ROOMALERT11E-MIB: View SNMP OID List / Download MIB

VENDOR: AVTECH SOFTWARE


 Home MIB: ROOMALERT11E-MIB
Download as:   

Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 avtech 1.3.6.1.4.1.20916
             products 1.3.6.1.4.1.20916.1
                 roomalert11E 1.3.6.1.4.1.20916.1.3
                     sensors 1.3.6.1.4.1.20916.1.3.1
                         channel1 1.3.6.1.4.1.20916.1.3.1.1
                             sensor1_1 1.3.6.1.4.1.20916.1.3.1.1.1 integer read-only
The reading for internal switch sensor 1 (0 = OPEN, 1 = CLOSED).
                             sensor1_2 1.3.6.1.4.1.20916.1.3.1.1.2 integer read-only
The reading for internal switch sensor 2 (0 = OPEN, 1 = CLOSED).
                             sensor1_3 1.3.6.1.4.1.20916.1.3.1.1.3 integer read-only
The reading for internal switch sensor 3 (0 = OPEN, 1 = CLOSED).
                             sensor1_4 1.3.6.1.4.1.20916.1.3.1.1.4 integer read-only
The reading for internal switch sensor 4 (0 = OPEN, 1 = CLOSED).
                             sensor1_5 1.3.6.1.4.1.20916.1.3.1.1.5 integer read-only
The reading for internal switch sensor 5 (0 = OPEN, 1 = CLOSED).
                             sensor1_6 1.3.6.1.4.1.20916.1.3.1.1.6 integer read-only
The reading for internal switch sensor 6 (0 = OPEN, 1 = CLOSED).
                             sensor1_7 1.3.6.1.4.1.20916.1.3.1.1.7 integer read-only
The reading for internal switch sensor 7 (0 = OPEN, 1 = CLOSED).
                             sensor1_8 1.3.6.1.4.1.20916.1.3.1.1.8 integer read-only
The reading for internal switch sensor 8 (0 = OPEN, 1 = CLOSED).
                             switch_label_1 1.3.6.1.4.1.20916.1.3.1.1.9 octet string read-only
The label for switch sensor 1
                             switch_label_2 1.3.6.1.4.1.20916.1.3.1.1.10 octet string read-only
The label for switch sensor 2
                             switch_label_3 1.3.6.1.4.1.20916.1.3.1.1.11 octet string read-only
The label for switch sensor 3
                             switch_label_4 1.3.6.1.4.1.20916.1.3.1.1.12 octet string read-only
The label for switch sensor 4
                             switch_label_5 1.3.6.1.4.1.20916.1.3.1.1.13 octet string read-only
The label for switch sensor 5
                             switch_label_6 1.3.6.1.4.1.20916.1.3.1.1.14 octet string read-only
The label for switch sensor 6
                             switch_label_7 1.3.6.1.4.1.20916.1.3.1.1.15 octet string read-only
The label for switch sensor 7
                             switch_label_8 1.3.6.1.4.1.20916.1.3.1.1.16 octet string read-only
The label for switch sensor 8
                         channel2 1.3.6.1.4.1.20916.1.3.1.2
                             sensor2_1 1.3.6.1.4.1.20916.1.3.1.2.1 integer read-only
The reading for sensor 2-1. If a temp or temp/humidity sensor is connected, value will be current temperature in Celsius.
                             sensor2_2 1.3.6.1.4.1.20916.1.3.1.2.2 integer read-only
The reading for sensor 2-2. If a temp or temp/humidity sensor is connected, value will be current temperature in Fahrenheit.
                             sensor2_3 1.3.6.1.4.1.20916.1.3.1.2.3 integer read-only
The reading for sensor 2-3. If temp/humidity sensor is connected, value will be current %RH.
                             sensor2_4 1.3.6.1.4.1.20916.1.3.1.2.4 integer read-only
The reading for sensor 2-4. If temp/humidity sensor is connected, value will be current Heat Index in Fahrenheit.
                             sensor2_5 1.3.6.1.4.1.20916.1.3.1.2.5 integer read-only
The reading for sensor 2-5. If temp/humidity sensor is connected, value will be current Heat Index in Celsius.
                             sensor2_6_label 1.3.6.1.4.1.20916.1.3.1.2.6 octet string read-only
The label of this sensor
                         channel3 1.3.6.1.4.1.20916.1.3.1.3
                             sensor3_1 1.3.6.1.4.1.20916.1.3.1.3.1 integer read-only
The reading for sensor 3-1. If a temp or temp/humidity sensor is connected, value will be current temperature in Celsius.
                             sensor3_2 1.3.6.1.4.1.20916.1.3.1.3.2 integer read-only
The reading for sensor 3-2. If a temp or temp/humidity sensor is connected, value will be current temperature in Fahrenheit.
                             sensor3_3 1.3.6.1.4.1.20916.1.3.1.3.3 integer read-only
The reading for sensor 3-3. If temp/humidity sensor is connected, value will be current %RH.
                             sensor3_4 1.3.6.1.4.1.20916.1.3.1.3.4 integer read-only
The reading for sensor 3-4. If temp/humidity sensor is connected, value will be current Heat Index in Fahrenheit.
                             sensor3_5 1.3.6.1.4.1.20916.1.3.1.3.5 integer read-only
The reading for sensor 3-5. If temp/humidity sensor is connected, value will be current Heat Index in Celsius.
                             sensor3_6_label 1.3.6.1.4.1.20916.1.3.1.3.6 octet string read-only
The label of this sensor
                         channel4 1.3.6.1.4.1.20916.1.3.1.4
                             sensor4_1 1.3.6.1.4.1.20916.1.3.1.4.1 integer read-only
The reading for sensor 4-1. If a temp or temp/humidity sensor is connected, value will be current temperature in Celsius.
                             sensor4_2 1.3.6.1.4.1.20916.1.3.1.4.2 integer read-only
The reading for sensor 4-2. If a temp or temp/humidity sensor is connected, value will be current temperature in Fahrenheit.
                             sensor4_3 1.3.6.1.4.1.20916.1.3.1.4.3 integer read-only
The reading for sensor 4-3. If temp/humidity sensor is connected, value will be current %RH.
                             sensor4_4 1.3.6.1.4.1.20916.1.3.1.4.4 integer read-only
The reading for sensor 4-4. If temp/humidity sensor is connected, value will be current Heat Index in Fahrenheit.
                             sensor4_5 1.3.6.1.4.1.20916.1.3.1.4.5 integer read-only
The reading for sensor 4-5. If temp/humidity sensor is connected, value will be current Heat Index in Celsius.
                             sensor4_6_label 1.3.6.1.4.1.20916.1.3.1.4.6 octet string read-only
The label of this sensor
                     traps 1.3.6.1.4.1.20916.1.3.2
                         alarm1 1.3.6.1.4.1.20916.1.3.2.1 integer read-only
Alarm for sensor channel 1. The binary equivalent of the decimal number displayed will indicate which switch sensors are currently in an alarm state (0 = sensor ok, 1 = sensor in alarm state). For example, if switch sensors 1 and 4 are in alarm state, the value displayed will be 9, which equals 00001001 in binary.
                         alarm2 1.3.6.1.4.1.20916.1.3.2.2 integer read-only
Alarm for sensor channel 2. If a digital temperature/humidity or digital temperature sensor is connected to this channel, 0 = sensor ok, 1 = high temp alarm, 2 = low temp alarm, 3 = humidity alarm. If a Switch Sensor Expansion box is connected, the binary equivalent of the decimal number displayed will indicate which switch sensors are currently in an alarm state (0 = sensor ok, 1 = sensor in alarm state). For example, if switch sensors 1 and 4 are in alarm state, the value displayed will be 9, which equals 00001001 in binary.
                         alarm3 1.3.6.1.4.1.20916.1.3.2.3 integer read-only
Alarm for sensor channel 3. If a digital temperature/humidity or digital temperature sensor is connected to this channel, 0 = sensor ok, 1 = high temp alarm, 2 = low temp alarm, 3 = humidity alarm. If a Switch Sensor Expansion box is connected, the binary equivalent of the decimal number displayed will indicate which switch sensors are currently in an alarm state (0 = sensor ok, 1 = sensor in alarm state). For example, if switch sensors 1 and 4 are in alarm state, the value displayed will be 9, which equals 00001001 in binary.
                         alarm4 1.3.6.1.4.1.20916.1.3.2.4 integer read-only
Alarm for sensor channel 4. If a digital temperature/humidity or digital temperature sensor is connected to this channel, 0 = sensor ok, 1 = high temp alarm, 2 = low temp alarm, 3 = humidity alarm. If a Switch Sensor Expansion box is connected, the binary equivalent of the decimal number displayed will indicate which switch sensors are currently in an alarm state (0 = sensor ok, 1 = sensor in alarm state). For example, if switch sensors 1 and 4 are in alarm state, the value displayed will be 9, which equals 00001001 in binary.
                         alarmMessage1 1.3.6.1.4.1.20916.1.3.2.5 octet string read-only
Alarm Message from sensor channel 1 (Internal)
                         alarmMessage2 1.3.6.1.4.1.20916.1.3.2.6 octet string read-only
Alarm Message from sensor channel 2 (External)
                         alarmMessage3 1.3.6.1.4.1.20916.1.3.2.7 octet string read-only
Alarm Message from sensor channel 3 (External)
                         alarmMessage4 1.3.6.1.4.1.20916.1.3.2.8 octet string read-only
Alarm Message from sensor channel 4 (External)
                     thresholds 1.3.6.1.4.1.20916.1.3.3
                         channels 1.3.6.1.4.1.20916.1.3.3.1
                             channels1 1.3.6.1.4.1.20916.1.3.3.1.1
                                 threshold1_1 1.3.6.1.4.1.20916.1.3.3.1.1.1 integer read-only
Threshold 1 defined for Channel 1
                                 threshold1_2 1.3.6.1.4.1.20916.1.3.3.1.1.2 integer read-only
Threshold 2 defined for Channel 1
                                 threshold1_3 1.3.6.1.4.1.20916.1.3.3.1.1.3 integer read-only
Threshold 3 defined for Channel 1
                                 threshold1_4 1.3.6.1.4.1.20916.1.3.3.1.1.4 integer read-only
Threshold 4 defined for Channel 1
                                 threshold1_5 1.3.6.1.4.1.20916.1.3.3.1.1.5 integer read-only
Threshold 5 defined for Channel 1
                                 threshold1_6 1.3.6.1.4.1.20916.1.3.3.1.1.6 integer read-only
Threshold 6 defined for Channel 1
                                 threshold1_7 1.3.6.1.4.1.20916.1.3.3.1.1.7 integer read-only
Threshold 7 defined for Channel 1
                                 threshold1_8 1.3.6.1.4.1.20916.1.3.3.1.1.8 integer read-only
Threshold 8 defined for Channel 1
                             channels2 1.3.6.1.4.1.20916.1.3.3.1.2
                                 threshold2_1 1.3.6.1.4.1.20916.1.3.3.1.2.1 integer read-only
Threshold 1 defined for Channel 2
                                 threshold2_2 1.3.6.1.4.1.20916.1.3.3.1.2.2 integer read-only
Threshold 2 defined for Channel 2
                                 threshold2_3 1.3.6.1.4.1.20916.1.3.3.1.2.3 integer read-only
Threshold 3 defined for Channel 2
                                 threshold2_4 1.3.6.1.4.1.20916.1.3.3.1.2.4 integer read-only
Threshold 4 defined for Channel 2
                             channels3 1.3.6.1.4.1.20916.1.3.3.1.3
                                 threshold3_1 1.3.6.1.4.1.20916.1.3.3.1.3.1 integer read-only
Threshold 1 defined for Channel 3
                                 threshold3_2 1.3.6.1.4.1.20916.1.3.3.1.3.2 integer read-only
Threshold 2 defined for Channel 3
                                 threshold3_3 1.3.6.1.4.1.20916.1.3.3.1.3.3 integer read-only
Threshold 3 defined for Channel 3
                                 threshold3_4 1.3.6.1.4.1.20916.1.3.3.1.3.4 integer read-only
Threshold 4 defined for Channel 3
                             channels4 1.3.6.1.4.1.20916.1.3.3.1.4
                                 threshold4_1 1.3.6.1.4.1.20916.1.3.3.1.4.1 integer read-only
Threshold 1 defined for Channel 4
                                 threshold4_2 1.3.6.1.4.1.20916.1.3.3.1.4.2 integer read-only
Threshold 2 defined for Channel 4
                                 threshold4_3 1.3.6.1.4.1.20916.1.3.3.1.4.3 integer read-only
Threshold 3 defined for Channel 4
                                 threshold4_4 1.3.6.1.4.1.20916.1.3.3.1.4.4 integer read-only
Threshold 4 defined for Channel 4
                       tempAlarm1_11e 1.3.6.1.4.1.20916.1.30.1
A tempAlarm1 trap signifies that the current temperature on external sensor 1 is outside the defined high or low threshold.
                       room_alert_11E_SNMP_trap 1.3.6.1.4.1.20916.1.30.2
A Room Alert 11E SNMP Trap indicates that an alarm condition has occurred on the sensor inidcated by the alarmMessage variable.
                       tempAlarm2_11e 1.3.6.1.4.1.20916.1.30.3
A tempAlarm2 trap signifies that the current temperature on external sensor 2 is outside the defined high or low threshold.
                       tempClear2_11e 1.3.6.1.4.1.20916.1.30.4
A tempClear2 trap signifies that the current temperature on external sensor 2 has returned to a normal condition and is within the defined high or low threshold.
                       tempAlarm3_11e 1.3.6.1.4.1.20916.1.30.5
A tempAlarm3 trap signifies that the current temperature on external sensor 3 is outside the defined high or low threshold.
                       tempClear3_11e 1.3.6.1.4.1.20916.1.30.6
A tempClear3 trap signifies that the current temperature on external sensor 3 has returned to a normal condition and is within the defined high or low threshold.
                       humidityAlarm1_11e 1.3.6.1.4.1.20916.1.30.7
A humidityAlarm1 trap signifies that the current humidity on external sensor 1 is outside the defined high or low threshold.
                       humidityClear1_11e 1.3.6.1.4.1.20916.1.30.8
A humidityClear1 trap signifies that the current humidity on external sensor 1 has returned to a normal condition and is within the defined high or low threshold.
                       humidityAlarm2_11e 1.3.6.1.4.1.20916.1.30.9
A humidityAlarm2 trap signifies that the current humidity on external sensor 2 is outside the defined high or low threshold.
                       humidityClear2_11e 1.3.6.1.4.1.20916.1.30.10
A humidityClear2 trap signifies that the current humidity on external sensor 2 has returned to a normal condition and is within the defined high or low threshold.
                       humidityAlarm3_11e 1.3.6.1.4.1.20916.1.30.11
A humidityAlarm3 trap signifies that the current humidity on external sensor 3 is outside the defined high or low threshold.
                       humidityClear3_11e 1.3.6.1.4.1.20916.1.30.12
A humidityClear3 trap signifies that the current humidity on external sensor 3 has returned to a normal condition and is within the defined high or low threshold.
                       switchAlarm1_11e 1.3.6.1.4.1.20916.1.30.13
A switchAlarm1 trap signifies that switch sensor 1 is in an alarm state.
                       switchClear1_11e 1.3.6.1.4.1.20916.1.30.14
A switchClear1 trap signifies that the switch sensor 1 has returned to a normal state.
                       switchAlarm2_11e 1.3.6.1.4.1.20916.1.30.15
A switchAlarm2 trap signifies that switch sensor 2 is in an alarm state.
                       switchClear2_11e 1.3.6.1.4.1.20916.1.30.16
A switchClear2 trap signifies that the switch sensor 2 has returned to a normal state.
                       switchAlarm3_11e 1.3.6.1.4.1.20916.1.30.17
A switchAlarm1 trap signifies that switch sensor 1 is in an alarm state.
                       switchClear3_11e 1.3.6.1.4.1.20916.1.30.18
A switchClear3 trap signifies that the switch sensor 3 has returned to a normal state.
                       switchAlarm4_11e 1.3.6.1.4.1.20916.1.30.19
A switchAlarm4 trap signifies that switch sensor 4 is in an alarm state.
                       switchClear4_11e 1.3.6.1.4.1.20916.1.30.20
A switchClear4 trap signifies that the switch sensor 4 has returned to a normal state.
                       switchAlarm5_11e 1.3.6.1.4.1.20916.1.30.21
A switchAlarm5 trap signifies that switch sensor 5 is in an alarm state.
                       switchClear5_11e 1.3.6.1.4.1.20916.1.30.22
A switchClear5 trap signifies that the switch sensor 5 has returned to a normal state.
                       switchAlarm6_11e 1.3.6.1.4.1.20916.1.30.23
A switchAlarm6 trap signifies that switch sensor 6 is in an alarm state.
                       switchClear6_11e 1.3.6.1.4.1.20916.1.30.24
A switchClear6 trap signifies that the switch sensor 6 has returned to a normal state.
                       switchAlarm7_11e 1.3.6.1.4.1.20916.1.30.25
A switchAlarm7 trap signifies that switch sensor 7 is in an alarm state.
                       switchClear7_11e 1.3.6.1.4.1.20916.1.30.26
A switchClear7 trap signifies that the switch sensor 7 has returned to a normal state.
                       switchAlarm8_11e 1.3.6.1.4.1.20916.1.30.27
A switchAlarm8 trap signifies that switch sensor 8 is in an alarm state.
                       switchClear8_11e 1.3.6.1.4.1.20916.1.30.28
A switchClear8 trap signifies that the switch sensor 8 has returned to a normal state.