Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 directory 1.3.6.1.1
 mgmt 1.3.6.1.2
     mib_2 1.3.6.1.2.1
 experimental 1.3.6.1.3
     univPowerSupply 1.3.6.1.3.9999
               ident 1.3.6.1.3.9999.1
                   identDescr 1.3.6.1.3.9999.1.1 octet string read-only
The UPS description. This should include the vendor name, model number and software revision.
                   identSpecific 1.3.6.1.3.9999.1.2 object identifier read-only
A reference to MIB definitions specific to the particular UPS being managed. If this information is not present, its value should be set to the OBJECT IDENTIFIER { 0 0 }, which is a syntactically valid object identifier, and any conformant implementation of ASN.1 and BER must be able to generate and recognize this value.
               battery 1.3.6.1.3.9999.2
                   batTimeRemaining 1.3.6.1.3.9999.2.1 integer read-only
The estimated time to battery charge depletion. (Unit of measure: Minute)
                   batTemperature 1.3.6.1.3.9999.2.2 integer read-only
The battery temperature. (Unit of measure: Degree, Centigrade)
                   batVoltage 1.3.6.1.3.9999.2.3 integer read-only
The current battery voltage. (Unit of measure: volt)
                   batChargeCurrent 1.3.6.1.3.9999.2.4 integer read-only
The current battery charging current. (Unit of measure: Amp/10)
                   batDischargeCurrent 1.3.6.1.3.9999.2.5 integer read-only
The current battery discharging current. (Unit of measure: Amp/10)
                   batCapacity 1.3.6.1.3.9999.2.6 integer read-only
The current battery capacity in percentage of total available.
               input 1.3.6.1.3.9999.3
                   inputFrequency 1.3.6.1.3.9999.3.1 integer read-only
The current input frequency. (Unit of measure: mHz)
                   inputBrownOuts 1.3.6.1.3.9999.3.2 counter read-only
The number of brown-out conditions since the agent started.
                   inputBlackOuts 1.3.6.1.3.9999.3.3 counter read-only
The number of black-out conditions since the agent started.
                   inputTransients 1.3.6.1.3.9999.3.4 counter read-only
The number of transient (sag and surge) conditions since the agent started.
                   inputNumPhases 1.3.6.1.3.9999.3.5 integer read-only
The number of input phases utilized in this device. This entry indicates the number of rows in the input table. Enumeration: 'three': 3, 'one': 1.
                   inputTable 1.3.6.1.3.9999.3.6 no-access
                       inputEntry 1.3.6.1.3.9999.3.6.1 no-access
                           inputPhase 1.3.6.1.3.9999.3.6.1.1 integer read-only
The input phase.
                           inputVoltage 1.3.6.1.3.9999.3.6.1.2 integer read-only
The input voltage. (Unit of measure: Volt)
                           inputCurrent 1.3.6.1.3.9999.3.6.1.3 integer read-only
The input current. (Unit of measure: Amp/10)
                           inputVA 1.3.6.1.3.9999.3.6.1.4 integer read-only
The input volt-amps.
                           inputWatts 1.3.6.1.3.9999.3.6.1.5 integer read-only
The input power. (Unit of measure: Watt)
               output 1.3.6.1.3.9999.4
                   outputFrequency 1.3.6.1.3.9999.4.1 integer read-only
Measured in mHz.
                   outputInverterTemp 1.3.6.1.3.9999.4.2 integer read-only
The temperature of the inverter. (Unit of measure: degree, Centigrade)
                   outputControllerTemp 1.3.6.1.3.9999.4.3 integer read-only
The temperature of the controller. (Unit of measure: degree, Centigrade)
                   outputNumPhases 1.3.6.1.3.9999.4.4 integer read-only
The number of output phases utilized in this device. This entry indicates the number of rows in the output table. Enumeration: 'one': 1, 'three': 3, 'two': 2.
                   outputTable 1.3.6.1.3.9999.4.5 no-access
                       outputEntry 1.3.6.1.3.9999.4.5.1 no-access
                           outputPhase 1.3.6.1.3.9999.4.5.1.1 integer read-only
The output phase.
                           outputVoltage 1.3.6.1.3.9999.4.5.1.2 integer read-only
The output voltage. (Unit of measure: Volt)
                           outputCurrent 1.3.6.1.3.9999.4.5.1.3 integer read-only
The output current. (Unit of measure: Amp/10)
                           outputVA 1.3.6.1.3.9999.4.5.1.4 integer read-only
The output volt-amps.
                           outputWatts 1.3.6.1.3.9999.4.5.1.5 integer read-only
The output power. (Unit of measure: Watt)
               bypass 1.3.6.1.3.9999.5
                   bypassFrequency 1.3.6.1.3.9999.5.1 integer read-only
The bypass frequency. (Unit of measure: mHz)
                   bypassNumPhases 1.3.6.1.3.9999.5.2 integer read-only
The number of bypass phases utilized in this device. This entry indicates the number of rows in the input table. Enumeration: 'three': 3, 'one': 1.
                   bypassTable 1.3.6.1.3.9999.5.3 no-access
                       bypassEntry 1.3.6.1.3.9999.5.3.1 no-access
                           bypassPhase 1.3.6.1.3.9999.5.3.1.1 integer read-only
The bypass phase.
                           bypassVoltage 1.3.6.1.3.9999.5.3.1.2 integer read-only
The bypass voltage. (Unit of measure: Volt)
                           bypassCurrent 1.3.6.1.3.9999.5.3.1.3 integer read-only
The bypass current. (Unit of measure: Amp/10)
               status 1.3.6.1.3.9999.6
                   statSummary 1.3.6.1.3.9999.6.1 integer read-only
A summary of non-critical conditions. Each of the enumerated values are added to compute the value of this object. Enumeration: 'onLine': 1, 'replaceBatteries': 4, 'onBypass': 2.
               alarm 1.3.6.1.3.9999.7
                   alarmSummary 1.3.6.1.3.9999.7.1 integer read-only
A summary of critical conditions. Each of the enumerated values are added to compute the value of this object. Enumeration: 'lowBattery': 4, 'inputBad': 16, 'inputFreqError': 32, 'inverterTempBad': 256, 'bypassBad': 2048, 'batteryBad': 1, 'upsOff': 16384, 'onBypass': 1024, 'unixStopIssued': 4096, 'chargerFailed': 8192, 'batteryTempBad': 8, 'outputBad': 64, 'outputOverload': 128, 'controllerTempBad': 512, 'onBattery': 2.
               test 1.3.6.1.3.9999.8
                   testBattery 1.3.6.1.3.9999.8.1 integer read-write
Setting this variable to 'start' will initiate the battery test. Setting this variable to 'abort' will stop the battery test if the test is in- progress, otherwise it has no effect. Reading this variable will return zero. If 'testBatteryStatus' is remain in the failure state. Enumeration: 'start': 1, 'abort': 2.
                   testBatteryStatus 1.3.6.1.3.9999.8.2 integer read-only
The status of the battery test. Enumeration: 'unknown': 1, 'failed': 3, 'sysFailure': 5, 'passed': 2, 'inProgress': 4, 'notSupported': 6.
                   testDiag 1.3.6.1.3.9999.8.3 integer read-write
Setting this variable to 'start' will initiate the diagnostics test. Setting this variable to 'abort' will stop the diagnostics test if the test is in-progress, otherwise it has no effect. Reading this variable will return zero. Enumeration: 'start': 1, 'abort': 2.
                   testDiagStatus 1.3.6.1.3.9999.8.4 integer read-only
The status of the diagnostics test. Enumeration: 'unknown': 1, 'failed': 3, 'sysFailure': 5, 'passed': 2, 'inProgress': 4, 'notSupported': 6.
                   testIndicators 1.3.6.1.3.9999.8.5 integer read-write
Setting this variable to 'start' will initiate the indicators test. Setting this variable to 'abort' will stop the indicators test if the test is in-progress, otherwise it has no effect. Reading this variable will return zero. Enumeration: 'start': 1, 'abort': 2.
                   testIndicatorsStatus 1.3.6.1.3.9999.8.6 integer read-only
The status of the indicators test. Note: this test requires physical verification to be useful. Enumeration: 'unknown': 1, 'failed': 3, 'sysFailure': 5, 'passed': 2, 'inProgress': 4, 'notSupported': 6.
               schedule 1.3.6.1.3.9999.9
                   schedOutputOffDelay 1.3.6.1.3.9999.9.1 timeticks read-write
Setting this object will stop the output after the indicated number of TimeTicks. Setting this object to -1 will abort any shutdown sequence. The output will restart in the number of TimeTicks indicated by 'schedOutputOnDelay' unless it is equal to -1. In the later case, the output will remain inactive. This object will be set to -1 when the device is initialized on power-up or restart.
                   schedOutputOnDelay 1.3.6.1.3.9999.9.2 timeticks read-write
The length of time to delay before coming on- line. If this value is -1 the output will remain off. This object will be set to -1 when the device is initialized on power-up or restart.
                   schedSystemShutdown 1.3.6.1.3.9999.9.3 integer read-write
Setting this object to 'true' will shutdown the device. Enumeration: 'true': 1, 'false': 2.
                   schedUnixShutdown 1.3.6.1.3.9999.9.4 integer read-write
Setting this device to 'true' will cause unix shutdown traps to be issued at a system-dependent rate, or until this object is set to false. Enumeration: 'true': 1, 'false': 2.
               config 1.3.6.1.3.9999.10
                     configOutputVoltage 1.3.6.1.3.9999.10.1 integer read-only
The nominal output voltage. (Unit of measure: volt)
                     configInputVoltage 1.3.6.1.3.9999.10.2 integer read-only
The nominal input voltage. (Unit of measure: volt)
                     configOutputFreq 1.3.6.1.3.9999.10.3 integer read-only
The nominal output frequency. (Unit of measure: mHz)
                     configInputFreq 1.3.6.1.3.9999.10.4 integer read-only
The nominal input frequency. (Unit of measure: mHz)
                     configNominalBatTime 1.3.6.1.3.9999.10.5 integer read-only
The nominal battery time. (Unit of measure: minute)
                     configAudioStatus 1.3.6.1.3.9999.10.6 integer read-write
The status of the audio alarm. 'Off' indicates the alarm will not sound, while the 'squelch' value indicates the alarm has sounded and squelched. A squelched audio status will return to the previous state ('on' or 'off') when the alarm stops sounding. Enumeration: 'squelch': 3, 'on': 1, 'off': 2.
                     configAutoRestart 1.3.6.1.3.9999.10.7 integer read-write
Setting this object to 'on' will cause the device to restart after a shutdown. Enumeration: 'on': 1, 'off': 2.