Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 tslMIB 1.3.6.1.4.1.6853
           alarm 1.3.6.1.4.1.6853.2
               alarmIdent 1.3.6.1.4.1.6853.2.1 displaystring read-only
Equipment alarms description and version
               alarmTable 1.3.6.1.4.1.6853.2.2 no-access
The table of alarm entries
                   alarmEntry 1.3.6.1.4.1.6853.2.2.1 no-access
An alarm entry in the table
                       alarmTableIndex 1.3.6.1.4.1.6853.2.2.1.1 integer read-only
The index into the table
                       alarmType 1.3.6.1.4.1.6853.2.2.1.2 integer read-only
Alarm type Enumeration: 'psuFail': 4, 'currentAlarm': 5, 'internal': 1, 'gpi': 2, 'outputFail': 3.
                       alarmIndex 1.3.6.1.4.1.6853.2.2.1.3 integer read-only
Alarm type number
                       alarmText 1.3.6.1.4.1.6853.2.2.1.4 displaystring read-write
Alarm description
                       alarmState 1.3.6.1.4.1.6853.2.2.1.5 integer read-only
Alarm state Enumeration: 'active': 2, 'inactive': 1.
                       alarmPolarity 1.3.6.1.4.1.6853.2.2.1.6 integer read-write
Alarm active polarity (notApplicable for non-gpi alarms) Enumeration: 'normallyOpen': 2, 'notApplicable': 1, 'normallyClosed': 3.
                       alarmData 1.3.6.1.4.1.6853.2.2.1.7 opaque read-only
Additional alarm data of variable length, according to alarm type.
               alarmTotal 1.3.6.1.4.1.6853.2.3 integer read-only
The total number of alarms in the table
               alarmLocation 1.3.6.1.4.1.6853.2.4 displaystring read-write
The physical location of the equipment generating the alarm
               alarmEqptTemp 1.3.6.1.4.1.6853.2.5 integer read-only
Equipment temperature (in degrees Centigrade)
               alarmEqptTempHi 1.3.6.1.4.1.6853.2.6 integer read-write
Equipment temperature alarm point (degrees Centigrade)
           mdu12 1.3.6.1.4.1.6853.3
               mdu12Ident 1.3.6.1.4.1.6853.3.1 displaystring read-only
Equipment description and version
               mduPowerOn 1.3.6.1.4.1.6853.3.2 integer read-write
MDU power-on output sequence Enumeration: 'simultaneous': 1, 'sequential': 2, 'delayed': 3.
               mduSeqDelay 1.3.6.1.4.1.6853.3.3 integer read-write
Sequential mode delay between outputs
               mduOutputTable 1.3.6.1.4.1.6853.3.4 no-access
Table of output controls
                   mduOutputEntry 1.3.6.1.4.1.6853.3.4.1 no-access
An entry in the output table
                       mduOutputIndex 1.3.6.1.4.1.6853.3.4.1.1 integer read-only
Output number
                       mduOutputState 1.3.6.1.4.1.6853.3.4.1.2 integer read-write
MDU Output status Enumeration: 'locked-Off': 3, 'on': 2, 'off': 1, 'locked-On': 4.
                       mduOutputDelay 1.3.6.1.4.1.6853.3.4.1.3 integer read-write
Output on delay from power on (Delay mode only)
                       mduOutputlowerCurrent 1.3.6.1.4.1.6853.3.4.1.4 integer read-write
Lower current limit for output
                       mduOutputupperCurrent 1.3.6.1.4.1.6853.3.4.1.5 integer read-write
Upper current limit for output
                       mduOutputCurrent 1.3.6.1.4.1.6853.3.4.1.6 integer read-only
Output current
                       mduOutputpowerFactor 1.3.6.1.4.1.6853.3.4.1.7 integer read-only
Output power factor
                       mduOutputVA 1.3.6.1.4.1.6853.3.4.1.8 integer read-only
Output apparent power
                       mduOutputWatts 1.3.6.1.4.1.6853.3.4.1.9 integer read-only
Output real power
                       mduOutputCal 1.3.6.1.4.1.6853.3.4.1.10 integer read-write
Output current measure calibration data
               mduPowerStatus 1.3.6.1.4.1.6853.3.5 integer read-only
Status of MDU power inlets Enumeration: 'allOk': 4, 'input1OK': 2, 'input2OK': 3, 'totalLoss': 1.
               mduVoltageCal 1.3.6.1.4.1.6853.3.6 integer read-write
Voltage measure calibration data
               mduVoltage 1.3.6.1.4.1.6853.3.7 integer read-only
Voltage measurement
               mduVoltageFloor 1.3.6.1.4.1.6853.3.8 integer read-write
Voltage lower limit
               mduVoltageLimit 1.3.6.1.4.1.6853.3.9 integer read-write
Voltage upper limit
               mduTotalCurrent 1.3.6.1.4.1.6853.3.10 integer read-write
Total current measurement
               mduCurrentLimit 1.3.6.1.4.1.6853.3.11 integer read-write
Current total limit
               mduAuxRly1 1.3.6.1.4.1.6853.3.12 integer read-write
Auxiliary Relay 1 state Enumeration: 'on': 2, 'off': 1.
               mduAuxRly2 1.3.6.1.4.1.6853.3.13 integer read-write
Auxiliary Relay 2 state Enumeration: 'on': 2, 'off': 1.
             alarmTrap 1.3.6.1.4.1.68530.4
An entry in the alarm table has changed state
             alarmEqptTempHiTrap 1.3.6.1.4.1.68530.5
The equipment temperature has exceeded the maximum allowed
             alarmEqptTempOkTrap 1.3.6.1.4.1.68530.6
The equipment temperature is now within limits
             mduPowerStatusTrap 1.3.6.1.4.1.68530.7
The power input to the MDU has changed state
             mduVoltageStatusTrap 1.3.6.1.4.1.68530.8
The voltage to the MDU has traversed a limit
             mduTotalCurrentStatusTrap 1.3.6.1.4.1.68530.9
The total current through the MDU has traversed a limit