LIEBERT-GP-POWER-MIB: View SNMP OID List / Download MIB

VENDOR: VERTIV


 Home MIB: LIEBERT-GP-POWER-MIB
Download as:   

Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 liebertGlobalProductsPowerModule 1.3.6.1.4.1.476.1.42.1.6.1
The MIB module used to register Liebert POWER related SNMP OIDs. Copyright 2000-2008 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
 lgpPwrBattery 1.3.6.1.4.1.476.1.42.3.5.1
This sub-tree is used to register Liebert Power Battery object identifiers.
     lgpPwrNumberInstalledBatteryModules 1.3.6.1.4.1.476.1.42.3.5.1.1 integer32 read-only
The number of battery modules installed in the device.
     lgpPwrNumberFailedBatteryModules 1.3.6.1.4.1.476.1.42.3.5.1.2 integer32 read-only
The number of battery modules in the device that have failed.
     lgpPwrNumberRedundantBatteryModules 1.3.6.1.4.1.476.1.42.3.5.1.3 integer32 read-only
The number of redundant battery modules in the device.
     lgpPwrNumberActiveBatteryModules 1.3.6.1.4.1.476.1.42.3.5.1.4 integer32 read-only
The number of active battery modules in the device.
     lgpPwrConfigLowBatteryWarningTime 1.3.6.1.4.1.476.1.42.3.5.1.5 integer32 read-write
The value of the device's estimated minutes of remaining battery at which a lgpEventLowBatteryWarning notification will be sent.
     lgpPwrNumberBatteryModuleWarnings 1.3.6.1.4.1.476.1.42.3.5.1.6 integer32 read-only
The number of battery modules in the device that have a warning.
     lgpPwrBatteryCount 1.3.6.1.4.1.476.1.42.3.5.1.7 integer32 read-only
The number of batteries installed.
     lgpPwrBatteryTestResult 1.3.6.1.4.1.476.1.42.3.5.1.8 integer read-only
The outcome of the previous battery test. Enumeration: 'unknown': 1, 'systemFailure': 5, 'failed': 3, 'inhibited': 6, 'passed': 2, 'inProgress': 4.
     lgpPwrNominalBatteryCapacity 1.3.6.1.4.1.476.1.42.3.5.1.9 integer32 read-write
The nominal battery capacity of the system (in minutes) at full load.
     lgpPwrBatteryFloatVoltage 1.3.6.1.4.1.476.1.42.3.5.1.10 integer32 read-write
The battery float voltage of the system.
     lgpPwrBatteryEndOfDischargeVoltage 1.3.6.1.4.1.476.1.42.3.5.1.11 integer32 read-write
The battery voltage threshold at which the batteries are considered completely discharged.
     lgpPwrAutomaticBatteryTestInterval 1.3.6.1.4.1.476.1.42.3.5.1.12 integer32 read-write
The automatic battery test interval.
     lgpPwrAutomaticBatteryTestCountdown 1.3.6.1.4.1.476.1.42.3.5.1.13 integer32 read-write
The time remaining before the next battery test.
     lgpPwrBatteryChargeStatus 1.3.6.1.4.1.476.1.42.3.5.1.14 integer read-only
The present state of the system's battery charge. A value of 'charging' indicates the batteries are currently charging. A value of 'discharging' indicates the batteries are currently discharging. A value of 'fullycharged' indicates the batteries are charged to their full capacity. A value of 'notfullycharged' indicates the battery charge is neither fully charged, charging or discharging. Enumeration: 'fullycharged': 1, 'notfullycharged': 2, 'discharging': 4, 'charging': 3.
     lgpPwrBatteryLifeEnhancer 1.3.6.1.4.1.476.1.42.3.5.1.15 integer read-only
The state of the battery life enhancer. When 'on', it will preserve battery life. Enumeration: 'on': 1, 'off': 2.
     lgpPwrBatteryCharger 1.3.6.1.4.1.476.1.42.3.5.1.16 integer read-only
The state of the battery charger. Enumeration: 'on': 1, 'off': 2.
     lgpPwrBatteryChargeMode 1.3.6.1.4.1.476.1.42.3.5.1.17 integer read-only
The mode of the battery charger: 'float' charging or 'equalize' charging. Enumeration: 'float': 1, 'equalize': 2.
     lgpPwrBatteryTimeRemaining 1.3.6.1.4.1.476.1.42.3.5.1.18 integer32 read-only
An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off. NOTE: A UPS is expected to provide a battery time remaining value when not operating on battery. However, if the system is not capable of providing this information, then this point will return 65535 to indicate that the value is unavailable.
     lgpPwrBatteryCapacity 1.3.6.1.4.1.476.1.42.3.5.1.19 integer32 read-only
The present percentage of battery capacity.
     lgpPwrBatteryCabinet 1.3.6.1.4.1.476.1.42.3.5.1.20
This sub-tree contains items related to battery cabinets.
           lgpPwrBatteryCabinetCount 1.3.6.1.4.1.476.1.42.3.5.1.20.1 integer32 read-write
The number of battery cabinets installed with this device. Note some devices may not permit writing a value to this object.
           lgpPwrBatteryCabinetType 1.3.6.1.4.1.476.1.42.3.5.1.20.2 integer read-write
The type of battery cabinet(s) installed on this device. Enumeration definitions: notSpecified - The type has not been specified in the device's configuration. internal - Battery cabinets are internal to the device. external - Device has external battery cabinets installed. lrt - Long Run Time cabinets. Note some devices may not permit writing a value to this object. Enumeration: 'notSpecified': 1, 'internal': 2, 'lrt': 4, 'external': 3.
           lgpPwrBatteryCabinetRatedCapacity 1.3.6.1.4.1.476.1.42.3.5.1.20.3 integer32 read-write
Battery cabinet rated capacity (tenths of Amp-hours). This assumes that each cabinet is of the same type and capacity. This is not a sum of the rating for all attached cabinets. Note some devices may not permit writing a value to this object.
           lgpPwrBatteryLeadAcidCellCount 1.3.6.1.4.1.476.1.42.3.5.1.20.4 integer32 read-write
Battery cell count - lead-acid. The number of cells that comprise the lead acid battery string.
           lgpPwrBatteryNiCadCellCount 1.3.6.1.4.1.476.1.42.3.5.1.20.5 integer32 read-write
Battery cell count - nickel-cadmium. The number of cells that comprise the nickel-cadmium battery string.
     lgpPwrBatteryAmpHoursConsumed 1.3.6.1.4.1.476.1.42.3.5.1.21 integer32 read-write
The cumulative battery Amp-hours withdrawn over the life of the battery. This value persists across reboots. Typically, this value is reset back to zero when the batteries are replaced.
     lgpPwrBatteryAmpHoursDischargeConsumed 1.3.6.1.4.1.476.1.42.3.5.1.22 integer32 read-write
The battery Amp-hours withdrawn during the current/latest discharge. This value does not persist across reboots.
     lgpPwrBatteryLastDischargeTime 1.3.6.1.4.1.476.1.42.3.5.1.23 unsigned32 read-write
The date and time of the last battery discharge. Typically this is the time when the discharge starts. This value persists across reboots. The date and time are determined in seconds since the epoch on January 1, 1970.
     lgpPwrBatteryLastCommissionTime 1.3.6.1.4.1.476.1.42.3.5.1.24 unsigned32 read-write
The date and time when the battery system was put into service. This information persists across system reboot events. It is the responsibility of Service to reset this date/time when the batteries are replaced. The date and time are determined in seconds since the epoch on January 1, 1970.
     lgpPwrBatteryPresentDischargeTime 1.3.6.1.4.1.476.1.42.3.5.1.25 integer32 read-only
The total time spent on battery during the current or last discharge. NOTE: While not discharging, some systems may display zero instead of the last discharge.
     lgpPwrBatteryCapacityStatus 1.3.6.1.4.1.476.1.42.3.5.1.26 integer read-only
The indication of the capacity remaining in the UPS system's batteries. NOTE: In a single-module system, this point is intended to have the same behavior as the RFC1628 point upsBatteryStatus. Enumeration: 'unknown': 1, 'batteryNormal': 2, 'batteryDepleted': 4, 'batteryLow': 3.
     lgpPwrBatteryCircuitBreakerState 1.3.6.1.4.1.476.1.42.3.5.1.27 integer read-only
The state of the Battery Circuit Breaker. Enumeration: 'unknown': 0, 'open': 1, 'closed': 2.
 lgpPwrMeasurements 1.3.6.1.4.1.476.1.42.3.5.2
This sub-tree registers Liebert Power Measurement object identifiers. The sub-tree contains tables and well known power measurement points.
     lgpPwrWellKnownMeasurementPoints 1.3.6.1.4.1.476.1.42.3.5.2.1
This sub-tree registers well known Liebert Power Measurement Points. The object identifier names usually imply locations where the measurement is taken -- such as 'input', 'output' and 'bypass'.
         lgpPwrSource1Input 1.3.6.1.4.1.476.1.42.3.5.2.1.1
This sub-tree is used to register a source 1 input as a well known measurement point. It is intended that no sub-trees be created below this node. Power input to the managed device from power source 1. Many power systems contain more than one input source and many of them have more than one measurement point per input source. This identifier represents one input source for the system but does not necessarily represent the 'first' one. The input sources' numbering with respect to 'lgpPwrSource1Input' etc. may depend on the physical wiring of the system when it was installed.
         lgpPwrSource2Input 1.3.6.1.4.1.476.1.42.3.5.2.1.2
This sub-tree is used to register a source 2 input as a well known measurement point. It is intended that no sub-trees be created below this node. Power input to the managed device from power source 2. Many power systems contain more than one input source and many of them have more than one measurement point per input source. This identifier represents one input source for the system but does not necessarily represent the 'first' one. The input sources' numbering with respect to 'lgpPwrSource2Input' etc. may depend on the physical wiring of the system when it was installed.
         lgpPwrSourcePdu1Input 1.3.6.1.4.1.476.1.42.3.5.2.1.3
This sub-tree is used to register a source PDU 1 input as a well known measurement point. It is intended that no sub-trees be created below this node. Power input to the managed device from power distribution unit 1. Many power systems contain more than one input source and many of them have more than one measurement point per input source. This identifier represents one input source for the system but does not necessarily represent the 'first' one. The input sources' numbering with respect to 'lgpPwrSourcePdu1Input' etc. may depend on the physical wiring of the system when it was installed.
         lgpPwrSourcePdu2Input 1.3.6.1.4.1.476.1.42.3.5.2.1.4
This sub-tree is used to register a source PDU 2 input as a well known measurement point. It is intended that no sub-trees be created below this node. Power input to the managed device from power distribution unit 1. Many power systems contain more than one input source and many of them have more than one measurement point per input source. This identifier represents one input source for the system but does not necessarily represent the 'first' one. The input sources' numbering with respect to 'lgpPwrSourcePdu2Input' etc. may depend on the physical wiring of the system when it was installed.
         lgpPwrOutputToLoad 1.3.6.1.4.1.476.1.42.3.5.2.1.5
This sub-tree is used to register the output to the critical load as a well known measurement point. It is intended that no sub-trees be created below this node.
         lgpPwrMeasBattery 1.3.6.1.4.1.476.1.42.3.5.2.1.6
This sub-tree is used to register a battery as a well known measurement point. It is intended that no sub-trees be created below this node.
         lgpPwrMeasBypass 1.3.6.1.4.1.476.1.42.3.5.2.1.7
This sub-tree is used to register a bypass as a well known measurement point. It is intended that no sub-trees be created below this node.
         lgpPwrMeasDcBus 1.3.6.1.4.1.476.1.42.3.5.2.1.8
This sub-tree is used to register a DC bus as a well known measurement point. It is intended that no sub-trees be created below this node.
         lgpPwrMeasSystemOutput 1.3.6.1.4.1.476.1.42.3.5.2.1.9
This sub-tree is used to register the output of a multi-module system as a well known measurement point. It is intended that no sub-trees be created below this node. This identifier represents the power related data of the system.
         lgpPwrMeasBatteryCabinet 1.3.6.1.4.1.476.1.42.3.5.2.1.10
This sub-tree is used to register the voltage between the most negative and the most postive terminals of a battery cabinet. To determine the cabinet being described in a multi-cabinet system, this point implements an additional two indexes. The first index describes the module the cabinet is located in. The second index describes the cabinet number. In an SMS(Single-Module System) the first index is always 1. Example: lgpPwrMeasBatteryCabinet.2.4 'lgpPwrMeasBatteryCabinet' = Point is a battery cabinet. '.2' = Cabinet is in the second module. '.4' = Cabinet number 4
     lgpPwrMeasurementPointTable 1.3.6.1.4.1.476.1.42.3.5.2.2 no-access
This table contains a list of AC power measurement point entries. The table contains zero, one, or many rows, depending upon the number of power related measurement points available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device. Each row in the table represents a series of measurements on a given point or location within the system. Measurement points/locations are identified by the object identifier 'lgpPwrMeasurementPointId' in the 'LgpPwrMeasurementPointEntry' object. The actual measurement being taken at that identified point is identified by the other corresponding columns in the LgpPwrMeasurementPointEntry for the particular row of the table.
         lgpPwrMeasurementPointEntry 1.3.6.1.4.1.476.1.42.3.5.2.2.1 no-access
This entry defines the measurements to be populated in the various columns of the 'lgpPwrMeasurementPointTable'.
             lgpPwrMeasurementPointIndex 1.3.6.1.4.1.476.1.42.3.5.2.2.1.1 unsigned32 no-access
This is the index that indicates the row of the 'lgpPwrMeasurementPointTable' for a power measurement point.
             lgpPwrMeasurementPointId 1.3.6.1.4.1.476.1.42.3.5.2.2.1.2 object identifier read-only
An OID representing a well known measurement point. These object identifiers indicate a point or location of power measurement in a power system. The OID's name usually implies a location of the measurement point such as 'input', 'output', 'bypass' etc.
             lgpPwrMeasurementPointNumLines 1.3.6.1.4.1.476.1.42.3.5.2.2.1.3 integer32 read-only
The number of lines on the indicated power measurement point. (i.e. the number of phases on the power source being measured.)
             lgpPwrMeasurementPointNomVolts 1.3.6.1.4.1.476.1.42.3.5.2.2.1.4 integer32 read-only
The magnitude of the nominal voltage on the power source being measured.
             lgpPwrMeasurementPointNomFrequency 1.3.6.1.4.1.476.1.42.3.5.2.2.1.5 integer32 read-only
The nominal or configured/expected frequency for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
             lgpPwrMeasurementPointFrequency 1.3.6.1.4.1.476.1.42.3.5.2.2.1.6 integer32 read-only
The present (actual) frequency for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
             lgpPwrMeasurementPointApparentPower 1.3.6.1.4.1.476.1.42.3.5.2.2.1.7 integer32 read-only
The present apparent AC power for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
             lgpPwrMeasurementPointTruePower 1.3.6.1.4.1.476.1.42.3.5.2.2.1.8 integer32 read-only
The present AC power for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
             lgpPwrMeasurementPointPowerFactor 1.3.6.1.4.1.476.1.42.3.5.2.2.1.9 integer32 read-only
The present Power Factor for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
             lgpPwrMeasurementPointWattHours 1.3.6.1.4.1.476.1.42.3.5.2.2.1.10 integer32 read-only
The present number of Watt Hours for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
             lgpPwrMeasurementPointVAPercent 1.3.6.1.4.1.476.1.42.3.5.2.2.1.11 integer32 read-only
The percentage of the rated apparent AC power of the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
             lgpPwrMeasurementPointNeutralCurrent 1.3.6.1.4.1.476.1.42.3.5.2.2.1.12 integer32 read-only
The present neutral current of the power point indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
             lgpPwrMeasurementPointGroundCurrent 1.3.6.1.4.1.476.1.42.3.5.2.2.1.13 integer32 read-only
The present ground current of the power point indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
             lgpPwrMeasurementPointNomCurrent 1.3.6.1.4.1.476.1.42.3.5.2.2.1.14 integer32 read-only
The nominal or configured/expected current of the power point indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
             lgpPwrMeasurementPointNomPowerFactor 1.3.6.1.4.1.476.1.42.3.5.2.2.1.15 integer32 read-only
The nominal or configured/expected power factor of the power point indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
             lgpPwrMeasurementPointNomVA 1.3.6.1.4.1.476.1.42.3.5.2.2.1.16 integer32 read-write
The nominal or configured/expected apparent AC power for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
             lgpPwrMeasurementPointNomW 1.3.6.1.4.1.476.1.42.3.5.2.2.1.17 integer32 read-write
The nominal or configured/expected true AC power for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
             lgpPwrMeasurementPointPowerFactorTag 1.3.6.1.4.1.476.1.42.3.5.2.2.1.19 integer read-only
The present description of the Power Factor for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable. If Leading, the load is said to be capacitive and the phase of the current leads the voltage. If Lagging, the load is said to be inductive and the phase of the current lags the voltage. Enumeration: 'leading': 1, 'lagging': 2.
     lgpPwrLineMeasurementTable 1.3.6.1.4.1.476.1.42.3.5.2.3 no-access
A list of power measurements for each phase/line for a given power measurement point/location in the 'lgpPwrMeasurementPointTable'. The lgpPwrMeasurementPointIndex in this table corresponds to the index in the lgpPwrMeasurementPointTable. This table contains zero, one, or many rows, depending upon the number of power line source objects available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device.
         lgpPwrLineMeasurementEntry 1.3.6.1.4.1.476.1.42.3.5.2.3.1 no-access
This entry defines the contents of the columns for the table 'lgpPwrLineMeasurementTable'.
             lgpPwrMeasurementPtIndex 1.3.6.1.4.1.476.1.42.3.5.2.3.1.1 unsigned32 no-access
This is the index indicating the row of the table 'lgpPwrMeasurementPointTable' for a power measurement point.
             lgpPwrLineMeasurementIndex 1.3.6.1.4.1.476.1.42.3.5.2.3.1.2 unsigned32 no-access
This is the index indicating the row of the table 'lgpPwrLineMeasurementTable' for a power measurement point.
             lgpPwrMeasurementPoint 1.3.6.1.4.1.476.1.42.3.5.2.3.1.3 object identifier read-only
An OID representing a well known measurement point. These object identifiers indicate a point or location of power measurement in a power system. The OID name usually implies a location of the measurement point such as 'input', 'output', 'bypass', etc.
             lgpPwrLineMeasurementVoltsLL 1.3.6.1.4.1.476.1.42.3.5.2.3.1.4 integer32 read-only
The present Line-to-Line voltage measurement for the indicated source. The line being measured is given by the lgpPwrLineMeasurementIndex [1 = AB, 2 = BC, 3 = CA].
             lgpPwrLineMeasurementVoltsLN 1.3.6.1.4.1.476.1.42.3.5.2.3.1.5 integer32 read-only
The present Line-to-neutral voltage measurement for the indicated source. The line being measured is given by the lgpPwrLineMeasurementIndex where [1 = A, 2 = B, 3 = C].
             lgpPwrLineMeasurementCurrent 1.3.6.1.4.1.476.1.42.3.5.2.3.1.6 integer32 read-only
The present current measurement for the indicated source. The line being measured is given by the 'lgpPwrLineMeasurementIndex' where [1 = A, 2 = B, 3 = C].
             lgpPwrLineMeasurementCapacity 1.3.6.1.4.1.476.1.42.3.5.2.3.1.7 integer32 read-only
The percentage of the power capacity presently being used on this line.
             lgpPwrLineMeasurementVA 1.3.6.1.4.1.476.1.42.3.5.2.3.1.8 integer32 read-only
The present apparent AC line power.
             lgpPwrLineMeasurementTruePower 1.3.6.1.4.1.476.1.42.3.5.2.3.1.9 integer32 read-only
The present AC line power measured in watts.
             lgpPwrLineMeasurementVoltageTHD 1.3.6.1.4.1.476.1.42.3.5.2.3.1.10 integer32 read-only
The present total harmonic distortion on the AC line voltage.
             lgpPwrLineMeasurementCurrentTHD 1.3.6.1.4.1.476.1.42.3.5.2.3.1.11 integer32 read-only
The present total harmonic distortion on the AC line current.
             lgpPwrLineMeasurementKFactorCurrent 1.3.6.1.4.1.476.1.42.3.5.2.3.1.12 integer32 read-only
The present line K Factor.
             lgpPwrLineMeasurementCrestFactorCurrent 1.3.6.1.4.1.476.1.42.3.5.2.3.1.13 integer32 read-only
The present crest factor of the line current.
             lgpPwrLineMeasurementPowerFactor 1.3.6.1.4.1.476.1.42.3.5.2.3.1.14 integer32 read-only
The present Power Factor for the line.
             lgpPwrLineMeasurementPowerFactorTag 1.3.6.1.4.1.476.1.42.3.5.2.3.1.15 integer read-only
The present description of the Power Factor for the line. If Leading, the load is said to be capacitive and the phase of the current leads the voltage. If Lagging, the load is said to be inductive and the phase of the current lags the voltage. Enumeration: 'leading': 1, 'lagging': 2.
             lgpPwrLineMeasurementMaxVolts 1.3.6.1.4.1.476.1.42.3.5.2.3.1.16 integer32 read-only
The maximum voltage measurement recorded for the indicated source since the command 'lgpPwrStatisticsReset' was executed.
             lgpPwrLineMeasurementMinVolts 1.3.6.1.4.1.476.1.42.3.5.2.3.1.17 integer32 read-only
The minimum voltage measurement recorded for the indicated source since the command 'lgpPwrStatisticsReset' was executed.
             lgpPwrLineMeasurementVAR 1.3.6.1.4.1.476.1.42.3.5.2.3.1.18 integer32 read-only
The present reactive AC line power of the power source indicated by 'lgpPwrMeasurementPoint'.
             lgpPwrLineMeasurementPercentLoad 1.3.6.1.4.1.476.1.42.3.5.2.3.1.19 integer32 read-only
The present percent load of the AC line power.
             lgpPwrLineMeasurementVolts 1.3.6.1.4.1.476.1.42.3.5.2.3.1.20 integer32 read-only
The present voltage measurement for the indicated source.
             lgpPwrLineMeasurementVACapacity 1.3.6.1.4.1.476.1.42.3.5.2.3.1.21 integer32 read-only
The percentage of the apparent power capacity presently being used on this line.
     lgpPwrDcMeasurementPointTable 1.3.6.1.4.1.476.1.42.3.5.2.4 no-access
This table contains a list of DC power measurement point entries. The table contains zero, one, or many rows, depending upon the number of power related measurement points available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device. Each row in the table represents a series of measurements on a given point or location within the system. Measurement points/locations are identified by the object identifier 'lgpPwrDcMeasurementPointId' in the 'LgpPwrDcMeasurementPointEntry' object. The actual measurement being taken at that identified point is identified by the other corresponding columns in the LgpPwrDcMeasurementPointEntry for the particular row of the table.
         lgpPwrDcMeasurementPointEntry 1.3.6.1.4.1.476.1.42.3.5.2.4.1 no-access
This entry defines the measurements to be populated in the various columns of the 'lgpPwrDcMeasurementPointTable'.
             lgpPwrDcMeasurementPointIndex 1.3.6.1.4.1.476.1.42.3.5.2.4.1.1 unsigned32 no-access
This is the index that indicates the row of the 'lgpPwrMeasurementPointTable' for a power measurement point.
             lgpPwrDcMeasurementPointId 1.3.6.1.4.1.476.1.42.3.5.2.4.1.2 object identifier read-only
An OID representing a well known measurement point. These object identifiers indicate a point or location of power measurement in a power system. The OID's name usually implies a location of the measurement point such as 'input', 'output', 'bypass' etc.
             lgpPwrDcMeasurementPointSubID 1.3.6.1.4.1.476.1.42.3.5.2.4.1.3 integer32 read-only
The identifier used to differentiate between identical thresholds for a given point index and point ID in the DC measurements table.
             lgpPwrDcMeasurementPointVolts 1.3.6.1.4.1.476.1.42.3.5.2.4.1.4 integer32 read-only
The present DC voltage for the power source indicated by 'lgpPwrDcMeasurementPointId' in the corresponding row in the lgpPwrDcMeasurementPointTable.
             lgpPwrDcMeasurementPointCurrent 1.3.6.1.4.1.476.1.42.3.5.2.4.1.5 integer32 read-only
The present DC current for the power source indicated by 'lgpPwrDcMeasurementPointId' in the corresponding row in the lgpPwrDcMeasurementPointTable.
             lgpPwrDcMeasurementPointNomVolts 1.3.6.1.4.1.476.1.42.3.5.2.4.1.6 integer32 read-only
The nominal(configured/expected) DC voltage for the power source indicated by 'lgpPwrDcMeasurementPointId' in the corresponding row in the lgpPwrDcMeasurementPointTable.
             lgpPwrDcMeasurementPointTruePower 1.3.6.1.4.1.476.1.42.3.5.2.4.1.7 integer32 read-only
The present DC power for the power source indicated by 'lgpPwrDcMeasurementPointId' in the corresponding row in the lgpPwrDcMeasurementPointTable.
     lgpPwrWellKnownMeasurementTypes 1.3.6.1.4.1.476.1.42.3.5.2.5
This sub-tree registers well known Liebert Power Measurement Types. The object identifier names usually encompass units of measure, lines of reference, and device location. The OID's name usually implies a measurement type such as 'voltsAC', 'current', 'voltsDc', 'VoltsLL', etc.
         lgpPwrVoltsAc 1.3.6.1.4.1.476.1.42.3.5.2.5.1
This identifier represents an AC voltage.
         lgpPwrVoltsDc 1.3.6.1.4.1.476.1.42.3.5.2.5.2
This identifier represents a DC voltage.
         lgpPwrAmpsNeutral 1.3.6.1.4.1.476.1.42.3.5.2.5.3
This identifier represents a current measurement in Amps on the neutral line.
 lgpPwrStatus 1.3.6.1.4.1.476.1.42.3.5.3
This sub-tree registers Liebert Power Status object identifiers. This is the location of power related status information that does not fit into a more specific category such as the lgpPwrConversion sub-tree.
     lgpPwrTransferCount 1.3.6.1.4.1.476.1.42.3.5.3.1 integer32 read-only
Number of times that the output load has been transferred between the available input sources.
     lgpPwrAutoTransferTimer 1.3.6.1.4.1.476.1.42.3.5.3.2 integer32 read-only
The required wait time between output load auto transfer attempts between available input sources.
     lgpPwrAutoReTransferEnabled 1.3.6.1.4.1.476.1.42.3.5.3.3 integer read-only
The ability to retransfer the output load automatically to the well known measurement source from the 'lgpPwrWellKnownMeasurements' sub-tree that is the preferred input source of the system Enumeration: 'yes': 1, 'no': 0.
     lgpPwrSyncPhaseAngle 1.3.6.1.4.1.476.1.42.3.5.3.4 integer32 read-only
The phase angle difference of source 1 in relation to source 2.
     lgpPwrParallelSystemOutputToLoadSource 1.3.6.1.4.1.476.1.42.3.5.3.5 integer read-only
The source supporting the parallel system's load. Enumeration: 'battery': 2, 'unknown': 0, 'none': 4, 'bypass': 3, 'utility': 1.
     lgpPwrDcToDcConverter 1.3.6.1.4.1.476.1.42.3.5.3.6 integer read-only
The state of the DC to DC converter. Enumeration: 'on': 1, 'off': 2.
     lgpPwrOutputToLoadOnInverter 1.3.6.1.4.1.476.1.42.3.5.3.7 integer read-only
The present source of output power is the Inverter. Enumeration: 'yes': 1, 'no': 2.
     lgpPwrBatteryChargeCompensating 1.3.6.1.4.1.476.1.42.3.5.3.8 integer read-only
The system is adjusting the battery charging algorithm to accommodate for the battery temperature. Enumeration: 'yes': 1, 'no': 2.
     lgpPwrInverterReady 1.3.6.1.4.1.476.1.42.3.5.3.9 integer read-only
The ability of the inverter to support the output load of the system. Enumeration: 'yes': 1, 'no': 2.
     lgpPwrOutputToLoadOnBypass 1.3.6.1.4.1.476.1.42.3.5.3.10 integer read-only
The present source of output power is the Bypass. Enumeration: 'yes': 1, 'no': 2.
     lgpPwrBoost 1.3.6.1.4.1.476.1.42.3.5.3.11 integer read-only
The present state of the boost circuitry Enumeration: 'on': 1, 'off': 2.
     lgpPwrBuck 1.3.6.1.4.1.476.1.42.3.5.3.12 integer read-only
The present state of the buck circuitry Enumeration: 'on': 1, 'off': 2.
     lgpPwrShutdownOverTemperature 1.3.6.1.4.1.476.1.42.3.5.3.13 integer read-only
The system has previously shutdown due to an over temperature condition. Enumeration: 'yes': 1, 'no': 2.
     lgpPwrShutdownOverload 1.3.6.1.4.1.476.1.42.3.5.3.14 integer read-only
The system has previously shutdown due to an over load condition. Enumeration: 'yes': 1, 'no': 2.
     lgpPwrShutdownDcBusOverload 1.3.6.1.4.1.476.1.42.3.5.3.15 integer read-only
The system has previously shutdown due to a DC bus over load condition. Enumeration: 'yes': 1, 'no': 2.
     lgpPwrShutdownOutputShort 1.3.6.1.4.1.476.1.42.3.5.3.16 integer read-only
The system has previously shutdown due to an output short condition. Enumeration: 'yes': 1, 'no': 2.
     lgpPwrShutdownLineSwap 1.3.6.1.4.1.476.1.42.3.5.3.17 integer read-only
The system has previously shutdown due to a condition where the line and neutral were reversed. Enumeration: 'yes': 1, 'no': 2.
     lgpPwrShutdownLowBattery 1.3.6.1.4.1.476.1.42.3.5.3.18 integer read-only
The system has previously shutdown due to a low battery condition. Enumeration: 'yes': 1, 'no': 2.
     lgpPwrShutdownRemote 1.3.6.1.4.1.476.1.42.3.5.3.19 integer read-only
The system has previously shutdown due to a remote shutdown command. Enumeration: 'yes': 1, 'no': 2.
     lgpPwrShutdownInputUnderVoltage 1.3.6.1.4.1.476.1.42.3.5.3.20 integer read-only
The system has previously shutdown due to an under voltage condition during startup. Enumeration: 'yes': 1, 'no': 2.
     lgpPwrShutdownPowerFactorCorrectionFailure 1.3.6.1.4.1.476.1.42.3.5.3.21 integer read-only
The system has previously shutdown due to a power factor correction startup failure. Enumeration: 'yes': 1, 'no': 2.
     lgpPwrShutdownHardware 1.3.6.1.4.1.476.1.42.3.5.3.22 integer read-only
The system has previously shutdown due external shutdown signal. Enumeration: 'yes': 1, 'no': 2.
     lgpPwrRedundantSubModule 1.3.6.1.4.1.476.1.42.3.5.3.23 integer read-only
The system has a redundant battery module installed. Enumeration: 'yes': 1, 'no': 2.
     lgpPwrBypassReady 1.3.6.1.4.1.476.1.42.3.5.3.24 integer read-only
The ability of the bypass to support the output load of the system. If Yes, the bypass is available to transfer to. Enumeration: 'yes': 1, 'no': 2.
     lgpPwrGeneratorStatus 1.3.6.1.4.1.476.1.42.3.5.3.25 integer read-only
The state of the system generator. Enumeration: 'connected': 1, 'disconnected': 2.
     lgpPwrRotaryBreakerStatus 1.3.6.1.4.1.476.1.42.3.5.3.26 integer read-only
The state of the system rotary breaker. Enumeration: 'bypass': 5, 'normal': 4, 'unknown': 1, 'maintenance': 6, 'test': 3, 'closed': 2.
     lgpPwrPowerFactorCorrection 1.3.6.1.4.1.476.1.42.3.5.3.27 integer read-only
The state of the power factor correction circuitry of the system. Enumeration: 'on': 1, 'off': 2.
     lgpPwrBypassSyncDiff 1.3.6.1.4.1.476.1.42.3.5.3.28 integer32 read-only
The phase angle difference between the inverter output and bypass source. A positive value means the inverter leads the bypass source. A negative value means the inverter lags the bypass source.
     lgpPwrBypassOverloadShutdownTime 1.3.6.1.4.1.476.1.42.3.5.3.29 integer32 read-only
The calculated time remaining before bypass static switch shutdown due to the present overload condition. If the bypass is not in an overload condition, this object returns -1.
     lgpPwrInverterOverloadShutdownTime 1.3.6.1.4.1.476.1.42.3.5.3.30 integer32 read-only
The calculated time remaining before inverter shutdown. The calculated time of inverter operation remaining for the present overload event. Note: If the inverter is not experiencing an overload event this point will return 65535 indicating this value is unavailable.
     lgpPwrStateOutputSource 1.3.6.1.4.1.476.1.42.3.5.3.31 integer read-only
The UPS's output power source (inverter, bypass, or none). NOTE: It is possible that the load still has power from the Maintenance Bypass. Enumeration: 'maintenanceBypass': 4, 'inverter': 2, 'none': 1, 'bypass': 3.
     lgpPwrStateInputSource 1.3.6.1.4.1.476.1.42.3.5.3.32 integer read-only
The system input power source (none, utility, generator). Enumeration: 'none': 1, 'generator': 3, 'utility': 2.
     lgpPwrStateInputQualification 1.3.6.1.4.1.476.1.42.3.5.3.33 integer read-only
The current state of the system input. The unit may or may not operate normally under 'marginalLow' and 'marginalHigh' states. Enumeration: 'fail': 1, 'marginalHigh': 4, 'marginalLow': 2, 'normal': 3.
     lgpPwrStateBypassStaticSwitchState 1.3.6.1.4.1.476.1.42.3.5.3.34 integer read-only
The current state of the bypass static switch. Enumeration: 'on': 1, 'off': 2.
     lgpPwrStateBypassQualification 1.3.6.1.4.1.476.1.42.3.5.3.35 integer read-only
The current operational state of the bypass static switch. The unit may or may not operate normally under 'marginalLow' and 'marginalHigh' states. Enumeration: 'fail': 1, 'marginalHigh': 4, 'marginalLow': 2, 'normal': 3.
     lgpPwrStateDCBusQualification 1.3.6.1.4.1.476.1.42.3.5.3.36 integer read-only
The current operational state of the DC bus. The unit may or may not operate normally under 'marginalLow' and 'marginalHigh' states. Enumeration: 'fail': 1, 'marginalHigh': 4, 'marginalLow': 2, 'normal': 3.
     lgpPwrStateOutQualification 1.3.6.1.4.1.476.1.42.3.5.3.37 integer read-only
The current operational state of the output. The unit may or may not operate normally under 'marginalLow' and 'marginalHigh' states. Enumeration: 'fail': 1, 'marginalHigh': 4, 'marginalLow': 2, 'normal': 3.
     lgpPwrStateInverterQualification 1.3.6.1.4.1.476.1.42.3.5.3.38 integer read-only
The current operational state of the inverter. The unit may or may not operate normally under 'marginalLow' and 'marginalHigh' states. Enumeration: 'fail': 1, 'marginalHigh': 4, 'marginalLow': 2, 'normal': 3.
     lgpPwrStateInverterState 1.3.6.1.4.1.476.1.42.3.5.3.39 integer read-only
The current state of the inverter. Enumeration: 'on': 1, 'off': 2.
     lgpPwrStateRectifierState 1.3.6.1.4.1.476.1.42.3.5.3.40 integer read-only
The current state of the rectifier. Enumeration: 'on': 1, 'off': 2.
     lgpPwrStateModuleGroup 1.3.6.1.4.1.476.1.42.3.5.3.41
This group contains UPS module information.
           lgpPwrStateUpsModuleCount 1.3.6.1.4.1.476.1.42.3.5.3.41.1 integer32 read-write
Number of UPS modules in the system. In a single module system, this value is one.
           lgpPwrStateUpsModuleRedundantCount 1.3.6.1.4.1.476.1.42.3.5.3.41.2 integer32 read-only
Number of redundant UPS modules in the system. In a single module system, the value is zero. This value is dependent upon the present load and the number of modules (i.e. the value may change during normal operation based upon a load change). This value represents the number of extra modules above the minimum needed to support the load.
     lgpPwrStateBackfeedBrkrState 1.3.6.1.4.1.476.1.42.3.5.3.42 integer read-only
The state of the Static Bypass Switch Line Disconnect Breaker. Enumeration: 'notInstalled': 3, 'open': 1, 'closed': 2.
     lgpPwrStateLoadDisconnectState 1.3.6.1.4.1.476.1.42.3.5.3.43 integer read-only
The state of the Static Bypass Switch Load Disconnect Breaker. Enumeration: 'notInstalled': 3, 'open': 1, 'closed': 2.
     lgpPwrStateInputBrkrState 1.3.6.1.4.1.476.1.42.3.5.3.44 integer read-only
The state of the Input Disconnect Breaker. Enumeration: 'notInstalled': 3, 'open': 1, 'closed': 2.
     lgpPwrStateTrapFilterBrkrState 1.3.6.1.4.1.476.1.42.3.5.3.45 integer read-only
The state of the Trap Filter Disconnect Breaker. Enumeration: 'notInstalled': 3, 'open': 1, 'closed': 2.
     lgpPwrStateInvOutputBrkrState 1.3.6.1.4.1.476.1.42.3.5.3.46 integer read-only
The state of the Inverter Output Disconnect Breaker. Enumeration: 'notInstalled': 3, 'open': 1, 'closed': 2.
     lgpPwrStateIntBypassBrkrState 1.3.6.1.4.1.476.1.42.3.5.3.47 integer read-only
The state of the Internal Bypass Breaker. Enumeration: 'notInstalled': 3, 'open': 1, 'closed': 2.
     lgpPwrStateBypassIsolBrkrState 1.3.6.1.4.1.476.1.42.3.5.3.48 integer read-only
The state of the Bypass Isolation Breaker. Enumeration: 'notInstalled': 3, 'open': 1, 'closed': 2.
     lgpPwrStateRectifierIsolBrkrState 1.3.6.1.4.1.476.1.42.3.5.3.49 integer read-only
The state of the Rectifier Isolation Breaker. Enumeration: 'notInstalled': 3, 'open': 1, 'closed': 2.
     lgpPwrStateMaintBypassBrkrState 1.3.6.1.4.1.476.1.42.3.5.3.50 integer read-only
The state of the Maintenance Bypass Breaker. Enumeration: 'notInstalled': 3, 'open': 1, 'closed': 2.
     lgpPwrStateMaintIsolBrkrState 1.3.6.1.4.1.476.1.42.3.5.3.51 integer read-only
The state of the Maintenance Isolation Breaker. Enumeration: 'notInstalled': 3, 'open': 1, 'closed': 2.
     lgpPwrStateOutStaticSwState 1.3.6.1.4.1.476.1.42.3.5.3.52 integer read-only
The state of the Output Series Static Switch. Enumeration: 'on': 2, 'notInstalled': 3, 'off': 1.
     lgpPwrStateModuleOutBrkrState 1.3.6.1.4.1.476.1.42.3.5.3.53 integer read-only
The state of the Module Output Breaker. Enumeration: 'notInstalled': 3, 'open': 1, 'closed': 2.
     lgpPwrBypassReXfrRemainTime 1.3.6.1.4.1.476.1.42.3.5.3.54 integer32 read-only
The time remaining before an inverter overload or inverter fault can be cleared and auto retransfer from the bypass to the inverter can take place. Note: If an inverter overload or fault is not taking place, this point will return 65535.
     lgpPwrStateUpsOutputSource 1.3.6.1.4.1.476.1.42.3.5.3.55 integer read-only
The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker. NOTE: In a single-module system, this point is intended to have the same behavior as the RFC1628 point upsOutputSource. Enumeration: 'none': 2, 'normal': 3, 'battery': 5, 'reducer': 7, 'other': 1, 'bypass': 4, 'booster': 6.
     lgpPwrStateLoadBusSynchronization 1.3.6.1.4.1.476.1.42.3.5.3.56 integer read-only
The state of the Load Bus Synchronizer (LBS). Enumeration: 'active': 1, 'unknown': 0, 'abnormal': 2.
     lgpPwrStateCircuitBrkrStateGroup 1.3.6.1.4.1.476.1.42.3.5.3.57
This group contains Static Switch circuit breaker state information.
           lgpPwrStateSource1InputBrkrState 1.3.6.1.4.1.476.1.42.3.5.3.57.1 integer read-only
The states of Source 1 Input Breaker. Enumeration: 'notInstalled': 3, 'open': 1, 'closed': 2.
           lgpPwrStateSource2InputBrkrState 1.3.6.1.4.1.476.1.42.3.5.3.57.2 integer read-only
The states of Source 2 Input Breaker. Enumeration: 'notInstalled': 3, 'open': 1, 'closed': 2.
           lgpPwrStateSource1BypassBrkrState 1.3.6.1.4.1.476.1.42.3.5.3.57.3 integer read-only
The states of Source 1 Bypass Breaker. Enumeration: 'notInstalled': 3, 'open': 1, 'closed': 2.
           lgpPwrStateSource2BypassBrkrState 1.3.6.1.4.1.476.1.42.3.5.3.57.4 integer read-only
The states of Source 2 Bypass Breaker. Enumeration: 'notInstalled': 3, 'open': 1, 'closed': 2.
           lgpPwrStateOutputBrkrState 1.3.6.1.4.1.476.1.42.3.5.3.57.5 integer read-only
The states of Output Breaker. Enumeration: 'notInstalled': 3, 'open': 1, 'closed': 2.
           lgpPwrStateAuxOutputBrkrState 1.3.6.1.4.1.476.1.42.3.5.3.57.6 integer read-only
The states of Auxiliary Output Breaker. Enumeration: 'notInstalled': 3, 'open': 1, 'closed': 2.
           lgpPwrStateSource1PduInputBrkrState 1.3.6.1.4.1.476.1.42.3.5.3.57.7 integer read-only
The states of Source 1 PDU Input Breaker. Enumeration: 'notInstalled': 3, 'open': 1, 'closed': 2.
           lgpPwrStateSource2PduInputBrkrState 1.3.6.1.4.1.476.1.42.3.5.3.57.8 integer read-only
The states of Source 2 PDU Input Breaker. Enumeration: 'notInstalled': 3, 'open': 1, 'closed': 2.
     lgpPwrEconomicOperation 1.3.6.1.4.1.476.1.42.3.5.3.58 integer read-only
The present state of ECO mode operation, on(1) if system is on bypass due to ECO mode operation, off(0) any other time. Enumeration: 'on': 1, 'off': 0.
 lgpPwrSettings 1.3.6.1.4.1.476.1.42.3.5.4
This sub-tree registers Liebert Power Static Switch object identifiers.
     lgpPwrPreferredSource 1.3.6.1.4.1.476.1.42.3.5.4.1 object identifier read-only
The well known measurement source from the 'lgpPwrWellKnownMeasurements' sub-tree that is the preferred input source of the system.
     lgpPwrLoadOnSource 1.3.6.1.4.1.476.1.42.3.5.4.2 object identifier read-only
The well known measurement source from the 'lgpPwrWellKnownMeasurements' sub-tree that is currently powering the output (load).
     lgpPwrNominalVoltageDeviation 1.3.6.1.4.1.476.1.42.3.5.4.3 integer32 read-only
The nominal voltage deviation between the well known measurement source lgpPwrSource1Input and lgpPwrSource2Input.
     lgpPwrNominalVoltageDeviationPercent 1.3.6.1.4.1.476.1.42.3.5.4.4 integer32 read-only
The percentage of the nominal voltage deviation between the well known measurement source lgpPwrSource1Input and lgpPwrSource2Input.
     lgpPwrPhaseDifferenceLimit 1.3.6.1.4.1.476.1.42.3.5.4.5 integer32 read-only
The maximum phase difference (between the well known input sources ) in which a transfer to an available input source is permitted.
     lgpPwrFrequencyDeviationLimit 1.3.6.1.4.1.476.1.42.3.5.4.6 integer32 read-only
The maximum frequency deviation (between the well known input sources ) in which a transfer to an available input source is permitted.
     lgpPwrThresholdTable 1.3.6.1.4.1.476.1.42.3.5.4.7 no-access
A list of power thresholds for a given power measurement at a point/location in the system. The lgpPwrThresholdType in this table corresponds to the type of measurement the high and low thresholds applies to. This table contains zero, one, or many rows, depending upon the number of 'lgpPwrThresholdPoint' and 'lgpPwrThresholdSubID' available in the table. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device.
         lgpPwrThresholdEntry 1.3.6.1.4.1.476.1.42.3.5.4.7.1 no-access
This entry defines the contents of the columns for the table 'lgpPwrThresholdTable'.
             lgpPwrThresholdIndex 1.3.6.1.4.1.476.1.42.3.5.4.7.1.1 unsigned32 no-access
This is the index indicating the row of the table 'lgpPwrLineMeasurementTable' for a power measurement point.
             lgpPwrThresholdPoint 1.3.6.1.4.1.476.1.42.3.5.4.7.1.2 object identifier read-only
An OID representing a well known measurement point. These object identifiers indicate a point or location of power measurement in a power system. The OID's name usually implies a location of the measurement point such as 'input', 'output', 'bypass' etc.
             lgpPwrThresholdSubID 1.3.6.1.4.1.476.1.42.3.5.4.7.1.3 unsigned32 read-only
This is a sub identifier for the 'lgpPwrThresholdPoint'. It indicates the instance number of the well known threshold point.
             lgpPwrThresholdType 1.3.6.1.4.1.476.1.42.3.5.4.7.1.4 object identifier read-only
An OID representing a well known measurement type. These object identifiers indicate the type of measurement referenced by the row of the table. These object identifiers can encompass units of measure, lines of reference, and device location. The OID's name usually implies a measurement type such as 'voltsAc', 'current', 'voltsDc', 'VoltsLL', etc.
             lgpPwrThresholdHighWarning 1.3.6.1.4.1.476.1.42.3.5.4.7.1.5 integer32 read-write
The high warning threshold of a type of measurement designated by the 'lgpPwrThresholdType' at a location designated by the 'lgpPwrThresholdPoint'. If multiple thresholds are available at a single 'lgpPwrThresholdPoint', of the same 'lgpPwrThresholdType', then the 'lgpPwrThresholdSubID' will differentiate between them. When this threshold is met, the agent will send a notification.
             lgpPwrThresholdHighFailure 1.3.6.1.4.1.476.1.42.3.5.4.7.1.6 integer32 read-write
The high failure threshold of a type of measurement designated by the 'lgpPwrThresholdType' at a location designated by the 'lgpPwrThresholdPoint'. If multiple thresholds are available at a single 'lgpPwrThresholdPoint', of the same 'lgpPwrThresholdType', then the 'lgpPwrThresholdSubID' will differentiate between them. When this threshold is met, the agent will send a notification.
             lgpPwrThresholdLowWarning 1.3.6.1.4.1.476.1.42.3.5.4.7.1.7 integer32 read-write
The low warning threshold of a type of measurement designated by the 'lgpPwrThresholdType' at a location designated by the 'lgpPwrThresholdPoint'. If multiple thresholds are available at a single 'lgpPwrThresholdPoint', of the same 'lgpPwrThresholdType', then the 'lgpPwrThresholdSubID' will differentiate between them. When this threshold is met, the agent will send a notification.
             lgpPwrThresholdLowFailure 1.3.6.1.4.1.476.1.42.3.5.4.7.1.8 integer32 read-write
The low failure threshold of a type of measurement designated by the 'lgpPwrThresholdType' at a location designated by the 'lgpPwrThresholdPoint'. If multiple thresholds are available at a single 'lgpPwrThresholdPoint', of the same 'lgpPwrThresholdType', then the 'lgpPwrThresholdSubID' will differentiate between them. When this threshold is met, the agent will send a notification.
     lgpPwrUpsAutoRestart 1.3.6.1.4.1.476.1.42.3.5.4.8 integer read-write
The device will automatically restart when utility power is restored following a battery discharge. Enumeration: 'on': 1, 'off': 2.
     lgpPwrUpsAutoRestartDelay 1.3.6.1.4.1.476.1.42.3.5.4.9 integer32 read-write
The device will automatically delay a certain number of seconds and then restart after utility power is restored following a battery discharge. The number of seconds to delay is subject to the precision of the device and should be kept to 10 second intervals.
     lgpPwrAutoRestartBatteryChargeThreshold 1.3.6.1.4.1.476.1.42.3.5.4.10 integer32 read-write
The battery charge percentage required before the device can automatically restart.
     lgpPwrParallelModuleCount 1.3.6.1.4.1.476.1.42.3.5.4.11 integer32 read-write
The number of modules in the parallel system.
     lgpPwrParallelRedundancyCount 1.3.6.1.4.1.476.1.42.3.5.4.12 integer32 read-write
The number of redundant modules in the parallel system.
     lgpPwrLoadBusSyncMode 1.3.6.1.4.1.476.1.42.3.5.4.13 integer read-write
The configuration of Load Bus Synchronization (LBS) between independent systems. Enumeration: 'slave': 2, 'none': 3, 'master': 1.
     lgpPwrEconomicOperationMode 1.3.6.1.4.1.476.1.42.3.5.4.14 integer read-write
The configuration of the economic operation mode of the system. Enumeration: 'on': 1, 'off': 2.
     lgpPwrAutomaticBatteryTest 1.3.6.1.4.1.476.1.42.3.5.4.15 integer read-write
Automatic battery test option. If enabled, the battery will be tested on a fixed interval. If disabled, the battery test must be initiated by a battery test command. The interval at which a battery test is performed is defined by 'lgpPwrAutomaticBatteryTestInterval'. Enumeration: 'on': 1, 'off': 2.
     lgpPwrMinimumRedundantPowerModule 1.3.6.1.4.1.476.1.42.3.5.4.16 integer32 read-write
The minimum number of redundant power modules that must be present before sending a loss of power redundancy alarm. If 0, there is no redundant power functionality.
     lgpPwrMinimumRedundantBatteryModule 1.3.6.1.4.1.476.1.42.3.5.4.17 integer32 read-write
The minimum number of redundant battery modules that must be present before sending an alarm. If 0, the redundant battery module alarm is disabled.
     lgpPwrOutputToLoadUserOverloadLimit 1.3.6.1.4.1.476.1.42.3.5.4.18 integer32 read-write
This is the user specified maximum load the device can support without sending an alarm.
     lgpPwrNoLoadWarningLimit 1.3.6.1.4.1.476.1.42.3.5.4.19 integer32 read-write
The minimum current draw on the output in which the device considers there to be a load present on the output. The condition lgpConditionWarningNoLoadDetected will be triggered if the output current falls below this value. If this value is '-1' then the lgpConditionNoLoadDetectedWarning condition is 'disabled'.
     lgpPwrNoLoadWarningDelay 1.3.6.1.4.1.476.1.42.3.5.4.20 integer32 read-write
The amount of time to delay before annunciation of the condition lgpConditionNoLoadDetectedWarning after the output current load falls below the threshold lgpPwrOutputNoLoadWarningLimit.
     lgpPwrEconomicOperationModeControl 1.3.6.1.4.1.476.1.42.3.5.4.21 integer read-write
The configuration of the economic operation mode of the system. Note that this supersedes lgpPwrEconomicOperationMode in newer devices. Enumeration: 'disabled': 0, 'mode2': 2, 'mode1': 1.
 lgpPwrConversion 1.3.6.1.4.1.476.1.42.3.5.5
This sub-tree is used to register Liebert Power Conversion object identifiers.
     lgpPwrNumberInstalledPowerModules 1.3.6.1.4.1.476.1.42.3.5.5.1 integer32 read-only
The number of power modules installed in the device.
     lgpPwrNumberFailedPowerModules 1.3.6.1.4.1.476.1.42.3.5.5.2 integer32 read-only
The number of power modules in the device that have failed.
     lgpPwrNumberRedundantPowerModules 1.3.6.1.4.1.476.1.42.3.5.5.3 integer32 read-only
The number of redundant power modules installed in the device.
     lgpPwrNumberActivePowerModules 1.3.6.1.4.1.476.1.42.3.5.5.4 integer32 read-only
The number of active power modules in the device.
     lgpPwrNumberPowerModuleWarnings 1.3.6.1.4.1.476.1.42.3.5.5.6 integer32 read-only
The number of power modules in the device that have a warning.
     lgpPwrUpsInverterStandby 1.3.6.1.4.1.476.1.42.3.5.5.7 integer read-write
The output to the load is supported by the bypass and the inverter is on standby. Enumeration: 'on': 1, 'off': 2.
 lgpPwrControl 1.3.6.1.4.1.476.1.42.3.5.6
This sub-tree is used to register Liebert Power Control object identifiers.
     lgpPwrWellKnownControlPoints 1.3.6.1.4.1.476.1.42.3.5.6.1
This sub-tree registers well known Liebert Power Control Points. The object identifier names usually imply locations where control of a device is available -- such 'output' or 'load circuits'.
         lgpPwrLoadCircuit 1.3.6.1.4.1.476.1.42.3.5.6.1.1
The managed device's controllable load circuit. Many power systems contain more than one load circuit. This identifier represents one load circuit for the system but does not necessarily represent the 'first' one. The load circuits' numbering with respect to 'lgpPwrLoadCircuit1' etc. may depend on the physical wiring of the system when it was installed.
     lgpPwrLoadCircuitTable 1.3.6.1.4.1.476.1.42.3.5.6.2 no-access
A list of load circuits that can be controlled(opened or closed). The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device.
         lgpPwrLoadCircuitEntry 1.3.6.1.4.1.476.1.42.3.5.6.2.1 no-access
This entry defines the contents of the columns for the table 'lgpPwrLoadCircuitTable'.
             lgpPwrLoadCircuitIndex 1.3.6.1.4.1.476.1.42.3.5.6.2.1.1 unsigned32 no-access
This is the index indicating the row of the table 'lgpPwrLoadCircuitTable'.
             lgpPwrLoadCircuitId 1.3.6.1.4.1.476.1.42.3.5.6.2.1.2 object identifier read-only
An OID representing a well known load circuit identifier. These load circuit identifiers indicate the name or type of load circuit reference in the table.
             lgpPwrLoadCircuitSubID 1.3.6.1.4.1.476.1.42.3.5.6.2.1.3 unsigned32 read-only
This is a sub identifier for the 'lgpPwrLoadCircuitId'. It indicates the hardware identifier of the load control circuit.
             lgpPwrLoadCircuitState 1.3.6.1.4.1.476.1.42.3.5.6.2.1.4 integer read-write
This identifier indicates the state of the load circuit. When read, only a closed or open response will be returned. When written to, the state of the circuit will transition to desired state. Enumeration: 'default': 3, 'on': 1, 'off': 2.
             lgpPwrLoadCircuitStateAndControl 1.3.6.1.4.1.476.1.42.3.5.6.2.1.5 integer read-write
This identifier indicates the state of the load circuit. When read, only a closed or open response will be returned. When written to, the state of the circuit will transition to desired state. Enumeration: 'on': 1, 'off': 0, 'reboot': 2.
     lgpPwrAlarmSilence 1.3.6.1.4.1.476.1.42.3.5.6.3 integer32 read-write
Audible Alarm Silence Command. This command turns off the device's audible alarm. It will not affect the status of the alarm(s) that caused the audible alarm. This command should be sent with a parameter of 1. This variable doesn't return a value when read.
     lgpPwrBatteryTest 1.3.6.1.4.1.476.1.42.3.5.6.4 integer read-write
Battery Test Command. This command will initiate a battery test if one is not already in progress, or abort the current test if it is in progress. Enumeration: 'start': 1, 'abort': 2.
     lgpPwrUpsAbortCommand 1.3.6.1.4.1.476.1.42.3.5.6.5 integer32 read-write
UPS Abort command. This command will abort the pending command on the device. There is no guarantee a client using the abort command will cancel a command sent moments before from the same client. Another client could initiate a command and change what command is actually pending on the device. This command should be sent with a parameter of 1. This variable doesn't return a value when read.
     lgpPwrTransferToBypass 1.3.6.1.4.1.476.1.42.3.5.6.6 integer32 read-write
Transfer to Bypass Command. This command will initiate a transfer of the load to the bypass of the system. This command should be sent with a parameter of 1. This variable doesn't return a value when read.
     lgpPwrTransferToInverter 1.3.6.1.4.1.476.1.42.3.5.6.7 integer32 read-write
Transfer to Inverter Command. This command will initiate a transfer of the load to the inverter of the system. This command should be sent with a parameter of 1. This variable doesn't return a value when read.
     lgpPwrOutputOnDelay 1.3.6.1.4.1.476.1.42.3.5.6.8 integer32 read-write
Output On Delay Command. This command will turn on the output of the device after a user specified delay. The number of seconds to delay is subject to the precision of the device and should be kept to 10 second intervals.
     lgpPwrOutputOffDelayWithRestart 1.3.6.1.4.1.476.1.42.3.5.6.9 integer32 read-write
Output Off Delay with Restart Command. This command will turn off the output of the device after a user specified delay. The number of seconds to delay is subject to the precision of the device and should be kept to 10 second intervals. The device will then turn the output on again after a specified amount of time.
     lgpPwrOutputOffDelayWithoutRestart 1.3.6.1.4.1.476.1.42.3.5.6.10 integer32 read-write
Output Off Delay without Restart Command. This command will turn off the output of the device after a specified delay. The number of seconds to delay is subject to the precision of the device and should be kept to 10 second intervals. The device will NOT automatically turn the output on following this command.
 lgpPwrTopology 1.3.6.1.4.1.476.1.42.3.5.7
This sub-tree is used to register Liebert Power Topology object identifiers.
     lgpPwrUpsTopOffline 1.3.6.1.4.1.476.1.42.3.5.7.1 integer read-only
The UPS has an offline topology. Under normal operating conditions, AC power from the utility passes straight through the UPS to the critical load. The inverter is used to convert the DC power from the battery to create AC power to support the load when the utility fails. Normally the inverter is operating in the stand-by mode, keeping the batteries charged. Should the utility power go out of specification, the inverter will power the load by drawing energy from the battery. Enumeration: 'yes': 1, 'no': 2.
     lgpPwrUpsTopLineInteractive 1.3.6.1.4.1.476.1.42.3.5.7.2 integer read-only
The UPS has a line-interactive topology. This topology resembles the offline product, but inserts a transformer or inductor in series between the utility power source and the load. This inline inductor enables the UPS inverter to interact with incoming power and provide a measure of power conditioning to the load. This buck-and-boost circuitry helps with high and low input voltage conditions. Enumeration: 'yes': 1, 'no': 2.
     lgpPwrUPSTopDualInput 1.3.6.1.4.1.476.1.42.3.5.7.3 integer read-only
The system has separate input sources for the bypass and inverter. Enumeration: 'yes': 1, 'no': 2.
     lgpPwrTopFrequencyConverter 1.3.6.1.4.1.476.1.42.3.5.7.4 integer read-only
The system has a frequency converter. Enumeration: 'yes': 1, 'no': 2.
     lgpPwrTopVoltageConverter 1.3.6.1.4.1.476.1.42.3.5.7.5 integer read-only
The system has a voltage converter. Enumeration: 'yes': 1, 'no': 2.
     lgpPwrTopMaximumFrameCapacity 1.3.6.1.4.1.476.1.42.3.5.7.6 integer32 read-write
The maximum device system capacity.
     lgpPwrTopRedundantControlModules 1.3.6.1.4.1.476.1.42.3.5.7.7 integer read-only
The device has a redundant control module installed. Enumeration: 'yes': 1, 'no': 2.
     lgpPwrInputIsolationTransformerInstalled 1.3.6.1.4.1.476.1.42.3.5.7.8 integer read-only
Indicates whether the input isolation transformer is installed. Enumeration: 'notInstalled': 1, 'installed': 2.
     lgpPwrStateStaticSwitchType 1.3.6.1.4.1.476.1.42.3.5.7.9 integer read-only
Static switch type (N/A, continous duty, or momentary duty). Enumeration: 'notApplicable': 1, 'continuousDuty': 2, 'momentaryDuty': 3.
     lgpPwrStateModuleType 1.3.6.1.4.1.476.1.42.3.5.7.10 integer read-only
UPS module type. SMS -- Single Module System 1 + 1 -- Redundant system for capacity 1 + N -- Distributed multi-module system N + 1 -- A multi-module system with one bypass for the system SCC -- System Control Cabinet used in an N+1 system to provide a single bypass for the system. MSS -- Main Static Switch Enumeration: 'mainStaticSwitch': 6, 'singleModuleSystem': 1, 'module1plusN': 3, 'module1plus1': 2, 'systemControlCabinet': 5, 'moduleNplus1': 4.
     lgpPwrStateBypassInputConfig 1.3.6.1.4.1.476.1.42.3.5.7.11 integer read-only
Bypass input wire physical wiring configuration. singlePhase2WireL1WithReturn Single phase input with 2 wires (Line 1, and Return). twoPhase2WireL1L2 Two phase input with 2 wires (Line 1, and Line 2). twoPhase3WireL1L2WithNeutral Two phase input with 3 wires (Line 1, Line 2, and Neutral) threePhase3WireL1L2L3 Three phase input with 3 wires (Line 1, Line 2, and Line 3) threePhase4WireL1L2L3WithNeutral Three phase input with 4 wires (Line 1, Line 2, Line 3, and Neutral). Enumeration: 'threePhase3WireL1L2L3': 4, 'twoPhase3WireL1L2WithNeutral': 3, 'singlePhase2WireL1WithReturn': 1, 'twoPhase2WireL1L2': 2, 'threePhase4WireL1L2L3WithNeutral': 5.
     lgpPwrStateOutputConfig 1.3.6.1.4.1.476.1.42.3.5.7.12 integer read-only
Output wire physical wiring configuration. singlePhase2WireL1WithReturn Single phase output with 2 wires (Line 1, and Return). twoPhase2WireL1L2 Two phase output with 2 wires (Line 1, and Line 2). twoPhase3WireL1L2WithNeutral Two phase output with 3 wires (Line 1, Line 2, and Neutral) threePhase3WireL1L2L3 Three phase output with 3 wires (Line 1, Line 2, and Line 3) threePhase4WireL1L2L3WithNeutral Three phase output with 4 wires (Line 1, Line 2, Line 3, and Neutral). Enumeration: 'threePhase3WireL1L2L3': 4, 'twoPhase3WireL1L2WithNeutral': 3, 'singlePhase2WireL1WithReturn': 1, 'twoPhase2WireL1L2': 2, 'threePhase4WireL1L2L3WithNeutral': 5.
     lgpPwrRectifierPassiveFilterInstalled 1.3.6.1.4.1.476.1.42.3.5.7.13 integer read-only
Indicates whether the rectifier passive filter is installed. Enumeration: 'notInstalled': 1, 'installed': 2.
     lgpPwrRectifierTrapInstalled 1.3.6.1.4.1.476.1.42.3.5.7.14 integer read-only
Indicates whether the rectifier input passive filter is installed. Enumeration: 'notInstalled': 1, 'installed': 2.
     lgpPwrRectifierActiveFilterInstalled 1.3.6.1.4.1.476.1.42.3.5.7.15 integer read-only
Indicates whether the rectifier active filter is installed. Enumeration: 'notInstalled': 1, 'installed': 2.
 lgpPwrStatistic 1.3.6.1.4.1.476.1.42.3.5.8
This sub-tree is used to register Liebert Power Statistic object identifiers.
     lgpPwrBrownOutCount 1.3.6.1.4.1.476.1.42.3.5.8.1 integer32 read-only
The number of occurrences where the input line voltage has fallen below a pre-determined threshold for a specified amount of time. This number resets when the command 'lgpPwrStatisticsReset' is executed.
     lgpPwrBlackOutCount 1.3.6.1.4.1.476.1.42.3.5.8.2 integer32 read-only
The number of occurrences where there is a total loss of electric power. This number resets when the command 'lgpPwrStatisticsReset' is executed.
     lgpPwrTransientCount 1.3.6.1.4.1.476.1.42.3.5.8.3 integer32 read-only
The number of occurrences where the input line voltage spikes above a pre-determined threshold for a specified amount of time. This number resets when the command 'lgpPwrStatisticsReset' is executed.
     lgpPwrBatteryDischargeCount 1.3.6.1.4.1.476.1.42.3.5.8.4 integer32 read-only
The number of battery discharges since the last reset.
     lgpPwrBatteryDischargeTime 1.3.6.1.4.1.476.1.42.3.5.8.5 integer32 read-only
The total accumulated time spent on battery since the last reset.
     lgpPwrBatteryAmpHours 1.3.6.1.4.1.476.1.42.3.5.8.6 integer32 read-only
The total accumulated Amp-hours removed from the battery since last reset.
     lgpPwrBatteryWattHours 1.3.6.1.4.1.476.1.42.3.5.8.7 integer32 read-only
The total accumulated Watt-Hours removed from the battery since last reset. This command should be sent with a parameter of 1. This variable doesn't return a value when read.
     lgpPwrBatteryStatisticsReset 1.3.6.1.4.1.476.1.42.3.5.8.8 integer32 read-write
Battery statistics clear command. The command to reset all battery statistics stored by the device. This command should be sent with a parameter of 1. This variable doesn't return a value when read.
     lgpPwrStatisticsReset 1.3.6.1.4.1.476.1.42.3.5.8.9 integer32 read-write
Reset Power Statistics Command. This command will reset the power statistics stored in the system. This command should be sent with a parameter of 1. This variable doesn't return a value when read.
 lgpPwrConfig 1.3.6.1.4.1.476.1.42.3.5.9
This sub-tree is used to register Liebert Power Configuration Object identifiers.
     lgpPwrSysCapacity 1.3.6.1.4.1.476.1.42.3.5.9.1 integer32 read-write
The current device system capacity.
     lgpPwrUPSModuleMode 1.3.6.1.4.1.476.1.42.3.5.9.2 integer read-write
The module mode of the UPS. Enumeration: 'single': 1, 'hotmaster': 3, 'parallel': 2, 'hotslave': 4.
     lgpPwrMaxRatedCurrent 1.3.6.1.4.1.476.1.42.3.5.9.3 integer32 read-only
System output maximum amperage rating. The maximum rated amperage for the system. This value is based upon the model type and is typically limited by the wiring, breakers, power devices, etc.
     lgpPwrRectifierPulseCount 1.3.6.1.4.1.476.1.42.3.5.9.4 integer read-only
Rectifier pulse count per waveform cycle (6-, 12-, 18-, or 24-pulse). Enumeration: 'twelvePulse': 2, 'sixPulse': 1, 'eighteenPulse': 3, 'twentyFourPulse': 4.