TIC-RMTI4-G9000-G2020-MIB: View SNMP OID List / Download MIB

VENDOR: TOSHIBA


 Home MIB: TIC-RMTI4-G9000-G2020-MIB
Download as:   

Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 toshiba 1.3.6.1.4.1.186
         equ 1.3.6.1.4.1.186.1
             equUPS 1.3.6.1.4.1.186.1.19
                   ticUPS 1.3.6.1.4.1.186.1.19.2
                       rmti4 1.3.6.1.4.1.186.1.19.2.5
                           upsG9000_G2020 1.3.6.1.4.1.186.1.19.2.5.1
                               upsIdent 1.3.6.1.4.1.186.1.19.2.5.1.1
                                   upsIdentManufacturer 1.3.6.1.4.1.186.1.19.2.5.1.1.1 displaystring read-only
The name of the UPS manufacturer.
                                   upsIdentTypeform 1.3.6.1.4.1.186.1.19.2.5.1.1.2 displaystring read-only
The UPS Model designation.
                                   upsIdentUPSFirmwareVersion 1.3.6.1.4.1.186.1.19.2.5.1.1.3 displaystring read-only
The UPS firmware version.
                                   upsIdentSysName 1.3.6.1.4.1.186.1.19.2.5.1.1.4 displaystring read-write
A string identifying the UPS. This object is set by the administrator.
                                   upsIdentAttachedDevices 1.3.6.1.4.1.186.1.19.2.5.1.1.5 displaystring read-write
A string identifying the devices attached to the output(s) of the UPS. This object is set by the administrator.
                               upsInput 1.3.6.1.4.1.186.1.19.2.5.1.2
                                   upsInputNumOfPhases 1.3.6.1.4.1.186.1.19.2.5.1.2.1 nonnegativeinteger read-only
Number of input lines. This data is used by upsInputNumLines.
                                   upsInputLLVoltageAB 1.3.6.1.4.1.186.1.19.2.5.1.2.2 nonnegativeinteger read-only
The input line to line voltage for AB in RMS volts.
                                   upsInputLLVoltageBC 1.3.6.1.4.1.186.1.19.2.5.1.2.3 nonnegativeinteger read-only
The input line to line voltage for BC in RMS volts.
                                   upsInputLLVoltageCA 1.3.6.1.4.1.186.1.19.2.5.1.2.4 nonnegativeinteger read-only
The input line to line voltage for CA in RMS volts.
                                   upsInputLLVoltagePercentAB 1.3.6.1.4.1.186.1.19.2.5.1.2.5 nonnegativeinteger read-only
The input line to line voltage percent for AB.
                                   upsInputLLVoltagePercentBC 1.3.6.1.4.1.186.1.19.2.5.1.2.6 nonnegativeinteger read-only
The input line to line voltage percent for BC.
                                   upsInputLLVoltagePercentCA 1.3.6.1.4.1.186.1.19.2.5.1.2.7 nonnegativeinteger read-only
The input line to line voltage percent for CA.
                                   upsInputCurrentPhaseA 1.3.6.1.4.1.186.1.19.2.5.1.2.8 nonnegativeinteger read-only
The input phase current for Phase A.
                                   upsInputCurrentPhaseB 1.3.6.1.4.1.186.1.19.2.5.1.2.9 nonnegativeinteger read-only
The input phase current unit for Phase B.
                                   upsInputCurrentPhaseC 1.3.6.1.4.1.186.1.19.2.5.1.2.10 nonnegativeinteger read-only
The input phase current unit for Phase C.
                                   upsInputFrequency 1.3.6.1.4.1.186.1.19.2.5.1.2.11 nonnegativeinteger read-only
The input frequency unit 0.1 Hertz.
                                   upsInputActivePowerA 1.3.6.1.4.1.186.1.19.2.5.1.2.12 nonnegativeinteger read-only
The magnitude of the present input true power for phase A.
                                   upsInputActivePowerB 1.3.6.1.4.1.186.1.19.2.5.1.2.13 nonnegativeinteger read-only
The magnitude of the present input true power for phase B.
                                   upsInputActivePowerC 1.3.6.1.4.1.186.1.19.2.5.1.2.14 nonnegativeinteger read-only
The magnitude of the present input true power for phase C.
                                   upsInputTotalActivePower 1.3.6.1.4.1.186.1.19.2.5.1.2.15 nonnegativeinteger read-only
The magnitude of the total input true power.
                                   upsInputRatedLLVoltage 1.3.6.1.4.1.186.1.19.2.5.1.2.16 nonnegativeinteger read-only
The input line to line rated voltage in RMS volts.
                               upsOutput 1.3.6.1.4.1.186.1.19.2.5.1.3
                                   upsOutputSource 1.3.6.1.4.1.186.1.19.2.5.1.3.1 integer read-only
The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker. Enumeration: 'battery': 5, 'none': 2, 'other': 1, 'bypass': 4, 'normal': 3.
                                   upsOutputNumOfPhases 1.3.6.1.4.1.186.1.19.2.5.1.3.2 nonnegativeinteger read-only
The number of output lines utilized in this device.
                                   upsOutputLLVoltageAB 1.3.6.1.4.1.186.1.19.2.5.1.3.3 nonnegativeinteger read-only
The output line to line voltage for AB in RMS volts.
                                   upsOutputLLVoltageBC 1.3.6.1.4.1.186.1.19.2.5.1.3.4 nonnegativeinteger read-only
The output line to line voltage for BC in RMS volts.
                                   upsOutputLLVoltageCA 1.3.6.1.4.1.186.1.19.2.5.1.3.5 nonnegativeinteger read-only
The output line to line voltage for CA in RMS volts.
                                   upsOutputCurrentPhaseA 1.3.6.1.4.1.186.1.19.2.5.1.3.6 nonnegativeinteger read-only
The Output phase current for phase A in amps.
                                   upsOutputCurrentPhaseB 1.3.6.1.4.1.186.1.19.2.5.1.3.7 nonnegativeinteger read-only
The Output phase current for phase B in amps.
                                   upsOutputCurrentPhaseC 1.3.6.1.4.1.186.1.19.2.5.1.3.8 nonnegativeinteger read-only
The Output phase current for phase C in amps.
                                   upsOutputFrequency 1.3.6.1.4.1.186.1.19.2.5.1.3.9 nonnegativeinteger read-only
The Output Frequency for phase A in 1/10 of HZ.
                                   upsOutputCurrentPercentA 1.3.6.1.4.1.186.1.19.2.5.1.3.10 integer read-only
The output current for phase A in percent.
                                   upsOutputCurrentPercentB 1.3.6.1.4.1.186.1.19.2.5.1.3.11 integer read-only
The output current for phase B in percent.
                                   upsOutputCurrentPercentC 1.3.6.1.4.1.186.1.19.2.5.1.3.12 integer read-only
The output current for phase C in percent.
                                   upsOutputTotalActivePower 1.3.6.1.4.1.186.1.19.2.5.1.3.13 nonnegativeinteger read-only
The output active power.
                                   upsOutputTotalActivePowerPercent 1.3.6.1.4.1.186.1.19.2.5.1.3.14 nonnegativeinteger read-only
The output active power in percent.
                                   upsOutputPowerFactor 1.3.6.1.4.1.186.1.19.2.5.1.3.15 nonnegativeinteger read-only
The UPS output power factor.
                                   upsOutputRatedActivePower 1.3.6.1.4.1.186.1.19.2.5.1.3.16 nonnegativeinteger read-only
The output rated active power for the UPS.
                                   upsOutputRatedApparentPower 1.3.6.1.4.1.186.1.19.2.5.1.3.17 nonnegativeinteger read-only
The output rated apparent power for the UPS.
                                   upsOutputRatedLLVoltage 1.3.6.1.4.1.186.1.19.2.5.1.3.18 nonnegativeinteger read-only
The output rated line to line voltage for the UPS.
                               upsBypass 1.3.6.1.4.1.186.1.19.2.5.1.4
                                   upsBypassNumOfPhases 1.3.6.1.4.1.186.1.19.2.5.1.4.1 nonnegativeinteger read-only
The number of bypass lines utilized.
                                   upsBypassLLVoltageAB 1.3.6.1.4.1.186.1.19.2.5.1.4.2 nonnegativeinteger read-only
The Bypass line to line voltage for AB in RMS volts.
                                   upsBypassLLVoltageBC 1.3.6.1.4.1.186.1.19.2.5.1.4.3 nonnegativeinteger read-only
The Bypass line to line voltage for BC in RMS volts.
                                   upsBypassLLVoltageCA 1.3.6.1.4.1.186.1.19.2.5.1.4.4 nonnegativeinteger read-only
The Bypass line to line voltage for CA in RMS volts.
                                   upsBypassFrequency 1.3.6.1.4.1.186.1.19.2.5.1.4.5 nonnegativeinteger read-only
The Bypass frequency in 0.1 Hertz.
                               upsBattery 1.3.6.1.4.1.186.1.19.2.5.1.5
                                   upsBatteryStatus 1.3.6.1.4.1.186.1.19.2.5.1.5.1 integer read-only
The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run time sufficient to handle the load. A value of batteryLow indicates the battery level is low. Continued operation in battery mode will deplate batteries. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output). A value of batteryDischarging indicates UPS system is in Battery power. Enumeration: 'unknown': 1, 'batteryDepleted': 4, 'batteryFailure': 6, 'batteryNormal': 2, 'batteryLow': 3, 'batteryDischarging': 5.
                                   upsElapsedTimeOnBatteryPower 1.3.6.1.4.1.186.1.19.2.5.1.5.2 nonnegativeinteger read-only
If the unit is on battery power, the elapsed time since the UPS on battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.
                                   upsEstimatedBatteryRuntime 1.3.6.1.4.1.186.1.19.2.5.1.5.3 positiveinteger read-only
An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.
                                   upsBatteryVoltage 1.3.6.1.4.1.186.1.19.2.5.1.5.4 nonnegativeinteger read-only
The battery voltage DC.
                                   upsBatteryVoltagePercent 1.3.6.1.4.1.186.1.19.2.5.1.5.5 nonnegativeinteger read-only
Battery voltage in percent.
                                   upsBatteryEstimatedCharge 1.3.6.1.4.1.186.1.19.2.5.1.5.6 integer read-only
An estimate of the charge to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.
                                   upsBatteryDischargeCurrent 1.3.6.1.4.1.186.1.19.2.5.1.5.7 integer32 read-only
The present battery discharge Current in percent.
                                   upsBatteryChargeCurrent 1.3.6.1.4.1.186.1.19.2.5.1.5.8 integer32 read-only
The present battery charge Current in percent.
                                   upsBatteryModel 1.3.6.1.4.1.186.1.19.2.5.1.5.9 displaystring read-write
The Battery manufacturer.
                                   upsBatteryInSeries 1.3.6.1.4.1.186.1.19.2.5.1.5.10 nonnegativeinteger read-write
The Battery rated holding time in minutes.
                                   upsBatteryNumStrings 1.3.6.1.4.1.186.1.19.2.5.1.5.11 nonnegativeinteger read-write
The Battery rated holding time in minutes.
                                   upsBatteryRatedAmpereHour 1.3.6.1.4.1.186.1.19.2.5.1.5.12 nonnegativeinteger read-write
The Battery rated holding time in minutes.
                                   upsBatteryRatedBackupTime 1.3.6.1.4.1.186.1.19.2.5.1.5.13 displaystring read-write
The Battery rated holding time in minutes.
                                   upsBatteryInstallationDate 1.3.6.1.4.1.186.1.19.2.5.1.5.14 displaystring read-only
The battery install date.
                               upsAlarm 1.3.6.1.4.1.186.1.19.2.5.1.6
                                   upsAlarmsPresent 1.3.6.1.4.1.186.1.19.2.5.1.6.1 gauge32 read-only
The present number of active alarm conditions.
                                   upsAlarmTable 1.3.6.1.4.1.186.1.19.2.5.1.6.2 no-access
A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with upsAlarmId equal to 1, and increments the value of upsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of upsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because upsAlarmId might have wrapped. Alarms are named by an OBJECT IDENTIFIER, upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of upsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of upsAlarmsPresent.
                                       upsAlarmEntry 1.3.6.1.4.1.186.1.19.2.5.1.6.2.1 no-access
An entry containing information applicable to a particular alarm.
                                           upsAlarmId 1.3.6.1.4.1.186.1.19.2.5.1.6.2.1.1 positiveinteger no-access
A unique identifier for an alarm condition. This value must remain constant.
                                           upsAlarmDescr 1.3.6.1.4.1.186.1.19.2.5.1.6.2.1.2 autonomoustype read-only
A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.
                                           upsAlarmTime 1.3.6.1.4.1.186.1.19.2.5.1.6.2.1.3 timestamp read-only
The value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0.
                                   upsWellKnownAlarms 1.3.6.1.4.1.186.1.19.2.5.1.6.3
                                       upsAlarmFault 1.3.6.1.4.1.186.1.19.2.5.1.6.3.1 integer read-only
Fault: A UPS fault/Alarm condition exists.
                                       upsAlarmOnBattery 1.3.6.1.4.1.186.1.19.2.5.1.6.3.2 integer read-only
Info: The UPS is on Battery mode; it is supplying output power from its batteries.
                                       upsAlarmBatteryLow 1.3.6.1.4.1.186.1.19.2.5.1.6.3.3 integer read-only
Warning: The battery level is low. It has dropped to less than 90% of its nominal value. Continued operation in Battery Mode will deplete Batteries and result in UPS output shut down. Reduce critical load to increase battery runtime.
                                       upsAlarmBatteryDepleted 1.3.6.1.4.1.186.1.19.2.5.1.6.3.4 integer read-only
Warning: UPS contains depleted batteries, it will be unable to support critical loads. Shut down excess equipment to reduce Load.
                                       upsAlarmBatteryOverheat 1.3.6.1.4.1.186.1.19.2.5.1.6.3.5 integer read-only
Fault: Detection of over temperature at the batteries.
                                       upsAlarmBatteryVoltageAbnormal 1.3.6.1.4.1.186.1.19.2.5.1.6.3.6 integer read-only
Fault: Battery voltage is abnormality.
                                       upsAlarmUPSOverheat 1.3.6.1.4.1.186.1.19.2.5.1.6.3.7 integer read-only
Fault: The UPS is overheating (warning is given when the internal temperature reaches and exceeds 50?C rise @ 40?C ambient). Check to see if the ambient temperature is abnormally high (40?C or more). If so, turn on air conditioning. Also, check ventilation fan at the back of the UPS for operation or obstructions. Otherwise, shut down the UPS and contact your Toshiba authorized service center.
                                       upsAlarmPowerFailure 1.3.6.1.4.1.186.1.19.2.5.1.6.3.8 integer read-only
Info: Power Failure.
                                       upsAlarmUPSOverload 1.3.6.1.4.1.186.1.19.2.5.1.6.3.9 integer read-only
Fault: The UPS is overloaded. UPS will switch to bypass operation or shut down if no action is taken. Shut down excess equipment to reduce Load.
                                       upsAlarmUserDefinedOverloadWarning 1.3.6.1.4.1.186.1.19.2.5.1.6.3.10 integer read-only
Warning: The inverter output load % is greater than the user defined overload set point (default: 110%).
                                       upsAlarmOnBypass 1.3.6.1.4.1.186.1.19.2.5.1.6.3.11 integer read-only
Warning: The UPS is in Stop (Bypass) mode.
                                       upsAlarmOutputOff 1.3.6.1.4.1.186.1.19.2.5.1.6.3.12 integer read-only
Info: The UPS output is off.
                                       upsAlarmAsyncOperation 1.3.6.1.4.1.186.1.19.2.5.1.6.3.13 integer read-only
Warning: Async Operation
                                       upsAlarmDCBusOverCurrent 1.3.6.1.4.1.186.1.19.2.5.1.6.3.14 integer read-only
Fault: UPS is reporting a DC bus overcurrent condition. Contact your Toshiba authorized service center for examination of a DCOC fault.
                                       upsAlarmDCBusOverVoltage 1.3.6.1.4.1.186.1.19.2.5.1.6.3.15 integer read-only
Fault: UPS is reporting a DC bus overvoltage condition. Contact your Toshiba authorized service center for examination of a DCOV fault.
                                       upsAlarmDCBusUnderVoltage 1.3.6.1.4.1.186.1.19.2.5.1.6.3.16 integer read-only
Fault: UPS is reporting a DC bus undervoltage condition. Contact your Toshiba authorized service center for examination of a DCUV fault.
                                       upsAlarmDCBusImbalanced 1.3.6.1.4.1.186.1.19.2.5.1.6.3.17 integer read-only
Fault: The DC imbalanced alarm detection.
                                       upsAlarmOutputUnderVoltage 1.3.6.1.4.1.186.1.19.2.5.1.6.3.18 integer read-only
Fault: UPS is reporting an output undervoltage condition. Contact your Toshiba authorized service center for examination of a INVUV fault.
                                       upsAlarmOutputOverVoltage 1.3.6.1.4.1.186.1.19.2.5.1.6.3.19 integer read-only
Fault: UPS is reporting an output overvoltage condition. Contact your Toshiba authorized service center for examination of a INVOV fault.
                                       upsAlarmInverterOverload 1.3.6.1.4.1.186.1.19.2.5.1.6.3.20 integer read-only
Fault: Short time over-current has been detected.
                                       upsAlarmInverterOvercurrent 1.3.6.1.4.1.186.1.19.2.5.1.6.3.21 integer read-only
Fault: Detection of inverter overcurrent.
                                       upsAlarmRemotEyeCommError 1.3.6.1.4.1.186.1.19.2.5.1.6.3.22 integer read-only
Warning: Communication error between the RemotEye 4 and the UPS.
                               upsConfig 1.3.6.1.4.1.186.1.19.2.5.1.7
                                   upsConfigModelIDString 1.3.6.1.4.1.186.1.19.2.5.1.7.1 displaystring read-only
UPS Model ID string. This string contains codes for the UPS series,input voltage, output voltage, output VA, and addition option.
                                   upsConfigUPSFirmwareVersion 1.3.6.1.4.1.186.1.19.2.5.1.7.2 displaystring read-only
The G9000 software version.
                                   upsConfigInputNumOfPhases 1.3.6.1.4.1.186.1.19.2.5.1.7.3 nonnegativeinteger read-only
Number of input lines. This data is used by upsInputNumLines.
                                   upsConfigRatedInputFrequency 1.3.6.1.4.1.186.1.19.2.5.1.7.4 nonnegativeinteger read-only
The nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.
                                   upsConfigRatedInputLLVoltage 1.3.6.1.4.1.186.1.19.2.5.1.7.5 nonnegativeinteger read-write
The magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.
                                   upsConfigRatedInputPowerFactor 1.3.6.1.4.1.186.1.19.2.5.1.7.6 positiveinteger read-only
UNITS are in hundredths. For 0.95 = 95.
                                   upsConfigOutputNumOfPhases 1.3.6.1.4.1.186.1.19.2.5.1.7.7 nonnegativeinteger read-only
Number of output lines. This data is used by upsOutputNumLines.
                                   upsConfigRatedOutputFrequency 1.3.6.1.4.1.186.1.19.2.5.1.7.8 nonnegativeinteger read-only
The nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., bad Value for SNMPv1, or inconsistent Value for SNMPv2.
                                   upsConfigRatedOutputLLVoltage 1.3.6.1.4.1.186.1.19.2.5.1.7.9 nonnegativeinteger read-write
The magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., bad Value for SNMPv1, or inconsistent Value for SNMPv2.
                                   upsConfigRatedOutputApperentPower 1.3.6.1.4.1.186.1.19.2.5.1.7.10 nonnegativeinteger read-only
The magnitude of the nominal Volt-Amp rating.
                                   upsConfigRatedOutputActivePower 1.3.6.1.4.1.186.1.19.2.5.1.7.11 nonnegativeinteger read-only
The magnitude of the nominal true power rating.
                                   upsConfigRatedOutputPowerFactor 1.3.6.1.4.1.186.1.19.2.5.1.7.12 nonnegativeinteger read-only
UNITS are in hundredths. For 0.70 = 70.
                                   upsConfigBypassNumOfPhases 1.3.6.1.4.1.186.1.19.2.5.1.7.13 nonnegativeinteger read-only
The number of bypass lines utilized.
                                   upsConfigLowVoltageTransferPoint 1.3.6.1.4.1.186.1.19.2.5.1.7.14 nonnegativeinteger read-write
The minimum input line voltage allowed before the UPS system transfers to battery backup.
                                   upsConfigHighVoltageTransferPoint 1.3.6.1.4.1.186.1.19.2.5.1.7.15 nonnegativeinteger read-write
The maximum line voltage allowed before the UPS system transfers to battery backup.
                                   upsConfigBatteryInSeries 1.3.6.1.4.1.186.1.19.2.5.1.7.16 nonnegativeinteger read-write
The number of batteries in each string connected in series.
                                   upsConfigBatteryNumStrings 1.3.6.1.4.1.186.1.19.2.5.1.7.17 nonnegativeinteger read-write
The number of parallel battery strings.
                                   upsConfigRatedBatteryVoltage 1.3.6.1.4.1.186.1.19.2.5.1.7.18 nonnegativeinteger read-write
Rated voltage of a single battery.
                                   upsConfigRatedBatteryAmpereHour 1.3.6.1.4.1.186.1.19.2.5.1.7.19 integer read-write
The rated battery in ampere hour.
                                   upsConfigBatteryModel 1.3.6.1.4.1.186.1.19.2.5.1.7.20 displaystring read-write
The manufacturer of the battery.
                                   upsConfigBatteryRatedBackupTime 1.3.6.1.4.1.186.1.19.2.5.1.7.21 nonnegativeinteger read-write
The rated duration batteries can hold when unit is in backup mode with full load.
                                   upsConfigUserDefinedOverloadSetPoint 1.3.6.1.4.1.186.1.19.2.5.1.7.22 integer read-write
The maximum output load % defined by the user.
                                   upsConfigBatteryInstallationDate 1.3.6.1.4.1.186.1.19.2.5.1.7.23 displaystring read-write
The battery install date.
                                   upsConfigSysName 1.3.6.1.4.1.186.1.19.2.5.1.7.24 displaystring read-write
A string identifying the UPS. This object is set by the administrator.
                                   upsConfigAttachedDevices 1.3.6.1.4.1.186.1.19.2.5.1.7.25 displaystring read-write
A string identifying the devices attached to the output(s) of the UPS. This object is set by the administrator.
                                   upsConfigPassword 1.3.6.1.4.1.186.1.19.2.5.1.7.26 displaystring read-write
Password.
                               upsTime 1.3.6.1.4.1.186.1.19.2.5.1.8
                                   upsTimeRealDate 1.3.6.1.4.1.186.1.19.2.5.1.8.1 displaystring read-write
Present date: year-month-date-day of the week.
                                   upsTimeRealTime 1.3.6.1.4.1.186.1.19.2.5.1.8.2 displaystring read-write
Present time (military format): hour-minute-second. For example,2:00pm would be 14:00:00.
                               upsTrap 1.3.6.1.4.1.186.1.19.2.5.1.9
                                 upsTrapFault 1.3.6.1.4.1.186.1.19.2.5.10.1
Alarm: One or more fault/status alarm(s) reported.
                                 upsTrapFaultClear 1.3.6.1.4.1.186.1.19.2.5.10.2
Alarm Clear: One or more fault/status reported.
                                 upsTrapOnBattery 1.3.6.1.4.1.186.1.19.2.5.10.3
Info: The UPS is on Battery Mode.
                                 upsTrapOnBatteryClear 1.3.6.1.4.1.186.1.19.2.5.10.4
Info Clear: The UPS is on Battery Mode.
                                 upsTrapBatteryLow 1.3.6.1.4.1.186.1.19.2.5.10.5
Warning: Battery Low Voltage.
                                 upsTrapBatteryLowClear 1.3.6.1.4.1.186.1.19.2.5.10.6
Warning Clear: Battery Low Voltage.
                                 upsTrapBatteryDepleted 1.3.6.1.4.1.186.1.19.2.5.10.7
Warning: UPS contains depleted batteries, it will be unable to support critical loads. Shutdown excess equipment to reduce load.
                                 upsTrapBatteryDepletedClear 1.3.6.1.4.1.186.1.19.2.5.10.8
Warning Clear: UPS contains depleted batteries, it will be unable to support critical loads. Shutdown excess equipment to reduce load..
                                 upsTrapBatteryOverheat 1.3.6.1.4.1.186.1.19.2.5.10.9
Fault: Battery Overheat.
                                 upsTrapBatteryOverheatClear 1.3.6.1.4.1.186.1.19.2.5.10.10
Fault Clear: Battery Overheat.
                                 upsTrapBatteryVoltageAbnormal 1.3.6.1.4.1.186.1.19.2.5.10.11
Fault: Battery Voltage Abnormal. Contact your Toshiba authorized service center for examination.
                                 upsTrapBatteryVoltageAbnormalClear 1.3.6.1.4.1.186.1.19.2.5.10.12
Fault Clear: Battery Voltage Abnormal. Contact your Toshiba authorized service center for examination.
                                 upsTrapUPSOverheat 1.3.6.1.4.1.186.1.19.2.5.10.13
Fault: UPS Overheat, heatsinks temperature exceeds thermal settings. Contact your Toshiba authorized service center for examination.
                                 upsTrapUPSOverheatClear 1.3.6.1.4.1.186.1.19.2.5.10.14
Fault Clear: UPS Overheat, heatsinks temperature exceeds thermal settings. Contact your Toshiba authorized service center for examination.
                                 upsTrapPowerFailure 1.3.6.1.4.1.186.1.19.2.5.10.15
Info: Power Failure.
                                 upsTrapPowerFailureClear 1.3.6.1.4.1.186.1.19.2.5.10.16
Info Clear: PowerFailure.
                                 upsTrapUPSOverload 1.3.6.1.4.1.186.1.19.2.5.10.17
Fault: UPS Overload (OL), the output load exceeds the rated current. Decrease load.
                                 upsTrapUPSOverloadClear 1.3.6.1.4.1.186.1.19.2.5.10.18
Fault Clear: UPS Overload (OL), the output load exceeds the rated current. Decrease load.
                                 upsTrapUserDefinedOverloadWarning 1.3.6.1.4.1.186.1.19.2.5.10.19
Warning: The inverter output load % is greater than the user defined overload set point (default: 110%).
                                 upsTrapUserDefinedOverloadWarningClear 1.3.6.1.4.1.186.1.19.2.5.10.20
Warning Clear: The inverter output load % is greater than the user defined overload set point (default: 110%).
                                 upsTrapOnBypass 1.3.6.1.4.1.186.1.19.2.5.10.21
Warning:On Bypass.
                                 upsTrapOnBypassClear 1.3.6.1.4.1.186.1.19.2.5.10.22
Warning Clear: On Bypass.
                                 upsTrapOutputOff 1.3.6.1.4.1.186.1.19.2.5.10.23
Info: The UPS output is off.
                                 upsTrapOutputOffClear 1.3.6.1.4.1.186.1.19.2.5.10.24
Info Clear: The UPS output is off.
                                 upsTrapAsyncOperation 1.3.6.1.4.1.186.1.19.2.5.10.25
Warning: Inverter Synchronous.
                                 upsTrapAsyncOperationClear 1.3.6.1.4.1.186.1.19.2.5.10.26
Warning Clear: Inverter Synchronous.
                                 upsTrapDCBusOverCurrent 1.3.6.1.4.1.186.1.19.2.5.10.27
Fault: DC Overcurrent (DCOC). Contact your Toshiba authorized service center for examination.
                                 upsTrapDCBusOverCurrentClear 1.3.6.1.4.1.186.1.19.2.5.10.28
Fault Clear: DC Overcurrent (DCOC). Contact your Toshiba authorized service center for examination.
                                 upsTrapDCBusOverVoltage 1.3.6.1.4.1.186.1.19.2.5.10.29
Fault: DC Overvoltage (DCOV). Contact your Toshiba authorized service center for examination.
                                 upsTrapDCBusOverVoltageClear 1.3.6.1.4.1.186.1.19.2.5.10.30
Fault Clear: DC Overvoltage (DCOV). Contact your Toshiba authorized service center for examination.
                                 upsTrapDCBusUnderVoltage 1.3.6.1.4.1.186.1.19.2.5.10.31
Fault: DC Undervoltage (DCUV). Contact your Toshiba authorized service center for examination.
                                 upsTrapDCBusUnderVoltageClear 1.3.6.1.4.1.186.1.19.2.5.10.32
Fault Clear: DC Undervoltage (DCUV). Contact your Toshiba authorized service center for examination.
                                 upsTrapDCBusImbalance 1.3.6.1.4.1.186.1.19.2.5.10.33
Fault: DC Unbalance. Contact your Toshiba authorized service center for examination.
                                 upsTrapDCBusImbalanceClear 1.3.6.1.4.1.186.1.19.2.5.10.34
Fault Clear: DC Unbalance. Contact your Toshiba authorized service center for examination.
                                 upsTrapOutputUnderVoltage 1.3.6.1.4.1.186.1.19.2.5.10.35
Fault: Output Undervoltage. Contact your Toshiba authorized service center for examination.
                                 upsTrapOutputUnderVoltageClear 1.3.6.1.4.1.186.1.19.2.5.10.36
Fault Clear: Output Undervoltage. Contact your Toshiba authorized service center for examination.
                                 upsTrapOutputOverVoltage 1.3.6.1.4.1.186.1.19.2.5.10.37
Fault: Output Overvoltage (VLOV). Contact your Toshiba authorized service center for examination.
                                 upsTrapOutputOverVoltageClear 1.3.6.1.4.1.186.1.19.2.5.10.38
Fault Clear: Output Overvoltage (VLOV). Contact your Toshiba authorized service center for examination.
                                 upsTrapInverterOverload 1.3.6.1.4.1.186.1.19.2.5.10.39
Fault: UPS Overload, short time over-current has been detected during On-Line operation. Decrease Load.
                                 upsTrapInverterOverloadClear 1.3.6.1.4.1.186.1.19.2.5.10.40
Fault Clear: UPS Overload, short time over-current has been detected during On-Line operation. Decrease Load.
                                 upsTrapInverterOvercurrent 1.3.6.1.4.1.186.1.19.2.5.10.41
Fault: Inverter Overcurrent. Contact your Toshiba authorized service center for examination.
                                 upsTrapInverterOvercurrentClear 1.3.6.1.4.1.186.1.19.2.5.10.42
Fault Clear: Inverter Overcurrent. Contact your Toshiba authorized service center for examination.
                                 upsTrapRemotEyeCommError 1.3.6.1.4.1.186.1.19.2.5.10.43
Warning: RemotEye UPS communication error.
                                 upsTrapRemotEyeCommErrorClear 1.3.6.1.4.1.186.1.19.2.5.10.44
Warning Clear:RemotEye UPS communication error.