TEMPAGER3E-MIB: View SNMP OID List / Download MIB

VENDOR: AVTECH SOFTWARE


 Home MIB: TEMPAGER3E-MIB
Download as:   

Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 avtech 1.3.6.1.4.1.20916
             products 1.3.6.1.4.1.20916.1
                 TEMPAGER3E 1.3.6.1.4.1.20916.1.7
                     sensors 1.3.6.1.4.1.20916.1.7.1
                         internal 1.3.6.1.4.1.20916.1.7.1.1
                             temperature 1.3.6.1.4.1.20916.1.7.1.1.1
                                 internal_tempc 1.3.6.1.4.1.20916.1.7.1.1.1.1 integer read-only
The internal temperature reading in Celsius. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divided by 100 to get the actual value.
                                 internal_tempf 1.3.6.1.4.1.20916.1.7.1.1.1.2 integer read-only
The internal temperature reading in Fahrenheit. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divided by 100 to get the actual value.
                         digital 1.3.6.1.4.1.20916.1.7.1.2
                             digital_sen1 1.3.6.1.4.1.20916.1.7.1.2.1
                                 digital_sen1_1 1.3.6.1.4.1.20916.1.7.1.2.1.1 integer read-only
If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage.
                                 digital_sen1_2 1.3.6.1.4.1.20916.1.7.1.2.1.2 integer read-only
If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts.
                                 digital_sen1_3 1.3.6.1.4.1.20916.1.7.1.2.1.3 integer read-only
If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts.
                                 digital_sen1_4 1.3.6.1.4.1.20916.1.7.1.2.1.4 integer read-only
If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts.
                             digital_sen2 1.3.6.1.4.1.20916.1.7.1.2.2
                                 digital_sen2_1 1.3.6.1.4.1.20916.1.7.1.2.2.1 integer read-only
If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage.
                                 digital_sen2_2 1.3.6.1.4.1.20916.1.7.1.2.2.2 integer read-only
If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts.
                                 digital_sen2_3 1.3.6.1.4.1.20916.1.7.1.2.2.3 integer read-only
If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts.
                                 digital_sen2_4 1.3.6.1.4.1.20916.1.7.1.2.2.4 integer read-only
If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts.
                     traps 1.3.6.1.4.1.20916.1.7.2
                         alarmmessage 1.3.6.1.4.1.20916.1.7.2.1 octet string read-only
Last Alarm Message
                       tempager3e_snmp_trap 1.3.6.1.4.1.20916.1.70.2
A tempager3e-snmp-trap indicates that an alarm condition has occurred on the sensor indicated by the alarmmessage variable.