SOCOMECUPS-MIB-v2: View SNMP OID List / Download MIB

VENDOR: SOCOMEC SICON UPS


 Home MIB: SOCOMECUPS-MIB-v2
Download as:   

Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 socomecSicon 1.3.6.1.4.1.4555
           product 1.3.6.1.4.1.4555.1
               pduAgent 1.3.6.1.4.1.4555.1.1
                   iPDU 1.3.6.1.4.1.4555.1.1.20
                         ipduObjects 1.3.6.1.4.1.4555.1.1.20.1
                             ipduIdent 1.3.6.1.4.1.4555.1.1.20.1.1
                                 ipduIdentManufacturer 1.3.6.1.4.1.4555.1.1.20.1.1.1 displaystring read-write
The name of manufacturer.
                                 ipduIdentModel 1.3.6.1.4.1.4555.1.1.20.1.1.2 displaystring read-write
The Model designation of device.
                                 ipduIdentAgentSoftwareVersion 1.3.6.1.4.1.4555.1.1.20.1.1.3 displaystring read-only
The firmware version of the device.
                                 ipduIdentName 1.3.6.1.4.1.4555.1.1.20.1.1.4 displaystring read-write
A description of this device.
                             ipduAgent 1.3.6.1.4.1.4555.1.1.20.1.2
                                 ipduAgentConfig 1.3.6.1.4.1.4555.1.1.20.1.2.1
                                     ipduAgentMibVersion 1.3.6.1.4.1.4555.1.1.20.1.2.1.1 integer read-only
The Mib Version implemented on this device.
                                     ipduAgentLog 1.3.6.1.4.1.4555.1.1.20.1.2.1.4
                                         pduAgentDataLogInterval 1.3.6.1.4.1.4555.1.1.20.1.2.1.4.1 integer read-write
The interval of the updation of the data log. The value is in seconds
                                     ipduAgentControl 1.3.6.1.4.1.4555.1.1.20.1.2.1.5
                                         ipduAgentControlDefault 1.3.6.1.4.1.4555.1.1.20.1.2.1.5.1 integer read-write
Reset all parameters of the agent to default value. Enumeration: 'reset': 1, 'nothing': 2.
                                         ipduAgentControlRestart 1.3.6.1.4.1.4555.1.1.20.1.2.1.5.2 integer read-write
Restart the agent. Enumeration: 'nothing': 2, 'restart': 1.
                                     ipduAgentTrap 1.3.6.1.4.1.4555.1.1.20.1.2.1.6
                                         ipduAgentTrapRetryCount 1.3.6.1.4.1.4555.1.1.20.1.2.1.6.1 integer read-write
The count of repeat traps send to NMS before trap acknowledgement received.
                                         ipduAgentTrapRetryTime 1.3.6.1.4.1.4555.1.1.20.1.2.1.6.2 integer read-write
The time interval in seconds between retry traps sned to NMS.
                                         ipduAgentTrapAckSignature 1.3.6.1.4.1.4555.1.1.20.1.2.1.6.3 integer read-write
The signature of trap acknowledgement.
                                     ipduAgentTrapsReceiversTable 1.3.6.1.4.1.4555.1.1.20.1.2.1.7 no-access
A list of managers to send traps to. The number of entries is given by the value of agentConfigNumTrapReceivers
                                         ipduAgentTrapsReceiversEntry 1.3.6.1.4.1.4555.1.1.20.1.2.1.7.1 no-access
The managers to send traps to.
                                             trapsIndex 1.3.6.1.4.1.4555.1.1.20.1.2.1.7.1.1 integer read-only
The index to a trap receiver entry.
                                             trapsReceiverAddr 1.3.6.1.4.1.4555.1.1.20.1.2.1.7.1.2 ipaddress read-write
The IP address of the manager to send a trap to.
                                             receiverCommunityString 1.3.6.1.4.1.4555.1.1.20.1.2.1.7.1.3 displaystring read-write
The community name to use in the trap when sent to the manager.
                                             receiverNmsType 1.3.6.1.4.1.4555.1.1.20.1.2.1.7.1.4 integer read-write
The trap group that NMS desired. Enumeration: 'none': 1, 'iPDU-trap': 2.
                                             receiverSeverityLevel 1.3.6.1.4.1.4555.1.1.20.1.2.1.7.1.5 integer read-write
The severity level of traps to be received by this manager. Enumeration: 'severe': 3, 'warning': 2, 'informational': 1.
                                             receiverDescription 1.3.6.1.4.1.4555.1.1.20.1.2.1.7.1.6 displaystring read-write
Description of trap receivers
                                     ipduAgentAccessControlTable 1.3.6.1.4.1.4555.1.1.20.1.2.1.8 no-access
A list of managers which can access the device with private community string.
                                         ipduAgentAccessControlEntry 1.3.6.1.4.1.4555.1.1.20.1.2.1.8.1 no-access
The managers.
                                             accessIndex 1.3.6.1.4.1.4555.1.1.20.1.2.1.8.1.1 integer read-only
The index to a access control entry.
                                             accessControlAddr 1.3.6.1.4.1.4555.1.1.20.1.2.1.8.1.2 ipaddress read-write
The IP address of the manager to access the device.
                                             accessControlMode 1.3.6.1.4.1.4555.1.1.20.1.2.1.8.1.3 integer read-write
Access type, only read/Write access type can change parameter of the device. Enumeration: 'permitted': 1, 'denied': 2.
                                 ipduAgentTime 1.3.6.1.4.1.4555.1.1.20.1.2.2
                                     ipduAgentTimeDate 1.3.6.1.4.1.4555.1.1.20.1.2.2.1 displaystring read-write
The date in agent, format is (dd/mm/yyyy)
                                     ipduAgentTimeTime 1.3.6.1.4.1.4555.1.1.20.1.2.2.2 displaystring read-write
The time in agent, format is (hh:mm:ss)
                                     ipduAgentTimerFromNtp 1.3.6.1.4.1.4555.1.1.20.1.2.2.3 integer read-write
Enable or disable the agent to synchronize date/time with NTP server. Enumeration: 'disabled': 2, 'enabled': 1.
                                     ipduAgentNtpIpAddress 1.3.6.1.4.1.4555.1.1.20.1.2.2.4 ipaddress read-write
The ip address of NTP server.
                                     ipduAgentNtpTimeZone 1.3.6.1.4.1.4555.1.1.20.1.2.2.5 integer read-write
Time Zone to use when synchronize with NTP server. Enumeration: 'gMT-0400': 9, 'gMT-0500': 8, 'gMT1000': 26, 'gMT-0200': 12, 'gMT-0300': 11, 'gMT0330': 18, 'gMT-0000': 14, 'gMT1200': 28, 'gMT0500': 20, 'gMT-0100': 13, 'gMT1100': 27, 'gMT0600': 22, 'gMT-0800': 5, 'gMT0400': 19, 'gMT-0900': 4, 'gMT-1000': 3, 'gMT0300': 17, 'gMT-1200': 1, 'gMT-0600': 7, 'gMT-0700': 6, 'gMT0100': 15, 'gMT-0330': 10, 'gMT0200': 16, 'gMT0800': 24, 'gMT0700': 23, 'gMT0900': 25, 'gMT-1100': 2, 'gMT0530': 21.
                                     ipduAgentDayLightSaving 1.3.6.1.4.1.4555.1.1.20.1.2.2.6 integer read-write
Enable/disable the Day Light Saving when synchronize with NTP server. Enumeration: 'disabled': 2, 'enabled': 1.
                                 ipduAgentNetwork 1.3.6.1.4.1.4555.1.1.20.1.2.3
                                     ipduAgentNetworkIp 1.3.6.1.4.1.4555.1.1.20.1.2.3.1
                                         ipduAgentNetworkIpAdress 1.3.6.1.4.1.4555.1.1.20.1.2.3.1.1 ipaddress read-write
The ip address that NMS can identify the managed device.
                                         ipduAgentNetworkIpGateway 1.3.6.1.4.1.4555.1.1.20.1.2.3.1.2 ipaddress read-write
The default gateway that allow device managed through routers.
                                         ipduAgentNetworkIpSubnet 1.3.6.1.4.1.4555.1.1.20.1.2.3.1.3 ipaddress read-write
Internet address subnet mask
                                     ipduAgentNetworkDhcpControl 1.3.6.1.4.1.4555.1.1.20.1.2.3.2 integer read-write
Enable/disable DHCP protocol Enumeration: 'disabled': 2, 'enabled': 1.
                                     ipduAgentNetworkPingControl 1.3.6.1.4.1.4555.1.1.20.1.2.3.3 integer read-write
Enable/disable to response to PING request. Enumeration: 'disabled': 2, 'enabled': 1.
                                     ipduAgentNetworkTftpControl 1.3.6.1.4.1.4555.1.1.20.1.2.3.4 integer read-write
Enable/disable TFTP protocol Enumeration: 'disabled': 2, 'enabled': 1.
                                     ipduAgentNetworkTelnet 1.3.6.1.4.1.4555.1.1.20.1.2.3.5
                                         ipduAgentTelnetControl 1.3.6.1.4.1.4555.1.1.20.1.2.3.5.1 integer read-write
Enable/disable Telnet protocol. Enumeration: 'disabled': 2, 'enabled': 1.
                                         ipduAgentTelnetPort 1.3.6.1.4.1.4555.1.1.20.1.2.3.5.2 integer read-write
The TCP port for telnet
                                     ipduAgentNetworkHttp 1.3.6.1.4.1.4555.1.1.20.1.2.3.6
                                         ipduAgentHttpControl 1.3.6.1.4.1.4555.1.1.20.1.2.3.6.1 integer read-write
Enable/disable HTTP protocol. Enumeration: 'disabled': 2, 'enabled': 1.
                                         ipduAgentHttpPort 1.3.6.1.4.1.4555.1.1.20.1.2.3.6.2 integer read-write
The TCP port for HTTP.
                                     ipduAgentNetworkSnmp 1.3.6.1.4.1.4555.1.1.20.1.2.3.7
                                         ipduAgentSnmpControl 1.3.6.1.4.1.4555.1.1.20.1.2.3.7.1 integer read-write
Enable/disable SNMP protocol. Enumeration: 'disabled': 2, 'enabled': 1.
                                         ipduAgentSnmpPort 1.3.6.1.4.1.4555.1.1.20.1.2.3.7.2 integer read-write
The UDP port for SNMP.
                             ipduDevice 1.3.6.1.4.1.4555.1.1.20.1.3
                                 ipduDeviceInlet 1.3.6.1.4.1.4555.1.1.20.1.3.1
                                     ipduDeviceInletNumber 1.3.6.1.4.1.4555.1.1.20.1.3.1.1 integer read-only
The inlet number on this device.
                                     ipduDeviceInletConfigTable 1.3.6.1.4.1.4555.1.1.20.1.3.1.2 no-access
A list of inlet on this device.
                                         ipduDeviceInletConfigEntry 1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1 no-access
The inlet number of device.
                                             inletConfigIndex 1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.1 integer read-only
The index to a access inlet configuration table.
                                             inletConfigDesc 1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.2 displaystring read-write
A Description of inlet of device.
                                             inletConfigVoltageHigh 1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.3 integer read-write
The Inlet high voltage threshold, in volts.
                                             inletConfigVoltageHighAction 1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.4 integer read-write
Reaction of the device when inlet voltage higher than set point. Enumeration: 'nothing': 2, 'outletsOff': 1.
                                             inletConfigVoltageLow 1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.5 integer read-write
The Inlet low voltage threshold, in volts.
                                             inletConfigVoltageLowAction 1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.6 integer read-write
Reaction of the device when inlet voltage lower than set point. Enumeration: 'nothing': 2, 'outletsOff': 1.
                                             inletConfigCurrentHigh 1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.7 integer read-write
The Inlet low voltage threshold, in 0.1 amps.
                                             inletConfigCurrentHighAction 1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.8 integer read-write
Reaction of the device when inlet current higher than set point. Enumeration: 'nothing': 2, 'outletsOff': 1.
                                             inletConfigFrequencyHigh 1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.9 integer read-write
The Inlet high frequency threshold, in hz.
                                             inletConfigfrequencyHighAction 1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.10 integer read-write
Reaction of the device when inlet frequency higher than set point. Enumeration: 'nothing': 2, 'outletsOff': 1.
                                             inletConfigFrequencyLow 1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.11 integer read-write
The Inlet low frequency threshold, in hz.
                                             inletConfigfrequencyLowAction 1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.12 integer read-write
Reaction of the device when inlet frequency lower than set point. Enumeration: 'nothing': 2, 'outletsOff': 1.
                                     ipduDeviceInletStatusTable 1.3.6.1.4.1.4555.1.1.20.1.3.1.3 no-access
A list of inlet on this device.
                                         ipduDeviceInletStatusEntry 1.3.6.1.4.1.4555.1.1.20.1.3.1.3.1 no-access
The inlet number of device.
                                             inletStatusIndex 1.3.6.1.4.1.4555.1.1.20.1.3.1.3.1.1 integer read-only
The index to a access inlet configuration table.
                                             inletStatusVoltage 1.3.6.1.4.1.4555.1.1.20.1.3.1.3.1.2 integer read-only
The Inlet Voltage in 0.1 volts
                                             inletStatusCurrent 1.3.6.1.4.1.4555.1.1.20.1.3.1.3.1.3 integer read-only
The Inlet Current in 0.001 Amp.
                                             inletStatusFrequency 1.3.6.1.4.1.4555.1.1.20.1.3.1.3.1.4 integer read-only
The Inlet Frequency in 0.1 Hz
                                             inletStatusKwatt 1.3.6.1.4.1.4555.1.1.20.1.3.1.3.1.5 integer read-only
The Inlet Kwatt in 0.1 KW/H
                                             inletStatusWH 1.3.6.1.4.1.4555.1.1.20.1.3.1.3.1.6 integer read-only
The Inlet Kwatt in 0.1 W/H
                                     inletWattReset 1.3.6.1.4.1.4555.1.1.20.1.3.1.4 integer read-write
Reset inlet kw. Enumeration: 'none': 1, 'inlet2': 3, 'inlet1': 2.
                                 ipduDeviceOutlet 1.3.6.1.4.1.4555.1.1.20.1.3.2
                                     ipduDeviceOutletNumber 1.3.6.1.4.1.4555.1.1.20.1.3.2.1 integer read-only
The outlet number on this device.
                                     ipduDeviceOutletConfigTable 1.3.6.1.4.1.4555.1.1.20.1.3.2.2 no-access
A list of outlet on this device.
                                         ipduDeviceOutletConfigEntry 1.3.6.1.4.1.4555.1.1.20.1.3.2.2.1 no-access
The inlet number of device.
                                             outletConfigIndex 1.3.6.1.4.1.4555.1.1.20.1.3.2.2.1.1 integer read-only
The index to a access inlet configuration table.
                                             outletConfigDesc 1.3.6.1.4.1.4555.1.1.20.1.3.2.2.1.2 displaystring read-write
A Description of outlet of device.
                                             outletConfigLocation 1.3.6.1.4.1.4555.1.1.20.1.3.2.2.1.3 displaystring read-write
Location of device connectted to this outlet.
                                             outletConfigOnDelay 1.3.6.1.4.1.4555.1.1.20.1.3.2.2.1.4 integer read-write
The delay time before turn on tis outlet, in seconds.
                                             outletConfigOffDelay 1.3.6.1.4.1.4555.1.1.20.1.3.2.2.1.5 integer read-write
The delay time before turn off tis outlet, in seconds.
                                             outletConfigCurrentHigh 1.3.6.1.4.1.4555.1.1.20.1.3.2.2.1.6 integer read-write
The outlet high current threshold, in amp.
                                             outletConfigCurrentHighAction 1.3.6.1.4.1.4555.1.1.20.1.3.2.2.1.7 integer read-write
Reaction of the device when outlet current higher than set point. Enumeration: 'nothing': 2, 'outletOff': 1.
                                     ipduDeviceOutletStatusTable 1.3.6.1.4.1.4555.1.1.20.1.3.2.3 no-access
A list of outlet on this device.
                                         ipduDeviceOutletStatusEntry 1.3.6.1.4.1.4555.1.1.20.1.3.2.3.1 no-access
The outlet number of device.
                                             outletStatusIndex 1.3.6.1.4.1.4555.1.1.20.1.3.2.3.1.1 integer read-only
The index to a access outlet configuration table.
                                             outletStatusStatus 1.3.6.1.4.1.4555.1.1.20.1.3.2.3.1.2 integer read-only
Outlet state Enumeration: 'outletOff': 2, 'outletOn': 3, 'unknow': 1, 'outletCycling': 6, 'outletOffToOn': 4, 'outletOnToOff': 5.
                                             outletStatusCurrent 1.3.6.1.4.1.4555.1.1.20.1.3.2.3.1.3 integer read-only
The outlet Current in 0.001 Amp.
                                             outletStatusKwatt 1.3.6.1.4.1.4555.1.1.20.1.3.2.3.1.4 integer read-only
The outlet Kwatt in 0.001 KW/H.
                                             outletStatusWH 1.3.6.1.4.1.4555.1.1.20.1.3.2.3.1.5 integer read-only
The outlet Watt in 0.1 W/H.
                                             outletStatusStateTime 1.3.6.1.4.1.4555.1.1.20.1.3.2.3.1.6 integer read-only
Time in seconds since the outlet changed to current state.
                                             outletStatusTimeToGo 1.3.6.1.4.1.4555.1.1.20.1.3.2.3.1.7 integer read-only
Remain time the outlet state will be changed by agent, in seconds
                                     ipduDeviceOutletControlTable 1.3.6.1.4.1.4555.1.1.20.1.3.2.4 no-access
A list of outlet on this device.
                                         ipduDeviceOutletControlEntry 1.3.6.1.4.1.4555.1.1.20.1.3.2.4.1 no-access
The outlet number of device.
                                             outletControlIndex 1.3.6.1.4.1.4555.1.1.20.1.3.2.4.1.1 integer read-only
The index to a access outlet configuration table.
                                             outletControlControl 1.3.6.1.4.1.4555.1.1.20.1.3.2.4.1.2 integer read-write
Set to control the outlet perform action as requested. Enumeration: 'none': 1, 'cancelAction': 2, 'cycleByActionTimer': 8, 'offByActionTimer': 7, 'onByActionTimer': 6, 'offThenOnByActionTimers': 10, 'offImmediately': 4, 'cycleImmediately': 5, 'onImmediately': 3, 'onThenOffByActionTimers': 9.
                                     ipduDeviceOutletControlAll 1.3.6.1.4.1.4555.1.1.20.1.3.2.5 integer read-write
Set to control all outlets perform action as requested. Enumeration: 'onByActionTimers': 6, 'none': 1, 'cancelAction': 2, 'onThenOffByActionTimers': 9, 'offImmediately': 4, 'offThenOnByActionTimers': 10, 'cycleImmediately': 5, 'onImmediately': 3, 'cycleByActionTimers': 8, 'offByActionTimers': 7.
                                     ipduDeviceOutletWattReset 1.3.6.1.4.1.4555.1.1.20.1.3.2.6 integer read-write
Reset outlet kw. Enumeration: 'none': 1, 'outletl': 13, 'outletj': 11, 'outletk': 12, 'outleth': 9, 'outleti': 10, 'outletf': 7, 'outletg': 8, 'outletd': 5, 'outlete': 6, 'outletb': 3, 'outletc': 4, 'outleta': 2.
                                 ipduDeviceCcOut 1.3.6.1.4.1.4555.1.1.20.1.3.3
                                     ipduDeviceCcOutNumber 1.3.6.1.4.1.4555.1.1.20.1.3.3.1 integer read-only
The contact closure output number on this device.
                                     ipduDeviceCcOutConfigTable 1.3.6.1.4.1.4555.1.1.20.1.3.3.2 no-access
A list of contact closure output on this device.
                                         ipduDeviceCcOutConfigEntry 1.3.6.1.4.1.4555.1.1.20.1.3.3.2.1 no-access
The CC number of device.
                                             ccOutConfigIndex 1.3.6.1.4.1.4555.1.1.20.1.3.3.2.1.1 integer read-only
The index to access contact closure output configuration table.
                                             ccOutConfigDesc 1.3.6.1.4.1.4555.1.1.20.1.3.3.2.1.2 displaystring read-write
A Description of a contact closure output of device.
                                             ccOutConfigEventAction 1.3.6.1.4.1.4555.1.1.20.1.3.3.2.1.3 integer read-write
Enable/disble the contact closure output to react to events. Enumeration: 'yes': 1, 'no': 2.
                                             ccOutConfigCloseDelay 1.3.6.1.4.1.4555.1.1.20.1.3.3.2.1.4 integer read-write
The delay time in seconds when the contact closure output set to close.
                                             ccOutConfigOpenDelay 1.3.6.1.4.1.4555.1.1.20.1.3.3.2.1.5 integer read-write
The delay time in seconds when the contact closure output set to open.
                                     ipduDeviceCcOutStatusTable 1.3.6.1.4.1.4555.1.1.20.1.3.3.3 no-access
A list of contact closure output on this device.
                                         ipduDeviceCcOutStatusEntry 1.3.6.1.4.1.4555.1.1.20.1.3.3.3.1 no-access
The CC number of device.
                                             ccOutStatusIndex 1.3.6.1.4.1.4555.1.1.20.1.3.3.3.1.1 integer read-only
The index to access contact closure output configuration table.
                                             ccOutStatusStatus 1.3.6.1.4.1.4555.1.1.20.1.3.3.3.1.2 integer read-only
State of a contact closure output of device. Enumeration: 'open': 2, 'closed': 1.
                                             ccOutStatusTimeOnState 1.3.6.1.4.1.4555.1.1.20.1.3.3.3.1.3 integer read-only
Time in seconds since the contact closure output changed to current state.
                                     ipduDeviceCcOutControlTable 1.3.6.1.4.1.4555.1.1.20.1.3.3.4 no-access
A list of contact closure output on this device.
                                         ipduDeviceCcOutControlEntry 1.3.6.1.4.1.4555.1.1.20.1.3.3.4.1 no-access
The outlet number of device.
                                             ccOutControlIndex 1.3.6.1.4.1.4555.1.1.20.1.3.3.4.1.1 integer read-only
The index to a access contact closure output configuration table.
                                             ccOutControlControl 1.3.6.1.4.1.4555.1.1.20.1.3.3.4.1.2 integer read-write
Set to control the contact closure output perform action as requested. Enumeration: 'none': 1, 'cancelAction': 2, 'closeThenOpenByActionTimers': 9, 'cycleByActionTimer': 8, 'closeByCloseTimer': 6, 'closeImmediately': 3, 'openByOpenTimer': 7, 'openImmediately': 4, 'openThenCloseByActionTimers': 10, 'cycleImmediately': 5.
                             ipduSlave 1.3.6.1.4.1.4555.1.1.20.1.4
                                 ipduSlaveState 1.3.6.1.4.1.4555.1.1.20.1.4.1
                                     ipduSlaveStateTable 1.3.6.1.4.1.4555.1.1.20.1.4.1.1 no-access
A list of outlet on this device.
                                         ipduSlaveStateEntry 1.3.6.1.4.1.4555.1.1.20.1.4.1.1.1 no-access
The outlet number of device.
                                             slaveStateIndex 1.3.6.1.4.1.4555.1.1.20.1.4.1.1.1.1 integer read-only
The index to a access outlet configuration table.
                                             slaveStateControl01 1.3.6.1.4.1.4555.1.1.20.1.4.1.1.1.2 integer read-only
Set to control the outlet perform action as requested to slave outlet A Enumeration: 'connected': 2, 'disconnected': 1.
                                 ipduSlaveInlet 1.3.6.1.4.1.4555.1.1.20.1.4.2
                                     ipduSlaveInletStatus 1.3.6.1.4.1.4555.1.1.20.1.4.2.1
                                         ipduDeviceSlaveInletStatusTable 1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1 no-access
A list of inlet on this device.
                                             ipduDeviceSlaveInletStatusEntry 1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1 no-access
The inlet number of device.
                                                 inletSlaveStatusIndex 1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.1 integer read-only
The index to a access inlet configuration table.
                                                 inletSlaveStatusVoltage 1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.2 integer read-only
The Inlet Voltage in 0.1 volts
                                                 inletSlaveStatusCurrent 1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.3 integer read-only
The Inlet Current in 0.001 Amp.
                                                 inletSlaveStatusFrequency 1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.4 integer read-only
The Inlet Frequency in 0.1 Hz
                                                 inletSlaveStatusKwatt 1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.5 integer read-only
The Inlet Kwatt in 0.001 KW/H
                                                 inletSlaveStatusWH 1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.6 integer read-only
The Inlet Kwatt in 0.001 KW/H
                                                 inletSlaveStatusVoltage2 1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.7 integer read-only
The Inlet Voltage in 0.1 volts
                                                 inletSlaveStatusCurrent2 1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.8 integer read-only
The Inlet Current in 0.001 Amp.
                                                 inletSlaveStatusFrequency2 1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.9 integer read-only
The Inlet Frequency in 0.1 Hz
                                                 inletSlaveStatusKwatt2 1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.10 integer read-only
The Inlet Kwatt in 0.001 KW/H
                                                 inletSlaveStatusWH2 1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.11 integer read-only
The Inlet Kwatt in 0.001 KW/H
                                     ipduSlaveInletConfig 1.3.6.1.4.1.4555.1.1.20.1.4.2.2
                                         ipduDeviceslaveInletConfigTable 1.3.6.1.4.1.4555.1.1.20.1.4.2.2.1 no-access
A list of inlet on this device.
                                             ipduDeviceslaveInletConfigEntry 1.3.6.1.4.1.4555.1.1.20.1.4.2.2.1.1 no-access
The inlet number of device.
                                                 slaveInletConfigIndex 1.3.6.1.4.1.4555.1.1.20.1.4.2.2.1.1.1 integer read-only
The index to a access inlet configuration table.
                                                 slaveInletConfigVoltageHigh 1.3.6.1.4.1.4555.1.1.20.1.4.2.2.1.1.2 integer read-write
The Inlet high voltage threshold, in volts.
                                                 slaveInletConfigVoltageLow 1.3.6.1.4.1.4555.1.1.20.1.4.2.2.1.1.3 integer read-write
The Inlet low voltage threshold, in volts.
                                                 slaveInlet2ConfigVoltageHigh 1.3.6.1.4.1.4555.1.1.20.1.4.2.2.1.1.4 integer read-write
The Inlet 2 high voltage threshold, in volts.
                                                 slaveInlet2ConfigVoltageLow 1.3.6.1.4.1.4555.1.1.20.1.4.2.2.1.1.5 integer read-write
The Inlet low voltage threshold, in volts.
                                 ipduSlaveOutlet 1.3.6.1.4.1.4555.1.1.20.1.4.3
                                     ipduSlaveOutletConfig 1.3.6.1.4.1.4555.1.1.20.1.4.3.1
                                         ipduSlaveDeviceOutletNameTable 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1 no-access
A list of outlet on this device.
                                             ipduSlaveDeviceOutletNameEntry 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1 no-access
The outlet number of device.
                                                 slaveOutletNameIndex 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.1 integer read-only
The index to a access outlet configuration table.
                                                 slaveOutletName01 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.2 displaystring read-write
A Description of a outlet name of device.
                                                 slaveOutletName02 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.3 displaystring read-write
A Description of a outlet name of device.
                                                 slaveOutletName03 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.4 displaystring read-write
A Description of a outlet name of device.
                                                 slaveOutletName04 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.5 displaystring read-write
A Description of a outlet name of device.
                                                 slaveOutletName05 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.6 displaystring read-write
A Description of a outlet name of device.
                                                 slaveOutletName06 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.7 displaystring read-write
A Description of a outlet name of device.
                                                 slaveOutletName07 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.8 displaystring read-write
A Description of a outlet name of device.
                                                 slaveOutletName08 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.9 displaystring read-write
A Description of a outlet name of device.
                                                 slaveOutletName09 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.10 displaystring read-write
A Description of a outlet name of device.
                                                 slaveOutletName10 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.11 displaystring read-write
A Description of a outlet name of device.
                                                 slaveOutletName11 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.12 displaystring read-write
A Description of a outlet name of device.
                                                 slaveOutletName12 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.13 displaystring read-write
A Description of a outlet name of device.
                                         ipduSlaveDeviceOutletLocationTable 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2 no-access
A list of outlet on this device.
                                             ipduSlaveDeviceOutletLocationEntry 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1 no-access
The outlet number of device.
                                                 slaveOutletLocationIndex 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.1 integer read-only
The index to a access outlet configuration table.
                                                 slaveOutletLocation01 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.2 displaystring read-write
A Description of a outlet name of device.
                                                 slaveOutletLocation02 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.3 displaystring read-write
A Description of a outlet name of device.
                                                 slaveOutletLocation03 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.4 displaystring read-write
A Description of a outlet name of device.
                                                 slaveOutletLocation04 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.5 displaystring read-write
A Description of a outlet name of device.
                                                 slaveOutletLocation05 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.6 displaystring read-write
A Description of a outlet name of device.
                                                 slaveOutletLocation06 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.7 displaystring read-write
A Description of a outlet name of device.
                                                 slaveOutletLocation07 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.8 displaystring read-write
A Description of a outlet name of device.
                                                 slaveOutletLocation08 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.9 displaystring read-write
A Description of a outlet name of device.
                                                 slaveOutletLocation09 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.10 displaystring read-write
A Description of a outlet name of device.
                                                 slaveOutletLocation10 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.11 displaystring read-write
A Description of a outlet name of device.
                                                 slaveOutletLocation11 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.12 displaystring read-write
A Description of a outlet name of device.
                                                 slaveOutletLocation12 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.13 displaystring read-write
A Description of a outlet name of device.
                                         ipduSlaveDeviceOutletOnTimeTable 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3 no-access
A list of outlet on this device.
                                             ipduSlaveDeviceOutletOnTimeEntry 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1 no-access
The outlet number of device.
                                                 slaveOutletOnTimeIndex 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.1 integer read-only
The index to a access outlet configuration table.
                                                 slaveOutletOnTime01 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.2 integer read-write
The delay time before turn on tis outlet, in seconds.
                                                 slaveOutletOnTime02 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.3 integer read-write
The delay time before turn on tis outlet, in seconds.
                                                 slaveOutletOnTime03 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.4 integer read-write
The delay time before turn on tis outlet, in seconds.
                                                 slaveOutletOnTime04 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.5 integer read-write
The delay time before turn on tis outlet, in seconds.
                                                 slaveOutletOnTime05 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.6 integer read-write
The delay time before turn on tis outlet, in seconds.
                                                 slaveOutletOnTime06 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.7 integer read-write
The delay time before turn on tis outlet, in seconds.
                                                 slaveOutletOnTime07 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.8 integer read-write
The delay time before turn on tis outlet, in seconds.
                                                 slaveOutletOnTime08 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.9 integer read-write
The delay time before turn on tis outlet, in seconds.
                                                 slaveOutletOnTime09 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.10 integer read-write
The delay time before turn on tis outlet, in seconds.
                                                 slaveOutletOnTime10 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.11 integer read-write
The delay time before turn on tis outlet, in seconds.
                                                 slaveOutletOnTime11 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.12 integer read-write
The delay time before turn on tis outlet, in seconds.
                                                 slaveOutletOnTime12 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.13 integer read-write
The delay time before turn on tis outlet, in seconds.
                                         ipduSlaveDeviceOutletOffTimeTable 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4 no-access
A list of outlet on this device.
                                             ipduSlaveDeviceOutletOffTimeEntry 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1 no-access
The outlet number of device.
                                                 slaveOutletOffTimeIndex 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.1 integer read-only
The index to a access outlet configuration table.
                                                 slaveOutletOffTime01 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.2 integer read-write
The delay time before turn on tis outlet, in seconds.
                                                 slaveOutletOffTime02 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.3 integer read-write
The delay time before turn on tis outlet, in seconds.
                                                 slaveOutletOffTime03 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.4 integer read-write
The delay time before turn on tis outlet, in seconds.
                                                 slaveOutletOffTime04 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.5 integer read-write
The delay time before turn on tis outlet, in seconds.
                                                 slaveOutletOffTime05 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.6 integer read-write
The delay time before turn on tis outlet, in seconds.
                                                 slaveOutletOffTime06 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.7 integer read-write
The delay time before turn on tis outlet, in seconds.
                                                 slaveOutletOffTime07 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.8 integer read-write
The delay time before turn on tis outlet, in seconds.
                                                 slaveOutletOffTime08 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.9 integer read-write
The delay time before turn on tis outlet, in seconds.
                                                 slaveOutletOffTime09 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.10 integer read-write
The delay time before turn on tis outlet, in seconds.
                                                 slaveOutletOffTime10 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.11 integer read-write
The delay time before turn on tis outlet, in seconds.
                                                 slaveOutletOffTime11 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.12 integer read-write
The delay time before turn on tis outlet, in seconds.
                                                 slaveOutletOffTime12 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.13 integer read-write
The delay time before turn on tis outlet, in seconds.
                                         ipduSlaveDeviceOutletCurrThTable 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5 no-access
A list of outlet on this device.
                                             ipduSlaveDeviceOutletCurrThEntry 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1 no-access
The outlet number of device.
                                                 slaveOutletCurrThIndex 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.1 integer read-only
The index to a access outlet configuration table.
                                                 slaveOutletCurrTh01 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.2 integer read-write
The Outlet Current Threshold ,in 0.1 Amp.
                                                 slaveOutletCurrTh02 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.3 integer read-write
The Outlet Current Threshold ,in 0.1 Amp.
                                                 slaveOutletCurrTh03 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.4 integer read-write
The Outlet Current Threshold ,in 0.1 Amp.
                                                 slaveOutletCurrTh04 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.5 integer read-write
The Outlet Current Threshold ,in 0.1 Amp.
                                                 slaveOutletCurrTh05 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.6 integer read-write
The Outlet Current Threshold ,in 0.1 Amp.
                                                 slaveOutletCurrTh06 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.7 integer read-write
The Outlet Current Threshold ,in 0.1 Amp.
                                                 slaveOutletCurrTh07 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.8 integer read-write
The Outlet Current Threshold ,in 0.1 Amp.
                                                 slaveOutletCurrTh08 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.9 integer read-write
The Outlet Current Threshold ,in 0.1 Amp.
                                                 slaveOutletCurrTh09 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.10 integer read-write
The Outlet Current Threshold ,in 0.1 Amp.
                                                 slaveOutletCurrTh10 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.11 integer read-write
The Outlet Current Threshold ,in 0.1 Amp.
                                                 slaveOutletCurrTh11 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.12 integer read-write
The Outlet Current Threshold ,in 0.1 Amp.
                                                 slaveOutletCurrTh12 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.13 integer read-write
The Outlet Current Threshold ,in 0.1 Amp.
                                     ipduSlaveOutletStatus 1.3.6.1.4.1.4555.1.1.20.1.4.3.2
                                         ipduSlaveDeviceOutletCurrentTable 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1 no-access
A list of outlet on this device.
                                             ipduSlaveDeviceOutletCurrentEntry 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1 no-access
The outlet number of device.
                                                 slaveOutletCurrentIndex 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.1 integer read-only
The index to a access outlet configuration table.
                                                 slaveOutletCurrent01 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.2 integer read-only
The outlet A Current in 0.001 Amp.
                                                 slaveOutletCurrent02 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.3 integer read-only
The outlet B Current in 0.001 Amp.
                                                 slaveOutletCurrent03 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.4 integer read-only
The outlet C Current in 0.001 Amp.
                                                 slaveOutletCurrent04 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.5 integer read-only
The outlet D Current in 0.001 Amp.
                                                 slaveOutletCurrent05 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.6 integer read-only
The outlet E Current in 0.001 Amp.
                                                 slaveOutletCurrent06 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.7 integer read-only
The outlet F Current in 0.001 Amp.
                                                 slaveOutletCurrent07 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.8 integer read-only
The outlet G Current in 0.001 Amp.
                                                 slaveOutletCurrent08 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.9 integer read-only
The outlet H Current in 0.001 Amp.
                                                 slaveOutletCurrent09 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.10 integer read-only
The outlet I Current in 0.001 Amp.
                                                 slaveOutletCurrent10 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.11 integer read-only
The outlet J Current in 0.001 Amp.
                                                 slaveOutletCurrent11 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.12 integer read-only
The outlet K Current in 0.001 Amp.
                                                 slaveOutletCurrent12 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.13 integer read-only
The outlet L Current in 0.001 Amp.
                                         ipduSlaveDeviceOutletWattTable 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2 no-access
A list of outlet on this device.
                                             ipduSlaveDeviceOutletWattEntry 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1 no-access
The outlet number of device.
                                                 slaveOutletWattIndex 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.1 integer read-only
The index to a access outlet configuration table.
                                                 slaveOutletWatt01 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.2 integer read-only
The outlet A Watt in 0.1 W/H.
                                                 slaveOutletWatt02 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.3 integer read-only
The outlet B Watt in 0.1 W/H.
                                                 slaveOutletWatt03 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.4 integer read-only
The outlet C Watt in 0.1 W/H.
                                                 slaveOutletWatt04 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.5 integer read-only
The outlet D Watt in 0.1 W/H.
                                                 slaveOutletWatt05 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.6 integer read-only
The outlet E Watt in 0.1 W/H.
                                                 slaveOutletWatt06 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.7 integer read-only
The outlet F Watt in 0.1 W/H.
                                                 slaveOutletWatt07 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.8 integer read-only
The outlet G Watt in 0.1 W/H.
                                                 slaveOutletWatt08 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.9 integer read-only
The outlet H Watt in 0.1 W/H.
                                                 slaveOutletWatt09 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.10 integer read-only
The outlet I Watt in 0.1 W/H.
                                                 slaveOutletWatt10 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.11 integer read-only
The outlet J Watt in 0.1 W/H.
                                                 slaveOutletWatt11 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.12 integer read-only
The outlet K Watt in 0.1 W/H.
                                                 slaveOutletWatt12 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.13 integer read-only
The outlet L Watt in 0.1 W/H.
                                         ipduSlaveDeviceOutletKwattTable 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3 no-access
A list of outlet on this device.
                                             ipduSlaveDeviceOutletKwattEntry 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1 no-access
The outlet number of device.
                                                 slaveOutletKwattIndex 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.1 integer read-only
The index to a access outlet configuration table.
                                                 slaveOutletKwatt01 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.2 integer read-only
The outlet A Kwatt in 0.001 KW/H.
                                                 slaveOutletKwatt02 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.3 integer read-only
The outlet B Kwatt in 0.001 KW/H.
                                                 slaveOutletKwatt03 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.4 integer read-only
The outlet C Kwatt in 0.001 KW/H.
                                                 slaveOutletKwatt04 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.5 integer read-only
The outlet D Kwatt in 0.001 KW/H.
                                                 slaveOutletKwatt05 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.6 integer read-only
The outlet E Kwatt in 0.001 KW/H.
                                                 slaveOutletKwatt06 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.7 integer read-only
The outlet F Kwatt in 0.001 KW/H.
                                                 slaveOutletKwatt07 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.8 integer read-only
The outlet G Kwatt in 0.001 KW/H.
                                                 slaveOutletKwatt08 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.9 integer read-only
The outlet H Kwatt in 0.001 KW/H.
                                                 slaveOutletKwatt09 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.10 integer read-only
The outlet I Kwatt in 0.001 KW/H.
                                                 slaveOutletKwatt10 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.11 integer read-only
The outlet J Kwatt in 0.001 KW/H.
                                                 slaveOutletKwatt11 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.12 integer read-only
The outlet K Kwatt in 0.001 KW/H.
                                                 slaveOutletKwatt12 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.13 integer read-only
The outlet L Kwatt in 0.001 KW/H.
                                     ipduSlaveOutletAction 1.3.6.1.4.1.4555.1.1.20.1.4.3.3
                                         ipduSlaveDeviceOutletActionTable 1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1 no-access
A list of outlet on this device.
                                             ipduSlaveDeviceOutletActionEntry 1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1 no-access
The outlet number of device.
                                                 slaveOutletActionIndex 1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.1 integer read-only
The index to a access outlet configuration table.
                                                 slaveOutletAction01 1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.2 integer read-write
Set to control the outlet perform action as requested. Enumeration: 'none': 1, 'cancelAction': 2, 'cycleByActionTimer': 8, 'offByActionTimer': 7, 'onByActionTimer': 6, 'offThenOnByActionTimers': 10, 'offImmediately': 4, 'cycleImmediately': 5, 'onImmediately': 3, 'onThenOffByActionTimers': 9.
                                                 slaveOutletAction02 1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.3 integer read-write
Set to control the outlet perform action as requested. Enumeration: 'none': 1, 'cancelAction': 2, 'cycleByActionTimer': 8, 'offByActionTimer': 7, 'onByActionTimer': 6, 'offThenOnByActionTimers': 10, 'offImmediately': 4, 'cycleImmediately': 5, 'onImmediately': 3, 'onThenOffByActionTimers': 9.
                                                 slaveOutletAction03 1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.4 integer read-write
Set to control the outlet perform action as requested. Enumeration: 'none': 1, 'cancelAction': 2, 'cycleByActionTimer': 8, 'offByActionTimer': 7, 'onByActionTimer': 6, 'offThenOnByActionTimers': 10, 'offImmediately': 4, 'cycleImmediately': 5, 'onImmediately': 3, 'onThenOffByActionTimers': 9.
                                                 slaveOutletAction04 1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.5 integer read-write
Set to control the outlet perform action as requested. Enumeration: 'none': 1, 'cancelAction': 2, 'cycleByActionTimer': 8, 'offByActionTimer': 7, 'onByActionTimer': 6, 'offThenOnByActionTimers': 10, 'offImmediately': 4, 'cycleImmediately': 5, 'onImmediately': 3, 'onThenOffByActionTimers': 9.
                                                 slaveOutletAction05 1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.6 integer read-write
Set to control the outlet perform action as requested. Enumeration: 'none': 1, 'cancelAction': 2, 'cycleByActionTimer': 8, 'offByActionTimer': 7, 'onByActionTimer': 6, 'offThenOnByActionTimers': 10, 'offImmediately': 4, 'cycleImmediately': 5, 'onImmediately': 3, 'onThenOffByActionTimers': 9.
                                                 slaveOutletAction06 1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.7 integer read-write
Set to control the outlet perform action as requested. Enumeration: 'none': 1, 'cancelAction': 2, 'cycleByActionTimer': 8, 'offByActionTimer': 7, 'onByActionTimer': 6, 'offThenOnByActionTimers': 10, 'offImmediately': 4, 'cycleImmediately': 5, 'onImmediately': 3, 'onThenOffByActionTimers': 9.
                                                 slaveOutletAction07 1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.8 integer read-write
Set to control the outlet perform action as requested. Enumeration: 'none': 1, 'cancelAction': 2, 'cycleByActionTimer': 8, 'offByActionTimer': 7, 'onByActionTimer': 6, 'offThenOnByActionTimers': 10, 'offImmediately': 4, 'cycleImmediately': 5, 'onImmediately': 3, 'onThenOffByActionTimers': 9.
                                                 slaveOutletAction08 1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.9 integer read-write
Set to control the outlet perform action as requested. Enumeration: 'none': 1, 'cancelAction': 2, 'cycleByActionTimer': 8, 'offByActionTimer': 7, 'onByActionTimer': 6, 'offThenOnByActionTimers': 10, 'offImmediately': 4, 'cycleImmediately': 5, 'onImmediately': 3, 'onThenOffByActionTimers': 9.
                                                 slaveOutletAction09 1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.10 integer read-write
Set to control the outlet perform action as requested. Enumeration: 'none': 1, 'cancelAction': 2, 'cycleByActionTimer': 8, 'offByActionTimer': 7, 'onByActionTimer': 6, 'offThenOnByActionTimers': 10, 'offImmediately': 4, 'cycleImmediately': 5, 'onImmediately': 3, 'onThenOffByActionTimers': 9.
                                                 slaveOutletAction10 1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.11 integer read-write
Set to control the outlet perform action as requested. Enumeration: 'none': 1, 'cancelAction': 2, 'cycleByActionTimer': 8, 'offByActionTimer': 7, 'onByActionTimer': 6, 'offThenOnByActionTimers': 10, 'offImmediately': 4, 'cycleImmediately': 5, 'onImmediately': 3, 'onThenOffByActionTimers': 9.
                                                 slaveOutletAction11 1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.12 integer read-write
Set to control the outlet perform action as requested. Enumeration: 'none': 1, 'cancelAction': 2, 'cycleByActionTimer': 8, 'offByActionTimer': 7, 'onByActionTimer': 6, 'offThenOnByActionTimers': 10, 'offImmediately': 4, 'cycleImmediately': 5, 'onImmediately': 3, 'onThenOffByActionTimers': 9.
                                                 slaveOutletAction12 1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.13 integer read-write
Set to control the outlet perform action as requested. Enumeration: 'none': 1, 'cancelAction': 2, 'cycleByActionTimer': 8, 'offByActionTimer': 7, 'onByActionTimer': 6, 'offThenOnByActionTimers': 10, 'offImmediately': 4, 'cycleImmediately': 5, 'onImmediately': 3, 'onThenOffByActionTimers': 9.
                             ipduEnv 1.3.6.1.4.1.4555.1.1.20.1.5
                                 ipduEnvEmd 1.3.6.1.4.1.4555.1.1.20.1.5.1
                                     ipduEnvEmdStatus 1.3.6.1.4.1.4555.1.1.20.1.5.1.1
                                         ipduEnvEmdStatusEmdType 1.3.6.1.4.1.4555.1.1.20.1.5.1.1.1 integer read-only
EMD Type. Enumeration: 'disabled': 2, 'unknown': 1, 'eMD-T': 4, 'eMD-HT': 3.
                                         ipduEnvEmdStatusTemperature 1.3.6.1.4.1.4555.1.1.20.1.5.1.1.2 integer read-only
EMD Temperature in 0.1 degree C.
                                         ipduEnvEmdStatusHumidity 1.3.6.1.4.1.4555.1.1.20.1.5.1.1.3 integer read-only
EMD Humidity in 0.1%.
                                         ipduEnvEmdStatusAlarm1 1.3.6.1.4.1.4555.1.1.20.1.5.1.1.4 integer read-only
EMD Alarm-1 state. Enumeration: 'disabled': 2, 'unknown': 1, 'alarm': 3, 'normal': 4.
                                         ipduEnvEmdStatusAlarm2 1.3.6.1.4.1.4555.1.1.20.1.5.1.1.5 integer read-only
EMD Alarm-2 state. Enumeration: 'disabled': 2, 'unknown': 1, 'alarm': 3, 'normal': 4.
                                     ipduEnvEmdConfig 1.3.6.1.4.1.4555.1.1.20.1.5.1.2
                                         ipduEnvEmdConfigEmdPresence 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.1 integer read-write
Configure the EMD presence by auto-detect or not exist (disabled). Enumeration: 'disabled': 1, 'autoDetect': 2.
                                         ipduEnvEmdConfigEmdName 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.2 displaystring read-write
The name of Emd.
                                         ipduEnvEmdConfigTemp 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.3
                                             ipduEnvEmdConfigTempName 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.3.1 displaystring read-write
The name of EMD Temperature sensor.
                                             ipduEnvEmdConfigTempHighSetPoint 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.3.2 integer read-write
EMD Temperature set point high, alarm will active when temperature over this value, in degree C.
                                             ipduEnvEmdConfigTempHighStatus 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.3.3 integer read-write
Enabled/disabled the high setpoint be applied or not Enumeration: 'disabled': 2, 'enabled': 1.
                                             ipduEnvEmdConfigTempLowSetPoint 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.3.4 integer read-write
EMD Temperature set point high, alarm will active when temperature under this value, in degree C.
                                             ipduEnvEmdConfigTempLowStatus 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.3.5 integer read-write
Enabled/disabled the low setpoint be applied or not Enumeration: 'disabled': 2, 'enabled': 1.
                                             ipduEnvEmdConfigTempOffset 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.3.6 integer read-write
Offset of temperature in degree C to adjust EMD temperature measurement. Enumeration: 't3p0': 7, 't-3p0': 13, 't0p0': 1, 't-2p5': 12, 't-2p0': 11, 't0p5': 2, 't1p0': 3, 't-1p5': 10, 't1p5': 4, 't-1p0': 9, 't2p0': 5, 't-0p5': 8, 't2p5': 6.
                                         ipduEnvEmdConfigHumi 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.4
                                             ipduEnvEmdConfigHumiName 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.4.1 displaystring read-write
The name of EMD Humidity.
                                             ipduEnvEmdConfigHumiHighSetPoint 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.4.2 integer read-write
EMD humidity set point high, alarm will active when humidity over this value, in %.
                                             ipduEnvEmdConfigHumiHighStatus 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.4.3 integer read-write
Enabled/disabled the high setpoint be applied or not Enumeration: 'disabled': 2, 'enabled': 1.
                                             ipduEnvEmdConfigHumiLowSetPoint 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.4.4 integer read-write
EMD humidity set point low, alarm will active when humidity under this value, in %.
                                             ipduEnvEmdConfigHumiLowStatus 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.4.5 integer read-write
Enabled/disabled the high setpoint be applied or not Enumeration: 'disabled': 2, 'enabled': 1.
                                             ipduEnvEmdConfigHumiOffset 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.4.6 integer read-write
Emd Hum Offset; Enumeration: 'h-4p0': 11, 'h3p0': 4, 'h4p0': 5, 'h-3p0': 10, 'h0p0': 1, 'h-2p0': 9, 'h5p0': 6, 'h-6p0': 13, 'h1p0': 2, 'h6p0': 7, 'h-1p0': 8, 'h2p0': 3, 'h-5p0': 12.
                                         ipduEnvEmdConfigAlarm1 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.5
                                             ipduEnvEmdConfigAlarm1Name 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.5.1 displaystring read-write
The name of EMD Alarm-1.
                                             ipduEnvEmdConfigAlarm1Type 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.5.2 integer read-write
EMD Alarm-1 type Enumeration: 'disabled': 1, 'normalClose': 3, 'normalOpen': 2.
                                         ipduEnvEmdConfigAlarm2 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.6
                                             ipduEnvEmdConfigAlarm2Name 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.6.1 displaystring read-write
The name of EMD Alarm-2.
                                             ipduEnvEmdConfigAlarm2Type 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.6.2 integer read-write
EMD Alarm-2 type Enumeration: 'disabled': 1, 'normalClose': 3, 'normalOpen': 2.
                         ipduTraps 1.3.6.1.4.1.4555.1.1.20.2
                               ipduInletVoltageTooHigh 1.3.6.1.4.1.4555.1.1.20.20.1
CRITICAL: The input voltage over high threshold.
                               ipduInletVoltageNotTooHigh 1.3.6.1.4.1.4555.1.1.20.20.2
WARNING: The input voltage return from over high threshold.
                               ipduInletVoltageTooLow 1.3.6.1.4.1.4555.1.1.20.20.3
CRITICAL: The input voltage under low threshold.
                               ipduInletVoltageNotTooLow 1.3.6.1.4.1.4555.1.1.20.20.4
WARNING: The input voltage return from under low threshold.
                               ipduInletCurrentTooHigh 1.3.6.1.4.1.4555.1.1.20.20.5
CRITICAL: The input current over high threshold.
                               ipduInletCurrentNotTooHigh 1.3.6.1.4.1.4555.1.1.20.20.6
WARNING: The input current return from over high threshold.
                               ipduInletFrequencyTooHigh 1.3.6.1.4.1.4555.1.1.20.20.7
CRITICAL: The input frequency over high threshold.
                               ipduInletFrequencyNotTooHigh 1.3.6.1.4.1.4555.1.1.20.20.8
WARNING: The input frequency return from over high threshold.
                               ipduInletFrequencyTooLow 1.3.6.1.4.1.4555.1.1.20.20.9
CRITICAL: The input frequency under low threshold.
                               ipduInletFrequencyNotTooLow 1.3.6.1.4.1.4555.1.1.20.20.10
WARNING: The input frequency return from under low threshold.
                               ipduInlet2VoltageTooHigh 1.3.6.1.4.1.4555.1.1.20.20.11
CRITICAL: The input2 voltage over high threshold.
                               ipduInlet2VoltageNotTooHigh 1.3.6.1.4.1.4555.1.1.20.20.12
WARNING: The input2 voltage return from over high threshold.
                               ipduInlet2VoltageTooLow 1.3.6.1.4.1.4555.1.1.20.20.13
CRITICAL: The input2 voltage under low threshold.
                               ipduInlet2VoltageNotTooLow 1.3.6.1.4.1.4555.1.1.20.20.14
WARNING: The input2 voltage return from under low threshold.
                               ipduInlet2CurrentTooHigh 1.3.6.1.4.1.4555.1.1.20.20.15
CRITICAL: The input2 current over high threshold.
                               ipduInlet2CurrentNotTooHigh 1.3.6.1.4.1.4555.1.1.20.20.16
WARNING: The input2 current return from over high threshold.
                               ipduInlet2FrequencyTooHigh 1.3.6.1.4.1.4555.1.1.20.20.17
CRITICAL: The input2 frequency over high threshold.
                               ipduInlet2FrequencyNotTooHigh 1.3.6.1.4.1.4555.1.1.20.20.18
WARNING: The input2 frequency return from over high threshold.
                               ipduInlet2FrequencyTooLow 1.3.6.1.4.1.4555.1.1.20.20.19
CRITICAL: The input2 frequency under low threshold.
                               ipduInlet2FrequencyNotTooLow 1.3.6.1.4.1.4555.1.1.20.20.20
WARNING: The input2 frequency return from under low threshold.
                               ipduOutletCurrentTooHigh 1.3.6.1.4.1.4555.1.1.20.20.21
CRITICAL: The output current of outlet over high threshold.
                               ipduOutletCurrentNotTooHigh 1.3.6.1.4.1.4555.1.1.20.20.22
WARNING: The output current of outlet return from over high threshold.
                               ipduOutletStateChanged 1.3.6.1.4.1.4555.1.1.20.20.23
INFORMATION: The outlet state had changed from on to off, or from off to on.
                               ipduEmdTemperatureNotHigh 1.3.6.1.4.1.4555.1.1.20.20.24
INFORMATION: emd Temperature Not High.
                               ipduEmdTemperatureTooHigh 1.3.6.1.4.1.4555.1.1.20.20.25
WARNING: emd Temperature Too High.
                               ipduEmdTemperatureNotLow 1.3.6.1.4.1.4555.1.1.20.20.26
INFORMATION: emd Temperature Not Low.
                               ipduEmdTemperatureTooLow 1.3.6.1.4.1.4555.1.1.20.20.27
WARNING: emd Temperature Too Low.
                               ipduEmdHumidityNotHigh 1.3.6.1.4.1.4555.1.1.20.20.28
INFORMATION: emd Humidity Not High.
                               ipduEmdHumidityTooHigh 1.3.6.1.4.1.4555.1.1.20.20.29
WARNING: emd Humidity Too High.
                               ipduEmdHumidityNotLow 1.3.6.1.4.1.4555.1.1.20.20.30
INFORMATION: emd Humidity Not Low.
                               ipduEmdHumidityTooLow 1.3.6.1.4.1.4555.1.1.20.20.31
WARNING: emd Humidity Too Low.
                               ipduEmdAlarm1Normal 1.3.6.1.4.1.4555.1.1.20.20.32
INFORMATION: emd Alarm1 Normal.
                               ipduEmdAlarm1Active 1.3.6.1.4.1.4555.1.1.20.20.33
WARNING: emd Alarm1 Active.
                               ipduEmdAlarm2Normal 1.3.6.1.4.1.4555.1.1.20.20.34
INFORMATION: emd Alarm2 Normal.
                               ipduEmdAlarm2Active 1.3.6.1.4.1.4555.1.1.20.20.35
WARNING: emd Alarm2 Active.
                               ipduSlave01Inlet01OverHigh 1.3.6.1.4.1.4555.1.1.20.20.36
CRITICAL: The Slave01 input01 voltage over high threshold.
                               ipduSlave01Inlet01NotOverHigh 1.3.6.1.4.1.4555.1.1.20.20.37
CRITICAL: The Slave01 input01 voltage Not over high threshold.
                               ipduSlave01Inlet02OverHigh 1.3.6.1.4.1.4555.1.1.20.20.38
CRITICAL: The Slave01 input02 voltage over high threshold.
                               ipduSlave01Inlet02NotOverHigh 1.3.6.1.4.1.4555.1.1.20.20.39
CRITICAL: The Slave01 input02 voltage Not over high threshold.
                               ipduSlave01Inlet01UnderLow 1.3.6.1.4.1.4555.1.1.20.20.40
CRITICAL: The Slave01 input01 voltage under low threshold.
                               ipduSlave01Inlet01NotUnderLow 1.3.6.1.4.1.4555.1.1.20.20.41
CRITICAL: The Slave01 input01 voltage Not under low threshold.
                               ipduSlave01Inlet02UnderLow 1.3.6.1.4.1.4555.1.1.20.20.42
CRITICAL: The Slave01 input02 voltage under low threshold.
                               ipduSlave01Inlet02NotUnderLow 1.3.6.1.4.1.4555.1.1.20.20.43
CRITICAL: The Slave01 input02 voltage Not under low threshold.
                               ipduSlave01Inlet01CurrentOverTh 1.3.6.1.4.1.4555.1.1.20.20.44
CRITICAL: The Slave01 input01 current over high threshold.
                               ipduSlave01Inlet01NotCurrentOverTh 1.3.6.1.4.1.4555.1.1.20.20.45
CRITICAL: The Slave01 input01 current not over high threshold.
                               ipduSlave01Inlet02CurrentOverTh 1.3.6.1.4.1.4555.1.1.20.20.46
CRITICAL: The Slave01 input02 current over high threshold.
                               ipduSlave01Inlet02NotCurrentOverTh 1.3.6.1.4.1.4555.1.1.20.20.47
CRITICAL: The Slave01 input02 current not over high threshold.
                               ipduSlave01EmdTemperatureNotHigh 1.3.6.1.4.1.4555.1.1.20.20.48
INFORMATION: The Slave01 emd Temperature Not High.
                               ipduSlave01EmdTemperatureTooHigh 1.3.6.1.4.1.4555.1.1.20.20.49
WARNING: The Slave01 emd Temperature Too High.
                               ipduSlave01EmdTemperatureNotLow 1.3.6.1.4.1.4555.1.1.20.20.50
INFORMATION: The Slave01 emd Temperature Not Low.
                               ipduSlave01EmdTemperatureTooLow 1.3.6.1.4.1.4555.1.1.20.20.51
WARNING: The Slave01 emd Temperature Too Low.
                               ipduSlave01EmdHumidityNotHigh 1.3.6.1.4.1.4555.1.1.20.20.52
INFORMATION: The Slave01 emd Humidity Not High.
                               ipduSlave01EmdHumidityTooHigh 1.3.6.1.4.1.4555.1.1.20.20.53
WARNING: The Slave01 emd Humidity Too High.
                               ipduSlave01EmdHumidityNotLow 1.3.6.1.4.1.4555.1.1.20.20.54
INFORMATION: The Slave01 emd Humidity Not Low.
                               ipduSlave01EmdHumidityTooLow 1.3.6.1.4.1.4555.1.1.20.20.55
WARNING: The Slave01 emd Humidity Too Low.
                               ipduSlave01EmdAlarm1Normal 1.3.6.1.4.1.4555.1.1.20.20.56
INFORMATION: The Slave01 emd Alarm1 Normal.
                               ipduSlave01EmdAlarm1Active 1.3.6.1.4.1.4555.1.1.20.20.57
WARNING: The Slave01 emd Alarm1 Active.
                               ipduSlave01EmdAlarm2Normal 1.3.6.1.4.1.4555.1.1.20.20.58
INFORMATION: The Slave01 emd Alarm2 Normal.
                               ipduSlave01EmdAlarm2Active 1.3.6.1.4.1.4555.1.1.20.20.59
WARNING: The Slave01 emd Alarm2 Active.
                               ipduSlave01OutletCurrentOverTh 1.3.6.1.4.1.4555.1.1.20.20.60
WARNING: The Slave01 Outlet Current over threshold.
                               ipduSlave02Inlet01OverHigh 1.3.6.1.4.1.4555.1.1.20.20.61
CRITICAL: The Slave02 input01 voltage over high threshold.
                               ipduSlave02Inlet01NotOverHigh 1.3.6.1.4.1.4555.1.1.20.20.62
CRITICAL: The Slave02 input01 voltage Not over high threshold.
                               ipduSlave02Inlet02OverHigh 1.3.6.1.4.1.4555.1.1.20.20.63
CRITICAL: The Slave02 input02 voltage over high threshold.
                               ipduSlave02Inlet02NotOverHigh 1.3.6.1.4.1.4555.1.1.20.20.64
CRITICAL: The Slave02 input02 voltage Not over high threshold.
                               ipduSlave02Inlet01UnderLow 1.3.6.1.4.1.4555.1.1.20.20.65
CRITICAL: The Slave02 input01 voltage under low threshold.
                               ipduSlave02Inlet01NotUnderLow 1.3.6.1.4.1.4555.1.1.20.20.66
CRITICAL: The Slave02 input01 voltage Not under low threshold.
                               ipduSlave02Inlet02UnderLow 1.3.6.1.4.1.4555.1.1.20.20.67
CRITICAL: The Slave02 input02 voltage under low threshold.
                               ipduSlave02Inlet02NotUnderLow 1.3.6.1.4.1.4555.1.1.20.20.68
CRITICAL: The Slave02 input02 voltage Not under low threshold.
                               ipduSlave02Inlet01CurrentOverTh 1.3.6.1.4.1.4555.1.1.20.20.69
CRITICAL: The Slave02 input01 current over high threshold.
                               ipduSlave02Inlet01NotCurrentOverTh 1.3.6.1.4.1.4555.1.1.20.20.70
CRITICAL: The Slave02 input01 current not over high threshold.
                               ipduSlave02Inlet02CurrentOverTh 1.3.6.1.4.1.4555.1.1.20.20.71
CRITICAL: The Slave02 input02 current over high threshold.
                               ipduSlave02Inlet02NotCurrentOverTh 1.3.6.1.4.1.4555.1.1.20.20.72
CRITICAL: The Slave02 input02 current not over high threshold.
                               ipduSlave02EmdTemperatureNotHigh 1.3.6.1.4.1.4555.1.1.20.20.73
INFORMATION: The Slave02 emd Temperature Not High.
                               ipduSlave02EmdTemperatureTooHigh 1.3.6.1.4.1.4555.1.1.20.20.74
WARNING: The Slave02 emd Temperature Too High.
                               ipduSlave02EmdTemperatureNotLow 1.3.6.1.4.1.4555.1.1.20.20.75
INFORMATION: The Slave02 emd Temperature Not Low.
                               ipduSlave02EmdTemperatureTooLow 1.3.6.1.4.1.4555.1.1.20.20.76
WARNING: The Slave02 emd Temperature Too Low.
                               ipduSlave02EmdHumidityNotHigh 1.3.6.1.4.1.4555.1.1.20.20.77
INFORMATION: The Slave02 emd Humidity Not High.
                               ipduSlave02EmdHumidityTooHigh 1.3.6.1.4.1.4555.1.1.20.20.78
WARNING: The Slave02 emd Humidity Too High.
                               ipduSlave02EmdHumidityNotLow 1.3.6.1.4.1.4555.1.1.20.20.79
INFORMATION: The Slave02 emd Humidity Not Low.
                               ipduSlave02EmdHumidityTooLow 1.3.6.1.4.1.4555.1.1.20.20.80
WARNING: The Slave02 emd Humidity Too Low.
                               ipduSlave02EmdAlarm1Normal 1.3.6.1.4.1.4555.1.1.20.20.81
INFORMATION: The Slave02 emd Alarm1 Normal.
                               ipduSlave02EmdAlarm1Active 1.3.6.1.4.1.4555.1.1.20.20.82
WARNING: The Slave02 emd Alarm1 Active.
                               ipduSlave02EmdAlarm2Normal 1.3.6.1.4.1.4555.1.1.20.20.83
INFORMATION: The Slave02 emd Alarm2 Normal.
                               ipduSlave02EmdAlarm2Active 1.3.6.1.4.1.4555.1.1.20.20.84
WARNING: The Slave02 emd Alarm2 Active.
                               ipduSlave02OutletCurrentOverTh 1.3.6.1.4.1.4555.1.1.20.20.85
WARNING: The Slave02 Outlet Current over threshold.
                               ipduSlave03Inlet01OverHigh 1.3.6.1.4.1.4555.1.1.20.20.86
CRITICAL: The Slave03 input01 voltage over high threshold.
                               ipduSlave03Inlet01NotOverHigh 1.3.6.1.4.1.4555.1.1.20.20.87
CRITICAL: The Slave03 input01 voltage Not over high threshold.
                               ipduSlave03Inlet02OverHigh 1.3.6.1.4.1.4555.1.1.20.20.88
CRITICAL: The Slave03 input02 voltage over high threshold.
                               ipduSlave03Inlet02NotOverHigh 1.3.6.1.4.1.4555.1.1.20.20.89
CRITICAL: The Slave03 input02 voltage Not over high threshold.
                               ipduSlave03Inlet01UnderLow 1.3.6.1.4.1.4555.1.1.20.20.90
CRITICAL: The Slave03 input01 voltage under low threshold.
                               ipduSlave03Inlet01NotUnderLow 1.3.6.1.4.1.4555.1.1.20.20.91
CRITICAL: The Slave03 input01 voltage Not under low threshold.
                               ipduSlave03Inlet02UnderLow 1.3.6.1.4.1.4555.1.1.20.20.92
CRITICAL: The Slave03 input02 voltage under low threshold.
                               ipduSlave03Inlet02NotUnderLow 1.3.6.1.4.1.4555.1.1.20.20.93
CRITICAL: The Slave03 input02 voltage Not under low threshold.
                               ipduSlave03Inlet01CurrentOverTh 1.3.6.1.4.1.4555.1.1.20.20.94
CRITICAL: The Slave03 input01 current over high threshold.
                               ipduSlave03Inlet01NotCurrentOverTh 1.3.6.1.4.1.4555.1.1.20.20.95
CRITICAL: The Slave03 input01 current not over high threshold.
                               ipduSlave03Inlet02CurrentOverTh 1.3.6.1.4.1.4555.1.1.20.20.96
CRITICAL: The Slave03 input02 current over high threshold.
                               ipduSlave03Inlet02NotCurrentOverTh 1.3.6.1.4.1.4555.1.1.20.20.97
CRITICAL: The Slave03 input02 current not over high threshold.
                               ipduSlave03EmdTemperatureNotHigh 1.3.6.1.4.1.4555.1.1.20.20.98
INFORMATION: The Slave03 emd Temperature Not High.
                               ipduSlave03EmdTemperatureTooHigh 1.3.6.1.4.1.4555.1.1.20.20.99
WARNING: The Slave03 emd Temperature Too High.
                               ipduSlave03EmdTemperatureNotLow 1.3.6.1.4.1.4555.1.1.20.20.100
INFORMATION: The Slave03 emd Temperature Not Low.
                               ipduSlave03EmdTemperatureTooLow 1.3.6.1.4.1.4555.1.1.20.20.101
WARNING: The Slave03 emd Temperature Too Low.
                               ipduSlave03EmdHumidityNotHigh 1.3.6.1.4.1.4555.1.1.20.20.102
INFORMATION: The Slave03 emd Humidity Not High.
                               ipduSlave03EmdHumidityTooHigh 1.3.6.1.4.1.4555.1.1.20.20.103
WARNING: The Slave03 emd Humidity Too High.
                               ipduSlave03EmdHumidityNotLow 1.3.6.1.4.1.4555.1.1.20.20.104
INFORMATION: The Slave03 emd Humidity Not Low.
                               ipduSlave03EmdHumidityTooLow 1.3.6.1.4.1.4555.1.1.20.20.105
WARNING: The Slave03 emd Humidity Too Low.
                               ipduSlave03EmdAlarm1Normal 1.3.6.1.4.1.4555.1.1.20.20.106
INFORMATION: The Slave03 emd Alarm1 Normal.
                               ipduSlave03EmdAlarm1Active 1.3.6.1.4.1.4555.1.1.20.20.107
WARNING: The Slave03 emd Alarm1 Active.
                               ipduSlave03EmdAlarm2Normal 1.3.6.1.4.1.4555.1.1.20.20.108
INFORMATION: The Slave03 emd Alarm2 Normal.
                               ipduSlave03EmdAlarm2Active 1.3.6.1.4.1.4555.1.1.20.20.109
WARNING: The Slave03 emd Alarm2 Active.
                               ipduSlave03OutletCurrentOverTh 1.3.6.1.4.1.4555.1.1.20.20.110
WARNING: The Slave03 Outlet Current over threshold.
                               ipduSlave04Inlet01OverHigh 1.3.6.1.4.1.4555.1.1.20.20.111
CRITICAL: The Slave04 input01 voltage over high threshold.
                               ipduSlave04Inlet01NotOverHigh 1.3.6.1.4.1.4555.1.1.20.20.112
CRITICAL: The Slave04 input01 voltage Not over high threshold.
                               ipduSlave04Inlet02OverHigh 1.3.6.1.4.1.4555.1.1.20.20.113
CRITICAL: The Slave04 input02 voltage over high threshold.
                               ipduSlave04Inlet02NotOverHigh 1.3.6.1.4.1.4555.1.1.20.20.114
CRITICAL: The Slave04 input02 voltage Not over high threshold.
                               ipduSlave04Inlet01UnderLow 1.3.6.1.4.1.4555.1.1.20.20.115
CRITICAL: The Slave04 input01 voltage under low threshold.
                               ipduSlave04Inlet01NotUnderLow 1.3.6.1.4.1.4555.1.1.20.20.116
CRITICAL: The Slave04 input01 voltage Not under low threshold.
                               ipduSlave04Inlet02UnderLow 1.3.6.1.4.1.4555.1.1.20.20.117
CRITICAL: The Slave04 input02 voltage under low threshold.
                               ipduSlave04Inlet02NotUnderLow 1.3.6.1.4.1.4555.1.1.20.20.118
CRITICAL: The Slave04 input02 voltage Not under low threshold.
                               ipduSlave04Inlet01CurrentOverTh 1.3.6.1.4.1.4555.1.1.20.20.119
CRITICAL: The Slave04 input01 current over high threshold.
                               ipduSlave04Inlet01NotCurrentOverTh 1.3.6.1.4.1.4555.1.1.20.20.120
CRITICAL: The Slave04 input01 current not over high threshold.
                               ipduSlave04Inlet02CurrentOverTh 1.3.6.1.4.1.4555.1.1.20.20.121
CRITICAL: The Slave04 input02 current over high threshold.
                               ipduSlave04Inlet02NotCurrentOverTh 1.3.6.1.4.1.4555.1.1.20.20.122
CRITICAL: The Slave04 input02 current not over high threshold.
                               ipduSlave04EmdTemperatureNotHigh 1.3.6.1.4.1.4555.1.1.20.20.123
INFORMATION: The Slave04 emd Temperature Not High.
                               ipduSlave04EmdTemperatureTooHigh 1.3.6.1.4.1.4555.1.1.20.20.124
WARNING: The Slave04 emd Temperature Too High.
                               ipduSlave04EmdTemperatureNotLow 1.3.6.1.4.1.4555.1.1.20.20.125
INFORMATION: The Slave04 emd Temperature Not Low.
                               ipduSlave04EmdTemperatureTooLow 1.3.6.1.4.1.4555.1.1.20.20.126
WARNING: The Slave04 emd Temperature Too Low.
                               ipduSlave04EmdHumidityNotHigh 1.3.6.1.4.1.4555.1.1.20.20.127
INFORMATION: The Slave04 emd Humidity Not High.
                               ipduSlave04EmdHumidityTooHigh 1.3.6.1.4.1.4555.1.1.20.20.128
WARNING: The Slave04 emd Humidity Too High.
                               ipduSlave04EmdHumidityNotLow 1.3.6.1.4.1.4555.1.1.20.20.129
INFORMATION: The Slave04 emd Humidity Not Low.
                               ipduSlave04EmdHumidityTooLow 1.3.6.1.4.1.4555.1.1.20.20.130
WARNING: The Slave04 emd Humidity Too Low.
                               ipduSlave04EmdAlarm1Normal 1.3.6.1.4.1.4555.1.1.20.20.131
INFORMATION: The Slave04 emd Alarm1 Normal.
                               ipduSlave04EmdAlarm1Active 1.3.6.1.4.1.4555.1.1.20.20.132
WARNING: The Slave04 emd Alarm1 Active.
                               ipduSlave04EmdAlarm2Normal 1.3.6.1.4.1.4555.1.1.20.20.133
INFORMATION: The Slave04 emd Alarm2 Normal.
                               ipduSlave04EmdAlarm2Active 1.3.6.1.4.1.4555.1.1.20.20.134
WARNING: The Slave04 emd Alarm2 Active.
                               ipduSlave04OutletCurrentOverTh 1.3.6.1.4.1.4555.1.1.20.20.135
WARNING: The Slave04 Outlet Current over threshold.
                               ipduSlave05Inlet01OverHigh 1.3.6.1.4.1.4555.1.1.20.20.136
CRITICAL: The Slave05 input01 voltage over high threshold.
                               ipduSlave05Inlet01NotOverHigh 1.3.6.1.4.1.4555.1.1.20.20.137
CRITICAL: The Slave05 input01 voltage Not over high threshold.
                               ipduSlave05Inlet02OverHigh 1.3.6.1.4.1.4555.1.1.20.20.138
CRITICAL: The Slave05 input02 voltage over high threshold.
                               ipduSlave05Inlet02NotOverHigh 1.3.6.1.4.1.4555.1.1.20.20.139
CRITICAL: The Slave05 input02 voltage Not over high threshold.
                               ipduSlave05Inlet01UnderLow 1.3.6.1.4.1.4555.1.1.20.20.140
CRITICAL: The Slave05 input01 voltage under low threshold.
                               ipduSlave05Inlet01NotUnderLow 1.3.6.1.4.1.4555.1.1.20.20.141
CRITICAL: The Slave05 input01 voltage Not under low threshold.
                               ipduSlave05Inlet02UnderLow 1.3.6.1.4.1.4555.1.1.20.20.142
CRITICAL: The Slave05 input02 voltage under low threshold.
                               ipduSlave05Inlet02NotUnderLow 1.3.6.1.4.1.4555.1.1.20.20.143
CRITICAL: The Slave05 input02 voltage Not under low threshold.
                               ipduSlave05Inlet01CurrentOverTh 1.3.6.1.4.1.4555.1.1.20.20.144
CRITICAL: The Slave05 input01 current over high threshold.
                               ipduSlave05Inlet01NotCurrentOverTh 1.3.6.1.4.1.4555.1.1.20.20.145
CRITICAL: The Slave05 input01 current not over high threshold.
                               ipduSlave05Inlet02CurrentOverTh 1.3.6.1.4.1.4555.1.1.20.20.146
CRITICAL: The Slave05 input02 current over high threshold.
                               ipduSlave05Inlet02NotCurrentOverTh 1.3.6.1.4.1.4555.1.1.20.20.147
CRITICAL: The Slave05 input02 current not over high threshold.
                               ipduSlave05EmdTemperatureNotHigh 1.3.6.1.4.1.4555.1.1.20.20.148
INFORMATION: The Slave05 emd Temperature Not High.
                               ipduSlave05EmdTemperatureTooHigh 1.3.6.1.4.1.4555.1.1.20.20.149
WARNING: The Slave05 emd Temperature Too High.
                               ipduSlave05EmdTemperatureNotLow 1.3.6.1.4.1.4555.1.1.20.20.150
INFORMATION: The Slave05 emd Temperature Not Low.
                               ipduSlave05EmdTemperatureTooLow 1.3.6.1.4.1.4555.1.1.20.20.151
WARNING: The Slave05 emd Temperature Too Low.
                               ipduSlave05EmdHumidityNotHigh 1.3.6.1.4.1.4555.1.1.20.20.152
INFORMATION: The Slave05 emd Humidity Not High.
                               ipduSlave05EmdHumidityTooHigh 1.3.6.1.4.1.4555.1.1.20.20.153
WARNING: The Slave05 emd Humidity Too High.
                               ipduSlave05EmdHumidityNotLow 1.3.6.1.4.1.4555.1.1.20.20.154
INFORMATION: The Slave05 emd Humidity Not Low.
                               ipduSlave05EmdHumidityTooLow 1.3.6.1.4.1.4555.1.1.20.20.155
WARNING: The Slave05 emd Humidity Too Low.
                               ipduSlave05EmdAlarm1Normal 1.3.6.1.4.1.4555.1.1.20.20.156
INFORMATION: The Slave05 emd Alarm1 Normal.
                               ipduSlave05EmdAlarm1Active 1.3.6.1.4.1.4555.1.1.20.20.157
WARNING: The Slave05 emd Alarm1 Active.
                               ipduSlave05EmdAlarm2Normal 1.3.6.1.4.1.4555.1.1.20.20.158
INFORMATION: The Slave05 emd Alarm2 Normal.
                               ipduSlave05EmdAlarm2Active 1.3.6.1.4.1.4555.1.1.20.20.159
WARNING: The Slave05 emd Alarm2 Active.
                               ipduSlave05OutletCurrentOverTh 1.3.6.1.4.1.4555.1.1.20.20.160
WARNING: The Slave05 Outlet Current over threshold.