356.1.4.1 | integer | read-only |
The current state of the UPS. If the UPS is unable to determine the state of the UPS this variable is set to unknown(1). Enumeration: 'onBypass': 4, 'unknown': 1, 'onBattery': 3, 'shutdown': 5, 'onLine': 2. |
upsOutputLoad | 1.3.6.1.4.1.1356.1.4.2 | integer | read-only |
The current UPS load expressed in percent of rated capacity. |
upsOutputFrequency | 1.3.6.1.4.1.1356.1.4.3 | integer | read-only |
The present output frequency, format: 0.1 Hertz. |
upsOutputVoltage | 1.3.6.1.4.1.1356.1.4.4 | integer | read-only |
The present output voltage, format: RMS Volts. |
upsTest | 1.3.6.1.4.1.1356.1.5 | |||
upsRunTest | 1.3.6.1.4.1.1356.1.5.1 | integer | read-write |
Set this value to run a test. If this this variable is set to NoTest(0) no test will be initiated. Enumeration: 'batteryCustomTest': 2, 'batteryTest': 1, 'selfTest': 4, 'batteryFullTest': 3, 'noTest': 0. |
upsLastTestPerformed | 1.3.6.1.4.1.1356.1.5.2 | integer | read-only |
This value shows which last test was performed. If this value is set to noTest(0) no test has been run since startup. Enumeration: 'batteryCustomTest': 2, 'batteryTest': 1, 'selfTest': 4, 'batteryFullTest': 3, 'noTest': 0. |
upsLastTestResult | 1.3.6.1.4.1.1356.1.5.3 | integer | read-only |
The current UPS Test Result. If this value is undefined(0) no test has been run since startup. Enumeration: 'failed': 2, 'notSupported': 3, 'undefined': 0, 'success': 1. |
upsLastTestedBackupTime | 1.3.6.1.4.1.1356.1.5.4 | integer | read-only |
This value shows the last tested backup time in minutes. To acquire a new value perform one of battery test's. |
upsControl | 1.3.6.1.4.1.1356.1.6 | |||
upsRunShutdownRestore | 1.3.6.1.4.1.1356.1.6.1 | integer | read-write |
Set this value to run a shutdown procedure. If this this variable is set to (0) nothing happens. Enumeration: 'restore': 2, 'undefined': 0, 'shutdown': 1, 'shutdownRestore': 3. |
upsShutdownSecs | 1.3.6.1.4.1.1356.1.6.2 | integer | read-write |
This value indicates the time in seconds after which a ups shutdown will be performed. If this value is (0) shutdown executes immediately. |
upsRestoreSecs | 1.3.6.1.4.1.1356.1.6.3 | integer | read-write |
This value indicates the time in seconds after which a ups restore will be performed. If this value is (0) restore executes immediately. |
upsAlarms | 1.3.6.1.4.1.1356.1.7 | |||
upsAlarmFatalFaultStatus | 1.3.6.1.4.1.1356.1.7.1 | integer | read-only |
CRITICAL ALARM : A fatal fault in the UPS has been detected. Detailed information by referring to UpsAlarmFatalFaultDetail Possible causes: Fatal Fault none (-1), Abnormal output (1), main circuit failure (2), fuse blown (3), fan fault (4), abnormal control (5), abnormal battery (6), others (7). Enumeration: 'mainCircuitFailure': 2, 'ohterFatalFaults': 7, 'abnormalControl': 5, 'fatalFaultNone': -1, 'abnormalBattery': 6, 'abnormalOutput': 1, 'fuseBlown': 3, 'fanFault': 4. |
upsAlarmWarningStatus | 1.3.6.1.4.1.1356.1.7.2 | integer | read-only |
WARNING : The UPS has detect a minor fault, warning level. Detailed information by referring to UpsAlarmWarningDetail. Enumeration: 'none': -1, 'occurred': 1. |
upsAlarmInputBadStatus | 1.3.6.1.4.1.1356.1.7.3 | integer | read-only |
An abnormal condition of the input in the UPS has been detected. Detailed information by referring to UpsAlarmInputBadDetail. Enumeration: 'none': -1, 'occurred': 1. |
upsAlarmOutputOverloadStatus | 1.3.6.1.4.1.1356.1.7.4 | integer | read-only |
An abnormal output overload in the UPS has been detected. Enumeration: 'none': -1, 'occurred': 1. |
upsAlarmBatteryBadStatus | 1.3.6.1.4.1.1356.1.7.5 | integer | read-only |
An abnormal condition of the battery in the UPS has been detected. Detailed information by referring to UpsAlarmBatteryBadDetail. Enumeration: 'none': -1, 'occurred': 1. |
upsAlarmTempBadStatus | 1.3.6.1.4.1.1356.1.7.6 | integer | read-only |
An abnormal condition of the temperature in the UPS has been detected. Detailed information by referring to UpsAlarmTempBadDetail. Enumeration: 'none': -1, 'occurred': 1. |
mgmt | 1.3.6.1.4.1.1356.2 | |||
communicationLost | 1.3.6.1.4.1.13560.1 |
SEVERE: Communication to the UPS has been lost. Check cable or network connections, steps to reestablish communication are in progress. |
||
upsOverload | 1.3.6.1.4.1.13560.2 |
SEVERE: The UPS has sensed a load greater than 100 percent of its rated capcity. |
||
upsTurnedOff | 1.3.6.1.4.1.13560.3 |
WARNING: The UPS has been turned 'off' by the management station. |
||
communicationEstablished | 1.3.6.1.4.1.13560.4 |
INFORMATION: Communication with the UPS has been established. |
||
powerRestored | 1.3.6.1.4.1.13560.5 |
INFORMATION: Utility power has been restored. |
||
upsOnBattery | 1.3.6.1.4.1.13560.6 |
WARNING: The UPS has switched to battery backup power. |
||
testStarted | 1.3.6.1.4.1.13560.7 |
INFORMATION: A UPS test was started. |
||
testCompleted | 1.3.6.1.4.1.13560.8 |
INFORMATION: A UPS test is completed. Now a test result should be available in upsTest.lastTestResult. |
||
upsBatteryLow | 1.3.6.1.4.1.13560.9 |
WARNING: Battery Low. |
||
upsShutdownImminent | 1.3.6.1.4.1.13560.10 |
INFORMATION: Server Shutdown imminent. |
||
upsmanStarted | 1.3.6.1.4.1.13560.11 |
INFORMATION: The UpsMan service has been started. |
||
upsmanTrapInputBad | 1.3.6.1.4.1.13560.12 |
An abnormal condition of input UPS has been detected. |
||
upsmanTrapOutputOverloadRemoved | 1.3.6.1.4.1.13560.13 |
The UPS has returned from an overload situation to normal operation. |
||
upsmanTrapBatteryBad | 1.3.6.1.4.1.13560.14 |
An abnormal condition of the UPS batteries has been detected. |
||
upsmanTrapTempBad | 1.3.6.1.4.1.13560.15 |
An abnormal UPS temperature has been detected. |
||
upsmanTrapTempBadRemoved | 1.3.6.1.4.1.13560.16 |
The abnormal UPS temperature is back to normal level. |
||
upsmanTrapFatalFault | 1.3.6.1.4.1.13560.17 |
A fatal fault in the UPS has been detected. The UPS can not backup, contact your UPS service team. |