PSNA-PS-psmA-MIB: View SNMP OID List / Download MIB

VENDOR: VERTIV TECH CO.,LTD.


 Home MIB: PSNA-PS-psmA-MIB
Download as:   

Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 emersonNetworkPower 1.3.6.1.4.1.13400
             products 1.3.6.1.4.1.13400.2
                 psm 1.3.6.1.4.1.13400.2.8
                     psAgent 1.3.6.1.4.1.13400.2.8.1
                         agentRevision 1.3.6.1.4.1.13400.2.8.1.1 integer read-only
The firmware revision of the agent.
                         agentManagersNum 1.3.6.1.4.1.13400.2.8.1.2 integer read-only
The number of managers that can manage the agent.
                         agentManagersTable 1.3.6.1.4.1.13400.2.8.1.3 no-access
A list of managers of the agent. The number of entries is given by the value of agentManagersNum.
                             agentManagersEntry 1.3.6.1.4.1.13400.2.8.1.3.1 no-access
The managers of the agent.
                                 managerIndex 1.3.6.1.4.1.13400.2.8.1.3.1.1 integer read-only
The index of the managers entry.
                                 managerAddr 1.3.6.1.4.1.13400.2.8.1.3.1.2 ipaddress read-write
The IP address of the manager.
                                 publicCommunityString 1.3.6.1.4.1.13400.2.8.1.3.1.3 displaystring read-write
The public community name to use in the query request.
                                 privateCommunityString 1.3.6.1.4.1.13400.2.8.1.3.1.4 displaystring read-write
The private community name to use in the control request.
                                 managerPrivilege 1.3.6.1.4.1.13400.2.8.1.3.1.5 integer read-write
The privilege of the manager to access the agent. setting forbidden(0) indicates the manager have no any privilege to access the agent, setting query(1) indicates the manager can GET information from agent only, setting control(2) indicates the manager can GET information from agent and send control command to the agent. setting administrator(3) indicates the manager has all management privilege including set or modify this managers table. Enumeration: 'control': 2, 'query': 1, 'forbidden': 0, 'administrator': 3.
                                 acceptTrapLevel 1.3.6.1.4.1.13400.2.8.1.3.1.6 integer read-write
The severity threshold of traps to send to the manager. traps are labeled in severity as informational(1), warning(2), severe(3). Only traps of equal or greater severity than this value are sent to the manager. setting noTraps(4) indicates agent do not send any traps to the manager. Enumeration: 'information': 1, 'severe': 3, 'warning': 2, 'noTraps': 4.
                                 managerAccept 1.3.6.1.4.1.13400.2.8.1.3.1.7 integer read-write
An entry will be added if new(1), will be modified if modify(2), and will be removed if delete(3). Enumeration: 'new': 1, 'view': 0, 'modify': 2, 'delete': 3.
                     psCommon 1.3.6.1.4.1.13400.2.8.2
                         psIdent 1.3.6.1.4.1.13400.2.8.2.1
                             psIdentControllerModel 1.3.6.1.4.1.13400.2.8.2.1.1 displaystring read-only
The controller model of the Power System.
                             psIdentFirmwareRevision 1.3.6.1.4.1.13400.2.8.2.1.2 displaystring read-only
The firmware revision of the controller of the Power System.
                             psIdentFactory 1.3.6.1.4.1.13400.2.8.2.1.3 displaystring read-only
The name of the Power System manufacturer.
                     psSpecial 1.3.6.1.4.1.13400.2.8.3
                         psm_a 1.3.6.1.4.1.13400.2.8.3.1
                             psBattery 1.3.6.1.4.1.13400.2.8.3.1.2
                                 psBatteryVoltage 1.3.6.1.4.1.13400.2.8.3.1.2.1 integer read-only
The voltage of battery in 0.1 VDC.
                                 psBatteryCurrent 1.3.6.1.4.1.13400.2.8.3.1.2.2 integer read-only
The total current of the batteries in 0.1 ADC.
                                 psBatteryTemperature 1.3.6.1.4.1.13400.2.8.3.1.2.3 integer read-only
The temperature around the battery in 0.1 Celsius degree.
                             psInput 1.3.6.1.4.1.13400.2.8.3.1.3
                                 psInputLineAVoltage 1.3.6.1.4.1.13400.2.8.3.1.3.1 integer read-only
The AC line A voltage in 0.1 VAC.
                                 psInputLineBVoltage 1.3.6.1.4.1.13400.2.8.3.1.3.2 integer read-only
The AC line B voltage in 0.1 VAC.
                                 psInputLineCVoltage 1.3.6.1.4.1.13400.2.8.3.1.3.3 integer read-only
The AC line C voltage in 0.1 VAC.
                             psOutput 1.3.6.1.4.1.13400.2.8.3.1.4
                                 psOutputVoltage 1.3.6.1.4.1.13400.2.8.3.1.4.1 integer read-only
The DC voltage of the Power System in 0.1 VDC.
                                 psOutputCurrent 1.3.6.1.4.1.13400.2.8.3.1.4.2 integer read-only
The DC current of the Power System in 0.1 ADC.
                             psStatus 1.3.6.1.4.1.13400.2.8.3.1.5
                                 psStatusAlarm 1.3.6.1.4.1.13400.2.8.3.1.5.1 integer read-only
The alarm status of the Power System. Enumeration: 'unknown': 1, 'alarm': 3, 'normal': 2.
                                 psStatusCommunication 1.3.6.1.4.1.13400.2.8.3.1.5.2 integer read-only
The status of communication with the Power System. interrupt(3) indicates some errors occurred between Power System and agent. Enumeration: 'interrupt': 3, 'unknown': 1, 'normal': 2.
                                 psStatusControlMode 1.3.6.1.4.1.13400.2.8.3.1.5.3 integer read-only
The AUTO/MANUAL control mode of the Power System. Enumeration: 'unknown': 1, 'manual': 3, 'auto': 2.
                                 psStatusChargingMode 1.3.6.1.4.1.13400.2.8.3.1.5.4 integer read-only
The status of battery charging, floatCharging(2), equalizeCharging(3), testing(4). Enumeration: 'unknown': 1, 'floatCharging': 2, 'testing': 4, 'equalizeCharging': 3.
                             psTest 1.3.6.1.4.1.13400.2.8.3.1.6
                             psControl 1.3.6.1.4.1.13400.2.8.3.1.7
                             psConfig 1.3.6.1.4.1.13400.2.8.3.1.8
                         psm_a9 1.3.6.1.4.1.13400.2.8.3.2
                     psAlarm 1.3.6.1.4.1.13400.2.8.4
                         psAlarmPresentNum 1.3.6.1.4.1.13400.2.8.4.1 integer read-only
The present number of active alarams.
                         psAlarmPresentTable 1.3.6.1.4.1.13400.2.8.4.2 no-access
A list of current alarms, The number of entries is given by the value of psAlarmPresentNum.
                             psAlarmPresentEntry 1.3.6.1.4.1.13400.2.8.4.2.1 no-access
The present alarms list.
                                 presentAlarmIndex 1.3.6.1.4.1.13400.2.8.4.2.1.1 integer read-only
The index of the present alaram entry.
                                 presentAlarmTime 1.3.6.1.4.1.13400.2.8.4.2.1.2 displaystring read-only
The time of the alarm generated, format as mm/dd/yyyy hh:mm:ss
                                 presentAlarmId 1.3.6.1.4.1.13400.2.8.4.2.1.3 integer read-only
The alarm ID.
                                 presentAlarmName 1.3.6.1.4.1.13400.2.8.4.2.1.4 displaystring read-only
The name of the alarm.
                                 presentAlaramLevel 1.3.6.1.4.1.13400.2.8.4.2.1.5 integer read-only
The alarm level. Enumeration: 'information': 1, 'severe': 3, 'warning': 2.
                         trapArgsString 1.3.6.1.4.1.13400.2.8.4.2008 displaystring read-only
This OID allows Power System traps to be sent with an octet string argument that may not be defined in the PSNA_PS_MIB. A get of this OID will return a NULL string.
                       psOnNormal 1.3.6.1.4.1.13400.2.80.1
INFORMATION: The Power System is on normal status.
                       communicationLost 1.3.6.1.4.1.13400.2.80.2
SEVERE: Communication with the Power System lost.
                       communicationResumed 1.3.6.1.4.1.13400.2.80.3
INFORMATION: Communication with the Power System Resumed.
                       acFail 1.3.6.1.4.1.13400.2.80.4
SEVERE: AC Power failed.
                       acResumed 1.3.6.1.4.1.13400.2.80.5
INFORMATION: AC power Resumed.
                       acVoltageoutofRange 1.3.6.1.4.1.13400.2.80.6
SEVERE: AC voltage is out of normal range.
                       acVoltageNormal 1.3.6.1.4.1.13400.2.80.7
INFORMATION: AC voltage is normal.
                       dcVoltageoutofRange 1.3.6.1.4.1.13400.2.80.8
SEVERE: DC voltage is out of normal range.
                       dcVoltageNormal 1.3.6.1.4.1.13400.2.80.9
INFORMATION: DC voltage is normal.
                       llvd 1.3.6.1.4.1.13400.2.80.10
SEVERE: Load low voltage disconnected.
                       llvdResumed 1.3.6.1.4.1.13400.2.80.11
INFORMATION: Load low voltage disconnection resumed.
                       blvd 1.3.6.1.4.1.13400.2.80.12
SEVERE: Battery low voltage disconnected.
                       blvdResumed 1.3.6.1.4.1.13400.2.80.13
INFORMATION: Battery low voltage disconnection resumed.
                       highTemperature 1.3.6.1.4.1.13400.2.80.14
SEVERE: The temperature around battery is too high.
                       highTemperatureResumed 1.3.6.1.4.1.13400.2.80.15
INFORMATION: The temperature around battery is normal.
                       dcRouteDisconnect 1.3.6.1.4.1.13400.2.80.16
SEVERE: Some DC route(s) disconnected.
                       dcRouteDisconnectResumed 1.3.6.1.4.1.13400.2.80.17
INFORMATION: DC route(s) disconnection resumed.
                       batteryRouteDisconnect 1.3.6.1.4.1.13400.2.80.18
SEVERE: The battery route(s) disconnected.
                       batteryRouteDisconnectResumed 1.3.6.1.4.1.13400.2.80.19
INFORMATION: The battery route(s) disconnection resumed.
                       acSPDfault 1.3.6.1.4.1.13400.2.80.20
SEVERE: AC SPD fault.
                       acSPDfaultResumed 1.3.6.1.4.1.13400.2.80.21
INFORMATION: AC SPD fault resumed.
                       acCircuitBreakerfault 1.3.6.1.4.1.13400.2.80.22
SEVERE: AC circuit breaker fault.
                       acCircuitBreakerfaultResumed 1.3.6.1.4.1.13400.2.80.23
INFORMATION: AC circuit breaker fault resumed.
                       batteryCurrentOver 1.3.6.1.4.1.13400.2.80.24
SEVERE: Battery current is over limit.
                       batteryCurrentOverResumed 1.3.6.1.4.1.13400.2.80.25
INFORMATION: Battery current over resumed.
                       rectifierFault 1.3.6.1.4.1.13400.2.80.26
SEVERE: Some Rectifier(s) fault.
                       rectifierFaultResumed 1.3.6.1.4.1.13400.2.80.27
INFORMATION: Rectifier(s) fault resumed.
                       rectifierProtection 1.3.6.1.4.1.13400.2.80.28
SEVERE: Some Rectifier(s) protection.
                       rectifierProtectionResumed 1.3.6.1.4.1.13400.2.80.29
INFORMATION: Rectifier(s) protection resumed.
                       rectifierFanFault 1.3.6.1.4.1.13400.2.80.30
SEVERE: Some Rectifier(s) fan fault.
                       rectifierFanFaultResumed 1.3.6.1.4.1.13400.2.80.31
INFORMATION: Rectifier(s) fan fault resumed.
                       rectifierOverTemperature 1.3.6.1.4.1.13400.2.80.32
SEVERE: Some Rectifier(s) over temperature.
                       rectifierOverTemperatureResumed 1.3.6.1.4.1.13400.2.80.33
INFORMATION: Rectifier(s) over temperature resumed.
                       communicationACDLost 1.3.6.1.4.1.13400.2.80.34
SEVERE: Power System communication with ACD lost.
                       communicationACDResumed 1.3.6.1.4.1.13400.2.80.35
INFORMATION: Power System communication with ACD resumed.
                       communicationDCDLost 1.3.6.1.4.1.13400.2.80.36
SEVERE: Power System communication with DCD lost.
                       communicationDCDResumed 1.3.6.1.4.1.13400.2.80.37
INFORMATION: Power System communication with DCD resumed.
                       communicationRectifierLost 1.3.6.1.4.1.13400.2.80.38
SEVERE: Power System communication with rectifier lost.
                       communicationRectifierResumed 1.3.6.1.4.1.13400.2.80.39
INFORMATION: Power System communication with rectifier resumed.
                       dcdcFault 1.3.6.1.4.1.13400.2.80.40
SEVERE: DC/DC convertor fault.
                       dcdcFaultResumed 1.3.6.1.4.1.13400.2.80.41
INFORMATION: DC/DC convertor fault resumed.