Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 socomecSicon 1.3.6.1.4.1.4555
           software 1.3.6.1.4.1.4555.1
               network 1.3.6.1.4.1.4555.1.1
                   netvision 1.3.6.1.4.1.4555.1.1.1
                       upsObjects 1.3.6.1.4.1.4555.1.1.1.1
                           upsIdent 1.3.6.1.4.1.4555.1.1.1.1.1
                               upsIdentModel 1.3.6.1.4.1.4555.1.1.1.1.1.1 displaystring read-only
The UPS Model designation.
                               upsIdentUPSFirmwareVersion 1.3.6.1.4.1.4555.1.1.1.1.1.2 displaystring read-only
The UPS firmware version.
                               upsIdentAgentSoftwareVersion 1.3.6.1.4.1.4555.1.1.1.1.1.3 displaystring read-only
The UPS Net Vision software version.
                               upsIdentUpsSerialNumber 1.3.6.1.4.1.4555.1.1.1.1.1.4 displaystring read-only
The UPS serial no.
                           upsBattery 1.3.6.1.4.1.4555.1.1.1.1.2
                               upsBatteryStatus 1.3.6.1.4.1.4555.1.1.1.1.2.1 integer read-only
The present battery status Enumeration: 'unknown': 1, 'upsOff': 7, 'batteryDepleted': 4, 'batteryFailure': 6, 'batteryNormal': 2, 'batteryLow': 3, 'batteryDischarging': 5.
                               upsSecondsOnBattery 1.3.6.1.4.1.4555.1.1.1.1.2.2 integer read-only
If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. -1 shall be returned if the unit is not on battery power.
                               upsEstimatedMinutesRemaining 1.3.6.1.4.1.4555.1.1.1.1.2.3 integer read-only
An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.
                               upsEstimatedChargeRemaining 1.3.6.1.4.1.4555.1.1.1.1.2.4 integer read-only
An estimate of the battery charge remaining expressed as a percent of full charge.
                               upsBatteryVoltage 1.3.6.1.4.1.4555.1.1.1.1.2.5 integer read-only
The magnitude of the present battery voltage in 0.1 Volt DC.
                               upsBatteryTemperature 1.3.6.1.4.1.4555.1.1.1.1.2.6 integer read-only
The ambient temperature at or near the UPS Battery casing.
                           upsInput 1.3.6.1.4.1.4555.1.1.1.1.3
                               upsInputNumLines 1.3.6.1.4.1.4555.1.1.1.1.3.1 integer read-only
The number of input lines utilized in this device. This variable indicates the number of rows in the input table.
                               upsInputFrequency 1.3.6.1.4.1.4555.1.1.1.1.3.2 integer read-only
The current input frequency to the UPS system in 0.1 HZ.
                               upsInputTable 1.3.6.1.4.1.4555.1.1.1.1.3.3 no-access
A list of input table entries. The number of entries is given by the value of upsInputNumLines.
                                   upsInputEntry 1.3.6.1.4.1.4555.1.1.1.1.3.3.1 no-access
An entry containing information applicable to a particular input line.
                                       upsInputLineIndex 1.3.6.1.4.1.4555.1.1.1.1.3.3.1.1 integer read-only
                                       upsInputVoltage 1.3.6.1.4.1.4555.1.1.1.1.3.3.1.2 integer read-only
The input utility line voltage in 0.1 volts.
                                       upsInputCurrent 1.3.6.1.4.1.4555.1.1.1.1.3.3.1.3 integer read-only
The magnitude of the present input current in 0.1 A.
                                       upsInputVoltageMax 1.3.6.1.4.1.4555.1.1.1.1.3.3.1.4 integer read-only
The maximum utility line voltage in 0.1 VAC for last 1 minute.
                                       upsInputVoltageMin 1.3.6.1.4.1.4555.1.1.1.1.3.3.1.5 integer read-only
The minimum utility line voltage in 0.1 VAC for last 1 minute.
                           upsOutput 1.3.6.1.4.1.4555.1.1.1.1.4
                               upsOutputSource 1.3.6.1.4.1.4555.1.1.1.1.4.1 integer read-only
The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker. Enumeration: 'onBypass': 5, 'standby': 6, 'unknown': 1, 'upsOff': 8, 'ecoMode': 4, 'normalMode': 9, 'onMaintenanceBypass': 7, 'onMains': 3, 'onInverter': 2.
                               upsOutputFrequency 1.3.6.1.4.1.4555.1.1.1.1.4.2 integer read-only
The current output frequency of the UPS system in 0.1 of HZ.
                               upsOutputNumLines 1.3.6.1.4.1.4555.1.1.1.1.4.3 integer read-only
The number of output lines utilized in this device. This variable indicates the number of rows in the output table.
                               upsOutputTable 1.3.6.1.4.1.4555.1.1.1.1.4.4 no-access
A list of output table entries. The number of entries is given by the value of upsOutputNumLines.
                                   upsOutputEntry 1.3.6.1.4.1.4555.1.1.1.1.4.4.1 no-access
An entry containing information applicable to a particular output line.
                                       upsOutputLineIndex 1.3.6.1.4.1.4555.1.1.1.1.4.4.1.1 integer read-only
The output line identifier.
                                       upsOutputVoltage 1.3.6.1.4.1.4555.1.1.1.1.4.4.1.2 integer read-only
The output voltage of the UPS system in 0.1 volts.
                                       upsOutputCurrent 1.3.6.1.4.1.4555.1.1.1.1.4.4.1.3 integer read-only
The output current of the UPS system in 0.1 Amps.
                                       upsOutputPercentLoad 1.3.6.1.4.1.4555.1.1.1.1.4.4.1.4 integer read-only
The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.
                                       upsOutputKva 1.3.6.1.4.1.4555.1.1.1.1.4.4.1.5 integer read-only
Output KVA.
                           upsBypass 1.3.6.1.4.1.4555.1.1.1.1.5
                               upsBypassFrequency 1.3.6.1.4.1.4555.1.1.1.1.5.1 integer read-only
The present bypass frequency.
                               upsBypassNumLines 1.3.6.1.4.1.4555.1.1.1.1.5.2 integer read-only
The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.
                               upsBypassTable 1.3.6.1.4.1.4555.1.1.1.1.5.3 no-access
A list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.
                                   upsBypassEntry 1.3.6.1.4.1.4555.1.1.1.1.5.3.1 no-access
An entry containing information applicable to a particular bypass input.
                                       upsBypassLineIndex 1.3.6.1.4.1.4555.1.1.1.1.5.3.1.1 integer read-only
The bypass line identifier.
                                       upsBypassVoltage 1.3.6.1.4.1.4555.1.1.1.1.5.3.1.2 integer read-only
The present bypass voltage.
                                       upsBypassCurrent 1.3.6.1.4.1.4555.1.1.1.1.5.3.1.3 integer read-only
The present bypass current.
                           upsAlarm 1.3.6.1.4.1.4555.1.1.1.1.6
                               upsAlarmsPresent 1.3.6.1.4.1.4555.1.1.1.1.6.1 integer read-only
The present number of active alarm conditions.
                               upsAlarmTable 1.3.6.1.4.1.4555.1.1.1.1.6.2 no-access
A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with upsAlarmId equal to 1, and increments the value of upsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of upsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because upsAlarmId might have wrapped. Alarms are named by an OBJECT IDENTIFIER, upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of upsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of upsAlarmsPresent.
                                   upsAlarmEntry 1.3.6.1.4.1.4555.1.1.1.1.6.2.1 no-access
An entry containing information applicable to a particular alarm.
                                       upsAlarmId 1.3.6.1.4.1.4555.1.1.1.1.6.2.1.1 positiveinteger read-only
A unique identifier for an alarm condition. This value must remain constant.
                                       upsAlarmDescr 1.3.6.1.4.1.4555.1.1.1.1.6.2.1.2 autonomoustype read-only
A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.
                                       upsAlarmTime 1.3.6.1.4.1.4555.1.1.1.1.6.2.1.3 timestamp read-only
The value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0.
                                       upsAlarmExtDes 1.3.6.1.4.1.4555.1.1.1.1.6.2.1.4 displaystring read-only
Extra description.
                               upsWellKnownAlarms 1.3.6.1.4.1.4555.1.1.1.1.6.3
                                   upsAlarmBatteryBad 1.3.6.1.4.1.4555.1.1.1.1.6.3.1 integer read-only
One or more batteries have been determined to require replacement.
                                   upsAlarmOnBattery 1.3.6.1.4.1.4555.1.1.1.1.6.3.2 integer read-only
The UPS is drawing power from the batteries.
                                   upsAlarmLowBattery 1.3.6.1.4.1.4555.1.1.1.1.6.3.3 integer read-only
The remaining battery run-time is less than or equal to upsConfigLowBattTime.
                                   upsAlarmDepletedBattery 1.3.6.1.4.1.4555.1.1.1.1.6.3.4 integer read-only
The UPS will be unable to sustain the present load when and if the utility power is lost.
                                   upsAlarmTempBad 1.3.6.1.4.1.4555.1.1.1.1.6.3.5 integer read-only
A temperature is out of tolerance.
                                   upsAlarmInputBad 1.3.6.1.4.1.4555.1.1.1.1.6.3.6 integer read-only
An input condition is out of tolerance.
                                   upsAlarmOutputBad 1.3.6.1.4.1.4555.1.1.1.1.6.3.7 integer read-only
An output condition (other than OutputOverload) is out of tolerance.
                                   upsAlarmOutputOverload 1.3.6.1.4.1.4555.1.1.1.1.6.3.8 integer read-only
The output load exceeds the UPS output capacity.
                                   upsAlarmOnBypass 1.3.6.1.4.1.4555.1.1.1.1.6.3.9 integer read-only
The Bypass is presently engaged on the UPS.
                                   upsAlarmBypassBad 1.3.6.1.4.1.4555.1.1.1.1.6.3.10 integer read-only
The Bypass is out of tolerance.
                                   upsAlarmOutputOffAsRequested 1.3.6.1.4.1.4555.1.1.1.1.6.3.11 integer read-only
The UPS has shutdown as requested, i.e., the output is off.
                                   upsAlarmUpsOffAsRequested 1.3.6.1.4.1.4555.1.1.1.1.6.3.12 integer read-only
The entire UPS has shutdown as commanded.
                                   upsAlarmChargerFailed 1.3.6.1.4.1.4555.1.1.1.1.6.3.13 integer read-only
An uncorrected problem has been detected within the UPS charger subsystem.
                                   upsAlarmUpsOutputOff 1.3.6.1.4.1.4555.1.1.1.1.6.3.14 integer read-only
The output of the UPS is in the off state.
                                   upsAlarmUpsSystemOff 1.3.6.1.4.1.4555.1.1.1.1.6.3.15 integer read-only
The UPS system is in the off state.
                                   upsAlarmFanFailure 1.3.6.1.4.1.4555.1.1.1.1.6.3.16 integer read-only
The failure of one or more fans in the UPS has been detected.
                                   upsAlarmFuseFailure 1.3.6.1.4.1.4555.1.1.1.1.6.3.17 integer read-only
The failure of one or more fuses has been detected.
                                   upsAlarmGeneralFault 1.3.6.1.4.1.4555.1.1.1.1.6.3.18 integer read-only
A general fault in the UPS has been detected.
                                   upsAlarmDiagnosticTestFailed 1.3.6.1.4.1.4555.1.1.1.1.6.3.19 integer read-only
The result of the last diagnostic test indicates a failure.
                                   upsAlarmCommunicationLost 1.3.6.1.4.1.4555.1.1.1.1.6.3.20 integer read-only
A problem has been encountered in the communications between the agent and the UPS.
                                   upsAlarmAwaitingPower 1.3.6.1.4.1.4555.1.1.1.1.6.3.21 integer read-only
The UPS output is off and the UPS is awaiting the return of input power.
                                   upsAlarmShutdownPending 1.3.6.1.4.1.4555.1.1.1.1.6.3.22 integer read-only
A upsShutdownAfterDelay countdown is underway.
                                   upsAlarmShutdownImminent 1.3.6.1.4.1.4555.1.1.1.1.6.3.23 integer read-only
The UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.
                                   upsAlarmTestInProgress 1.3.6.1.4.1.4555.1.1.1.1.6.3.24 integer read-only
A test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-TYPE macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-TYPE.
                                   upsAlarmPowerSupplyFault 1.3.6.1.4.1.4555.1.1.1.1.6.3.25 integer read-only
Digital power supply fault.
                                   upsAlarmAuxMainFail 1.3.6.1.4.1.4555.1.1.1.1.6.3.26 integer read-only
Auxiliary mains out of tolerance.
                                   upsAlarmManualBypassClose 1.3.6.1.4.1.4555.1.1.1.1.6.3.27 integer read-only
Manual By-pass closed
                                   upsAlarmShortCircuit 1.3.6.1.4.1.4555.1.1.1.1.6.3.28 integer read-only
Short Circuit on UPS output.
                                   upsAlarmBatteryChargerFailure 1.3.6.1.4.1.4555.1.1.1.1.6.3.29 integer read-only
Battery charger failure.
                                   upsAlarmInverterOverCurrent 1.3.6.1.4.1.4555.1.1.1.1.6.3.30 integer read-only
Inverter Over-current.
                                   upsAlarmInverterDistorsion 1.3.6.1.4.1.4555.1.1.1.1.6.3.31 integer read-only
Excessive Inverter Distorsion.
                                   upsAlarmPrechargeVoltageFail 1.3.6.1.4.1.4555.1.1.1.1.6.3.32 integer read-only
Precharge voltage out of tolerance.
                                   upsAlarmBoostTooLow 1.3.6.1.4.1.4555.1.1.1.1.6.3.33 integer read-only
Boost output voltage too low.
                                   upsAlarmBoostTooHigh 1.3.6.1.4.1.4555.1.1.1.1.6.3.34 integer read-only
Boost output voltage too high.
                                   upsAlarmBatteryTooHigh 1.3.6.1.4.1.4555.1.1.1.1.6.3.35 integer read-only
Battery voltage too high.
                                   upsAlarmImproperCondition 1.3.6.1.4.1.4555.1.1.1.1.6.3.36 integer read-only
Improper condition of use
                                   upsAlarmOverloadTimeout 1.3.6.1.4.1.4555.1.1.1.1.6.3.37 integer read-only
Overload timeout blocking Inverter.
                                   upsAlarmControlSystemFailure 1.3.6.1.4.1.4555.1.1.1.1.6.3.38 integer read-only
Microprocessor control system failure
                                   upsAlarmDataCorrupted 1.3.6.1.4.1.4555.1.1.1.1.6.3.39 integer read-only
Configuration data map corrupted.
                                   upsAlarmPllFault 1.3.6.1.4.1.4555.1.1.1.1.6.3.40 integer read-only
Pll fault.
                                   upsAlarmInputGeneralAlarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.41 integer read-only
Input mains general alarm.
                                   upsAlarmRectifierGeneralAlarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.42 integer read-only
Rectifier general alarm.
                                   upsAlarmBoostGeneralAlarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.43 integer read-only
Boost general alarm.
                                   upsAlarmInverterGeneralAlarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.44 integer read-only
Inverter general alarm.
                                   upsAlarmBatteryGeneralAlarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.45 integer read-only
Bettery charger general alarm.
                                   upsAlarmOutputOver 1.3.6.1.4.1.4555.1.1.1.1.6.3.46 integer read-only
Output voltage over limit.
                                   upsAlarmOutputUnder 1.3.6.1.4.1.4555.1.1.1.1.6.3.47 integer read-only
Output voltage under limit.
                                   upsAlarmBypassGeneralAlarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.48 integer read-only
Bypass charger general alarm.
                                   upsAlarmStopForOverload 1.3.6.1.4.1.4555.1.1.1.1.6.3.49 integer read-only
Stop for overload.
                                   upsAlarmImminentStop 1.3.6.1.4.1.4555.1.1.1.1.6.3.50 integer read-only
UPS imminent stop
                                   upsAlarmModule1Alarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.51 integer read-only
Module 1 in parallel general alarm.
                                   upsAlarmModule2Alarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.52 integer read-only
Module 2 in parallel general alarm.
                                   upsAlarmModule3Alarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.53 integer read-only
Module 3 in parallel general alarm.
                                   upsAlarmModule4Alarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.54 integer read-only
Module 4 in parallel general alarm.
                                   upsAlarmModule5Alarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.55 integer read-only
Module 5 in parallel general alarm.
                                   upsAlarmModule6Alarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.56 integer read-only
Module 6 in parallel general alarm.
                                   upsAlarmExternalAlarm1 1.3.6.1.4.1.4555.1.1.1.1.6.3.57 integer read-only
External Alarm 1.
                                   upsAlarmExternalAlarm2 1.3.6.1.4.1.4555.1.1.1.1.6.3.58 integer read-only
External Alarm 2.
                                   upsAlarmExternalAlarm3 1.3.6.1.4.1.4555.1.1.1.1.6.3.59 integer read-only
External Alarm 3.
                                   upsAlarmExternalAlarm4 1.3.6.1.4.1.4555.1.1.1.1.6.3.60 integer read-only
External Alarm 4.
                                   upsAlarmEService 1.3.6.1.4.1.4555.1.1.1.1.6.3.61 integer read-only
E-Service General Alarm
                                   upsAlarmRedundancyLost 1.3.6.1.4.1.4555.1.1.1.1.6.3.62 integer read-only
Redundancy lost
                                   upsAlarmPeriodicServiceCheck 1.3.6.1.4.1.4555.1.1.1.1.6.3.63 integer read-only
Periodic service check up.
                                   upsAlarmAllTransferDisabled 1.3.6.1.4.1.4555.1.1.1.1.6.3.64 integer read-only
Automatic and manual transfer disabled
                                   upsAlarmAutoTransferDisabled 1.3.6.1.4.1.4555.1.1.1.1.6.3.65 integer read-only
Automatic transfer disabled
                                   upsAlarmBatteryRoom 1.3.6.1.4.1.4555.1.1.1.1.6.3.66 integer read-only
Battery room alarm
                                   upsAlarmManualBypass 1.3.6.1.4.1.4555.1.1.1.1.6.3.67 integer read-only
Manual bypass alarm
                                   upsAlarmBatteryDischarged 1.3.6.1.4.1.4555.1.1.1.1.6.3.68 integer read-only
Battery Discharged
                                   upsAlarmInsufficientResources 1.3.6.1.4.1.4555.1.1.1.1.6.3.69 integer read-only
Insufficient resources
                                   upsAlarmOptionalBoards 1.3.6.1.4.1.4555.1.1.1.1.6.3.70 integer read-only
Optional boards general alarm
                                   upsAlarmRectifierFault 1.3.6.1.4.1.4555.1.1.1.1.6.3.71 integer read-only
Rectifier fault
                                   upsAlarmBoostFault 1.3.6.1.4.1.4555.1.1.1.1.6.3.72 integer read-only
Boost fault
                                   upsAlarmInverterFault 1.3.6.1.4.1.4555.1.1.1.1.6.3.73 integer read-only
Inverter fault
                                   upsAlarmParallelModuleFault 1.3.6.1.4.1.4555.1.1.1.1.6.3.74 integer read-only
Parallel module fault
                                   upsAlarmGenSetGeneral 1.3.6.1.4.1.4555.1.1.1.1.6.3.75 integer read-only
Gen-set general alarm
                                   upsAlarmGenSetFault 1.3.6.1.4.1.4555.1.1.1.1.6.3.76 integer read-only
Gen-set fault
                                   upsAlarmEmergencyStopActive 1.3.6.1.4.1.4555.1.1.1.1.6.3.77 integer read-only
Emergency stop active
                                   upsAlarmBatteryCircuitOpen 1.3.6.1.4.1.4555.1.1.1.1.6.3.78 integer read-only
Battery circuit open
                                   upsAlarmFansFailure 1.3.6.1.4.1.4555.1.1.1.1.6.3.79 integer read-only
Fans failure
                                   upsAlarmPhaseRotationFault 1.3.6.1.4.1.4555.1.1.1.1.6.3.80 integer read-only
Phase rotation fault
                                   upsAlarmA62 1.3.6.1.4.1.4555.1.1.1.1.6.3.81 integer read-only
A62.
                                   upsAlarmA63 1.3.6.1.4.1.4555.1.1.1.1.6.3.82 integer read-only
A63.
                           upsTest 1.3.6.1.4.1.4555.1.1.1.1.7
                               upsTestId 1.3.6.1.4.1.4555.1.1.1.1.7.1 object identifier read-write
The test named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of test, including the well known tests identified in this document as well as those introduced by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. Setting this variable initiates the named test. Sets to this variable require the presence of upsTestSpinLock in the same SNMP message. The set request will be rejected with an appropriate error message if the requested test cannot be performed, including attempts to start a test when another test is already in progress. Tests in progress may be aborted by setting this variable to upsTestAbortTestInProgress. Read operations return the value of the name of the test in progress if a test is in progress or the name of the last test performed if no test is in progress, unless no test has bee run, in which case the well known value upsTestNoTestsInitiated is returned.
                               upsTestSpinLock 1.3.6.1.4.1.4555.1.1.1.1.7.2 testandincr read-write
A spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress as follows: try_again: get (upsTestSpinLock) while (upsTestResultsSummary == inProgress) { /* loop while a test is running for another manager */ short delay get (upsTestSpinLock) } lock_value = upsTestSpinLock /* no test in progress, start the test */ set (upsTestSpinLock = lock_value, upsTestId = requested_test) if (error_index == 1) { /* (upsTestSpinLock failed) */ /* if problem is not access control, then some other manager slipped in ahead of us */ goto try_again } if (error_index == 2) { /* (upsTestId) */ /* cannot perform the test */ give up } /* test started ok */ /* wait for test completion by polling upsTestResultsSummary */ get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) while (upsTestResultsSummary == inProgress) { short delay get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) } /* when test completes, retrieve any additional test results */ /* if upsTestSpinLock == lock_value + 1, then these are our test */ /* results (as opposed to another manager's */ The initial value of upsTestSpinLock at agent initialization shall be 1.
                               upsTestResultsSummary 1.3.6.1.4.1.4555.1.1.1.1.7.3 integer read-only
The results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results. Enumeration: 'notActive': 1, 'failed': 4, 'inProgress': 2, 'byPass': 3.
                               upsTestResultsDetail 1.3.6.1.4.1.4555.1.1.1.1.7.4 displaystring read-only
Additional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.
                               upsTestStartTime 1.3.6.1.4.1.4555.1.1.1.1.7.5 timestamp read-only
The value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestStartTime has the value 0.
                               upsTestElapsedTime 1.3.6.1.4.1.4555.1.1.1.1.7.6 timeinterval read-only
The amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestElapsedTime has the value 0.
                               upsWellKnownTests 1.3.6.1.4.1.4555.1.1.1.1.7.7
                                   upsTestNoTestsInitiated 1.3.6.1.4.1.4555.1.1.1.1.7.7.1 integer read-only
No tests have been initiated and no test is in progress.
                                   upsTestAbortTestInProgress 1.3.6.1.4.1.4555.1.1.1.1.7.7.2 integer read-only
The test in progress is to be aborted / the test in progress was aborted.
                                   upsTestGeneralSystemsTest 1.3.6.1.4.1.4555.1.1.1.1.7.7.3 integer read-only
The manufacturer's standard test of UPS device systems.
                                   upsTestQuickBatteryTest 1.3.6.1.4.1.4555.1.1.1.1.7.7.4 integer read-only
A test that is sufficient to determine if the battery needs replacement.
                                   upsDeepBatteryCalibration 1.3.6.1.4.1.4555.1.1.1.1.7.7.5 integer read-only
The system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high degree of confidence. WARNING: this test will leave the battery in a low charge state and will require time for recharging to a level sufficient to provide normal battery duration for the protected load.
                           upsControl 1.3.6.1.4.1.4555.1.1.1.1.8
                               upsControlStatusControl 1.3.6.1.4.1.4555.1.1.1.1.8.1 integer read-write
This object Control UPS status Enumeration: 'upsStandbyOff': 2, 'upsEcoMode': 3, 'upsCommandReset': 6, 'upsStandbyOn': 1, 'upsBuzzerOff': 7, 'upsOnInverter': 9, 'upsOnBypass': 8, 'upsNormalMode': 4, 'upsAlarmReset': 5.
                               upsShutdownDelay 1.3.6.1.4.1.4555.1.1.1.1.8.2 integer read-write
This object set the delay time (in seconds) to turn UPS off after Net Vision broadcast shutdown request to connected clients
                               upsTurnOffAfterShutdown 1.3.6.1.4.1.4555.1.1.1.1.8.3 integer read-write
This object enable/disable UPS turn off function after shutdown process complete Enumeration: 'enable': 1, 'disable': 2.
                               upsControlShutdownParametersTable 1.3.6.1.4.1.4555.1.1.1.1.8.4 no-access
Table which describes the parametes for shutdown process when shutdown event occurs
                                   shutdownParametersEntry 1.3.6.1.4.1.4555.1.1.1.1.8.4.1 no-access
                                       upsControlEventDescr 1.3.6.1.4.1.4555.1.1.1.1.8.4.1.1 displaystring read-only
The shutdown event identification
                                       upsControlEventStatus 1.3.6.1.4.1.4555.1.1.1.1.8.4.1.2 integer read-write
Status of the corresponding shutdown Event. When set to disable(), shutdown process will not start when corresponding event occured. Enumeration: 'enable': 1, 'disable': 2.
                                       upsControlDelay 1.3.6.1.4.1.4555.1.1.1.1.8.4.1.3 integer read-write
The Delay after the occurance of the curresponding shutdown event that Net Vision should issue shutdown request to connected clients. For WeeklyScheduledShutdown and SpecialScheduledShutdown, this is the time before the configured Shutdowntime when Net Vision will start sending the warning message to the connected clients. The value is in units of minutes.
                                       upsControlFirstWarning 1.3.6.1.4.1.4555.1.1.1.1.8.4.1.4 integer read-write
The delay after the occurance of the curresponding shutdown event that the Net Vision will start sending the warning message to the connected clients. The value is in units of seconds
                                       upsControlWarningInterval 1.3.6.1.4.1.4555.1.1.1.1.8.4.1.5 integer read-write
The frequency of sending warning messages to the connected clients when the curresponding shutdown event occurs. The value is in units of seconds.
                                       upsControlSeverity 1.3.6.1.4.1.4555.1.1.1.1.8.4.1.6 integer read-write
Shutdown daemon severity.
                               upsControlWeeklyScheduleTable 1.3.6.1.4.1.4555.1.1.1.1.8.5 no-access
The table to schedule shutting down the ups by weekly.
                                   upsControlWeeklyScheduleEntry 1.3.6.1.4.1.4555.1.1.1.1.8.5.1 no-access
The entries for each day.
                                       upsControlWeeklyIndex 1.3.6.1.4.1.4555.1.1.1.1.8.5.1.1 integer read-only
The index of scheduled events.
                                       upsControlWeeklyShutdownDay 1.3.6.1.4.1.4555.1.1.1.1.8.5.1.2 integer read-write
The weekday on which the UPS should shut down. Enumeration: 'none': 8, 'monday': 2, 'tuesday': 3, 'friday': 6, 'wednesday': 4, 'thursday': 5, 'sunday': 1, 'saturday': 7.
                                       upsControlWeeklyShutdownTime 1.3.6.1.4.1.4555.1.1.1.1.8.5.1.3 displaystring read-write
The time that the process of shutting down the UPS will be initiated in hh:mm:ss format.
                                       upsControlWeeklyRestartDay 1.3.6.1.4.1.4555.1.1.1.1.8.5.1.4 integer read-write
The weekday on which the UPS should restart Enumeration: 'none': 8, 'monday': 2, 'tuesday': 3, 'friday': 6, 'wednesday': 4, 'thursday': 5, 'sunday': 1, 'saturday': 7.
                                       upsControlWeeklyRestartTime 1.3.6.1.4.1.4555.1.1.1.1.8.5.1.5 displaystring read-write
The time the UPS will restart in hh:mm:ss format.
                               upsControlSpecialScheduleTable 1.3.6.1.4.1.4555.1.1.1.1.8.6 no-access
The table to schedule shutting down the ups.
                                   upsControlSpecialScheduleEntry 1.3.6.1.4.1.4555.1.1.1.1.8.6.1 no-access
The entries for each day.
                                       upsControlSpecialIndex 1.3.6.1.4.1.4555.1.1.1.1.8.6.1.1 integer read-only
The index of scheduled events.
                                       upsControlSpecialShutdownDay 1.3.6.1.4.1.4555.1.1.1.1.8.6.1.2 displaystring read-write
The date on which the UPS should shut down in dd/mm/yyyy format.
                                       upsControlSpecialShutdownTime 1.3.6.1.4.1.4555.1.1.1.1.8.6.1.3 displaystring read-write
The time that the process of shutting down the UPS will be initiated in hh:mm:ss format
                                       upsControlSpecialRestartDay 1.3.6.1.4.1.4555.1.1.1.1.8.6.1.4 displaystring read-write
The date on which the UPS should restart in dd/mm/yyyy format
                                       upsControlSpecialRestartTime 1.3.6.1.4.1.4555.1.1.1.1.8.6.1.5 displaystring read-write
The time the UPS will restart in hh:mm:ss format.
                               upsControlEcoModeScheduleTable 1.3.6.1.4.1.4555.1.1.1.1.8.7 no-access
The table to schedule enable/disable ups eco/mode by weekly.
                                   upsControlEcoModeScheduleEntry 1.3.6.1.4.1.4555.1.1.1.1.8.7.1 no-access
The entries for each day.
                                       upsControlEcoModeIndex 1.3.6.1.4.1.4555.1.1.1.1.8.7.1.1 integer read-only
The index of scheduled events.
                                       upsControlEcoModeStartDay 1.3.6.1.4.1.4555.1.1.1.1.8.7.1.2 integer read-write
The weekday on which the UPS Eco/Mode should enable. Enumeration: 'none': 8, 'monday': 2, 'tuesday': 3, 'friday': 6, 'wednesday': 4, 'thursday': 5, 'sunday': 1, 'saturday': 7.
                                       upsControlEcoModeStartTime 1.3.6.1.4.1.4555.1.1.1.1.8.7.1.3 displaystring read-write
The time that the UPS Eco/Mode will be enabled, in hh:mm:ss format.
                                       upsControlEcoModeEndDay 1.3.6.1.4.1.4555.1.1.1.1.8.7.1.4 integer read-write
The weekday on which the UPS Eco/Mode should disable Enumeration: 'none': 8, 'monday': 2, 'tuesday': 3, 'friday': 6, 'wednesday': 4, 'thursday': 5, 'sunday': 1, 'saturday': 7.
                                       upsControlEcoModeEndTime 1.3.6.1.4.1.4555.1.1.1.1.8.7.1.5 displaystring read-write
The time the UPS Eco/Mode will disabled, in hh:mm:ss format.
                           upsConfig 1.3.6.1.4.1.4555.1.1.1.1.9
                               upsConfigInputVoltage 1.3.6.1.4.1.4555.1.1.1.1.9.1 integer read-only
The magnitude of the nominal input voltage.
                               upsConfigInputFreq 1.3.6.1.4.1.4555.1.1.1.1.9.2 integer read-only
The nominal input frequency.
                               upsConfigOutputVoltage 1.3.6.1.4.1.4555.1.1.1.1.9.3 integer read-only
The magnitude of the nominal output voltage.
                               upsConfigOutputFreq 1.3.6.1.4.1.4555.1.1.1.1.9.4 integer read-only
The nominal output frequency.
                               upsDevicesTable 1.3.6.1.4.1.4555.1.1.1.1.9.5 no-access
The devices powered by UPS and registered to Net Vision
                                   upsDevicesEntry 1.3.6.1.4.1.4555.1.1.1.1.9.5.1 no-access
The devices protected by Net Vision
                                       indexOfDevice 1.3.6.1.4.1.4555.1.1.1.1.9.5.1.1 integer read-only
The index of the device that is plugged into the UPS.
                                       addrOfDevice 1.3.6.1.4.1.4555.1.1.1.1.9.5.1.2 ipaddress read-only
The ip address of the device.
                                       nameOfDevice 1.3.6.1.4.1.4555.1.1.1.1.9.5.1.3 displaystring read-only
The name/description of the device plugged into the UPS.
                                       timeOfConnection 1.3.6.1.4.1.4555.1.1.1.1.9.5.1.4 displaystring read-only
The that device registered to Net Vision
                                       statusOfConnection 1.3.6.1.4.1.4555.1.1.1.1.9.5.1.5 integer read-only
status
                                       severityOfConnection 1.3.6.1.4.1.4555.1.1.1.1.9.5.1.6 integer read-only
severity
                           upsAgent 1.3.6.1.4.1.4555.1.1.1.1.10
                                 upsAgentIpaddress 1.3.6.1.4.1.4555.1.1.1.1.10.1 ipaddress read-write
The ip address that NMS can identify the managed device
                                 upsAgentGateway 1.3.6.1.4.1.4555.1.1.1.1.10.2 ipaddress read-write
The default gateway that allow device managed through routers
                                 upsAgentSubnetMask 1.3.6.1.4.1.4555.1.1.1.1.10.3 ipaddress read-write
Internet address subnet mask
                                 upsAgentDate 1.3.6.1.4.1.4555.1.1.1.1.10.4 displaystring read-write
The date in agent, format is (dd/mm/yyyy)
                                 upsAgentTime 1.3.6.1.4.1.4555.1.1.1.1.10.5 displaystring read-write
The time in agent, format is (hh:mm:ss)
                                 upsAgentNtpTimeServer 1.3.6.1.4.1.4555.1.1.1.1.10.6 displaystring read-write
                                 upsAgentNtpTimeZone 1.3.6.1.4.1.4555.1.1.1.1.10.7 integer read-write
Enumeration: 'gmt0500mumbai': 51, 'gmt0000monrovia': 27, 'gmt1000hobart': 72, 'gmt0900darwin': 68, 'gmt0100azores': 25, 'gmt0300nairobi': 43, 'gmt0200jerusalem': 39, 'gmt0600jayawardenepura': 55, 'gmt0500ekaterinburg': 48, 'gmt1000hawaii': 4, 'gmt0100paris': 31, 'gmt1200kwajalein': 2, 'gmt0400kabul': 47, 'gmt0800tijuana': 6, 'gmt0300greenland': 23, 'gmt0400yerevan': 46, 'gmt1200fiji': 76, 'gmt0900alaska': 5, 'gmt0600saskatchewan': 13, 'gmt0700mountain': 9, 'gmt0500quito': 14, 'gmt0600dhaka': 54, 'gmt0300georgetown': 22, 'gmt1300alofa': 77, 'gmt0300maghdad': 40, 'gmt0400atime': 17, 'gmt1100magadan': 74, 'gmt0600ctime': 11, 'gmt1000guam': 71, 'gmt0200minsk': 34, 'gmt0300newfoundland': 20, 'gmt0600rangoon': 56, 'gmt0000london': 28, 'gmt0600novosibirsk': 53, 'gmt0200vilnius': 38, 'gmt0800irkutsk': 60, 'gmt0500tashkent': 49, 'gmt0100prague': 30, 'gmt0200atlantic': 24, 'gmt0900tokyo': 64, 'gmt0500calcutta': 50, 'gmt0800beijing': 59, 'gmt0100wcafrica': 33, 'gmt1000brisbane': 69, 'gmt0800singapore': 61, 'gmt0300tehran': 44, 'gmt0100cvi': 26, 'gmt0300volgograd': 42, 'gmt0100zagreb': 32, 'gmt0700krasnoyarsk': 58, 'gmt0500indiana': 16, 'gmt0700bangkok': 57, 'gmt1200dateLineWest': 1, 'gmt1000vladivostok': 73, 'gmt0700arizona': 7, 'gmt0900adelaide': 67, 'gmt1100samoa': 3, 'gmt0600camerica': 10, 'gmt0500etime': 15, 'gmt0900yakutsk': 66, 'gmt0400caracas': 18, 'gmt1200auckland': 75, 'gmt0800taipei': 63, 'gmt0500kathmand': 52, 'gmt0700chihuahua': 8, 'gmt0600guadalajara': 12, 'gmt0100vienna': 29, 'gmt0800perth': 62, 'gmt1000canberra': 70, 'gmt0200bucharest': 35, 'gmt0400muscat': 45, 'gmt0200cairo': 36, 'gmt0300riyadh': 41, 'gmt0200pretoria': 37, 'gmt0900seoul': 65, 'gmt0400santiago': 19, 'gmt0300brasilia': 21.
                                 upsAgentHistoryLogFrequency 1.3.6.1.4.1.4555.1.1.1.1.10.8 integer read-write
The frequency of the updation of the history log. The value is in seconds
                                 upsAgentExtHistoryLogFrequency 1.3.6.1.4.1.4555.1.1.1.1.10.9 integer read-write
The ups parameters are sampled at the rate governed by the mconfigHistroyLogFrequency. These sampled values are further conslidated over period of time which is determined by this object.
                                 upsAgentPollRate 1.3.6.1.4.1.4555.1.1.1.1.10.10 integer read-write
The frequency that proxy agent polls the connected UPS in JBUS protocol. (unit : second)
                                 upsAgentBaudRate 1.3.6.1.4.1.4555.1.1.1.1.10.11 integer read-write
The serial port communication speed (2400/9600 allowed). Enumeration: 'br2400': 1, 'br19200': 3, 'br9600': 2.
                                 upsAgentDhcpStatus 1.3.6.1.4.1.4555.1.1.1.1.10.12 integer read-write
Enable or disable DHCP-BootP capability Enumeration: 'disabled': 2, 'enabled': 1.
                                 upsAgentTelnetStatus 1.3.6.1.4.1.4555.1.1.1.1.10.13 integer read-write
Enable or disable telnet access Enumeration: 'disabled': 2, 'enabled': 1.
                                 upsAgentTftpStatus 1.3.6.1.4.1.4555.1.1.1.1.10.14 integer read-write
Enable or disable network upgrade capability Enumeration: 'disabled': 2, 'enabled': 1.
                                 upsAgentResetToDefault 1.3.6.1.4.1.4555.1.1.1.1.10.15 integer read-write
Reset all parameters of Net Vision to default value Enumeration: 'reset': 1, 'nothing': 2.
                                 upsAgentRestart 1.3.6.1.4.1.4555.1.1.1.1.10.16 integer read-write
Restart Net Vision Enumeration: 'nothing': 2, 'restart': 1.
                                 upsAgentClearAgentLog 1.3.6.1.4.1.4555.1.1.1.1.10.17 integer read-write
Clear agent log data Enumeration: 'nothing': 2, 'clear': 1.
                                 upsAgentClearEventLog 1.3.6.1.4.1.4555.1.1.1.1.10.18 integer read-write
Clear event log data Enumeration: 'nothing': 2, 'clear': 1.
                                 upsAgentClearExtHistoryLog 1.3.6.1.4.1.4555.1.1.1.1.10.19 integer read-write
Clear extented history log data Enumeration: 'nothing': 2, 'clear': 1.
                                 upsAgentClearHistoryLog 1.3.6.1.4.1.4555.1.1.1.1.10.20 integer read-write
Clear history log data Enumeration: 'nothing': 2, 'clear': 1.
                                 upsAgentTrapsReceiversTable 1.3.6.1.4.1.4555.1.1.1.1.10.21 no-access
A list of managers to send traps to. The number of entries is given by the value of upsAgentNumTrapReceivers
                                       upsAgentTrapsReceiversEntry 1.3.6.1.4.1.4555.1.1.1.1.10.21.1 no-access
The managers to send traps to.
                                           trapsIndex 1.3.6.1.4.1.4555.1.1.1.1.10.21.1.1 integer read-only
The index to a trap receiver entry.
                                           trapsReceiverAddr 1.3.6.1.4.1.4555.1.1.1.1.10.21.1.2 displaystring read-write
The IP address of the manager to send a trap to.
                                           receiverCommunityString 1.3.6.1.4.1.4555.1.1.1.1.10.21.1.3 displaystring read-write
The community name to use in the trap when sent to the manager.
                                           receiverDescription 1.3.6.1.4.1.4555.1.1.1.1.10.21.1.4 displaystring read-write
Description of trap receivers
                                 upsAgentAccessControlTable 1.3.6.1.4.1.4555.1.1.1.1.10.22 no-access
A list of managers which can access Net Vision with private community string.
                                       upsAgentAccessControlEntry 1.3.6.1.4.1.4555.1.1.1.1.10.22.1 no-access
The managers.
                                           accessIndex 1.3.6.1.4.1.4555.1.1.1.1.10.22.1.1 integer read-only
The index to a access control entry.
                                           accessControlAddr 1.3.6.1.4.1.4555.1.1.1.1.10.22.1.2 displaystring read-write
The IP address of the manager to access Net Vision
                                           accessCommunityString 1.3.6.1.4.1.4555.1.1.1.1.10.22.1.3 displaystring read-write
The community name to use in the manager when access Net Vision
                                           accessControlMode 1.3.6.1.4.1.4555.1.1.1.1.10.22.1.4 integer read-write
Access type, only read-Write access type can change parameter of Net Vision Enumeration: 'readWrite': 2, 'readOnly': 1, 'notAccess': 3.
                                 upsAgentMibVersion 1.3.6.1.4.1.4555.1.1.1.1.10.23 integer read-only
The version of MIB spec.
                                 upsAgentTrapString 1.3.6.1.4.1.4555.1.1.1.1.10.50 displaystring read-only
This OID allows traps to be sent with an octet string argument that my not be defined in the. A get of this OID will return error or NULL string.
                           emdStatus 1.3.6.1.4.1.4555.1.1.1.1.11
                                 emdSatatusTemperature 1.3.6.1.4.1.4555.1.1.1.1.11.1 integer read-only
The measurement of EMD temperature, in 0.1 degree
                                 emdSatatusHumidity 1.3.6.1.4.1.4555.1.1.1.1.11.2 integer read-only
The measurement of EMD humidity, in 0.1 degree
                       upsTraps 1.3.6.1.4.1.4555.1.1.1.2
                             upsTrapOnBattery 1.3.6.1.4.1.4555.1.1.1.20.1
The UPS is operating on battery power. This trap is persistent and is resent at one minute intervals until the UPS either turns off or is no longer running on battery.
                             upsTrapTestCompleted 1.3.6.1.4.1.4555.1.1.1.20.2
This trap is sent upon completion of a UPS diagnostic test.
                             upsTrapAlarmEntryAdded 1.3.6.1.4.1.4555.1.1.1.20.3
This trap is sent each time an alarm is inserted into to the alarm table. It is sent on the insertion of all alarms except for upsAlarmOnBattery and upsAlarmTestInProgress.
                             upsTrapAlarmEntryRemoved 1.3.6.1.4.1.4555.1.1.1.20.4
This trap is sent each time an alarm is removed from the alarm table. It is sent on the removal of all alarms except for upsAlarmTestInProgress.
                             upsTrapUpsNormal 1.3.6.1.4.1.4555.1.1.1.20.5
INFORMATION: The UPS status is normal.
                             upsTrapUpsBattTestFailed 1.3.6.1.4.1.4555.1.1.1.20.6
SEVERE: UPS failed the last test of battery.
                             upsTrapOnBatteryPower 1.3.6.1.4.1.4555.1.1.1.20.7
WARNING: The UPS has switched to battery backup power.
                             upsTrapBatteryLow 1.3.6.1.4.1.4555.1.1.1.20.8
SEVERE: Battery is near to be discharged.
                             upsTrapPowerRestored 1.3.6.1.4.1.4555.1.1.1.20.9
INFORMATION: Input power has been restored.
                             upsTrapImminentStop 1.3.6.1.4.1.4555.1.1.1.20.10
SEVERE: The UPS is near to switch off the output power.
                             upsTrapTurnedOff 1.3.6.1.4.1.4555.1.1.1.20.11
WARNING: The UPS has been turned off by the management station.
                             upsTrapOverTemperature 1.3.6.1.4.1.4555.1.1.1.20.12
SEVERE: The UPS has sensed a temperature greater than its limit.
                             upsTrapOverload 1.3.6.1.4.1.4555.1.1.1.20.13
SEVERE: The UPS has sensed a load greater than 100 percent of its rated capacity.
                             upsTrapOnMains 1.3.6.1.4.1.4555.1.1.1.20.14
SEVERE: The UPS output is on mains.
                             upsTrapRedoundancyLost 1.3.6.1.4.1.4555.1.1.1.20.15
SEVERE: Redoundancy is lost.
                             upsTrapEmdTempLow 1.3.6.1.4.1.4555.1.1.1.20.16
SEVERE: EMD Sensor detected low temperature.
                             upsTrapEmdTempHigh 1.3.6.1.4.1.4555.1.1.1.20.17
SEVERE: EMD Sensor detected high temperature.
                             upsTrapEmdHumidityLow 1.3.6.1.4.1.4555.1.1.1.20.18
SEVERE: EMD Sensor detected low humidity.
                             upsTrapEmdHumidityHigh 1.3.6.1.4.1.4555.1.1.1.20.19
SEVERE: EMD Sensor detected high humidity.
                             upsTrapEmdFirstInputActive 1.3.6.1.4.1.4555.1.1.1.20.20
SEVERE: The input is active.
                             upsTrapEmdFirstInputRestored 1.3.6.1.4.1.4555.1.1.1.20.21
INFORMATION: The input is restored.
                             upsTrapEmdSecondInputActive 1.3.6.1.4.1.4555.1.1.1.20.22
SEVERE: The input is active.
                             upsTrapEmdSecondInputRestored 1.3.6.1.4.1.4555.1.1.1.20.23
INFORMATION: The input is restored.