VENDOR: SCHLEIFENBAUER PRODUCTS BV
Home | MIB: SDEVICE-MIB | |||
---|---|---|---|---|
Download as: |
Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
|
|||
Object Name | OID | Type | Access | Info |
schleifenbauer | 1.3.6.1.4.1.31034 |
This MIB describes the functions of the Schleifenbauer device family. |
||
device0 | 1.3.6.1.4.1.31034.2 | |||
identification | 1.3.6.1.4.1.31034.2.3 | |||
spdmVersion | 1.3.6.1.4.1.31034.2.3.1 | integer32 | read-only |
Data model version, currently 1.10 |
firmwareVersion | 1.3.6.1.4.1.31034.2.3.2 | integer32 | read-only |
The units firmware revision number. |
buildNumber | 1.3.6.1.4.1.31034.2.3.3 | displaystring | read-only |
Date and time of latest build of the firmware. |
salesOrderNumber | 1.3.6.1.4.1.31034.2.3.4 | displaystring | read-only |
SP sales order number. |
productId | 1.3.6.1.4.1.31034.2.3.5 | displaystring | read-only |
SP product id. |
serialNumber | 1.3.6.1.4.1.31034.2.3.6 | displaystring | read-only |
SP serial number. |
hardwareAddress | 1.3.6.1.4.1.31034.2.3.7 | displaystring | read-only |
Hardware serial number; cannot be changed. Can be used as backup unit address. format as 3 unsigned ints separated by dashes: int - int - int |
macAddress | 1.3.6.1.4.1.31034.2.3.8 | displaystring | read-only |
The ethernet interfaces unique hardware address. |
unitAddress | 1.3.6.1.4.1.31034.2.3.9 | integer32 | read-write |
User defined address; this will be used for addressing the unit. |
deviceName | 1.3.6.1.4.1.31034.2.3.10 | displaystring | read-write |
User configurable device name or identifier. |
deviceLocation | 1.3.6.1.4.1.31034.2.3.11 | displaystring | read-write |
User configurable device location identifier. |
vanityTag | 1.3.6.1.4.1.31034.2.3.12 | displaystring | read-write |
Characters to be displayed as vanity tekst in display. |
configuration | 1.3.6.1.4.1.31034.2.4 | |||
noPhases | 1.3.6.1.4.1.31034.2.4.1 | integer32 | read-only |
Either zero, one or three for no input metering, single or three phase system |
noOutletsTotal | 1.3.6.1.4.1.31034.2.4.2 | integer32 | read-only |
Total number of outlets, even hardwired without switch/measure modules. |
noSwitchedOutlets | 1.3.6.1.4.1.31034.2.4.3 | integer32 | read-only |
Number of switched outlets. If outlet numbering is non-contiguous: the highest outlet number. |
noMeasuredOutlets | 1.3.6.1.4.1.31034.2.4.4 | integer32 | read-only |
Number of measured outlets. If outlet numbering is non-contiguous: the highest outlet number. |
noSensors | 1.3.6.1.4.1.31034.2.4.5 | integer32 | read-only |
The number of external, digital environmental sensors: 0 for none, 1 to 16 depending on number of reported sensors |
maximumLoad | 1.3.6.1.4.1.31034.2.4.6 | integer32 | read-only |
Maximum rated load of device per phase, usually either 16 or 32 A. |
systemstatus | 1.3.6.1.4.1.31034.2.5 | |||
deviceStatusCode | 1.3.6.1.4.1.31034.2.5.1 | integer32 | read-only |
Returns an internal status or error code. 0 = OK, 16 = watchdog timer caused reset, 128 = slave module was reset, 144 = both previous. |
temperatureAlert | 1.3.6.1.4.1.31034.2.5.2 | integer32 | read-only |
An alert has been raised due to temperature exceeding treshhold; 0= no alert; 1= internal unit temp, 2= external sensor. |
inputCurrentAlert | 1.3.6.1.4.1.31034.2.5.3 | integer32 | read-only |
An alert has been raised due to current exceeding treshhold; 0=no alert; 1-3 for input phase. |
outputCurrentAlert | 1.3.6.1.4.1.31034.2.5.4 | integer32 | read-only |
An alert has been raised due to current exceeding treshhold; 0=no alert; 1-48 for outlet. |
inputVoltageAlert | 1.3.6.1.4.1.31034.2.5.5 | integer32 | read-only |
An alert has been raised due to a voltage dip; 0=no alert; 1-3 for input phase. |
oCurrentDropAlert | 1.3.6.1.4.1.31034.2.5.6 | integer32 | read-only |
An alert has been raised due to the current of a measured outlet suddenly dropping to near zero, possibly indicating a blown fuse; 0=no alert; 1-48 for outlet. |
iCurrentDropAlert | 1.3.6.1.4.1.31034.2.5.7 | integer32 | read-only |
An alert has been raised due to the current of a measured input suddenly dropping to near zero, possibly indicating a blown fuse; 0=no alert; 1-3 for phase. |
reset | 1.3.6.1.4.1.31034.2.6 | |||
rebootDevice | 1.3.6.1.4.1.31034.2.6.1 | integer32 | read-write |
Warm reboot/reset of device; note: this will have no effect on outlet status! |
resetAlerts | 1.3.6.1.4.1.31034.2.6.2 | integer32 | read-write |
Reset all alert signals. |
zeroInputKWhSubtotal | 1.3.6.1.4.1.31034.2.6.3 | integer32 | read-write |
Reset of input kWh subtotal counters to zero. |
zeroOutKWhSubtotal | 1.3.6.1.4.1.31034.2.6.4 | integer32 | read-write |
Reset of outlet kWh subtotal counter to zero. |
resetPeakValues | 1.3.6.1.4.1.31034.2.6.5 | integer32 | read-write |
Reset all peak values to zero, as well input as output metering, voltages dips, current peaks and temperatures. |
settings | 1.3.6.1.4.1.31034.2.7 | |||
general | 1.3.6.1.4.1.31034.2.7.1 | |||
peakDuration | 1.3.6.1.4.1.31034.2.7.1.4 | milliseconds | read-write |
A current peak should last at least [stpkdr] MilliSeconds before an alert is raised; max about a minute. |
fixedOutletDelay | 1.3.6.1.4.1.31034.2.7.1.5 | milliseconds | read-write |
Minimal delay between two successive relay switches in milliseconds. Minimal delay is 100 ms. Will always be respected! |
powerSaverMode | 1.3.6.1.4.1.31034.2.7.1.6 | seconds | read-write |
Set backlight on time in seconds; 0 keeps display always on. Note that keeping the backlight on may decrease luminosity over time. Setting this to other values than 10, 60, 120 or 240 is incompatible with the gateway! |
outletPowerupMode | 1.3.6.1.4.1.31034.2.7.1.7 | integer32 | read-write |
Behaviour of outlet on power-up: 0=off; 1=same state as at power down; 2=same state, but delayed by individual delay timer. |
maximumTemperature | 1.3.6.1.4.1.31034.2.7.1.8 | integer32 | read-write |
An alert should be generated whenever the temperature of the first connected T sensor is above this value. Zero means disabled. |
displayOrientation | 1.3.6.1.4.1.31034.2.7.1.9 | integer32 | read-write |
0 no display; display off; 1 vertical, display on top; 2 vertical, upside down; 3 horizontal, display at left; 4 horizontal, display at right |
localAlertReset | 1.3.6.1.4.1.31034.2.7.1.10 | integer32 | read-write |
Allow alerts to be reset locally on device by pushing one of the buttons. [replaces dipDuration] |
currentDropDetection | 1.3.6.1.4.1.31034.2.7.1.11 | integer32 | read-write |
Enables the current drop detection function. 0 = always off (default), 1 = input (s) only, 2 = output(s) only, 3 = both inputs and outputs. |
wirelessDisplayPower | 1.3.6.1.4.1.31034.2.7.1.12 | integer32 | read-write |
Controls the transit power of the wireless display transciever (if installed). Set to zero to completely disable the module. |
inputmeasuresTable | 1.3.6.1.4.1.31034.2.8 | no-access |
This table contains all measures related to the measured inputs of the DEVICE. Note: either 1 or 3 channels, depending on number of phases measured. |
|
1.3.6.1.4.1.31034.2.8.1 | no-access |
The record containing the registers for the channel selected by channelIndex. |
||
channelIndex6 | 1.3.6.1.4.1.31034.2.8.1.1 | integer32 | no-access |
The channel. Its value ranges between 1 and 48, depending on the number of channels, usually 1. |
kWhTotalI | 1.3.6.1.4.1.31034.2.8.1.2 | kilowatthour | read-only |
Either the only phase in a single phase measurement; or one of the three phases in a multiphase measurement. |
kWhSubtotalI | 1.3.6.1.4.1.31034.2.8.1.3 | kilowatthour | read-only |
kWh subtotal register of the only phase in a single phase measurement; or one of three phases in a multiphase measurement. Reset to zero with [rsimks]. |
powerFactorI | 1.3.6.1.4.1.31034.2.8.1.4 | decipowerfactor | read-only |
The effective power factor in percent. |
actualCurrentI | 1.3.6.1.4.1.31034.2.8.1.5 | deciamps | read-only |
Actual apparent, RMS current. |
peakCurrentI | 1.3.6.1.4.1.31034.2.8.1.6 | deciamps | read-only |
Peak apparent, RMS current; highest value since last reset of the alerts. |
actualVoltageI | 1.3.6.1.4.1.31034.2.8.1.7 | decivolts | read-only |
The actual voltage. |
minVoltageI | 1.3.6.1.4.1.31034.2.8.1.8 | decivolts | read-only |
RMS voltage dip; lowest value since reset of alerts. |
powerVAI | 1.3.6.1.4.1.31034.2.8.1.9 | integer32 | read-only |
Power value calculated, not in data model of device. |
powerWattI | 1.3.6.1.4.1.31034.2.8.1.10 | integer32 | read-only |
Power value calculated by the gateway, not in data model of device. |
maxInletAmps | 1.3.6.1.4.1.31034.2.8.1.11 | deciamps | read-write |
Maximum current per input phase in A; should last at least [stpkdr] MilliSeconds before triggering an alert. |
inputCTratio | 1.3.6.1.4.1.31034.2.8.1.12 | integer32 | read-write |
The multiplier to use in case of use of /5 current transformers. Defaults to 1. |
inputName | 1.3.6.1.4.1.31034.2.8.1.13 | displaystring | read-write |
User configurable naming of inputs or phases. Useful if channels are used to measure branches.. |
outletsTable | 1.3.6.1.4.1.31034.2.9 | no-access |
This table contains the customer specific settings, determining toutlestablehe behaviour of the DEVICE. |
|
1.3.6.1.4.1.31034.2.9.1 | no-access |
The record containing the registers forthe channel selected by channelIndex. |
||
channelIndex4 | 1.3.6.1.4.1.31034.2.9.1.1 | integer32 | no-access |
The channel. Its value ranges between 1 and 48, depending on the number of channels, usually 1. |
outletName | 1.3.6.1.4.1.31034.2.9.1.2 | displaystring | read-only |
User configurable naming of individual outlets. Useful to distinguish outlets based on customer or device name. |
outputmeasuresTable | 1.3.6.1.4.1.31034.2.10 | no-access |
This table contains all measures related to the measured outputs of the DEVICE. Note: up to 48 channels, depending on number of measured outlets. |
|
1.3.6.1.4.1.31034.2.10.1 | no-access |
The record containing the registers for the channel selected by channelIndex. |
||
channelIndex7 | 1.3.6.1.4.1.31034.2.10.1.1 | integer32 | no-access |
The channel. Its value ranges between 1 and 48, depending on the number of channels, usually 1. |
kWhTotalO | 1.3.6.1.4.1.31034.2.10.1.2 | kilowatthour | read-only |
Total kWh of selected output. |
kWhSubtotalO | 1.3.6.1.4.1.31034.2.10.1.3 | kilowatthour | read-only |
kWh subtotal register of selected output. Reset to zero with [rsomks]. |
powerFactorO | 1.3.6.1.4.1.31034.2.10.1.4 | decipowerfactor | read-only |
Power factor of output. |
actualCurrentO | 1.3.6.1.4.1.31034.2.10.1.5 | deciamps | read-only |
Actual apparent, RMS current. |
peakCurrentO | 1.3.6.1.4.1.31034.2.10.1.6 | deciamps | read-only |
Peak apparent, RMS current; highest value since last reset of alerts. |
actualVoltageO | 1.3.6.1.4.1.31034.2.10.1.7 | decivolts | read-only |
Actual voltage on output. |
maxOutletAmps | 1.3.6.1.4.1.31034.2.10.1.8 | deciamps | read-write |
Maximum current per outlet in A; should last at least [stpkdr] MilliSeconds before triggering an alert. |
outputCTratio | 1.3.6.1.4.1.31034.2.10.1.9 | integer32 | read-write |
The multiplier to use in case of use of /5 current transformers. Defaults to 1. |
switchedoutletsTable | 1.3.6.1.4.1.31034.2.11 | no-access |
This table contains the current status of switchable DEVICE's. |
|
1.3.6.1.4.1.31034.2.11.1 | no-access |
The record containing the registers for the channel selected by channelIndex. |
||
channelIndex5 | 1.3.6.1.4.1.31034.2.11.1.1 | integer32 | no-access |
The channel. Its value ranges between 1 and 48, depending on the number of channels, usually 1. |
currentState | 1.3.6.1.4.1.31034.2.11.1.2 | integer32 | read-write |
The actual state of the outlet relays. The hardware will contain max 48 outlets. Writing is only effective after setting [swounl]. |
scheduled | 1.3.6.1.4.1.31034.2.11.1.3 | integer32 | read-only |
A one indicates pending activity; the switch delay has not yet expired. |
unlock | 1.3.6.1.4.1.31034.2.11.1.4 | integer32 | read-write |
Setting the value to one will release the safety for this outlet for a couple seconds; switching and rebooting are then temporarily enabled. |
individualOutletDelay | 1.3.6.1.4.1.31034.2.11.1.5 | seconds | read-write |
Delay before an individual outlet switches on at power-up in Seconds. |
sensorTable | 1.3.6.1.4.1.31034.2.12 | no-access |
This table contains the environmental measurements. As well internal temperature as external temperature probes. |
|
1.3.6.1.4.1.31034.2.12.1 | no-access |
The record containing the registers for the channel selected by channelIndex. |
||
channelIndex8 | 1.3.6.1.4.1.31034.2.12.1.1 | integer32 | no-access |
The channel. Its value ranges between 1 and 48, depending on the number of channels, usually 1. |
sensorType | 1.3.6.1.4.1.31034.2.12.1.2 | displaystring | read-only |
Type of connected sensor, either T, H or I for respectively Temperature (C), Humidity (%) or dry switch contact |
sensorValue | 1.3.6.1.4.1.31034.2.12.1.3 | decivalue | read-only |
Value of connected sensor |
sensorName | 1.3.6.1.4.1.31034.2.12.1.4 | displaystring | read-write |
User definable name for sensors. |
conformance | 1.3.6.1.4.1.31034.99 | |||
compliances | 1.3.6.1.4.1.31034.99.1 | |||
compliance | 1.3.6.1.4.1.31034.99.1.1 |
The requirements for conformance to the SPGW-MIB. |
||
groups | 1.3.6.1.4.1.31034.99.2 | |||
identificationGroup | 1.3.6.1.4.1.31034.99.2.1 |
A collection of objects providing identification information about the device. |
||
configurationGroup | 1.3.6.1.4.1.31034.99.2.2 |
A collection of objects providing configuration information about the device. |
||
systemStatusGroup | 1.3.6.1.4.1.31034.99.2.3 |
A collection of objects providing status information about the device. |
||
resetGroup | 1.3.6.1.4.1.31034.99.2.4 |
Groups resettable attributes op the device. |
||
settingsGroup | 1.3.6.1.4.1.31034.99.2.5 |
A collection of objects providing the actual settings about the device. |
||
switchedOutletsGroup | 1.3.6.1.4.1.31034.99.2.6 |
A collection of objects providing the actual outlet status of the device. |
||
inputMeasuresGroup | 1.3.6.1.4.1.31034.99.2.7 |
A collection of objects providing the actual input measurements of the device. |
||
outputMeasuresGroup | 1.3.6.1.4.1.31034.99.2.8 |
A collection of objects providing the actual output measurements of the device. |
||
sensorsGroup | 1.3.6.1.4.1.31034.99.2.9 |
A collection of objects providing the actual environmental measurements of the device. |