UBQS-ENVMON-MIB: View SNMP OID List / Download MIB

VENDOR: PREMIER NETWORK CO., LTD


 Home MIB: UBQS-ENVMON-MIB
Download as:   

Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 ubiEnvMonMIB 1.3.6.1.4.1.7800.100.2
The UBQS-ENVMON-MIB is used for getting the environment information of the system.
     ubiEnvMonObjects 1.3.6.1.4.1.7800.100.2.1
         ubiEnvMonTemperatureTable 1.3.6.1.4.1.7800.100.2.1.1 no-access
The table of ambient temperature status maintained by the environmental monitor.
             ubiEnvMonTemperatureEntry 1.3.6.1.4.1.7800.100.2.1.1.1 no-access
An entry in the ambient temperature status table, representing the status of the associated testpoint maintained by the environmental monitor.
                 ubiEnvMonTemperatureIndex 1.3.6.1.4.1.7800.100.2.1.1.1.1 integer32 no-access
Unique index for the testpoint being instrumented. This index is for SNMP purposes only, and has no intrinsic meaning.
                 ubiEnvMonTemperatureDescr 1.3.6.1.4.1.7800.100.2.1.1.1.2 displaystring read-only
Textual description of the testpoint being instrumented.
                 ubiEnvMonTemperatureValue 1.3.6.1.4.1.7800.100.2.1.1.1.3 gauge32 read-only
The current measurement of the testpoint being instrumented.
                 ubiEnvMonTemperatureHighThreshold 1.3.6.1.4.1.7800.100.2.1.1.1.4 integer32 read-write
A high threshold for the temperature. If a particular value isn't set, this object displays the default value.
                 ubiEnvMonTemperatureLowThreshold 1.3.6.1.4.1.7800.100.2.1.1.1.5 integer32 read-write
A low threshold for the temperature. If a particular value isn't set, this object displays the default value.
                 ubiEnvMonTemperatureState 1.3.6.1.4.1.7800.100.2.1.1.1.6 ubienvmonstate read-only
The current state of the testpoint being instrumented. Represents the temperature state of a device being monitored. Valid values are: normal(1): the environment is good, such as low temperature. warning(2): the environment is bad, such as temperature above normal operation range but not too high. critical(3): the environment is very bad, such as temperature much higher than normal operation limit. notPresent(5): the environmental monitor is not present, such as temperature sensors do not exist.
         ubiEnvMonFanTable 1.3.6.1.4.1.7800.100.2.1.2 no-access
The table of fan status maintained by the environmental monitor.
             ubiEnvMonFanEntry 1.3.6.1.4.1.7800.100.2.1.2.1 no-access
An entry in the fan status table, representing the status of the associated fan maintained by the environmental monitor.
                 ubiEnvMonFanIndex 1.3.6.1.4.1.7800.100.2.1.2.1.1 integer32 no-access
Unique index for the fan being instrumented. This index is for SNMP purposes only, and has no intrinsic meaning.
                 ubiEnvMonFanDescr 1.3.6.1.4.1.7800.100.2.1.2.1.2 displaystring read-only
Textual description of the fan being instrumented.
                 ubiEnvMonFanState 1.3.6.1.4.1.7800.100.2.1.2.1.3 ubienvmonstate read-only
The current state of the fan being instrumented. Represents the fan state of a device being monitored. Valid values are: normal(1): the environment is good, such as low temperature. notPresent(5): the environmental monitor is not present, such as temperature sensors do not exist. notFunctioning(6): the environmental monitor does not function properly.
         ubiEnvMonSupplyTable 1.3.6.1.4.1.7800.100.2.1.3 no-access
The table of power supply status maintained by the environmental monitor card.
             ubiEnvMonSupplyEntry 1.3.6.1.4.1.7800.100.2.1.3.1 no-access
An entry in the power supply status table, representing the status of the associated power supply maintained by the environmental monitor card.
                 ubiEnvMonSupplyIndex 1.3.6.1.4.1.7800.100.2.1.3.1.1 integer32 no-access
Unique index for the power supply being instrumented. This index is for SNMP purposes only, and has no intrinsic meaning.
                 ubiEnvMonSupplyDescr 1.3.6.1.4.1.7800.100.2.1.3.1.2 displaystring read-only
Textual description of the power supply being instrumented.
                 ubiEnvMonSupplyState 1.3.6.1.4.1.7800.100.2.1.3.1.3 ubienvmonstate read-only
The current state of the power supply being instrumented. Represents the power state of a device being monitored. Valid values are: normal(1): the environment is good, such as low temperature. notPresent(5): the environmental monitor is not present, such as temperature sensors do not exist. notFunctioning(6): the environmental monitor does not function properly.
                 ubiEnvMonSupplySource 1.3.6.1.4.1.7800.100.2.1.3.1.4 integer read-only
The power supply source. ac - AC power supply dc - DC power supply Enumeration: 'none': 0, 'ac': 1, 'dc': 2.
                 ubiEnvMonExternalAlarmAc 1.3.6.1.4.1.7800.100.2.1.3.1.5 integer read-only
The power supply convertor AC. nomal (1) fail (2) Enumeration: 'fail': 2, 'normal': 1.
                 ubiEnvMonExternalAlarmUnit 1.3.6.1.4.1.7800.100.2.1.3.1.6 integer read-only
The power supply convertor unit. nomal (1) fail (2) Enumeration: 'fail': 2, 'normal': 1.
         ubiEnvMonSupplyChannelTable 1.3.6.1.4.1.7800.100.2.1.4 no-access
The table represents the extension status for DC power supply.
             ubiEnvMonSupplyChannelEntry 1.3.6.1.4.1.7800.100.2.1.4.1 no-access
An entry in this table, representing the extended status of the associated DC power supply maintained by the environmental monitor card.
                 ubiEnvMonSupplyChannelType 1.3.6.1.4.1.7800.100.2.1.4.1.1 integer read-only
Unique index for the DC power supply channel. Enumeration: 'dc-48v-a': 1, 'dc-48v-b': 2.
                 ubiEnvMonSupplyChannelState 1.3.6.1.4.1.7800.100.2.1.4.1.2 ubienvmonstate read-only
The current state of the DC power supply channel being instrumented. Represents the power state of a device being monitored. Valid values are: normal(1): the environment is good, such as low temperature. notPresent(5): the environmental monitor is not present, such as temperature sensors do not exist. notFunctioning(6): the environmental monitor does not function properly.
     ubiEnvMonMIBNotificationEnables 1.3.6.1.4.1.7800.100.2.2
         ubiEnvMonEnableTempStatusChange 1.3.6.1.4.1.7800.100.2.2.1 truthvalue read-write
This variable indicates whether the system produces the ubiEnvMonTempStatusChangeNotif. A false value prevents temperature notifications from being sent by this entity.
         ubiEnvMonEnableFanStatusChange 1.3.6.1.4.1.7800.100.2.2.2 truthvalue read-write
This variable indicates whether the system produces the ubiEnvMonFanStatusChangeNotif. A false value prevents fan notifications from being sent by this entity.
         ubiEnvMonEnableSupplyStatusChange 1.3.6.1.4.1.7800.100.2.2.3 truthvalue read-write
This variable indicates whether the system produces the ubiEnvMonSuppStatusChangeNotif. A false value prevents redundant supply notifications from being generated by this system.
         ubiEnvMonEnableSupplyChannelStatusChange 1.3.6.1.4.1.7800.100.2.2.4 truthvalue read-write
This variable indicates whether the system produces the ubiEnvMonSuppExtStatusChangeNotif. A false value prevents redundant supply notifications from being generated by this system.
     ubiEnvMonMIBNotificationPrefix 1.3.6.1.4.1.7800.100.2.3
         ubiEnvMonMIBNotifications 1.3.6.1.4.1.7800.100.2.3.0
             ubiEnvMonTempStatusChange 1.3.6.1.4.1.7800.100.2.3.0.1
A ubiEnvMonTempStatusChangeNotif is sent if there is change in the state of a device being monitored by ubiEnvMonTemperatureState.
             ubiEnvMonFanStatusChange 1.3.6.1.4.1.7800.100.2.3.0.2
A ubiEnvMonFanStatusChangeNotif is sent if there is change in the state of a device being monitored by ubiEnvMonFanState.
             ubiEnvMonSupplyStatusChange 1.3.6.1.4.1.7800.100.2.3.0.3
A ubiEnvMonSupplyStatChangeNotif is sent if there is change in the state of a device being monitored by ubiEnvMonSupplyState.
             ubiEnvMonSupplyChannelStatusChange 1.3.6.1.4.1.7800.100.2.3.0.4
A ubiEnvMonSuppExtStatusChangeNotif is sent if there is change in the state of a device being monitored by ubiEnvMonSupplyExtChannelStatus.
     ubiEnvMonMIBConformance 1.3.6.1.4.1.7800.100.2.4
         ubiEnvMonMIBCompliances 1.3.6.1.4.1.7800.100.2.4.1
             ubiEnvMonMIBCompliance 1.3.6.1.4.1.7800.100.2.4.1.1
The compliance statement for entities which implement the Ubiquoss Environmental Monitor MIB.
         ubiEnvMonMIBGroups 1.3.6.1.4.1.7800.100.2.4.2
             ubiEnvMonMIBGroup 1.3.6.1.4.1.7800.100.2.4.2.1
A collection of objects providing environmental monitoring capability to a ubi chassis.
             ubiEnvMonMIBNotifGroup 1.3.6.1.4.1.7800.100.2.4.2.2
A notification group providing notification for environmental monitoring.