ORION-BASE-MIB: View SNMP OID List / Download MIB

VENDOR: DELTA ELECTRONICS (SWITZERLAND) AG


 Home MIB: ORION-BASE-MIB
Download as:   

Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 orionBaseMibModule 1.3.6.1.4.1.20246.2.1.1.2
MIB for managing a DC power system with PSC 3.
     orionBaseMib 1.3.6.1.4.1.20246.2.3.1.1.1
         controllerConfs 1.3.6.1.4.1.20246.2.3.1.1.1.1
             controllerGroups 1.3.6.1.4.1.20246.2.3.1.1.1.1.1
                 systemInfoGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.1
The collection of system info scalar objects.
                 systemAlarmGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.2
The collection of system alarm scalar objects.
                 systemMonitorGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.3
The collection of system monitor scalar objects.
                 rectifierGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.4
The collection of rectifier scalar objects.
                 eventHistoryTableGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.5
The collection of event history table objects.
                 alarmTableGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.6
The collection of alarm table objects.
                 rectifierTableGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.7
The collection of rectifier table objects.
                 notificationsGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.8
The group of all controller notifications.
                 genericAlarmTableGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.9
Assignment of events to alarm table entries.
                 batteryGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.10
The collection of battery scalar objects.
                 controlEventTableGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.11
Assignment of control events to table entries.
                 trapDestinationTableGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.12
Trap destionation table.
                 miscGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.13
The collection of miscellaneous objects.
                 rectifierGroupTableGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.14
The collection of rectifier group table objects.
                 batteryStringTableGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.15
The collection of battery string table objects.
                 defaultLogEventTableGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.16
The collection of default log event table objects.
                 eventProcessingEventTableGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.17
The collection of event processing event table objects.
                 lvdTableGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.18
The collection of LVD table objects.
                 powerLimitationTableGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.19
The collection of power limitation table objects.
                 measurementTableGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.20
The collection of measurement table objects.
                 meterPanelEventTableGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.21
The collection of meter panel event table objects.
             controllerCompl 1.3.6.1.4.1.20246.2.3.1.1.1.1.2
                 controllerBasicCompl 1.3.6.1.4.1.20246.2.3.1.1.1.1.2.1
The basic implementation requirements for the controller MIB.
         controllerObjects 1.3.6.1.4.1.20246.2.3.1.1.1.2
             dcSystemInfo 1.3.6.1.4.1.20246.2.3.1.1.1.2.1
                 dcSiteName 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.1 displaystring read-write
An administratively-assigned site name for this DC-power system.
                 dcSystemName 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.2 displaystring read-write
An administratively-assigned system name for this DC-power system.
                 dcSystemDateTime 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.3 displaystring read-write
ISO 8601 representation of controllers local date/time. The value is in the format YYYY-MM-DDThh:mm:ss. An example of a valid string is: '2004-10-04T13:45:00'.
                 dcSoftwareVersion 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.4 displaystring read-only
The controllers software version e.g V2.50Build1.
             dcSystemAlarms 1.3.6.1.4.1.20246.2.3.1.1.1.2.2
                 dcEventHistoryTable 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1 no-access
Controllers event history table that shows the content of the default log file.
                     dcEventHistoryEntry 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1 no-access
A particular Event History entry.
                         dcEventHistoryIndex 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.1 integer32 no-access
Table index.
                         dcEventHistoryTimestamp 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.2 displaystring read-only
ISO8601 timestamp representation of a particular entry in the form YYYY-MM-DDThh:mm:ss.
                         dcEventHistoryMessage 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.3 displaystring read-only
Event message of a particular entry.
                 dcAlarmTable 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2 no-access
Table that shows all currently active alarm sources causing urgent or non-urgent alarm(s).
                     dcAlarmEntry 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1 no-access
A particular active alarm source entry.
                         dcAlarmIndex 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.1 integer32 no-access
Table index.
                         dcAlarmEventCategory 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.2 integer read-only
Specifies the type of alarm source. Enumeration: 'unknown': 1, 'nonUrgent': 3, 'critical': 4, 'urgent': 2.
                         dcAlarmEventName 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.3 displaystring read-only
Name of a particular alarm source entry.
                         dcAlarmEventIdentifier 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.4 gauge32 read-only
Unique alarm event identifier.
                         dcAlarmEventValue 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.5 integer read-only
Event status that corresponds to alarm event identifier. Enumeration: 'true': 3, 'false': 1.
                 dcNumberUrgentAlarms 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.3 gauge32 read-only
Number of currently active urgent alarm sources. A zero value indicates that urgent alarm is not active.
                 dcNumberNonUrgentAlarms 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.4 gauge32 read-only
Number of currently active non urgent alarm sources. A zero value indicates that non urgent alarm is not active.
                 dcMainsFailureAlarm 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.5 integer read-only
Mains failure alarm. Enumeration: 'active': 2, 'inactive': 1.
                 dcUrgentAlarmIdentifier 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.6 gauge32 read-only
Current unique urgent alarm event identifier. A zero value indicates that urgent alarm is not active.
                 dcUrgentAlarmValue 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.7 integer read-only
Current urgent alarm event status that corresponds to the urgent alarm identifier. If the urgent alarm identifier is zero then the alarm value is false. Enumeration: 'true': 3, 'indeterminate': 2, 'false': 1.
                 dcNonUrgentAlarmIdentifier 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.8 gauge32 read-only
Current unique non urgent alarm event identifier. A zero value indicates that non urgent alarm is not active.
                 dcNonUrgentAlarmValue 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.9 integer read-only
Current non urgent alarm event status that corresponds to non urgent alarm identifier. If the non urgent alarm identifier is zero then the alarm value is false. Enumeration: 'true': 3, 'indeterminate': 2, 'false': 1.
                 dcUrgentAlarmName 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.10 displaystring read-only
Current alarm name for urgent alarm that corresponds to urgent alarm identifier.
                 dcNonUrgentAlarmName 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.11 displaystring read-only
Current alarm name for active non urgent alarm that corresponds to non urgent alarm identifier.
                 dcGenericAlarmTable 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12 no-access
Table that shows ten alarm event assignments that can be configured via WEB interface.
                       dcGenericAlarmEntry 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1 no-access
A particular generic alarm entry.
                           dcGenericAlarmIndex 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.1 integer32 no-access
Table index.
                           dcGenericAlarmEventName 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.2 displaystring read-only
Plain text name of the assigned alarm event. Empty if not configured.
                           dcGenericAlarmEventIdentifier 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.3 gauge32 read-only
Unique numeric identifier of the assigned alarm event. Zero if not configured.
                           dcGenericAlarmEventValue 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.4 integer read-only
Current value of the assigned alarm event. Value is false if not configured. Enumeration: 'true': 2, 'false': 1.
                 dcNumberCriticalAlarms 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.13 gauge32 read-only
Number of currently active critical alarm sources. A zero value indicates that critical alarm is not active.
                 dcCriticalAlarmIdentifier 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.14 gauge32 read-only
Current unique critical alarm event identifier. A zero value indicates that critical alarm is not active.
                 dcCriticalAlarmValue 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.15 integer read-only
Current critical alarm event status that corresponds to the critical alarm identifier. If the critical alarm identifier is zero then the alarm value is false. Enumeration: 'true': 3, 'indeterminate': 2, 'false': 1.
                 dcCriticalAlarmName 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.16 displaystring read-only
Current alarm name for active critical alarm that corresponds to critical alarm identifier.
             dcSystemMonitor 1.3.6.1.4.1.20246.2.3.1.1.1.2.3
                 dcSystemVoltage 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.1 integer32 read-only
The measured system voltage. The max. value 2147483647 is used to indicate an invalid value.
                 dcLoadCurrent 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.2 integer32 read-only
The measured load current. The max. value 2147483647 is used to indicate an invalid value.
                 dcBatteryCurrent 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.3 integer32 read-only
The measured battery current. The max. value 2147483647 is used to indicate an invalid value.
                 dcBatteryTemperature 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.4 integer32 read-only
The measured battery temperature. The max. value 2147483647 is used to indicate an invalid value.
                 dcChargeState 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.5 integer read-only
Battery charge state. Enumeration: 'sepCharge': 7, 'float': 1, 'battTest': 5, 'evCtrlCharge': 8, 'equalize': 3, 'discharge': 2, 'boost': 4, 'recharge': 6.
                 dcCurrentLimit 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.6 integer read-only
Battery current limit. Enumeration: 'active': 2, 'inactive': 1.
                 dcRectifierCurrent 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.7 integer32 read-only
Total current of all working rectifier modules. The maximum value 2147483647 is used to indicate an invalid value.
                 dcSystemPower 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.8 integer32 read-only
Calculated system power. The maximum value 2147483647 is used to indicate an invalid value.
             dcRectifier 1.3.6.1.4.1.20246.2.3.1.1.1.2.4
                 dcNumberRectifiers 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.1 gauge32 read-only
The configured number of rectifiers plugged into the system. The maximum number of rectifiersi is 128.
                 dcNumberRectifiersFailure 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.2 gauge32 read-only
Number of rectifiers that are not properly working.
                 dcNumberRectifiersOkay 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.3 gauge32 read-only
Number of rectifiers that are properly working.
                 dcRectifierTable 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4 no-access
Table that shows all currently active rectifier modules.
                     dcRectifierEntry 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1 no-access
A particular rectifier entry.
                         dcRectifierIndex 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.1 integer32 no-access
Table index.
                         dcRectifierIdentifier 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.2 displaystring read-only
Unique rectifier identifier. If positioning active the position number scheme is used otherwise the rectifier instance is used to identify a rectifier.
                         dcRectifierStatus 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.3 integer read-only
Specifies status of rectifiers. Enumeration: 'unknown': 1, 'off': 2, 'on': 3.
                 dcRectifierGroupTable 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5 no-access
Table that shows all available rectifier groups.
                     dcRectifierGroupEntry 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1 no-access
A particular rectifier group entry.
                         dcRectifierGroupIndex 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.1 integer32 no-access
Table index.
                         dcRectifierGroupName 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.2 displaystring read-only
Rectifier group name to identify an individual device parameter set.
                         dcRectifierGroupRectifierType 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.3 integer read-only
Rectifier type defined for this group. Enumeration: 'unknown60V': 9, 'dPR7200B48': 6, 'dPR850B48': 20, 'dPR1600B48': 14, 'unknown24V': 8, 'dPR2400B48': 16, 'dPR4000B48': 17, 'dPR600B48': 5, 'dPR300B48': 13, 'dPR600B60': 10, 'dPR1500B48': 4, 'fR48V2000W': 2, 'dPR4000B48to60': 19, 'dPR2000B48': 21, 'dPR2900B48': 18, 'dPR3500B24': 12, 'dPR2700B48': 15, 'unknown48V': 1, 'fR48to60V2000W': 7, 'dPR1200B48': 3, 'dPR3500B48': 11.
                         dcRectifierGroupDefaultVoltage 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.4 integer32 read-write
This default voltage is used by rectifiers when there is no connection to PSC 3.
                         dcRectifierGroupDefaultCurrentLimit 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.5 integer32 read-write
This default current limit is used by rectifiers when there is no connection to PSC 3.
                         dcRectifierGroupDefaultPowerLimit 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.6 integer32 read-write
This default power limit is used by rectifiers when there is no connection to PSC 3.
                         dcRectifierGroupInputLowOff 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.7 integer32 read-write
Threshold for low AC input voltage. It can is used to adjust the behaviour of the power system to the available AC network limitation.
                         dcRectifierGroupInputLowOn 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.8 integer32 read-write
For details see dcRectifierGroupInputLowOff.
                         dcRectifierGroupStartupVoltage 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.9 integer32 read-write
Startup parameters are the values that rectifiers use during the start-up phase. These parameters allow starting the system smoothly after a mains failure even on a discharged battery and even without PSC 3.
                         dcRectifierGroupStartupCurrentLimit 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.10 integer32 read-write
For details see dcRectifierGroupStartupVoltage.
                         dcRectifierGroupStartupPowerLimit 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.11 integer32 read-write
For details see dcRectifierGroupStartupVoltage.
                         dcRectifierGroupStartupTimeLimit 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.12 gauge32 read-write
For details see dcRectifierGroupStartupVoltage.
                         dcRectifierGroupPowerupDelay 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.13 gauge32 read-write
This parameter is used after a mains failure to delay the start-up of all rectifiers.
                         dcRectifierGroupPowerupTime 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.14 gauge32 read-write
This parameter used after a mains failure and allows defining a time within all rectifiers needs to start-up one after another.
                         dcRectifierGroupUmaxOff 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.15 integer32 read-write
Overvoltage protection value.
                 dcRectifierFunctions 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6
                     dcEfficiencyCycling 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1
                         dcEfficiencyCyclingEnabled 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.1 integer read-write
Enable/disable efficiency cycling. Enumeration: 'yes': 2, 'no': 1.
                         dcLimitSwitchingTimes 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.2 integer read-write
Enable/disable limit switching times. Enumeration: 'yes': 2, 'no': 1.
                         dcForceSwitchingOncePerMonth 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.3 integer read-write
Enable/disable force switching once per month. Enumeration: 'yes': 2, 'no': 1.
                         dcMaximumLoadStep 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.4 integer32 read-write
Maximum load setup.
                         dcMinimumLoadStep 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.5 integer32 read-write
Minimum load setup.
                     dcPowerLimitation 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2
                         dcPowerLimitationTable 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1 no-access
Table that shows parameters of the available power limitation functions.
                             dcPowerLimitationEntry 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1 no-access
A particular power limitation entry.
                                 dcPowerLimitationIndex 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1.1 integer32 no-access
Table index.
                                 dcPowerLimitationEventName 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1.2 displaystring read-only
Name of the power limitation event.
                                 dcPowerLimitationStatus 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1.3 integer read-only
Status of power limitation. Enumeration: 'disabled': 1, 'powerLimit': 3, 'inactive': 2.
                                 dcPowerLimitationType 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1.4 integer read-only
Power limitation type. Enumeration: 'fixedLimit': 2, 'dynamic': 1.
                                 dcPowerLimitationLimit 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1.5 integer32 read-write
Limit used for power limitation.
                                 dcPowerLimitationNoBatteryDischarge 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1.6 integer read-write
Enable/disable no battery discharge during power limitation. Enumeration: 'yes': 2, 'no': 1.
             dcBattery 1.3.6.1.4.1.20246.2.3.1.1.1.2.5
                 dcFloatCharge 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.1
                     dcUsys20 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.1.1 integer32 read-write
Voltage to regulate to at 20C. If temperature compensation is used, this voltage will vary.
                 dcBatteryTest 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2
                     dcBatteryTestParameter 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1
                         dcBatteryTestUsupport 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.1 integer32 read-write
Support charge voltage for the battery.
                         dcBatteryTestDuration 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.2 gauge32 read-write
Battery test duration.
                         dcBatteryTestInterval 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.3 gauge32 read-write
Minimal time between programmed battery tests as start condition.
                         dcBatteryTestDischargeCurrent 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.4 integer32 read-write
Battery discharge current. The maximum value 2147483647 is used to indicate an invalid value.
                         dcBatteryTestMinDuration 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.5 gauge32 read-write
Minimum battery test duration during which time a battery test is not stopped in case of a voltage below the support voltage or a current difference higher than the specified value defined in Idiff measurement is detected.
                         dcBatteryTestVoltageWithinUfloat 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.6 integer32 read-write
Battery voltage must be within Ufloat +/- set voltage for a given time (see also dcBatteryTestVoltageWithinUfloatPeriod) in order to start a battery test.
                         dcBatteryTestVoltageWithinUfloatPeriod 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.7 gauge32 read-write
For details see dcBatteryTestVoltageWithinUfloat parameter.
                         dcBatteryTestTempFrom 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.8 integer32 read-write
Battery temperature must be within temperature range given by dcBatteryTestTempFrom and dcBatteryTestTempTo, so that a battery test can be started.
                         dcBatteryTestTempTo 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.9 integer32 read-write
For details see dcBatteryTestTempFrom parameter.
                         dcBatteryTestIntervalEnabled 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.10 integer read-write
Enable/disable interval. For more details see dcBatteryTestInterval. Enumeration: 'yes': 2, 'no': 1.
                         dcBatteryTestStartTimeFrom 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.11 displaystring read-write
Defines start time window for battery test. The possible time window is defined as the range between dcBatteryTestStartTimeFrom and dcBatteryTestStartTimeTo. The value is in the format 'hh:mm:ss'.
                         dcBatteryTestStartTimeTo 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.12 displaystring read-write
For details see dcBatteryTestStartTimeFrom.
                     dcBatteryTestResults 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2
                         dcBatteryTestDateTime 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2.1 displaystring read-only
ISO 8601 representation of the last performed battery test. The value is in the format YYYY-MM-DDThh:mm:ss. This parameter is valid only if there is a test result available.
                         dcBatteryTestResult 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2.2 integer read-only
Result of last performed battery test. Enumeration: 'none': 1, 'okay': 5, 'abortedInhibitEv': 8, 'abortedManual': 6, 'failed': 2, 'aborted': 3, 'abortedEvCtrlCharge': 7, 'loadFailure': 4.
                         dcBatteryTestEndVoltage 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2.3 integer32 read-only
System voltage at the end of the last performed battery test. The maximum value 2147483647 is used to indicate an invalid value.
                     dcBatteryTestControl 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.3 integer read-write
Start/stop of battery test. This special charge mode is used to check the capacity of a battery. Please note that a battery test can be started even if the battery is not fully charged. In this case the test result is ambiguous and the set failure event will become active. Enumeration: 'start': 1, 'stop': 2.
                     dcBatteryTestStatus 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.4 integer read-only
Status of battery test. Enumeration: 'constantCurrent': 4, 'recovery': 7, 'realLoad': 8, 'timeBased': 5, 'stop': 9, 'inactive': 1, 'stopping': 3, 'starting': 2, 'energyBased': 6.
                     dcBatteryTestFailureEvent 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.5 integer read-write
Reset battery test failure event. Enumeration: 'reset': 1.
                     dcBatteryTestType 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.6 integer read-write
Battery test type used. Enumeration: 'realLoad': 5, 'none': 1, 'constantCurrent': 2.
                 dcBatteryParameter 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3
                     dcTotalBatteryCapacity 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.1 gauge32 read-only
Total battery capacity for all available batteries.
                     dcBatteryStringTable 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2 no-access
Table that shows parameters of the available battery strings.
                         dcBatteryStringEntry 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1 no-access
A particular battery string entry.
                             dcBatteryStringIndex 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1.1 integer32 no-access
Table index.
                             dcBatteryStringName 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1.2 displaystring read-only
Name of the battery string.
                             dcBatteryStringMaxIBatt 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1.3 integer32 read-write
Maximum battery charging current for this string. This parameter can be set individually for each battery. PSC 3 then regulates the system voltage such that the maximum battery charging current of each battery is respected.
                             dcBatteryStringCapacity 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1.4 gauge32 read-write
Capacity of battery can be defined individually. It is used to calculate the expected backup time of the system.
                     dcLossOfBackupTime 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.3
                         dcLossOfBackupTimeEnabled 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.3.1 integer read-write
Enable/disable loss of backup time functionality. Enumeration: 'yes': 2, 'no': 1.
                         dcLossOfBackupTimeStatus 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.3.2 integer read-only
Status of loss of backup time functionality. Enumeration: 'fail': 4, 'occured': 3, 'inactive': 1, 'ok': 2.
                         dcExpectedBackupTime 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.3.3 gauge32 read-write
Expected backup time value. Based on the given value for the parameter expected backup time, the corresponding maximum discharge current is calculated.
                 dcEqualize 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4
                     dcEqualizeControl 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.1 integer read-write
Start/stop of battery equalize which is a special charge mode that applies a higher voltage to the batteries than the float charge. This ensures that the cells are all equally charged. Enumeration: 'start': 1, 'stop': 2.
                     dcEqualizeStatus 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.2 integer read-only
Current status of battery equalize. Enumeration: 'recovering': 6, 'cooking': 5, 'inactive': 1, 'preparing': 4, 'stopping': 3, 'starting': 2.
                     dcEqualizeEnabled 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.3 integer read-write
Enable/disable equalize. Enumeration: 'yes': 2, 'no': 1.
                     dcEqualizeParameter 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4
                         dcEqualizeVoltage 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.1 integer32 read-write
Voltage used for equalize.
                         dcEqualizeDuration 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.2 gauge32 read-write
Duration of equalize.
                         dcEqualizeUseBattRoomFanEnabled 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.3 integer read-write
Enable/disable battery room fan during equalize. Enumeration: 'yes': 2, 'no': 1.
                         dcEqualizeLeadTime 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.4 gauge32 read-write
Lead time for equalize.
                         dcEqualizeTimeLag 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.5 gauge32 read-write
Time lag for equalize.
                         dcEqualizeInterval 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.6 gauge32 read-write
Interval for equalize as start condition.
                         dcEqualizeStartTimeIntervalFrom 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.7 displaystring read-write
Defines start time window for equqlize. The possible time window is defined as the range between dcEqualizeStartTimeIntervalFrom and dcEqualizeStartTimeIntervalTo. The value is in the format 'hh:mm:ss'.
                         dcEqualizeStartTimeIntervalTo 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.8 displaystring read-write
For detail see dcEqualizeStartTimeIntervalFrom.
                         dcEqualizeInhibitAfterBoost 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.9 gauge32 read-write
Inhibit after boost as start condition.
                 dcBoostCharge 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5
                     dcBoostChargeControl 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.1 integer read-write
Start/stop of boost charge which is a special charge mode that applies a higher voltage to the batteries than the float charge. This mode is started after a discharge phase to recharge the batteries faster. Enumeration: 'start': 1, 'stop': 2.
                     dcBoostChargeStatus 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.2 integer read-only
Current status of boost charge. Enumeration: 'stopping': 3, 'inactive': 1, 'starting': 2, 'cooking': 4, 'recovering': 5.
                     dcBoostChargeType 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.3 integer read-write
Boost charge type. Enumeration: 'currentBased': 2, 'timeBased': 3, 'none': 1, 'energyBased': 4.
                     dcBoostChargeParameter 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4
                         dcBoostChargeVoltage 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4.1 integer32 read-write
Voltage used for boost charge.
                         dcBoostChargeMaxDuration 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4.2 gauge32 read-write
Defines the maximum allowed time for boost charge to prevent that the battery is charged forever.
                         dcBoostChargeUseBattRoomFanEnabled 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4.3 integer read-write
Enable/disable battery room fan during boost charge. Enumeration: 'yes': 2, 'no': 1.
                         dcBoostChargeTimeLag 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4.4 gauge32 read-write
Time lag used for boost charge.
                         dcBoostChargeIstart 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4.5 integer32 read-write
For current based boost charge, the parameters Istart and Istop are the battery current values at which boost charge starts or stops.
                         dcBoostChargeIstop 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4.6 integer32 read-write
For details see dcBoostChargeIstart.
                         dcBoostChargeInhibitTime 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4.7 gauge32 read-write
A start condition for all types of boost charge. It defines the time from last boost charge stop to the next acceptable boost charge start.
                 dcSystemVoltageSupervision 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6
                     dcUaMax 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.1 integer32 read-write
If the system voltage is outside the range specified by the values UaMin (lower alarm voltage)/UaMax (upper alarm voltage), the system event 'S Ua low'/'S Ua high' is activated. The values for the parameters UaMin and UaMax are not temperature compensated.
                     dcUaMin 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.2 integer32 read-write
For details see dcUaMax.
                     dcUsMax 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.3 integer32 read-write
If the voltage is outside the range defined by the parameters UsMin (lower safety voltage)/UsMax (upper safety voltage), the system event 'S Us low'/'S Us high' is activated. If temperature compensation is enabled, the levels for Us min and / Us max are automatically temperature compensated to correspond to the required system voltage. The parameters are defined at 20C.
                     dcUsMin 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.4 integer32 read-write
For details see dcUsMax.
                     dcBoD 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.5 integer32 read-write
Voltage threshold for Battery on Discharge alarm.
                     dcHysteresis 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.6 integer32 read-write
Hysteresis used for Ua and Us.
                     dcSuppressUaLowEnabled 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.7 integer read-write
Suppress Ua Low alarm during mains failure. Enumeration: 'yes': 2, 'no': 1.
                     dcSuppressUsLowEnabled 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.8 integer read-write
Suppress Us Low alarm during mains failure. Enumeration: 'yes': 2, 'no': 1.
                     dcEnableUsTempComp 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.9 integer read-write
Checkbox to enable the automatic temperature compensation for the Us thresholds (Us min, Us max). Enumeration: 'yes': 2, 'no': 1.
                 dcEvtCtrlCharge 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7
                     dcEvtCtrlChargeStatus 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.1 integer read-only
Event control charge status. Enumeration: 'currentLimitation': 4, 'inactive': 1, 'voltageControlled': 2, 'noBatteryCharge': 3.
                     dcEvtCtrlChargeType 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.2 integer read-write
Selected event control charge type. Enumeration: 'currentLimitation': 4, 'none': 1, 'voltageControlled': 2, 'noBatteryCharge': 3.
                     dcEvtCtrlChargeParameter 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.3
                         dcEvtCtrlChargeVoltage 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.3.1 integer32 read-write
Voltage used for event control charge.
                         dcEvtCtrlChargeTempCompEnabled 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.3.2 integer read-write
Enable/disable temperature compensation during event control charge. Enumeration: 'yes': 2, 'no': 1.
                         dcEvtCtrlChargeMaxIBatt 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.3.3 integer32 read-write
Max. IBatt used for event control charge.
                 dcTempComp 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8
                     dcTempCompType 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.1 integer read-write
Enable/disable battery temperature compensation. Enumeration: 'multi-stage': 3, 'linear': 2, 'no': 1.
                     dcSlope 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.2 integer32 read-write
Temperature compensation coefficient for system voltage.
                     dcStartTemp 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.3 integer32 read-write
Lower limit for the area in which the temperature compensation is active.
                     dcStopTemp 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.4 integer32 read-write
Upper limit for the area in which the temperature compensation is active.
                     dcMaxVoltage 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.5 integer32 read-write
Upper limit for the area in which the temperature compensation is not controlling the system voltage.
                     dcLowStopVoltage 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.6 integer32 read-write
The temperature compensation will not control the charging voltage above this parameter at low temperatures.
                     dcLowStartTemp 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.7 integer32 read-write
High temperature limit of the lower range.
                     dcLowTempSlope 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.8 integer32 read-write
Compensation factor applied inside the low range.
                     dcHighStartTemp 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.9 integer32 read-write
The low temperature limit of the higher range.
                     dcHighTempSlope 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.10 integer32 read-write
Compensation factor applied inside the high range.
                     dcHighStopVoltage 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.11 integer32 read-write
The temperature compensation will not control the charging voltage below this parameter at high temperatures.
                     dcRunawayTemp 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.12 integer32 read-write
A threshold for detecting thermal runaway of the battery.
                     dcRunawayVoltage 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.13 integer32 read-write
Charging voltage while Runaway Temp has been exceeded.
                 dcTempSupervision 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.9
                     dcHighTemp 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.9.1 integer32 read-write
Temperature threshold for high battery temperature alarm 10C ... 70C
                     dcHighTempHyst 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.9.2 integer32 read-write
Hysteresis for the High Temp 1C ... 70C
             dcInputOutput 1.3.6.1.4.1.20246.2.3.1.1.1.2.6
                 dcControlEventTable 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1 no-access
Table that shows ten output event assignments that can be configured via WEB interface.
                     dcControlEventEntry 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1 no-access
A particular generic output entry.
                         dcControlEventIndex 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.1 integer32 no-access
Table index.
                         dcControlEventName 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.2 displaystring read-only
Plain text name of the assigned control event. Empty if not configure.
                         dcControlEventIdentifier 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.3 gauge32 read-only
Unique numeric identifier of the assigned control event. Zero if not configured.
                         dcControlEventValue 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.4 integer read-write
Current value of the assigned control event. Value is false if not configured. Enumeration: 'true': 2, 'false': 1.
             dcMisc 1.3.6.1.4.1.20246.2.3.1.1.1.2.7
                 dcTrapDestinationTable 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1 no-access
Trap table that shows all configured trap destinations.
                     dcTrapDestinationEntry 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1 no-access
A particular trap destination entry.
                         dcTrapDestinationIndex 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.1 integer32 no-access
Table index.
                         dcTrapDestinationIp 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.2 ipaddress read-write
IP address of the trap destination. Value is 0.0.0.0 if IP address is not configured.
                         dcTrapDestinationPort 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.3 gauge32 read-write
Port number of the trap destination. By default port 162 is used.
                 dcFileProcessingStatus 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.2 integer read-only
File processing status for software and setup up/downloads. Enumeration: 'successful': 3, 'unknown': 5, 'idle': 1, 'inProgress': 2, 'error': 4.
                 dcResendActiveAlarmTraps 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.4 integer read-write
Resend all active Urgent, Non Urgent, and Critical Alarm Traps. Enumeration: 'resend': 1.
             dcConfig 1.3.6.1.4.1.20246.2.3.1.1.1.2.8
                 dcDefaultLogEventTable 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1 no-access
Event config table for default log.
                     dcDefaultLogEventEntry 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1.1 no-access
A particular event entry.
                         dcDefaultLogEventIndex 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1.1.1 integer32 no-access
Table index.
                         dcDefaultLogEventName 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1.1.2 displaystring read-only
Plain text name of the event that can be logged.
                         dcDefaultLogEventLogged 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1.1.3 integer read-write
If yes then this event is logged otherwise not. Enumeration: 'yes': 2, 'no': 1.
                 dcEventProcessingEventTable 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2 no-access
Event config table for event ORs.
                     dcEventProcessingEventEntry 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1 no-access
A particular event entry.
                         dcEventProcessingEventIndex 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1.1 integer32 no-access
Table index.
                         dcEventProcessingEventName 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1.2 displaystring read-only
Plain text name of the input event.
                         dcEventProcessingEventAssigned 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1.3 integer read-write
If yes then the input event is assigned to the selected event. Please note, that it is only possible to change assignment of event ORs. Enumeration: 'yes': 2, 'no': 1.
                         dcEventProcessingEventType 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1.4 integer read-only
Type of the input event. Enumeration: 'eventOR': 2, 'unknown': 1.
                 dcEventProcessingEventSelected 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.3 gauge32 read-write
Reference to dcEventProcessingEventIndex in order to select a specific event.
                 dcLvdTable 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4 no-access
Table lists all available LVDs.
                     dcLvdEntry 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1 no-access
A particular LVD entry.
                         dcLvdIndex 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.1 integer32 no-access
Table index.
                         dcLvdName 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.2 displaystring read-only
Name of the LVD.
                         dcLvdDisconnectDelay 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.3 displaystring read-write
Time delay from the activation of the source event, after which the LVD event is switched. The value is in the format 'hh:mm:ss'.
             dcMeasurement 1.3.6.1.4.1.20246.2.3.1.1.1.2.9
                 dcMeasurementTable 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1 no-access
Table lists all available measurements.
                     dcMeasurementEntry 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1 no-access
A particular measurement entry.
                         dcMeasurementIndex 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.1 integer32 no-access
Table index.
                         dcMeasurementName 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.2 displaystring read-only
Name of the measurement.
                         dcMeasurementValue 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.3 integer32 read-only
Unscaled calibrated value of the measurement.
                         dcMeasurementScaleFactor 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.4 integer32 read-only
Scale factor as power of 10 to be multiplied with measurement value.
                         dcMeasurementUnit 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.5 integer read-only
Unit of the measurement. Enumeration: 'none': 2, 'voltAmpere': 14, 'seconds': 11, 'unknown': 1, 'percent': 12, 'hertz': 13, 'voltAmpereReactiveHour': 16, 'ampereHour': 6, 'wattHour': 10, 'degreeCelsius': 7, 'watt': 9, 'voltDC': 3, 'ampere': 5, 'temperatureCoefficient': 8, 'voltAmpereReactive': 15, 'voltAC': 4.
             dcMeterPanel 1.3.6.1.4.1.20246.2.3.1.1.1.2.10
                   dcMeterPanelEventTable 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1 no-access
Table lists all available meter panel events.
                       dcMeterPanelEventEntry 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1 no-access
A particular meter panel event entry.
                           dcMeterPanelEventIndex 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1.1 integer32 no-access
Table index.
                           dcMeterPanelEventName 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1.2 displaystring read-only
Name of the event.
                           dcMeterPanelEventValue 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1.3 integer read-only
Value of the event. Enumeration: 'true': 3, 'indeterminate': 2, 'false': 1.
                           dcMeterPanelEventHourMeterValue 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1.4 gauge32 read-only
Value of the hour meter event.
         controllerEvents 1.3.6.1.4.1.20246.2.3.1.1.1.3
             controllerEventObjects 1.3.6.1.4.1.20246.2.3.1.1.1.3.1
                 controllerEventsV2 1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0
                     systemNonUrgentAlarm 1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0.1
The controller reports that one or more elements have changed into none urgent alarm state.
                     systemUrgentAlarm 1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0.2
The controller reports that one or more elements have changed into urgent alarm state.
                     systemCriticalAlarm 1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0.3
The controller reports that one or more elements have changed into critical alarm state.