Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 atsa 1.3.6.1.4.1.26854
             atsaCorporate 1.3.6.1.4.1.26854.1
                 siteMonitoringMIB 1.3.6.1.4.1.26854.1.1
Alpha Innovations SNMP corporate naming convention Organises the SNMP OIDs according to the design centres that generate the different MIBs
             atsaUs 1.3.6.1.4.1.26854.2
             atsaEu 1.3.6.1.4.1.26854.3
                 atsaEuDevices 1.3.6.1.4.1.26854.3.1
                 siteMonitoring 1.3.6.1.4.1.26854.3.2
                     siteV1 1.3.6.1.4.1.26854.3.2.1
                         siteV1GlobalStatus 1.3.6.1.4.1.26854.3.2.1.1 displaystring read-only
A textual string (alarms, normal or unknown) containing the status of the Site
                         siteV1GlobalAlarmSeverityType 1.3.6.1.4.1.26854.3.2.1.2 displaystring read-only
The alarm severity type (critical, major, minor, warning, none, disabled) of the Site
                         siteV1GlobalAlarmSeverityLevel 1.3.6.1.4.1.26854.3.2.1.3 integer32 read-only
The alarm severity level (0-9) of the Site
                         siteV1GlobalAlarmSeverityTypeInt 1.3.6.1.4.1.26854.3.2.1.4 integer32 read-only
The alarm severity type as integer (critical=4, major=3, minor=2, warning=1, none=0) of the Site
                         siteV1Description 1.3.6.1.4.1.26854.3.2.1.10
                               siteV1DescriptionNumber 1.3.6.1.4.1.26854.3.2.1.10.1 integer32 read-only
The number of entries in the Site Description table
                               siteV1DescriptionTable 1.3.6.1.4.1.26854.3.2.1.10.2 no-access
The Description table of the Site
                                   siteV1DescriptionEntry 1.3.6.1.4.1.26854.3.2.1.10.2.1 no-access
A Description entry
                                       siteV1DescriptionIndex 1.3.6.1.4.1.26854.3.2.1.10.2.1.1 unsigned32 no-access
Description Index
                                       siteV1DescriptionName 1.3.6.1.4.1.26854.3.2.1.10.2.1.2 displaystring read-only
Description Name
                                       siteV1DescriptionValue 1.3.6.1.4.1.26854.3.2.1.10.2.1.3 displaystring read-only
Description Value
                                       siteV1DescriptionEntryStatus 1.3.6.1.4.1.26854.3.2.1.10.2.1.4 rowstatus read-only
The status of this table entry
                               siteV1DescriptionList 1.3.6.1.4.1.26854.3.2.1.10.3
                                   siteV1DescDescriptionSiteNumber 1.3.6.1.4.1.26854.3.2.1.10.3.1 displaystring read-write
The identification number of the site
                                   siteV1DescDescriptionSiteName 1.3.6.1.4.1.26854.3.2.1.10.3.2 displaystring read-write
The name of the site
                                   siteV1DescDescriptionShortDescription 1.3.6.1.4.1.26854.3.2.1.10.3.3 displaystring read-write
A short description of the site
                                   siteV1DescDescriptionInfo 1.3.6.1.4.1.26854.3.2.1.10.3.4 displaystring read-write
Some more information about the site
                                   siteV1DescDescriptionDescription 1.3.6.1.4.1.26854.3.2.1.10.3.5 displaystring read-write
A free text zone to write a system description
                                   siteV1DescDescriptionReference 1.3.6.1.4.1.26854.3.2.1.10.3.6 displaystring read-write
A free text zone to write the customer reference of the system
                                   siteV1DescDescriptionContactName 1.3.6.1.4.1.26854.3.2.1.10.3.7 displaystring read-write
Contact Name
                                   siteV1DescDescriptionPhoneNumber 1.3.6.1.4.1.26854.3.2.1.10.3.8 displaystring read-write
Phone Number
                                   siteV1DescDescriptionStreet 1.3.6.1.4.1.26854.3.2.1.10.3.11 displaystring read-write
Street part of the site address
                                   siteV1DescDescriptionCity 1.3.6.1.4.1.26854.3.2.1.10.3.12 displaystring read-write
City part of the site address
                                   siteV1DescDescriptionProvince 1.3.6.1.4.1.26854.3.2.1.10.3.13 displaystring read-write
Province part of the site address
                                   siteV1DescDescriptionPostalCode 1.3.6.1.4.1.26854.3.2.1.10.3.14 displaystring read-write
Postal Code part of the site address
                                   siteV1DescDescriptionRegion 1.3.6.1.4.1.26854.3.2.1.10.3.15 displaystring read-write
Region part of the site address
                                   siteV1DescDescriptionCountry 1.3.6.1.4.1.26854.3.2.1.10.3.16 displaystring read-write
Country part of the site address
                                   siteV1DescDescriptionGroup1 1.3.6.1.4.1.26854.3.2.1.10.3.21 displaystring read-write
Group Level 1 (For Armada Clustering)
                                   siteV1DescDescriptionGroup2 1.3.6.1.4.1.26854.3.2.1.10.3.22 displaystring read-write
Group Level 2 (For Armada Clustering)
                                   siteV1DescDescriptionGroup3 1.3.6.1.4.1.26854.3.2.1.10.3.23 displaystring read-write
Group Level 3 (For Armada Clustering)
                                   siteV1DescDescriptionGroup4 1.3.6.1.4.1.26854.3.2.1.10.3.24 displaystring read-write
Group Level 4 (For Armada Clustering)
                                   siteV1DescDescriptionGroup5 1.3.6.1.4.1.26854.3.2.1.10.3.25 displaystring read-write
Group Level 5 (For Armada Clustering)
                                   siteV1DescDescriptionLatitude 1.3.6.1.4.1.26854.3.2.1.10.3.31 displaystring read-write
The latitude of the site
                                   siteV1DescDescriptionLongitude 1.3.6.1.4.1.26854.3.2.1.10.3.32 displaystring read-write
The longitude of the site
                                   siteV1DescDescriptionAltitude 1.3.6.1.4.1.26854.3.2.1.10.3.33 displaystring read-write
The altitude of the site
                                   siteV1DescControllerSoftwareRevision 1.3.6.1.4.1.26854.3.2.1.10.3.91 displaystring read-only
The software revision of Comp@s (read only)
                                   siteV1DescControllerOperatingSystemRevision 1.3.6.1.4.1.26854.3.2.1.10.3.92 displaystring read-only
The operating system of Comp@s (read only)
                                   siteV1DescControllerCPU 1.3.6.1.4.1.26854.3.2.1.10.3.93 displaystring read-only
Information about the CPU
                                   siteV1DescControllerCard 1.3.6.1.4.1.26854.3.2.1.10.3.94 displaystring read-only
Information about the hardware system containing Compas
                                   siteV1DescControllerStarterVersion 1.3.6.1.4.1.26854.3.2.1.10.3.100 displaystring read-only
Information about the starter component of Compas
                                   siteV1DescControllerFactoryCompasVersion 1.3.6.1.4.1.26854.3.2.1.10.3.105 displaystring read-only
Information about the revision of Compas in Factory folder
                                   siteV1DescControllerUserCompasVersion 1.3.6.1.4.1.26854.3.2.1.10.3.106 displaystring read-only
Information about the revision of Compas in user folder
                                   siteV1DescControllerFactoryFTPServerVersion 1.3.6.1.4.1.26854.3.2.1.10.3.110 displaystring read-only
Information about the revision of Ftp Server in Factory folder
                                   siteV1DescControllerUserFTPServerVersion 1.3.6.1.4.1.26854.3.2.1.10.3.111 displaystring read-only
Information about the revision of Ftp Server in Factory folder
                         siteV1Alarm 1.3.6.1.4.1.26854.3.2.1.11
                               siteV1AlarmNumber 1.3.6.1.4.1.26854.3.2.1.11.1 integer32 read-only
The number of entries in the Site Alarm table
                               siteV1AlarmTable 1.3.6.1.4.1.26854.3.2.1.11.2 no-access
The table of Alarm entries
                                   siteV1AlarmEntry 1.3.6.1.4.1.26854.3.2.1.11.2.1 no-access
An alarm entry
                                       siteV1AlarmIndex 1.3.6.1.4.1.26854.3.2.1.11.2.1.1 unsigned32 no-access
Alarm Index
                                       siteV1AlarmName 1.3.6.1.4.1.26854.3.2.1.11.2.1.2 displaystring read-only
Alarm Name
                                       siteV1AlarmActive 1.3.6.1.4.1.26854.3.2.1.11.2.1.3 displaystring read-only
Is the Alarm active ? 'true' for active, 'false' for not-active
                                       siteV1AlarmSeverityType 1.3.6.1.4.1.26854.3.2.1.11.2.1.4 displaystring read-write
The alarm severity type (major, minor, warning, none, disabled) of this alarm entry
                                       siteV1AlarmSeverityLevel 1.3.6.1.4.1.26854.3.2.1.11.2.1.5 displaystring read-write
The alarm severity level (0-9) of this alarm entry
                                       siteV1AlarmStartTime 1.3.6.1.4.1.26854.3.2.1.11.2.1.6 displaystring read-only
The last start time of this alarm entry (null if never active)
                                       siteV1AlarmStopTime 1.3.6.1.4.1.26854.3.2.1.11.2.1.7 displaystring read-only
The last stop time of this alarm entry (null if alarm active)
                                       siteV1AlarmEntryStatus 1.3.6.1.4.1.26854.3.2.1.11.2.1.8 rowstatus read-only
The status of this table entry - not used, only for MIB compliance
                               siteV1AlarmSummary 1.3.6.1.4.1.26854.3.2.1.11.3 bits read-only
Summary bit vector with all the alarms state of the Site. A '1' means alarm active, '0' means not active. Unimplemented alarms are always '0'. Bits: 'inventoryCANBusFail': 0, 'xMLXMLHeartbeatPostFail': 20, 'inventoryCANBusAddressingError': 1, 'inventoryRunningCANFirmwareUpgrade': 4, 'inventoryRunningCANLSSDeviceDetection': 3, 'controllerControllerRebootRequired': 10, 'inventoryMissingCANBusNodeIDs': 2, 'controllerLastConfChangesUnsaved': 14.
                         siteV1Event 1.3.6.1.4.1.26854.3.2.1.12
                               siteV1EventNumber 1.3.6.1.4.1.26854.3.2.1.12.1 integer32 read-only
The number of entries in the Event Table related to the Site
                               siteV1EventTable 1.3.6.1.4.1.26854.3.2.1.12.2 no-access
The Event table related to the Site
                                   siteV1EventEntry 1.3.6.1.4.1.26854.3.2.1.12.2.1 no-access
.
                                       siteV1EventIndex 1.3.6.1.4.1.26854.3.2.1.12.2.1.1 unsigned32 no-access
Event Index
                                       siteV1EventId 1.3.6.1.4.1.26854.3.2.1.12.2.1.2 unsigned32 read-only
Event Index
                                       siteV1EventName 1.3.6.1.4.1.26854.3.2.1.12.2.1.3 displaystring read-only
Event Name
                                       siteV1EventDateTime 1.3.6.1.4.1.26854.3.2.1.12.2.1.4 displaystring read-only
The date and time of the event
                                       siteV1EventSeverityType 1.3.6.1.4.1.26854.3.2.1.12.2.1.5 displaystring read-only
The event severity type ('major', 'minor', 'warning' or 'none')
                                       siteV1EventSeverityLevel 1.3.6.1.4.1.26854.3.2.1.12.2.1.6 displaystring read-only
The event severity level (0-9)
                                       siteV1EventEntryStatus 1.3.6.1.4.1.26854.3.2.1.12.2.1.7 rowstatus read-only
The status of this table entry
                         siteV1Data 1.3.6.1.4.1.26854.3.2.1.13
                               siteV1DataNumber 1.3.6.1.4.1.26854.3.2.1.13.1 integer32 read-only
The number of entries in the Data Table related to the Site
                               siteV1DataTable 1.3.6.1.4.1.26854.3.2.1.13.2 no-access
The table of Data entries
                                   siteV1DataEntry 1.3.6.1.4.1.26854.3.2.1.13.2.1 no-access
A data entry
                                       siteV1DataIndex 1.3.6.1.4.1.26854.3.2.1.13.2.1.1 unsigned32 no-access
The data index
                                       siteV1DataName 1.3.6.1.4.1.26854.3.2.1.13.2.1.2 displaystring read-only
The data name
                                       siteV1DataValue 1.3.6.1.4.1.26854.3.2.1.13.2.1.3 displaystring read-only
The data value
                                       siteV1DataEntryStatus 1.3.6.1.4.1.26854.3.2.1.13.2.1.4 rowstatus read-only
The status of this table entry - not used, only present for compliance
                               siteV1DataList 1.3.6.1.4.1.26854.3.2.1.13.3
                                   siteV1DataNetworkCurrentIPAddress 1.3.6.1.4.1.26854.3.2.1.13.3.1 integer32 read-only
This is the actual IP address of the Comp@s platform. If the Ethernet cable is not correctly connected, the address will be 0.0.0.0.
                                   siteV1DataNetworkCurrentIPMask 1.3.6.1.4.1.26854.3.2.1.13.3.2 integer32 read-only
This is the actual IP address of the Comp@s platform. If the Ethernet cable is not correctly connected, the address will be 0.0.0.0.
                                   siteV1DataNetworkCurrentMACAddress 1.3.6.1.4.1.26854.3.2.1.13.3.3 integer32 read-only
This is the MAC address of IP interface.
                                   siteV1DataControllerLicensedOptions 1.3.6.1.4.1.26854.3.2.1.13.3.11 integer32 read-only
This is the options of the actual license.
                                   siteV1DataTimeDateAndTimeLocal 1.3.6.1.4.1.26854.3.2.1.13.3.21 displaystring read-only
This is the local time of the monitoring.
                                   siteV1DataTimeDateAndTimeUTC 1.3.6.1.4.1.26854.3.2.1.13.3.22 displaystring read-only
This is the UTC time of the monitoring.
                                   siteV1DataControllerMonitoringMemoryUsed 1.3.6.1.4.1.26854.3.2.1.13.3.31 integer32 read-only
This is actual amount of RAM memory used by the application.
                                   siteV1DataControllerCPUPercentageUsage 1.3.6.1.4.1.26854.3.2.1.13.3.32 integer32 read-only
This is actual percentage of CPU used
                                   siteV1DataControllerFreeFlashMemorySpace 1.3.6.1.4.1.26854.3.2.1.13.3.33 integer32 read-only
This is free flash memory available on the Comp@s card, in Megabytes
                                   siteV1DataControllerFTPServerStatus 1.3.6.1.4.1.26854.3.2.1.13.3.35 displaystring read-only
Status of the FTP Server. Compatible only with version >= 2.26.X.X. The configuration is available at controller -> FTP Server page.
                                   siteV1DataDataRecordsTotalFifoSizeOfSecondRecords 1.3.6.1.4.1.26854.3.2.1.13.3.41 integer32 read-only
NA
                                   siteV1DataDataRecordsTotalFifoSizeOfMinuteRecords 1.3.6.1.4.1.26854.3.2.1.13.3.42 integer32 read-only
NA
                                   siteV1DataDataRecordsTotalFifoSizeOfHourRecords 1.3.6.1.4.1.26854.3.2.1.13.3.43 integer32 read-only
NA
                                   siteV1DataDataRecordsTotalFifoSizeOfDayRecords 1.3.6.1.4.1.26854.3.2.1.13.3.44 integer32 read-only
NA
                                   siteV1DataInventoryCANBusNodeIDs 1.3.6.1.4.1.26854.3.2.1.13.3.51 integer32 read-only
The coma separated list of the node ids present on the CAN bus.
                                   siteV1DataCloudLinkCloudLinkState 1.3.6.1.4.1.26854.3.2.1.13.3.166 displaystring read-only
Cloud Link State
                         siteV1Config 1.3.6.1.4.1.26854.3.2.1.15
                               siteV1ConfigNumber 1.3.6.1.4.1.26854.3.2.1.15.1 integer32 read-only
The number of entries in the Config table related to the Site
                               siteV1ConfigTable 1.3.6.1.4.1.26854.3.2.1.15.2 no-access
The table of Config entries related to the Site
                                   siteV1ConfigEntry 1.3.6.1.4.1.26854.3.2.1.15.2.1 no-access
A Config entry
                                       siteV1ConfigIndex 1.3.6.1.4.1.26854.3.2.1.15.2.1.1 unsigned32 no-access
The Config entry Index
                                       siteV1ConfigName 1.3.6.1.4.1.26854.3.2.1.15.2.1.2 displaystring read-only
The Config entry name
                                       siteV1ConfigValue 1.3.6.1.4.1.26854.3.2.1.15.2.1.3 displaystring read-write
The Config entry value
                                       siteV1ConfigEntryStatus 1.3.6.1.4.1.26854.3.2.1.15.2.1.4 rowstatus read-only
The status of this table entry - not used, only for compliance
                               siteV1ConfigList 1.3.6.1.4.1.26854.3.2.1.15.3
                                   siteV1CfgNetworkDHCPEnabled 1.3.6.1.4.1.26854.3.2.1.15.3.1 displaystring read-write
The monitoring will try to get an IP with the DHCP protocol if this parameter is set to True. By default, this parameter is set to False.
                                   siteV1CfgNetworkIPAddressIfStatic 1.3.6.1.4.1.26854.3.2.1.15.3.2 displaystring read-write
The static IP address of the monitoring. This configuration parameter is not used if the DHCP is enabled. The default IP is 192.168.45.2.
                                   siteV1CfgNetworkSubnetMaskIfStatic 1.3.6.1.4.1.26854.3.2.1.15.3.3 displaystring read-write
The static Subnet Mask of the monitoring. This configuration parameter is not used if the DHCP is enabled. The default mask is 255.255.255.0.
                                   siteV1CfgNetworkDefaultGatewayIfStatic 1.3.6.1.4.1.26854.3.2.1.15.3.4 displaystring read-write
The static Default Gateway of the monitoring. This configuration parameter is not used if DHCP is enabled. This is only useful if the monitoring have to use a gateway, this is generally not necessary. The default gateway is 192.168.45.1.
                                   siteV1CfgNetworkDNSIfStatic 1.3.6.1.4.1.26854.3.2.1.15.3.5 displaystring read-write
The static DNS of the monitoring. This configuration parameter is used to resolve URI and server name. This is not necessary if you are only IP address as target server. The default DNS server is 192.168.45.1.
                                   siteV1CfgNetworkMaxTransmissionUnit 1.3.6.1.4.1.26854.3.2.1.15.3.8 displaystring read-write
Specifies the TCP/IP MTU for the network interface
                                   siteV1CfgTimeSNTPTimeServer 1.3.6.1.4.1.26854.3.2.1.15.3.11 displaystring read-write
The address of the server acting as SNTP timer server. If this server is not valid, the monitoring cannot update automatically his time. You can use several time server by usin a coma separator without space.
                                   siteV1CfgTimeTimeZoneName 1.3.6.1.4.1.26854.3.2.1.15.3.14 displaystring read-write
The Time Zone of the site
                                   siteV1CfgTimeSNTPTimeRefresh 1.3.6.1.4.1.26854.3.2.1.15.3.15 displaystring read-write
Set the time between synchronisation with the SNTP server (max 1000 hours, by default 178)
                                   siteV1CfgTimeSNTPTimeRecoveryRefresh 1.3.6.1.4.1.26854.3.2.1.15.3.16 displaystring read-write
Set the time to wait before retry if a synchronisation fail (max 1000 hours, by default 24)
                                   siteV1CfgWebServerWebServerSecurityEnabled 1.3.6.1.4.1.26854.3.2.1.15.3.22 displaystring read-write
This is a True/False parameter used to activate or deactivate the access control to the web server.
                                   siteV1CfgWebServerWebServerPort 1.3.6.1.4.1.26854.3.2.1.15.3.23 displaystring read-write
This is an unsigned integer parameter used to configure the port at which the web server is accessible. By default, the port is 80. If you change this port, you must be sure that the traffic is allowed by your switches and routers on this port.
                                   siteV1CfgWebServerWebAuthenticationMethod 1.3.6.1.4.1.26854.3.2.1.15.3.24 displaystring read-write
The web access security can be managed with 3 authentication methods: Basic Access, Digest Access or Basic with Radius.
                                   siteV1CfgWebServerHttpsWebServerPort 1.3.6.1.4.1.26854.3.2.1.15.3.26 displaystring read-write
This is a port number to activate or deactivate the https web server - 0 or 443 by default
                                   siteV1CfgWebServerDefaultPage 1.3.6.1.4.1.26854.3.2.1.15.3.31 displaystring read-write
The default page displayed on logon (dashboard, site, summary, alarm_event, ...)
                                   siteV1CfgXMLXMLEventPostingActivated 1.3.6.1.4.1.26854.3.2.1.15.3.41 displaystring read-write
This is a True/False parameter used to activate or deactivate the XML event posting.
                                   siteV1CfgXMLXMLEventPostingRefreshTime 1.3.6.1.4.1.26854.3.2.1.15.3.42 displaystring read-write
The minimal time in second between to calculation of the XML events to send. By default, this is done every two seconds.
                                   siteV1CfgXMLXMLEventPostingTimeout 1.3.6.1.4.1.26854.3.2.1.15.3.43 displaystring read-write
The timeout in millisecond when trying to post XML data to a Web Server.
                                   siteV1CfgXMLXMLEventPostingToSecOnlyIfPrimFail 1.3.6.1.4.1.26854.3.2.1.15.3.45 displaystring read-write
If this parameter is set to true, the events will be sent to secondary only if primary server is not available. If this parameter is set to false, all the events will be sent to primary and secondary server
                                   siteV1CfgXMLXMLTablesToPostOnXMLEvent 1.3.6.1.4.1.26854.3.2.1.15.3.46 displaystring read-write
The list of the tables to send when an event is generated. (description,alarm,data,config,control). This allows to have armada database updated on event.
                                   siteV1CfgXMLXMLHeartbeatTime 1.3.6.1.4.1.26854.3.2.1.15.3.51 displaystring read-write
This is the time between 2 XML Post of heartbeat. If set to 0, no heartbeat.
                                   siteV1CfgSNMPSNMPActivated 1.3.6.1.4.1.26854.3.2.1.15.3.61 displaystring read-write
This is a True/False parameter used to activate or deactivate the SNMP agent.
                                   siteV1CfgSNMPSNMPTrapVersion 1.3.6.1.4.1.26854.3.2.1.15.3.63 displaystring read-write
Traps/Notification can be sent with SNMP V1, V2c or V3 format.
                                   siteV1CfgSNMPSNMPGETMinSecurityLevel 1.3.6.1.4.1.26854.3.2.1.15.3.64 displaystring read-write
4 choices are available: No Authentication, V1 Community, V2c Community or V3.
                                   siteV1CfgSNMPSNMPSETMinSecurityLevel 1.3.6.1.4.1.26854.3.2.1.15.3.65 displaystring read-write
4 choices are available: No Authentication, V1 Community, V2c Community or V3.
                                   siteV1CfgSNMPSNMPV3AuthAlgorithm 1.3.6.1.4.1.26854.3.2.1.15.3.66 displaystring read-write
3 choices are available: MD5, SHA, Any
                                   siteV1CfgSNMPSNMPV3PrivacyAlgorithm 1.3.6.1.4.1.26854.3.2.1.15.3.67 displaystring read-write
3 choices are available: DES, AES, 3DES
                                   siteV1CfgSNMPSNMPV3PrivacyPassword 1.3.6.1.4.1.26854.3.2.1.15.3.68 displaystring read-write
The global SNMP V3 Encryption Password. This one is common for all the users to avoid complexity
                                   siteV1CfgSNMPSNMPV3EngineID 1.3.6.1.4.1.26854.3.2.1.15.3.69 displaystring read-write
The SNMP V3 Local Engine ID string
                                   siteV1CfgSNMPSNMPV3TrapAuthAlgorithm 1.3.6.1.4.1.26854.3.2.1.15.3.72 displaystring read-write
2 choices are available: MD5, SHA
                                   siteV1CfgSNMPSNMPV3TrapPrivacyAlgorithm 1.3.6.1.4.1.26854.3.2.1.15.3.73 displaystring read-write
3 choices are available: DES, AES, 3DES
                                   siteV1CfgSNMPSNMPV3TrapUsername 1.3.6.1.4.1.26854.3.2.1.15.3.74 displaystring read-write
The SNMP V3 Trap UserName used for all the SNMP V3 traps
                                   siteV1CfgSNMPSNMPV3TrapAuthPassword 1.3.6.1.4.1.26854.3.2.1.15.3.75 displaystring read-write
The SNMP V3 Trap Authentication Password
                                   siteV1CfgSNMPSNMPV3TrapPrivacyPassword 1.3.6.1.4.1.26854.3.2.1.15.3.76 displaystring read-write
The SNMP V3 Trap Privacy Password
                                   siteV1CfgSNMPSiteDescriptionIdsIncludedInTraps 1.3.6.1.4.1.26854.3.2.1.15.3.77 displaystring read-write
List of site Description Elements to send on traps. (to have the site reference and the city in each trap for example). The list is separated with ';'
                                   siteV1CfgGenericGenerateEventOnConfChanges 1.3.6.1.4.1.26854.3.2.1.15.3.81 displaystring read-write
This is a True/False parameter used to activate or deactivate the tracking of configuration changes
                                   siteV1CfgDataRecordsAutoArchivePeriodDataRecord 1.3.6.1.4.1.26854.3.2.1.15.3.82 displaystring read-write
Period in hour to auto save records (when detailled and long duration records are needed). 0 means disabled.
                                   siteV1CfgGenericGenerateEventOnControlExecution 1.3.6.1.4.1.26854.3.2.1.15.3.83 displaystring read-write
This is a True/False parameter used to activate or deactivate the tracking of control execution
                                   siteV1CfgGenericGenerateEventOnAlarmAcknowledge 1.3.6.1.4.1.26854.3.2.1.15.3.84 displaystring read-write
This is a True/False parameter used to activate or deactivate the tracking of alarm acknowledgment
                                   siteV1CfgInventoryRequiredCANBusNodeIDs 1.3.6.1.4.1.26854.3.2.1.15.3.91 displaystring read-write
This is a coma separated list with the required CAN bus node ids
                                   siteV1CfgInventoryLSSCANidrange 1.3.6.1.4.1.26854.3.2.1.15.3.92 displaystring read-write
By default 50-80, means up to 50 Can Nodes like rectifiers with CAN Id 50 to 80. To support up to 100 rectifiers, change it to 1-100.
                                   siteV1CfgInventorySystemNodesDefinition 1.3.6.1.4.1.26854.3.2.1.15.3.93 displaystring read-write
dc3(30-100)
                                   siteV1CfgInventoryLSSCANOpenSavedConf 1.3.6.1.4.1.26854.3.2.1.15.3.95 displaystring read-write
NA
                                   siteV1CfgUsersAdministratorLoginPassword 1.3.6.1.4.1.26854.3.2.1.15.3.101 displaystring read-write
This is the login and the password of the administrator. It is saved with a special syntax. First the login in clear, followed of 2 points, followed of the MD5 hashed password. If you change the login:password by entering a non hashed password, this last is automatically hashed.
                                   siteV1CfgUsersUser1LoginPassword 1.3.6.1.4.1.26854.3.2.1.15.3.102 displaystring read-write
This is the login and the password of the user number 1.
                                   siteV1CfgUsersUser2LoginPassword 1.3.6.1.4.1.26854.3.2.1.15.3.103 displaystring read-write
This is the login and the password of the user number 2.
                                   siteV1CfgUsersUser3LoginPassword 1.3.6.1.4.1.26854.3.2.1.15.3.104 displaystring read-write
This is the login and the password of the user number 3.
                                   siteV1CfgUsersUser4LoginPassword 1.3.6.1.4.1.26854.3.2.1.15.3.105 displaystring read-write
This is the login and the password of the user number 4.
                                   siteV1CfgUsersUser5LoginPassword 1.3.6.1.4.1.26854.3.2.1.15.3.106 displaystring read-write
This is the login and the password of the user number 5.
                                   siteV1CfgRadiusAuthenticationRadiusServer 1.3.6.1.4.1.26854.3.2.1.15.3.111 displaystring read-write
Radius Server address. If you have a secondary server, you could use a coma to separate it.
                                   siteV1CfgRadiusAuthenticationRadiusPort 1.3.6.1.4.1.26854.3.2.1.15.3.112 displaystring read-write
Radius Port. If you have a secondary server, you could use a coma to separate it.
                                   siteV1CfgRadiusAuthenticationRadiusSecret 1.3.6.1.4.1.26854.3.2.1.15.3.113 displaystring read-write
Radius PassPhrase
                                   siteV1CfgEmailEnableEmailFeature 1.3.6.1.4.1.26854.3.2.1.15.3.120 displaystring read-write
Enable/Disable the email feature
                                   siteV1CfgEmailSmtpServer 1.3.6.1.4.1.26854.3.2.1.15.3.121 displaystring read-write
Smtp Server. If you are using a domain name, make sure you configured the network Dns (CF5)
                                   siteV1CfgEmailSmtpDomain 1.3.6.1.4.1.26854.3.2.1.15.3.122 displaystring read-write
Smtp Domain. (Required by some servers.)
                                   siteV1CfgEmailSmtpUserLoginPassword 1.3.6.1.4.1.26854.3.2.1.15.3.123 displaystring read-write
Smtp Login and Password. The password is encrypted. To enter a new login and password, enter login:password and validate, the password will be encrypted.
                                   siteV1CfgEmailMailSender 1.3.6.1.4.1.26854.3.2.1.15.3.130 displaystring read-write
Mail Sender (The 'From' of the emails you will receive)
                                   siteV1CfgEmailMailRecipients 1.3.6.1.4.1.26854.3.2.1.15.3.131 displaystring read-write
Mail Recipients, separated with semicolon ';'
                                   siteV1CfgEmailMinimalSeverityTypeToSendMail 1.3.6.1.4.1.26854.3.2.1.15.3.135 displaystring read-write
This is the minimal severity of the event to send a Summary Mail
                                   siteV1CfgControllerAutomaticReboot 1.3.6.1.4.1.26854.3.2.1.15.3.150 displaystring read-write
Cron rules used in order to restart automatically the controller. Before rebooting configuration, events and data records are saved.
                                   siteV1CfgCloudLinkCloudEnabled 1.3.6.1.4.1.26854.3.2.1.15.3.161 displaystring read-write
Enable Cloud Connection
                                   siteV1CfgCloudLinkCloudServer 1.3.6.1.4.1.26854.3.2.1.15.3.162 displaystring read-write
Cloud Server
                                   siteV1CfgCloudLinkCloudPort 1.3.6.1.4.1.26854.3.2.1.15.3.163 displaystring read-write
Cloud Port
                                   siteV1CfgCloudLinkCloudCredential 1.3.6.1.4.1.26854.3.2.1.15.3.164 displaystring read-write
Enter Credential of your AlphaCloud account in order to connect. You have to enter username:password in order to save your credential.
                                   siteV1CfgCloudLinkCloudCluster 1.3.6.1.4.1.26854.3.2.1.15.3.165 displaystring read-write
Cloud Cluster
                                   siteV1CfgInventoryRS485ExtensionsConf 1.3.6.1.4.1.26854.3.2.1.15.3.210 displaystring read-write
The configuration string for RS485 Extensions
                                   siteV1CfgInventoryEthernetExtensionsConf 1.3.6.1.4.1.26854.3.2.1.15.3.220 displaystring read-write
The configuration string for Ethernet Extensions
                                   siteV1CfgScriptingEnabledscripts 1.3.6.1.4.1.26854.3.2.1.15.3.250 displaystring read-write
This parameter enable all CompasLua Scripting capabilities. You can control scripts in Files -> Files manager > scripting tab.
                                   siteV1CfgScriptingNumberofErrorsbeforetriggeringalarm 1.3.6.1.4.1.26854.3.2.1.15.3.251 displaystring read-write
Number of errors before triggering the scripting error alarm. When number of error is higher than this parameter, the alarm is triggered. If 0 is set, the alarm is deactivated
                                   siteV1CfgGenericReadAccessUserNumbers 1.3.6.1.4.1.26854.3.2.1.15.3.521 displaystring read-write
The list of the user numbers which have read access to this equipment. The user numbers are coma separated. The accepted user id are 1,2,3,4 and 5. Ex: 1,3,4
                                   siteV1CfgGenericWriteAccessUserNumbers 1.3.6.1.4.1.26854.3.2.1.15.3.522 displaystring read-write
The list of the user numbers which have write access to this equipment. This means that these users can modify the configuration element, the alarm settings and use the control elements. The user numbers are coma separated. The accepted user ids are 1,2,3,4 and 5. Ex: 1,3,4
                                   siteV1CfgGenericEventTableLength 1.3.6.1.4.1.26854.3.2.1.15.3.601 displaystring read-write
The maximum length of the table. The value must be comprised between 10 and 4000
                                   siteV1CfgSNMPSNMPTrapTargetsIP 1.3.6.1.4.1.26854.3.2.1.15.3.611 displaystring read-write
One or multiple target IP to send traps, coma separated. Ex: 130.145.23.1, 130.23.12.45
                                   siteV1CfgSNMPMinimalEventSeverityForTraps 1.3.6.1.4.1.26854.3.2.1.15.3.612 displaystring read-write
This is the minimal severity of the event to send a SNMP trap
                                   siteV1CfgXMLXMLEventsPrimPostURL 1.3.6.1.4.1.26854.3.2.1.15.3.651 displaystring read-write
This is the first URL at which the events related to this equipment must be posted. The XML ETSI standard is used in the posted data content.
                                   siteV1CfgXMLXMLEventsPrimPostLogin 1.3.6.1.4.1.26854.3.2.1.15.3.652 displaystring read-write
The login which must be used when posting events to the primary server
                                   siteV1CfgXMLXMLEventsPrimPostPassword 1.3.6.1.4.1.26854.3.2.1.15.3.653 displaystring read-write
The password which must be used when posting events to the primary server
                                   siteV1CfgXMLXMLEventsSecPostURL 1.3.6.1.4.1.26854.3.2.1.15.3.661 displaystring read-write
This is the second URL at which the events related to this equipment must be posted. The XML ETSI standard is used in the posted data content. This allows having redundancy with the management server.
                                   siteV1CfgXMLXMLEventsSecPostLogin 1.3.6.1.4.1.26854.3.2.1.15.3.662 displaystring read-write
The login which must be used when posting events to the secondary server
                                   siteV1CfgXMLXMLEventsSecPostPassword 1.3.6.1.4.1.26854.3.2.1.15.3.663 displaystring read-write
The password which must be used when posting events to the secondary server
                                   siteV1CfgPLCNumberOfPLCData 1.3.6.1.4.1.26854.3.2.1.15.3.901 displaystring read-write
The number of PLC data. Every equipment can manage up to 30 user programmable data. Data elements are automatically added in the data table. Configuration parameters are added to set the PLC Data Name and the PLC Data Mathematical calculation. In order to use these functionalities, you need a license with the 'PLC' module
                                   siteV1CfgPLCNumberOfPLCAlarm 1.3.6.1.4.1.26854.3.2.1.15.3.902 displaystring read-write
The number of PLC alarm. Every equipment can manage up to 30 user programmable alarms. Alarm elements are automatically added in the alarm table. The alarm parameters are added to set the PLC Alarm Name and the PLC Alarm Boolean condition. In order to use these functionalities, you need a licence with the 'PLC' module
                         siteV1Control 1.3.6.1.4.1.26854.3.2.1.16
                               siteV1ControlNumber 1.3.6.1.4.1.26854.3.2.1.16.1 integer32 read-only
The number of entries in the Control table related to the Site
                               siteV1ControlTable 1.3.6.1.4.1.26854.3.2.1.16.2 no-access
The table of Control entries related to the Site
                                   siteV1ControlEntry 1.3.6.1.4.1.26854.3.2.1.16.2.1 no-access
A Control entry
                                       siteV1ControlIndex 1.3.6.1.4.1.26854.3.2.1.16.2.1.1 unsigned32 no-access
The Control entry Index
                                       siteV1ControlName 1.3.6.1.4.1.26854.3.2.1.16.2.1.2 displaystring read-only
The Control entry name
                                       siteV1ControlValue 1.3.6.1.4.1.26854.3.2.1.16.2.1.3 displaystring read-write
The Control entry value
                                       siteV1ControlEntryStatus 1.3.6.1.4.1.26854.3.2.1.16.2.1.4 rowstatus read-only
The status of this table entry - not used, only for compliance
                               siteV1ControlList 1.3.6.1.4.1.26854.3.2.1.16.3
                                   siteV1CtrlControllerRebootController 1.3.6.1.4.1.26854.3.2.1.16.3.1 displaystring read-write
Writing a '1' to this control element will reboot the monitoring. Events and Records will be saved.
                                   siteV1CtrlControllerSaveConfAndRebootController 1.3.6.1.4.1.26854.3.2.1.16.3.2 displaystring read-write
Writing a '1' to this control element will first save the actual configuration and will reboot the monitoring after.
                                   siteV1CtrlControllerRebootControllerWithoutSavingRecords 1.3.6.1.4.1.26854.3.2.1.16.3.3 displaystring read-write
Writing a '1' to this control element will reboot the monitoring without saving records
                                   siteV1CtrlNetworkApplyNetworkConf 1.3.6.1.4.1.26854.3.2.1.16.3.6 displaystring read-write
Writing a '1' to this control element will reconfigure the ethernet according to the Network Configuration. If you change the IP address in the config table without using this command after, the configuration is not applied.
                                   siteV1CtrlTimeForceSNTPTimeRefresh 1.3.6.1.4.1.26854.3.2.1.16.3.11 displaystring read-write
Writing a '1' to this control element will force the monitoring to try to refresh his time with the configured SNTP Time Server.
                                   siteV1CtrlTimeSetLocalTime 1.3.6.1.4.1.26854.3.2.1.16.3.12 displaystring read-write
Writing a date and time to this control element allows to manually change the local time of the monitoring. The syntax of the date and the time is: 2007-11-19T13:02:34
                                   siteV1CtrlTimeSetUTCTime 1.3.6.1.4.1.26854.3.2.1.16.3.13 displaystring read-write
Writing a date and time to this control element allows to manually change the UTC time of the monitoring. The syntax of the date and the time is: 2007-11-19T13:02:34
                                   siteV1CtrlTimeResetUptime 1.3.6.1.4.1.26854.3.2.1.16.3.14 displaystring read-write
Writing a '1' to this control element will reset the uptime of the monitoring.
                                   siteV1CtrlControllerCleanandSaveXMLUserConf 1.3.6.1.4.1.26854.3.2.1.16.3.20 displaystring read-write
Writing a '1' to this control element will remove the configuration sections related to missing equipments, than save all the configuration of all the connected equipment in a XML format. This file is read when the monitoring is starting in order to configure the monitoring. This file is also accessible trough the FTP server or can be downloaded trough the web interface.
                                   siteV1CtrlControllerSaveXMLUserConf 1.3.6.1.4.1.26854.3.2.1.16.3.21 displaystring read-write
Writing a '1' to this control element will save all the configuration of all the connected (or previously connected) equipment in a XML format. This file is read when the monitoring is starting in order to configure the monitoring. This file is also accessible trough the FTP server or can be downloaded trough the web interface.
                                   siteV1CtrlControllerSaveInventory 1.3.6.1.4.1.26854.3.2.1.16.3.22 displaystring read-write
Writing a '1' to this control element will save save the inventory in a XML format. This file is read when the monitoring is starting in order to configure the monitoring. This file is also accessible trough the FTP server or can be downloaded trough the web interface.
                                   siteV1CtrlDataRecordsSaveDataRecords 1.3.6.1.4.1.26854.3.2.1.16.3.33 displaystring read-write
Writing a '1' to this control element will force the monitoring to save all the data records. This is useful if you want to unpower the Comp@s monitoring. This function is called automatically everyday.
                                   siteV1CtrlDataRecordsExportDataRecordsinCSV 1.3.6.1.4.1.26854.3.2.1.16.3.34 displaystring read-write
Writing a '1' to this control element will force the monitoring to save all the CVS records files. The CSV files are stored in the records folder.
                                   siteV1CtrlDataRecordsArchiveDataRecords 1.3.6.1.4.1.26854.3.2.1.16.3.35 displaystring read-write
Writing a '1' to this control element will force the monitoring to save all the data records. This is useful if you want to unpower the Comp@s monitoring. This function is called automatically everyday.
                                   siteV1CtrlDataRecordsDeleteAllDataRecords 1.3.6.1.4.1.26854.3.2.1.16.3.36 displaystring read-write
Writing a '1' to this control element will force the monitoring to save all the data records. This is useful if you want to unpower the Comp@s monitoring. This function is called automatically everyday.
                                   siteV1CtrlControllerEmulateRecords 1.3.6.1.4.1.26854.3.2.1.16.3.40 displaystring read-write
NA
                                   siteV1CtrlControllerReloadTranslations 1.3.6.1.4.1.26854.3.2.1.16.3.41 displaystring read-write
Writing a '1' to this control element will reload all the csv translation files
                                   siteV1CtrlControllerReloadLicense 1.3.6.1.4.1.26854.3.2.1.16.3.51 displaystring read-write
Writing a '1' to this control element will reload the license file
                                   siteV1CtrlControllerManageFTPServer 1.3.6.1.4.1.26854.3.2.1.16.3.55 displaystring read-write
This Control is used to manage the FTP Server
                                   siteV1CtrlInventoryRemoveAbsentEquipments 1.3.6.1.4.1.26854.3.2.1.16.3.61 displaystring read-write
NA
                                   siteV1CtrlInventoryResetCANBusNode 1.3.6.1.4.1.26854.3.2.1.16.3.81 displaystring read-write
Writing a valid CAN bus node id to this control element will reset the correspondent device.
                                   siteV1CtrlInventorySaveCANOpenLSSConf 1.3.6.1.4.1.26854.3.2.1.16.3.82 displaystring read-write
NA
                                   siteV1CtrlInventoryStartNewInventory 1.3.6.1.4.1.26854.3.2.1.16.3.83 displaystring read-write
NA
                                   siteV1CtrlInventoryUpgradeNodeFirmware 1.3.6.1.4.1.26854.3.2.1.16.3.91 displaystring read-write
This control element is used to start the firmware upgrade of a CAN bus Node. You need to upload first the firmware trough ftp in the /user/firmware path. Then you need to write the id number of the CAN Node, followed by a coma, followed by the file name. Example : '101,SOFT_0000030_01.txt'.
                                   siteV1CtrlInventoryCancelFirmwareUpgrade 1.3.6.1.4.1.26854.3.2.1.16.3.92 displaystring read-write
This control element is used to cancel the running firmware upgrade of a CAN bus Node.
                                   siteV1CtrlFilesFlashBinary 1.3.6.1.4.1.26854.3.2.1.16.3.103 displaystring read-write
This control element is used to start a binary flash update. You need to upload first the firmware trough ftp in the /user/firmware path.
                                   siteV1CtrlFilesDownloadFileFromUrl 1.3.6.1.4.1.26854.3.2.1.16.3.110 displaystring read-write
This control element is used to download a file wiht HTTP get, the argument is an url. The file is saved in the upload folder
                                   siteV1CtrlFilesDeleteUserUploadedFile 1.3.6.1.4.1.26854.3.2.1.16.3.111 displaystring read-write
This control element is used to delete a file in the user-upload folder. This is riskless as these files are not used, they are temporary files.
                                   siteV1CtrlFilesMoveUserUploadedFile 1.3.6.1.4.1.26854.3.2.1.16.3.112 displaystring read-write
This control element is used to copy a file from the user-upload folder to another one. Be aware of what your are doing !
                                   siteV1CtrlFilesExtractZipFileinuserupload 1.3.6.1.4.1.26854.3.2.1.16.3.113 displaystring read-write
This control element is used to delete a file in the user-upload folder. This is riskless as these files are not used, they are temporary files.
                                   siteV1CtrlEmailSendSummaryEmail 1.3.6.1.4.1.26854.3.2.1.16.3.120 displaystring read-write
This control element is used to force the sending of a summary to the configured mail address
                                   siteV1CtrlScriptingControlLuaScript 1.3.6.1.4.1.26854.3.2.1.16.3.250 displaystring read-write
This control element is used to control the lua scripting system. Available command are: enable[Enable Lua Capabilities], disable[Disable Lua Capabilities], restart[Restart All Lua Capabilities], refresh[Read the folder script (if you added a file when system is running)], enable filename[enable filename.lua located in folder user/scripts], disable filename[disable filename.lua located in folder user/scripts], restart filename : Restart fileName[file must be enabled], reseterrors[Reset all errors counters], reseterrors filename[Reset errors from filename
                                   siteV1CtrlControllerAdvancedFunctionGenericCommandExecution 1.3.6.1.4.1.26854.3.2.1.16.3.300 displaystring read-write
This control is used to perform advanced operation.
                                   siteV1CtrlGenericClearMyEvents 1.3.6.1.4.1.26854.3.2.1.16.3.501 displaystring read-write
By writing '1' to this control element, all the events of this equipment will be cleared.
                                   siteV1CtrlGenericClearAllEvents 1.3.6.1.4.1.26854.3.2.1.16.3.502 displaystring read-write
By writing '1' to this control element, all the events of this equipment and all the events of all the sub-equipments will be cleared.
                                   siteV1CtrlGenericAddEvent 1.3.6.1.4.1.26854.3.2.1.16.3.511 displaystring read-write
This control element adds an event of severity none. The event name is the text written to this control element
                                   siteV1CtrlGenericAddMajorEvent 1.3.6.1.4.1.26854.3.2.1.16.3.512 displaystring read-write
This control element adds an event of severity major. The event name is the text written to this control element
                                   siteV1CtrlGenericResetDefaultNamesAndGroups 1.3.6.1.4.1.26854.3.2.1.16.3.521 displaystring read-write
This control element resets all the element Names, Groups and Subgroups to default values for this equipment
                                   siteV1CtrlGenericResetDefaultNamesAndGroupsRecursive 1.3.6.1.4.1.26854.3.2.1.16.3.522 displaystring read-write
This control element resets all the element Names, Groups and Subgroups to default values for this equipment and all sub equipments
                         siteV1Notifications 1.3.6.1.4.1.26854.3.2.1.18
                               siteV1NotificationPrefix 1.3.6.1.4.1.26854.3.2.1.18.0
                                   siteV1NotificationOfEvent 1.3.6.1.4.1.26854.3.2.1.18.0.1
Notification generated when a new event appears
                         siteV1Compliance 1.3.6.1.4.1.26854.3.2.1.19
                               siteV1ComplianceGroups 1.3.6.1.4.1.26854.3.2.1.19.1
                                   siteV1GlobalGroup 1.3.6.1.4.1.26854.3.2.1.19.1.1
text
                                   siteV1NotificationGroup 1.3.6.1.4.1.26854.3.2.1.19.1.2
text
                               siteV1FullCompliance 1.3.6.1.4.1.26854.3.2.1.19.2
The compliance statement for SNMPV2 entities which implement the SNMPV2 MIB.
                         energySystems 1.3.6.1.4.1.26854.3.2.1.20
                               es1 1.3.6.1.4.1.26854.3.2.1.20.1
                                   es1GlobalStatus 1.3.6.1.4.1.26854.3.2.1.20.1.1 displaystring read-only
A textual string (alarms, normal or unknown) containing the status of the Energy System
                                   es1GlobalAlarmSeverityType 1.3.6.1.4.1.26854.3.2.1.20.1.2 displaystring read-only
The alarm severity type (critical, major, minor, warning, none, disabled) of the Energy System
                                   es1GlobalAlarmSeverityLevel 1.3.6.1.4.1.26854.3.2.1.20.1.3 integer32 read-only
The alarm severity level (0-9) of the Energy System
                                   es1GlobalAlarmSeverityTypeInt 1.3.6.1.4.1.26854.3.2.1.20.1.4 integer32 read-only
The alarm severity type as integer (critical=4, major=3, minor=2, warning=1, none=0) of the Energy System
                                   es1Description 1.3.6.1.4.1.26854.3.2.1.20.1.10
                                         es1DescriptionNumber 1.3.6.1.4.1.26854.3.2.1.20.1.10.1 integer32 read-only
The number of entries in the Energy System Description table
                                         es1DescriptionTable 1.3.6.1.4.1.26854.3.2.1.20.1.10.2 no-access
The Description table of the Energy System
                                             es1DescriptionEntry 1.3.6.1.4.1.26854.3.2.1.20.1.10.2.1 no-access
A Description entry
                                                 es1DescriptionIndex 1.3.6.1.4.1.26854.3.2.1.20.1.10.2.1.1 unsigned32 no-access
Description Index
                                                 es1DescriptionName 1.3.6.1.4.1.26854.3.2.1.20.1.10.2.1.2 displaystring read-only
Description Name
                                                 es1DescriptionValue 1.3.6.1.4.1.26854.3.2.1.20.1.10.2.1.3 displaystring read-only
Description Value
                                                 es1DescriptionEntryStatus 1.3.6.1.4.1.26854.3.2.1.20.1.10.2.1.4 rowstatus read-only
The status of this table entry
                                         es1DescriptionList 1.3.6.1.4.1.26854.3.2.1.20.1.10.3
                                             es1DescDescriptionDescription 1.3.6.1.4.1.26854.3.2.1.20.1.10.3.1 displaystring read-write
A free text zone to write a system description
                                             es1DescDescriptionReference 1.3.6.1.4.1.26854.3.2.1.20.1.10.3.2 displaystring read-write
A free text zone to write the customer reference of the system
                                   es1Alarm 1.3.6.1.4.1.26854.3.2.1.20.1.11
                                         es1AlarmNumber 1.3.6.1.4.1.26854.3.2.1.20.1.11.1 integer32 read-only
The number of entries in the Energy System Alarm table
                                         es1AlarmTable 1.3.6.1.4.1.26854.3.2.1.20.1.11.2 no-access
The table of Alarm entries
                                             es1AlarmEntry 1.3.6.1.4.1.26854.3.2.1.20.1.11.2.1 no-access
An alarm entry
                                                 es1AlarmIndex 1.3.6.1.4.1.26854.3.2.1.20.1.11.2.1.1 unsigned32 no-access
Alarm Index
                                                 es1AlarmName 1.3.6.1.4.1.26854.3.2.1.20.1.11.2.1.2 displaystring read-only
Alarm Name
                                                 es1AlarmActive 1.3.6.1.4.1.26854.3.2.1.20.1.11.2.1.3 displaystring read-only
Is the Alarm active ? 'true' for active, 'false' for not-active
                                                 es1AlarmSeverityType 1.3.6.1.4.1.26854.3.2.1.20.1.11.2.1.4 displaystring read-write
The alarm severity type (major, minor, warning, none, disabled) of this alarm entry
                                                 es1AlarmSeverityLevel 1.3.6.1.4.1.26854.3.2.1.20.1.11.2.1.5 displaystring read-write
The alarm severity level (0-9) of this alarm entry
                                                 es1AlarmStartTime 1.3.6.1.4.1.26854.3.2.1.20.1.11.2.1.6 displaystring read-only
The last start time of this alarm entry (null if never active)
                                                 es1AlarmStopTime 1.3.6.1.4.1.26854.3.2.1.20.1.11.2.1.7 displaystring read-only
The last stop time of this alarm entry (null if alarm active)
                                                 es1AlarmEntryStatus 1.3.6.1.4.1.26854.3.2.1.20.1.11.2.1.8 rowstatus read-only
The status of this table entry - not used, only for MIB compliance
                                         es1AlarmSummary 1.3.6.1.4.1.26854.3.2.1.20.1.11.3 bits read-only
Summary bit vector with all the alarms state of the Energy System. A '1' means alarm active, '0' means not active. Unimplemented alarms are always '0'. Bits: 'none': 0.
                                   es1Event 1.3.6.1.4.1.26854.3.2.1.20.1.12
                                         es1EventNumber 1.3.6.1.4.1.26854.3.2.1.20.1.12.1 integer32 read-only
The number of entries in the Event Table related to the Energy System
                                         es1EventTable 1.3.6.1.4.1.26854.3.2.1.20.1.12.2 no-access
The Event table related to the Energy System
                                             es1EventEntry 1.3.6.1.4.1.26854.3.2.1.20.1.12.2.1 no-access
.
                                                 es1EventIndex 1.3.6.1.4.1.26854.3.2.1.20.1.12.2.1.1 unsigned32 no-access
Event Index
                                                 es1EventId 1.3.6.1.4.1.26854.3.2.1.20.1.12.2.1.2 unsigned32 read-only
Event Index
                                                 es1EventName 1.3.6.1.4.1.26854.3.2.1.20.1.12.2.1.3 displaystring read-only
Event Name
                                                 es1EventDateTime 1.3.6.1.4.1.26854.3.2.1.20.1.12.2.1.4 displaystring read-only
The date and time of the event
                                                 es1EventSeverityType 1.3.6.1.4.1.26854.3.2.1.20.1.12.2.1.5 displaystring read-only
The event severity type ('major', 'minor', 'warning' or 'none')
                                                 es1EventSeverityLevel 1.3.6.1.4.1.26854.3.2.1.20.1.12.2.1.6 displaystring read-only
The event severity level (0-9)
                                                 es1EventEntryStatus 1.3.6.1.4.1.26854.3.2.1.20.1.12.2.1.7 rowstatus read-only
The status of this table entry
                                   es1Data 1.3.6.1.4.1.26854.3.2.1.20.1.13
                                         es1DataNumber 1.3.6.1.4.1.26854.3.2.1.20.1.13.1 integer32 read-only
The number of entries in the Data Table related to the Energy System
                                   es1Config 1.3.6.1.4.1.26854.3.2.1.20.1.15
                                         es1ConfigNumber 1.3.6.1.4.1.26854.3.2.1.20.1.15.1 integer32 read-only
The number of entries in the Config table related to the Energy System
                                         es1ConfigTable 1.3.6.1.4.1.26854.3.2.1.20.1.15.2 no-access
The table of Config entries related to the Energy System
                                             es1ConfigEntry 1.3.6.1.4.1.26854.3.2.1.20.1.15.2.1 no-access
A Config entry
                                                 es1ConfigIndex 1.3.6.1.4.1.26854.3.2.1.20.1.15.2.1.1 unsigned32 no-access
The Config entry Index
                                                 es1ConfigName 1.3.6.1.4.1.26854.3.2.1.20.1.15.2.1.2 displaystring read-only
The Config entry name
                                                 es1ConfigValue 1.3.6.1.4.1.26854.3.2.1.20.1.15.2.1.3 displaystring read-write
The Config entry value
                                                 es1ConfigEntryStatus 1.3.6.1.4.1.26854.3.2.1.20.1.15.2.1.4 rowstatus read-only
The status of this table entry - not used, only for compliance
                                         es1ConfigList 1.3.6.1.4.1.26854.3.2.1.20.1.15.3
                                             es1CfgEnergyMeterNumberOfGenericPulseEnergyCounter 1.3.6.1.4.1.26854.3.2.1.20.1.15.3.100 displaystring read-write
NA
                                   es1Control 1.3.6.1.4.1.26854.3.2.1.20.1.16
                                         es1ControlNumber 1.3.6.1.4.1.26854.3.2.1.20.1.16.1 integer32 read-only
The number of entries in the Control table related to the Energy System
                                         es1ControlTable 1.3.6.1.4.1.26854.3.2.1.20.1.16.2 no-access
The table of Control entries related to the Energy System
                                             es1ControlEntry 1.3.6.1.4.1.26854.3.2.1.20.1.16.2.1 no-access
A Control entry
                                                 es1ControlIndex 1.3.6.1.4.1.26854.3.2.1.20.1.16.2.1.1 unsigned32 no-access
The Control entry Index
                                                 es1ControlName 1.3.6.1.4.1.26854.3.2.1.20.1.16.2.1.2 displaystring read-only
The Control entry name
                                                 es1ControlValue 1.3.6.1.4.1.26854.3.2.1.20.1.16.2.1.3 displaystring read-write
The Control entry value
                                                 es1ControlEntryStatus 1.3.6.1.4.1.26854.3.2.1.20.1.16.2.1.4 rowstatus read-only
The status of this table entry - not used, only for compliance
                                         es1ControlList 1.3.6.1.4.1.26854.3.2.1.20.1.16.3
                                             es1CtrlGenericClearMyEvents 1.3.6.1.4.1.26854.3.2.1.20.1.16.3.501 displaystring read-write
By writing '1' to this control element, all the events of this equipment will be cleared.
                                             es1CtrlGenericClearAllEvents 1.3.6.1.4.1.26854.3.2.1.20.1.16.3.502 displaystring read-write
By writing '1' to this control element, all the events of this equipment and all the events of all the sub-equipments will be cleared.
                                             es1CtrlGenericAddEvent 1.3.6.1.4.1.26854.3.2.1.20.1.16.3.511 displaystring read-write
This control element adds an event of severity none. The event name is the text written to this control element
                                             es1CtrlGenericAddMajorEvent 1.3.6.1.4.1.26854.3.2.1.20.1.16.3.512 displaystring read-write
This control element adds an event of severity major. The event name is the text written to this control element
                                             es1CtrlGenericResetDefaultNamesAndGroups 1.3.6.1.4.1.26854.3.2.1.20.1.16.3.521 displaystring read-write
This control element resets all the element Names, Groups and Subgroups to default values for this equipment
                                             es1CtrlGenericResetDefaultNamesAndGroupsRecursive 1.3.6.1.4.1.26854.3.2.1.20.1.16.3.522 displaystring read-write
This control element resets all the element Names, Groups and Subgroups to default values for this equipment and all sub equipments
                                   es1Notifications 1.3.6.1.4.1.26854.3.2.1.20.1.18
                                         es1NotificationPrefix 1.3.6.1.4.1.26854.3.2.1.20.1.18.0
                                             es1NotificationOfEvent 1.3.6.1.4.1.26854.3.2.1.20.1.18.0.1
Notification generated when a new event appears
                                   es1Compliance 1.3.6.1.4.1.26854.3.2.1.20.1.19
                                         es1ComplianceGroups 1.3.6.1.4.1.26854.3.2.1.20.1.19.1
                                             es1GlobalGroup 1.3.6.1.4.1.26854.3.2.1.20.1.19.1.1
text
                                             es1NotificationGroup 1.3.6.1.4.1.26854.3.2.1.20.1.19.1.2
text
                                         es1FullCompliance 1.3.6.1.4.1.26854.3.2.1.20.1.19.2
The compliance statement for SNMPV2 entities which implement the SNMPV2 MIB.
                                   es1DCSystems 1.3.6.1.4.1.26854.3.2.1.20.1.20
                                         es1dc1 1.3.6.1.4.1.26854.3.2.1.20.1.20.1
                                             es1dc1GlobalStatus 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.1 displaystring read-only
A textual string (alarms, normal or unknown) containing the status of the DC System
                                             es1dc1GlobalAlarmSeverityType 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.2 displaystring read-only
The alarm severity type (critical, major, minor, warning, none, disabled) of the DC System
                                             es1dc1GlobalAlarmSeverityLevel 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.3 integer32 read-only
The alarm severity level (0-9) of the DC System
                                             es1dc1GlobalAlarmSeverityTypeInt 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.4 integer32 read-only
The alarm severity type as integer (critical=4, major=3, minor=2, warning=1, none=0) of the DC System
                                             es1dc1Description 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10
                                                   es1dc1DescriptionNumber 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.1 integer32 read-only
The number of entries in the DC System Description table
                                                   es1dc1DescriptionTable 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.2 no-access
The Description table of the DC System
                                                       es1dc1DescriptionEntry 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.2.1 no-access
A Description entry
                                                           es1dc1DescriptionIndex 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.2.1.1 unsigned32 no-access
Description Index
                                                           es1dc1DescriptionName 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.2.1.2 displaystring read-only
Description Name
                                                           es1dc1DescriptionValue 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.2.1.3 displaystring read-only
Description Value
                                                           es1dc1DescriptionEntryStatus 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.2.1.4 rowstatus read-only
The status of this table entry
                                                   es1dc1DescriptionList 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3
                                                       es1dc1DescDescriptionDescription 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.1 displaystring read-write
A free text zone to write a system description
                                                       es1dc1DescDescriptionReference 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.2 displaystring read-write
A free text zone to write the customer reference of the system
                                                       es1dc1DescDescriptionProductName 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.11 displaystring read-only
The product name of the DC system monitoring
                                                       es1dc1DescDescriptionHardwareReference 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.12 displaystring read-only
The hardware reference of the DC system monitoring
                                                       es1dc1DescDescriptionSoftwareReference 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.14 displaystring read-only
The software reference of the DC system monitoring
                                                       es1dc1DescDescriptionSerialNumber 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.16 displaystring read-only
The serial number of the DC system monitoring
                                                       es1dc1DescDescriptionManufacturingDate 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.18 displaystring read-only
The production date of the DC system monitoring
                                                       es1dc1DescDescriptionDistributionModuleProductName 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.31 displaystring read-only
The product name of the Electronic Distribution/LVD Module
                                                       es1dc1DescDescriptionDistributionModuleHardwareReference 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.32 displaystring read-only
The hardware reference of the Electronic Distribution/LVD Module
                                                       es1dc1DescDescriptionDistributionModuleSoftwareReference 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.34 displaystring read-only
The software reference of the Electronic Distribution/LVD Module
                                                       es1dc1DescDescriptionDistributionModuleSerialNumber 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.36 displaystring read-only
The serial number of the Electronic Distribution/LVD Module
                                                       es1dc1DescDescriptionDistributionModuleManufacturingDate 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.10.3.38 displaystring read-only
The manufacturing date of the Electronic Distribution/LVD Module
                                             es1dc1Alarm 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11
                                                   es1dc1AlarmNumber 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.1 integer32 read-only
The number of entries in the DC System Alarm table
                                                   es1dc1AlarmTable 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.2 no-access
The table of Alarm entries
                                                       es1dc1AlarmEntry 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.2.1 no-access
An alarm entry
                                                           es1dc1AlarmIndex 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.2.1.1 unsigned32 no-access
Alarm Index
                                                           es1dc1AlarmName 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.2.1.2 displaystring read-only
Alarm Name
                                                           es1dc1AlarmActive 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.2.1.3 displaystring read-only
Is the Alarm active ? 'true' for active, 'false' for not-active
                                                           es1dc1AlarmSeverityType 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.2.1.4 displaystring read-write
The alarm severity type (major, minor, warning, none, disabled) of this alarm entry
                                                           es1dc1AlarmSeverityLevel 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.2.1.5 displaystring read-write
The alarm severity level (0-9) of this alarm entry
                                                           es1dc1AlarmStartTime 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.2.1.6 displaystring read-only
The last start time of this alarm entry (null if never active)
                                                           es1dc1AlarmStopTime 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.2.1.7 displaystring read-only
The last stop time of this alarm entry (null if alarm active)
                                                           es1dc1AlarmEntryStatus 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.2.1.8 rowstatus read-only
The status of this table entry - not used, only for MIB compliance
                                                   es1dc1AlarmSummary 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.11.3 bits read-only
Summary bit vector with all the alarms state of the DC System. A '1' means alarm active, '0' means not active. Unimplemented alarms are always '0'. Bits: 'dCBusDCBusExtraHigh': 3, 'dCBusDCBusVoltageSenseFail': 4, 'rectifiersMissingRectifiers': 11, 'batBatOnDischarge': 13, 'lVDBatLVDRelOpen': 16, 'rectifiersMoreThanOneRectifierFail': 10, 'rectifiersOneRectifierFail': 9, 'dCBusDCBusExtraLow': 0, 'aCBusMainsLow': 7, 'digInputsDigInput3': 28, 'digInputsDigInput2': 27, 'digInputsDigInput1': 26, 'batBatTempTooHigh': 17, 'dCBusDCBusLow': 1, 'digInputsDigInput4': 29, 'digInputsBatBreakerOpen': 25, 'digInputsDistributionBreakerOpen': 24, 'sensorsAmbientTempSensorFail': 22, 'sensorsAmbientTempTooHigh': 20, 'dCBusDCBusHigh': 2, 'sensorsAmbientTempTooLow': 21, 'aCBusMainsPartialFail': 6, 'batBatTempSensorFail': 19, 'aCBusMainsFail': 5, 'batBatTempTooLow': 18, 'batBatLastTestFailed': 12.
                                             es1dc1Event 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12
                                                   es1dc1EventNumber 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12.1 integer32 read-only
The number of entries in the Event Table related to the DC System
                                                   es1dc1EventTable 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12.2 no-access
The Event table related to the DC System
                                                       es1dc1EventEntry 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12.2.1 no-access
.
                                                           es1dc1EventIndex 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12.2.1.1 unsigned32 no-access
Event Index
                                                           es1dc1EventId 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12.2.1.2 unsigned32 read-only
Event Index
                                                           es1dc1EventName 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12.2.1.3 displaystring read-only
Event Name
                                                           es1dc1EventDateTime 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12.2.1.4 displaystring read-only
The date and time of the event
                                                           es1dc1EventSeverityType 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12.2.1.5 displaystring read-only
The event severity type ('major', 'minor', 'warning' or 'none')
                                                           es1dc1EventSeverityLevel 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12.2.1.6 displaystring read-only
The event severity level (0-9)
                                                           es1dc1EventEntryStatus 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.12.2.1.7 rowstatus read-only
The status of this table entry
                                             es1dc1Data 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13
                                                   es1dc1DataNumber 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.1 integer32 read-only
The number of entries in the Data Table related to the DC System
                                                   es1dc1DataTable 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.2 no-access
The table of Data entries
                                                       es1dc1DataEntry 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.2.1 no-access
A data entry
                                                           es1dc1DataIndex 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.2.1.1 unsigned32 no-access
The data index
                                                           es1dc1DataName 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.2.1.2 displaystring read-only
The data name
                                                           es1dc1DataValue 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.2.1.3 displaystring read-only
The data value
                                                           es1dc1DataEntryStatus 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.2.1.4 rowstatus read-only
The status of this table entry - not used, only present for compliance
                                                   es1dc1DataList 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3
                                                       es1dc1DataSystemDCMode 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.1 integer32 read-only
The DC system can have 5 values: 'Float'(0), 'Equalize'(1), 'Battery Test'(2), 'Ac Failure'(3) or 'Safe'(5)
                                                       es1dc1DataSystemPreviousDCMode 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.2 integer32 read-only
The previous value of the DC Mode : 'Float'(0), 'Equalize'(1), 'Battery Test'(2), 'Ac Failure'(3) or 'Safe'(5)
                                                       es1dc1DataSystemNiMHChargeMode 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.5 integer32 read-only
NA
                                                       es1dc1DataDCBusBusVoltage 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.11 integer32 read-only
The DC bus voltage in volt.
                                                       es1dc1DataSystemRatioDeliveredOnAvailablePower 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.12 integer32 read-only
This is the ratio of the delivered power divided by the installed power, in %.
                                                       es1dc1DataACBusMinutesSinceLastACFailBegin 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.13 integer32 read-only
The number of minute since the last AC Failure begin
                                                       es1dc1DataACBusMinutesSinceLastACFailEnd 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.14 integer32 read-only
The number of minute since the last AC Failure end
                                                       es1dc1DataRectifiersRectifiersOutPower 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.21 integer32 read-only
The sum of the delivered rectifier power
                                                       es1dc1DataRectifiersRectifiersOutCurrent 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.22 integer32 read-only
The sum of the delivered rectifier current
                                                       es1dc1DataRectifiersRectifiersOutPowerMax 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.23 integer32 read-only
The sum of the deliverable rectifier power
                                                       es1dc1DataRectifiersRectifiersOutCurrentMax 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.24 integer32 read-only
The sum of the deliverable rectifier current
                                                       es1dc1DataRectifiersNumberOfRectifierMax 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.31 integer32 read-only
The maximum possible number of rectifier in this dc system
                                                       es1dc1DataRectifiersNumberOfPresentRectifier 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.32 integer32 read-only
The actual number of present rectifier in this dc system
                                                       es1dc1DataRectifiersNumberOfAbsentRectifier 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.33 integer32 read-only
The actual number of absent rectifier in this dc system
                                                       es1dc1DataRectifiersNumberOfActiveRectifier 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.34 integer32 read-only
The actual number of active rectifier in this dc system. An active rectifier is a rectifier which is present, DC OK, AC OK and not in remote off.
                                                       es1dc1DataRectifiersNumberOfACFailRectifier 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.35 integer32 read-only
The actual number or rectifier in AC Failure.
                                                       es1dc1DataRectifiersNumberOfDCFailRectifier 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.36 integer32 read-only
The actual number or rectifier with DC Failure.
                                                       es1dc1DataRectifiersNumberOfRemoteOffRectifier 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.37 integer32 read-only
The actual number or rectifier in remote off.
                                                       es1dc1DataRectifiersNumberOfOverTempRectifier 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.38 integer32 read-only
The actual number or rectifier in Over Temperature.
                                                       es1dc1DataLoadLoadPower 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.51 integer32 read-only
Estimation of the load power consumption
                                                       es1dc1DataLoadLoadCurrent 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.52 integer32 read-only
Estimation of the load current consumption
                                                       es1dc1DataBatBatInputCurrent 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.61 integer32 read-only
Measurement of the battery input current. A negative value means that the battery is discharging
                                                       es1dc1DataBatBatInputPower 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.62 integer32 read-only
Measurement of the battery input power. A negative value means that the battery is discharging
                                                       es1dc1DataBatBatTemp 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.71 integer32 read-only
The battery temperature
                                                       es1dc1DataBatBatTestState 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.72 integer32 read-only
This is about the result of the last battery test. 10 values are possible : 'Never Tested'(0), 'Success'(1), 'On Going'(2), 'Failed: Timeout'(3), 'Failed: Vbus Too Low'(4), 'Failed: Load Too Low'(5), 'Failed: Ac Failure'(6), 'Failed: Canceled' (7), 'Failed: Lvd Opened'(8), 'Failed: No Battery'(9)
                                                       es1dc1DataBatLastBatTestDischargedCapacityRatio 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.73 integer32 read-only
This is the battery capacity, in percent, discharged during the last battery test. This value is updated at the end of the battery test.
                                                       es1dc1DataBatLastBatTestDischargedCapacity 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.74 integer32 read-only
This is the battery capacity, in ampere hour, discharged during the last battery test. This value is updated at the end of the battery test.
                                                       es1dc1DataBatLastBatTestFinalVoltage 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.75 integer32 read-only
This is the bus voltage at the end of the last battery test. This value is updated at the end of the battery test.
                                                       es1dc1DataBatBatTestDuration 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.76 integer32 read-only
The duration of the last battery test. This value is updated at the end of the battery test. This value can't be higher than 1440 minutes (24 hours).
                                                       es1dc1DataBatPreviousBatTestDischargedCapacityRatio 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.77 integer32 read-only
This is the battery capacity, in percent, discharged during the previous battery test. This value is shifted at the end of the battery test.
                                                       es1dc1DataBatPreviousBatTestDischargedCapacity 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.78 integer32 read-only
This is the battery capacity, in ampere hour, discharged during the previous battery test. This value is shifted at the end of the battery test.
                                                       es1dc1DataBatPreviousBatTestFinalVoltage 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.79 integer32 read-only
This is the bus voltage at the end of the previous battery test. This value is shifted at the end of the battery test.
                                                       es1dc1DataBatPreviousBatTestDuration 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.80 integer32 read-only
The duration of the previous battery test. This value is shifted at the end of the battery test. This value can't be higher than 1440 minutes (24 hours).
                                                       es1dc1DataBatPreviousBatTestState 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.81 integer32 read-only
The result of the previous battery test - 10 values are possible: 'Never Tested'(0), 'Success'(1), 'On Going'(2), 'Failed: Timeout'(3), 'Failed: Vbus Too Low'(4), 'Failed: Load Too Low'(5), 'Failed: Ac Failure'(6), 'Failed: Canceled', 'Failed: Lvd Opened'(8), 'Failed: No Battery'(9)
                                                       es1dc1DataBatMinutesSinceLastTestBat 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.82 integer32 read-only
The number of minute since the end of last battery test
                                                       es1dc1DataBatNextScheduledBatTest 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.84 integer32 read-only
The date and time of the next time the scheduled battery test will run
                                                       es1dc1DataBatBatChargeCapacity 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.91 integer32 read-only
The battery charge capacity, calculated by integration of the current.
                                                       es1dc1DataBatCalculatedAutonomy 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.92 integer32 read-only
Calculation of the remaining autonomy. This value can change following the load of your system and the maximal depth of dicharge configuration (CF39).
                                                       es1dc1DataBatBatCurrentIntegration 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.94 integer32 read-only
Actual value of the integration of the current, in Ampere * hour
                                                       es1dc1DataLVDLVDState 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.101 integer32 read-only
Actual state of the LVD
                                                       es1dc1DataRelsRel1State 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.111 integer32 read-only
Actual state of the Relay 1
                                                       es1dc1DataRelsRel2State 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.112 integer32 read-only
Actual state of the Relay 2
                                                       es1dc1DataRelsRel3State 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.113 integer32 read-only
Actual state of the Relay 3
                                                       es1dc1DataRelsRel4State 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.114 integer32 read-only
Actual state of the Relay 3
                                                       es1dc1DataSmartEnergyEfficiencyOptimizedNumberOfRectifier 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.121 integer32 read-only
The optimal number of ON rectifier for Efficiency Optimization
                                                       es1dc1DataSmartEnergySystemLossWithoutOptimisation 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.122 integer32 read-only
Estimation of the losses without optimisation
                                                       es1dc1DataSmartEnergySystemLossWithOptimisation 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.123 integer32 read-only
Estimation of the losses with optimisation
                                                       es1dc1DataSmartEnergyRectifierModelUsedForCalculation 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.124 integer32 read-only
The rectifier model used
                                                       es1dc1DataSmartEnergySmartEnergySavings 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.125 integer32 read-only
Estimation of the losses with optimisation
                                                       es1dc1DataSensorsAmbientTemp 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.151 integer32 read-only
The ambiant temperature (second temperature sense)
                                                       es1dc1DataSensorsPulseCounter4 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.204 integer32 read-only
The counter value of the digital input 4.
                                             es1dc1Config 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15
                                                   es1dc1ConfigNumber 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.1 integer32 read-only
The number of entries in the Config table related to the DC System
                                                   es1dc1ConfigTable 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.2 no-access
The table of Config entries related to the DC System
                                                       es1dc1ConfigEntry 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.2.1 no-access
A Config entry
                                                           es1dc1ConfigIndex 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.2.1.1 unsigned32 no-access
The Config entry Index
                                                           es1dc1ConfigName 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.2.1.2 displaystring read-only
The Config entry name
                                                           es1dc1ConfigValue 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.2.1.3 displaystring read-write
The Config entry value
                                                           es1dc1ConfigEntryStatus 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.2.1.4 rowstatus read-only
The status of this table entry - not used, only for compliance
                                                   es1dc1ConfigList 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3
                                                       es1dc1CfgDCBusDCBusFloatVoltageat25degC 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.1 displaystring read-write
The floating dc bus voltage of the system at 25 Celsius degree
                                                       es1dc1CfgDCBusDCBusVoltageExtraLow 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.2 displaystring read-write
The bus voltage under which the alarm 'DC Bus Voltage Extra Low' is set.
                                                       es1dc1CfgDCBusDCBusVoltageExtraLowHysteresis 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.3 displaystring read-write
The voltage hysteresis on the alarm 'DC Bus Voltage Extra Low'.
                                                       es1dc1CfgDCBusDCBusVoltageLow 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.4 displaystring read-write
The bus voltage under which the alarm 'DC Bus Voltage Low' is set.
                                                       es1dc1CfgDCBusDCBusVoltageLowHysteresis 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.5 displaystring read-write
The voltage hysteresis on the alarm 'DC Bus Voltage Low
                                                       es1dc1CfgDCBusDCBusVoltageHigh 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.6 displaystring read-write
The bus voltage over which the alarm 'DC Bus Voltage High' is set.
                                                       es1dc1CfgDCBusDCBusVoltageHighHysteresis 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.7 displaystring read-write
The voltage hysteresis on the alarm 'DC Bus Voltage High
                                                       es1dc1CfgDCBusDCBusVoltageExtraHigh 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.8 displaystring read-write
The bus voltage over which the alarm 'DC Bus Voltage Extra High' is set.
                                                       es1dc1CfgDCBusDCBusVoltageExtraHighHysteresis 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.9 displaystring read-write
The voltage hysteresis on the alarm 'DC Bus Voltage Extra High
                                                       es1dc1CfgLVDLVDDisconnectVoltage 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.10 displaystring read-write
The dc bus voltage under which the battery must be disconnected of the bus. This allows preserving the battery life. The load will be unpowered. This value has to be lower than the Battery test end voltage (CF70)
                                                       es1dc1CfgLVDLVDDisconnectDelay 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.11 displaystring read-write
The delay in second before disconnecting the battery if the dc bus voltage is under the configured disconnected voltage. This avoids disconnection during a low bus transient.
                                                       es1dc1CfgBatTempCompensationSlope 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.21 displaystring read-write
The slope of the battery temperature compensation in mv/degree. For a 48V system, -72mV/degree is often used.
                                                       es1dc1CfgBatMaxPosTempCompensation 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.22 displaystring read-write
The maximal allowed positive compensation.
                                                       es1dc1CfgBatMaxNegTempCompensation 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.23 displaystring read-write
The maximal allowed negative compensation.
                                                       es1dc1CfgRectifiersMinimalNumberOfPresentRectifiers 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.25 displaystring read-write
The minimal number of rectifier which must be present. If there is less present rectifiers, the alarm 'Missing Rectifiers' is set.
                                                       es1dc1CfgRectifiersRectifierModel 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.26 displaystring read-write
The rectifier model
                                                       es1dc1CfgRectifiersForcedRemoteOffRectifers 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.27 displaystring read-write
A list of rectifier which are forced in remote off. The id of the rectifier must be coma separated. Ex: 1,3 will maintain rectifier 1 and 3 off.
                                                       es1dc1CfgBatBatChargeCurrentLimit 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.31 displaystring read-write
The maximal battery current when the battery is charging. The monitoring regulates the bus voltage in order to satisfy this condition. This parameter is often equal to the nominal battery capacity divided by 10.
                                                       es1dc1CfgBatBatStringCapacity 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.32 displaystring read-write
The battery capacity in Ah.
                                                       es1dc1CfgBatBatTempLow 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.33 displaystring read-write
The temperature under which the alarm 'Battery Temperature Too Low' must be set.
                                                       es1dc1CfgBatBatTempHigh 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.34 displaystring read-write
The temperature over which the alarm 'Battery Temperature Too High' must be set.
                                                       es1dc1CfgBatBatTempHysteresis 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.35 displaystring read-write
The hysteresis on the 'Battery Temperature Too High' and 'Battery Temperature Too Low' alarms.
                                                       es1dc1CfgBatMinimalCurrentForDischargingAlarm 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.36 displaystring read-write
The minimal discharging current to set the 'Battery On Discharge' alarm.
                                                       es1dc1CfgBatCurrentHysteresisForDischargingAlarm 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.37 displaystring read-write
The hysteresis on the 'Battery On Discharge' alarm.
                                                       es1dc1CfgBatPeukertNumber 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.38 displaystring read-write
The Peukert number relates to the internal resistance of a battery and provides an indication of the excpected capacity. The ideal number is 1. This value can be calculated with the formula: (ln(t2)-ln(t1))/(ln(i1)-ln(i2)) where tx is the autonomy in hours at a constant discharge current of ix Amps. Often, we use t1 = 1h and t2 = 10h
                                                       es1dc1CfgBatMaxDepthOfDischargeforAutonomyEstimation 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.39 displaystring read-write
It is generally recommended to discharge maximum 60% of the battery capacity to enhance battery lifetime. By default, 100% is used for autonomy calculation. This parameter can also be used to take into account the age of the battery
                                                       es1dc1CfgBatBoostAutomatic 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.51 displaystring read-write
The boost mode must be automatically after the fact that during a mains failure, the bus voltage went under the configured 'Boost Activation Low Voltage'. This allows charging the battery faster.
                                                       es1dc1CfgBatBoostActivationLowVoltage 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.52 displaystring read-write
The voltage under which the boost mode can be activated.
                                                       es1dc1CfgBatBoostTerminationVoltage 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.53 displaystring read-write
The voltage over which the system must go back to floating mode.
                                                       es1dc1CfgBatBoostTerminationCurrent 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.54 displaystring read-write
The battery charging current under which the system must go back to floating mode.
                                                       es1dc1CfgBatBoostTerminationTime 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.55 displaystring read-write
The time in minute after which the system must go back in floating mode.
                                                       es1dc1CfgBatBatTestType 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.69 displaystring read-write
Type of the battery test:
Capacity based: The battery must give the requested capacity before falling lower than a value
Time Based: The battery must sustain a defined load during a defined time.
                                                       es1dc1CfgBatBatTestEndVoltage 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.70 displaystring read-write
The voltage at which any battery test must be stopped. This value has to be higher than the LVD Disconnect voltage (CF10)
                                                       es1dc1CfgBatBatTestDischargeRatio 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.71 displaystring read-write
The ratio of the battery capacity to discharge. If 30 is set, 30% of the battery will be discharged during the test
                                                       es1dc1CfgBatBatTestInterval 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.72 displaystring read-write
The number of days between two automatically started battery test. If this parameter is set to 0, the battery test is not started automatically. The user can remotely or locally start or force this test.
                                                       es1dc1CfgBatBatTestDischargeCurrent 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.73 displaystring read-write
The current at which the battery must be discharged during a battery test. The monitoring regulates the bus voltage in order to satisfy this condition. The load current must be of course higher than this parameter.
                                                       es1dc1CfgBatBatTestMinimalDischargeCurrent 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.74 displaystring read-write
The battery current under which the battery test must be stopped because the load is too low.
                                                       es1dc1CfgBatBatTestDuration 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.75 displaystring read-write
The timeout in minute after which the battery test must be stopped.
                                                       es1dc1CfgBatBatTestRequMinutesWithoutMainsFail 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.76 displaystring read-write
The minimal time in minute without mains failure in order to allow a battery start. This parameter is not taken into account when the battery test is forced.
                                                       es1dc1CfgBatBatTestSchedulerCronRule 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.77 displaystring read-write
NA
                                                       es1dc1CfgSmartEnergySmartEnergyBooleanCond 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.83 displaystring read-write
This is the boolean condition which allows or not to automatically optimize the number of rectifier in remote off.
                                                       es1dc1CfgLVDBatLVDNodeId 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.86 displaystring read-write
This is a list of the node id of the Smart Electronic LVDs, coma separated
                                                       es1dc1CfgDigInputsDigInput1Name 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.91 displaystring read-write
The name of the digital input 1
                                                       es1dc1CfgDigInputsDigInput1NormallyClosed 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.92 displaystring read-write
True/False value defining if the digital input 1 is normally closed. If this digital input is not in this default state, the related alarm is set.
                                                       es1dc1CfgDigInputsDigInput2Name 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.93 displaystring read-write
The name of the digital input 2
                                                       es1dc1CfgDigInputsDigInput2NormallyClosed 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.94 displaystring read-write
True/False value defining if the digital input 2 is normally closed. If this digital input is not in this default state, the related alarm is set.
                                                       es1dc1CfgDigInputsDigInput3Name 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.95 displaystring read-write
The name of the digital input 3
                                                       es1dc1CfgDigInputsDigInput3NormallyClosed 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.96 displaystring read-write
True/False value defining if the digital input 3 is normally closed. If this digital input is not in this default state, the related alarm is set.
                                                       es1dc1CfgDigInputsDigInput4Name 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.97 displaystring read-write
The name of the digital input 4
                                                       es1dc1CfgDigInputsDigInput4NormallyClosed 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.98 displaystring read-write
True/False value defining if the digital input 4 is normally closed. If this digital input is not in this default state, the related alarm is set.
                                                       es1dc1CfgDigInputsDigInput5Name 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.99 displaystring read-write
The name of the digital input 5
                                                       es1dc1CfgDigInputsDigInput5NormallyClosed 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.100 displaystring read-write
True/False value defining if the digital input 5 is normally closed. If this digital input is not in this default state, the related alarm is set.
                                                       es1dc1CfgDigInputsDigInput6Name 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.101 displaystring read-write
The name of the digital input 6
                                                       es1dc1CfgDigInputsDigInput6NormallyClosed 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.102 displaystring read-write
True/False value defining if the digital input 6 is normally closed. If this digital input is not in this default state, the related alarm is set.
                                                       es1dc1CfgRelsDryAlarm1AlternativeBooleanCond 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.111 displaystring read-write
Another Boolean condition to activate the dry alarm relay 1. The way to define boolean condition is detailed in the PLC chapter.
                                                       es1dc1CfgRelsDryAlarm2AlternativeBooleanCond 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.112 displaystring read-write
Another Boolean condition to activate the dry alarm relay 2. The way to define boolean condition is detailed in the PLC chapter.
                                                       es1dc1CfgRelsDryAlarm3AlternativeBooleanCond 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.113 displaystring read-write
Another Boolean condition to activate the dry alarm relay 3. The way to define boolean condition is detailed in the PLC chapter.
                                                       es1dc1CfgRelsDryAlarm4AlternativeBooleanCond 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.114 displaystring read-write
Another Boolean condition to activate the dry alarm relay 4. The way to define boolean condition is detailed in the PLC chapter.
                                                       es1dc1CfgSensorsAmbientTempLow 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.131 displaystring read-write
The temperature under which the alarm 'Ambiant Temperature Too Low' must be set.
                                                       es1dc1CfgSensorsAmbientTempHigh 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.132 displaystring read-write
The temperature under which the alarm 'Ambiant Temperature Too Low' must be set.
                                                       es1dc1CfgSensorsAmbientTempHysteresis 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.133 displaystring read-write
The hysteresis on the 'Battery Temperature Too High' and 'Battery Temperature Too Low' alarms.
                                                       es1dc1CfgGenericReadAccessUserNumbers 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.521 displaystring read-write
The list of the user numbers which have read access to this equipment. The user numbers are coma separated. The accepted user id are 1,2,3,4 and 5. Ex: 1,3,4
                                                       es1dc1CfgGenericWriteAccessUserNumbers 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.522 displaystring read-write
The list of the user numbers which have write access to this equipment. This means that these users can modify the configuration element, the alarm settings and use the control elements. The user numbers are coma separated. The accepted user ids are 1,2,3,4 and 5. Ex: 1,3,4
                                                       es1dc1CfgGenericEventTableLength 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.601 displaystring read-write
The maximum length of the table. The value must be comprised between 10 and 4000
                                                       es1dc1CfgGenericEventTableLengthByRectifier 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.602 displaystring read-write
The maximum length of the table. The value must be comprised between 10 and 4000
                                                       es1dc1CfgPLCNumberOfPLCData 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.901 displaystring read-write
The number of PLC data. Every equipment can manage up to 30 user programmable data. Data elements are automatically added in the data table. Configuration parameters are added to set the PLC Data Name and the PLC Data Mathematical calculation. In order to use these functionalities, you need a license with the 'PLC' module
                                                       es1dc1CfgPLCNumberOfPLCAlarm 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.15.3.902 displaystring read-write
The number of PLC alarm. Every equipment can manage up to 30 user programmable alarms. Alarm elements are automatically added in the alarm table. The alarm parameters are added to set the PLC Alarm Name and the PLC Alarm Boolean condition. In order to use these functionalities, you need a licence with the 'PLC' module
                                             es1dc1Control 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16
                                                   es1dc1ControlNumber 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.1 integer32 read-only
The number of entries in the Control table related to the DC System
                                                   es1dc1ControlTable 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.2 no-access
The table of Control entries related to the DC System
                                                       es1dc1ControlEntry 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.2.1 no-access
A Control entry
                                                           es1dc1ControlIndex 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.2.1.1 unsigned32 no-access
The Control entry Index
                                                           es1dc1ControlName 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.2.1.2 displaystring read-only
The Control entry name
                                                           es1dc1ControlValue 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.2.1.3 displaystring read-write
The Control entry value
                                                           es1dc1ControlEntryStatus 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.2.1.4 rowstatus read-only
The status of this table entry - not used, only for compliance
                                                   es1dc1ControlList 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3
                                                       es1dc1CtrlSystemBackToFloat 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.1 displaystring read-write
The dc system must go back in floating mode.
                                                       es1dc1CtrlSystemStartBatTest 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.2 displaystring read-write
The dc system must start a battery test.
                                                       es1dc1CtrlSystemForceBatTest 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.3 displaystring read-write
The dc system must force a battery test.
                                                       es1dc1CtrlSystemStartBoostMode 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.4 displaystring read-write
The dc system must go in boost mode.
                                                       es1dc1CtrlLVDOpenTheLVD 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.11 displaystring read-write
Try to open the LVD. It could not work if the LVD is electronic, and the request will be canceled after 15 sec.
                                                       es1dc1CtrlLVDCloseTheLVD 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.12 displaystring read-write
The LVD must be closed
                                                       es1dc1CtrlBatCorrectBatCurrentOffset 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.21 displaystring read-write
NA
                                                       es1dc1CtrlBatResetLastBatTestState 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.41 displaystring read-write
Reset the state of the last battery test. If an alarm 'Battery Last Test Failed' is set, the alarm will be cleared.
                                                       es1dc1CtrlSaveSaveConfInMCU 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.51 displaystring read-write
Save configuration parameters in the MCU microcontroller. If comp@s is not present, the system will be correctly managed.
                                                       es1dc1CtrlAdvancedSetMCUSpecificConfId 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.55 displaystring read-write
This control allows to reconfigure the MCU to support specific hardware configuration, with embedded distribution for example
                                                       es1dc1CtrlDigInputsSetDigInput4CounterValue 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.61 displaystring read-write
Set Counter Value
                                                       es1dc1CtrlRelsInvertRel1StateForXSeconds 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.111 displaystring read-write
Generate Pulse on relay 1
                                                       es1dc1CtrlRelsInvertRel2StateForXSeconds 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.112 displaystring read-write
Generate Pulse on relay 2
                                                       es1dc1CtrlRelsInvertRel3StateForXSeconds 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.113 displaystring read-write
Generate Pulse on relay 3
                                                       es1dc1CtrlRelsInvertRel4StateForXSeconds 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.114 displaystring read-write
Generate Pulse on relay 4
                                                       es1dc1CtrlGenericClearMyEvents 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.501 displaystring read-write
By writing '1' to this control element, all the events of this equipment will be cleared.
                                                       es1dc1CtrlGenericClearAllEvents 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.502 displaystring read-write
By writing '1' to this control element, all the events of this equipment and all the events of all the sub-equipments will be cleared.
                                                       es1dc1CtrlGenericAddEvent 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.511 displaystring read-write
This control element adds an event of severity none. The event name is the text written to this control element
                                                       es1dc1CtrlGenericAddMajorEvent 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.512 displaystring read-write
This control element adds an event of severity major. The event name is the text written to this control element
                                                       es1dc1CtrlGenericResetDefaultNamesAndGroups 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.521 displaystring read-write
This control element resets all the element Names, Groups and Subgroups to default values for this equipment
                                                       es1dc1CtrlGenericResetDefaultNamesAndGroupsRecursive 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.16.3.522 displaystring read-write
This control element resets all the element Names, Groups and Subgroups to default values for this equipment and all sub equipments
                                             es1dc1Notifications 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.18
                                                   es1dc1NotificationPrefix 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.18.0
                                                       es1dc1NotificationOfEvent 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.18.0.1
Notification generated when a new event appears
                                             es1dc1Compliance 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.19
                                                   es1dc1ComplianceGroups 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.19.1
                                                       es1dc1GlobalGroup 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.19.1.1
text
                                                       es1dc1NotificationGroup 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.19.1.2
text
                                                   es1dc1FullCompliance 1.3.6.1.4.1.26854.3.2.1.20.1.20.1.19.2
The compliance statement for SNMPV2 entities which implement the SNMPV2 MIB.
                                   es1InverterSystems 1.3.6.1.4.1.26854.3.2.1.20.1.25
                                   es1RemotePowerFeedingSystems 1.3.6.1.4.1.26854.3.2.1.20.1.28
                         extensions 1.3.6.1.4.1.26854.3.2.1.21