Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 liebertGlobalProductsFlexibleConditionsModule 1.3.6.1.4.1.476.1.42.1.11.1
The MIB module used to register Liebert SNMP OIDs. Copyright 2000-2016 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
   lgpFlexConditionsWellKnown 1.3.6.1.4.1.476.1.42.3.2.7.1
       lgpCondId4122SystemInputPowerProblem 1.3.6.1.4.1.476.1.42.3.2.7.1.4122
The input is not qualified to provide power to the system.
       lgpCondId4132BypassOverloadPhaseA 1.3.6.1.4.1.476.1.42.3.2.7.1.4132
An overload exists on output phase A while operating on the bypass.
       lgpCondId4133BypassOverloadPhaseB 1.3.6.1.4.1.476.1.42.3.2.7.1.4133
An overload exists on output phase B while operating on the bypass.
       lgpCondId4134BypassOverloadPhaseC 1.3.6.1.4.1.476.1.42.3.2.7.1.4134
An overload exists on output phase C while operating on the bypass.
       lgpCondId4135BypassNotAvailable 1.3.6.1.4.1.476.1.42.3.2.7.1.4135
A problem associated with the bypass has been detected.
       lgpCondId4137BypassAutoRetransferPrimed 1.3.6.1.4.1.476.1.42.3.2.7.1.4137
Automatic retransfer from bypass to inverter is possible.
       lgpCondId4138BypassAutoRetransferFailed 1.3.6.1.4.1.476.1.42.3.2.7.1.4138
After performing a recoverable transfer to bypass, an attempt to auto retransfer from bypass to inverter failed.
       lgpCondId4139BypassExcessAutoRetransfers 1.3.6.1.4.1.476.1.42.3.2.7.1.4139
The number of auto retransfers, from bypass to inverter, has exceeded the maximum for a specified time interval.
       lgpCondId4140BypassRestartInhibitExternal 1.3.6.1.4.1.476.1.42.3.2.7.1.4140
Restart of the bypass is inhibited by the state of an external signal.
       lgpCondId4141BypassBreakerClosed 1.3.6.1.4.1.476.1.42.3.2.7.1.4141
The bypass breaker is closed.
       lgpCondId4142BypassStaticSwitchOverload 1.3.6.1.4.1.476.1.42.3.2.7.1.4142
Bypass off due to static switch overload.
       lgpCondId4143BypassStaticSwitchUnavailable 1.3.6.1.4.1.476.1.42.3.2.7.1.4143
The static bypass is unavailable to support the critical load.
       lgpCondId4144BypassExcessivePulseParallel 1.3.6.1.4.1.476.1.42.3.2.7.1.4144
The system has performed too many pulse parallel operations within a specified time interval.
       lgpCondId4145BypassAutoTransferFailed 1.3.6.1.4.1.476.1.42.3.2.7.1.4145
An automatic transfer to static bypass failed.
       lgpCondId4146SystemInputPhsRotationError 1.3.6.1.4.1.476.1.42.3.2.7.1.4146
The power conductors on the input line are not wired to the UPS in the sequence preferred for the rectifier (A-B-C).
       lgpCondId4147SystemInputCurrentLimit 1.3.6.1.4.1.476.1.42.3.2.7.1.4147
The RMS input current has reached the input current limit threshold.
       lgpCondId4162BatteryLow 1.3.6.1.4.1.476.1.42.3.2.7.1.4162
The calculated battery time remaining has reached the low battery threshold.
       lgpCondId4163OutputOffEndofDischarge 1.3.6.1.4.1.476.1.42.3.2.7.1.4163
Output turned off due to battery reaching end-of-discharge.
       lgpCondId4164BatteryChargingError 1.3.6.1.4.1.476.1.42.3.2.7.1.4164
The battery is not charging properly.
       lgpCondId4165BatteryChargingReducedExtrnl 1.3.6.1.4.1.476.1.42.3.2.7.1.4165
Using a reduced battery charging algorithm due to an external signal.
       lgpCondId4166BatteryCapacityLow 1.3.6.1.4.1.476.1.42.3.2.7.1.4166
Battery capacity is low.
       lgpCondId4167OutputOff 1.3.6.1.4.1.476.1.42.3.2.7.1.4167
Output is off.
       lgpCondId4168BatteryDischarging 1.3.6.1.4.1.476.1.42.3.2.7.1.4168
The battery is discharging.
       lgpCondId4169BatteryTemperatureImbalance 1.3.6.1.4.1.476.1.42.3.2.7.1.4169
Excessive temperature differences between battery sensors detected.
       lgpCondId4170BatteryEqualize 1.3.6.1.4.1.476.1.42.3.2.7.1.4170
The rectifier output voltage is increased to equalize the battery voltage level.
       lgpCondId4171BatteryManualTestInProgress 1.3.6.1.4.1.476.1.42.3.2.7.1.4171
Manual battery test is in progress.
       lgpCondId4172BatteryAutoTestInProgress 1.3.6.1.4.1.476.1.42.3.2.7.1.4172
Automatic battery test is in progress.
       lgpCondId4173MainBatteryDisconnectOpen 1.3.6.1.4.1.476.1.42.3.2.7.1.4173
Main battery disconnect is open.
       lgpCondId4174BatteryTemperatureSensorFault 1.3.6.1.4.1.476.1.42.3.2.7.1.4174
A battery temperature sensor fault has been detected.
       lgpCondId4175BypassFrequencyError 1.3.6.1.4.1.476.1.42.3.2.7.1.4175
The bypass frequency is outside the inverter synchronization limits.
       lgpCondId4176BatteryCircuitBreaker1Open 1.3.6.1.4.1.476.1.42.3.2.7.1.4176
Battery circuit breaker 1 is open.
       lgpCondId4177BatteryBreaker1OpenFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.4177
Battery circuit breaker 1 failed to open.
       lgpCondId4178BatteryBreaker1CloseFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.4178
Battery circuit breaker 1 failed to close.
       lgpCondId4179BatteryCircuitBreaker2Open 1.3.6.1.4.1.476.1.42.3.2.7.1.4179
Battery circuit breaker 2 is open.
       lgpCondId4180BatteryBreaker2OpenFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.4180
Battery circuit breaker 2 failed to open.
       lgpCondId4181BatteryBreaker2CloseFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.4181
Battery circuit breaker 2 failed to close.
       lgpCondId4182BatteryCircuitBreaker3Open 1.3.6.1.4.1.476.1.42.3.2.7.1.4182
Battery circuit breaker 3 is open.
       lgpCondId4183BatteryBreaker3OpenFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.4183
Battery circuit breaker 3 failed to open.
       lgpCondId4184BatteryBreaker3CloseFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.4184
Battery circuit breaker 3 failed to close.
       lgpCondId4185BatteryCircuitBreaker4Open 1.3.6.1.4.1.476.1.42.3.2.7.1.4185
Battery circuit breaker 4 is open.
       lgpCondId4186BatteryBreaker4OpenFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.4186
Battery circuit breaker 4 failed to open.
       lgpCondId4187BatteryBreaker4CloseFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.4187
Battery circuit breaker 4 failed to close.
       lgpCondId4188BatteryCircuitBreaker5Open 1.3.6.1.4.1.476.1.42.3.2.7.1.4188
Battery circuit breaker 5 is open.
       lgpCondId4189BatteryBreaker5OpenFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.4189
Battery circuit breaker 5 failed to open.
       lgpCondId4190BatteryBreaker5CloseFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.4190
Battery circuit breaker 5 failed to close.
       lgpCondId4191BatteryCircuitBreaker6Open 1.3.6.1.4.1.476.1.42.3.2.7.1.4191
Battery circuit breaker 6 is open.
       lgpCondId4192BatteryBreaker6OpenFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.4192
Battery circuit breaker 6 failed to open.
       lgpCondId4193BatteryBreaker6CloseFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.4193
Battery circuit breaker 6 failed to close.
       lgpCondId4194BatteryCircuitBreaker7Open 1.3.6.1.4.1.476.1.42.3.2.7.1.4194
Battery circuit breaker 7 is open.
       lgpCondId4195BatteryBreaker7OpenFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.4195
Battery circuit breaker 7 failed to open.
       lgpCondId4196BatteryBreaker7CloseFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.4196
Battery circuit breaker 7 failed to close.
       lgpCondId4197BatteryCircuitBreaker8Open 1.3.6.1.4.1.476.1.42.3.2.7.1.4197
Battery circuit breaker 8 is open.
       lgpCondId4198BatteryBreaker8OpenFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.4198
Battery circuit breaker 8 failed to open.
       lgpCondId4199BatteryBreaker8CloseFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.4199
Battery circuit breaker 8 failed to close.
       lgpCondId4200BatteryChargingInhibited 1.3.6.1.4.1.476.1.42.3.2.7.1.4200
Battery charging is inhibited due to an external inhibit signal.
       lgpCondId4213SystemShutdownEPO 1.3.6.1.4.1.476.1.42.3.2.7.1.4213
System shutdown due to Emergency Power Off (EPO).
       lgpCondId4214SystemShutdownREPO 1.3.6.1.4.1.476.1.42.3.2.7.1.4214
System shutdown due to Remote Emergency Power Off (REPO).
       lgpCondId4215SystemOutputOff 1.3.6.1.4.1.476.1.42.3.2.7.1.4215
The system output is off.
       lgpCondId4216BypassBackfeedDetected 1.3.6.1.4.1.476.1.42.3.2.7.1.4216
The system detected a voltage on the bypass when none was expected.
       lgpCondId4217BypassManualXfrInhibited 1.3.6.1.4.1.476.1.42.3.2.7.1.4217
Manual transfer from inverter to bypass is inhibited - bypass not qualified.
       lgpCondId4218BypassManualRexfrInhibited 1.3.6.1.4.1.476.1.42.3.2.7.1.4218
Manual transfer from bypass to inverter is inhibited - inverter output not qualified.
       lgpCondId4219BatteryOverTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.4219
A battery temperature sensor is reporting a value above a threshold.
       lgpCondId4220BatteryExternalMonitor1 1.3.6.1.4.1.476.1.42.3.2.7.1.4220
External battery monitor 1 - battery maintenance required.
       lgpCondId4221BatteryExternalMonitor2 1.3.6.1.4.1.476.1.42.3.2.7.1.4221
External battery monitor 2 - battery maintenance required.
       lgpCondId4222BatteryGroundFault 1.3.6.1.4.1.476.1.42.3.2.7.1.4222
Battery system ground fault amperage exceeds the threshold.
       lgpCondId4229EmergencyPowerOffLatched 1.3.6.1.4.1.476.1.42.3.2.7.1.4229
System output is off - 'Emergency Power Off (EPO) - latched' requires manual reset.
       lgpCondId4230SystemOutputLowPowerFactor 1.3.6.1.4.1.476.1.42.3.2.7.1.4230
The system output power factor is low, resulting in reduced output capacity.
       lgpCondId4231OutputCurrentExceedsThreshold 1.3.6.1.4.1.476.1.42.3.2.7.1.4231
Output current for one or more phases exceeds a threshold.
       lgpCondId4233InverterFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.4233
Inverter failure - inverter output is off.
       lgpCondId4234InverterOverloadPhaseA 1.3.6.1.4.1.476.1.42.3.2.7.1.4234
Inverter is operating with an overload on phase A.
       lgpCondId4235InverterOverloadPhaseB 1.3.6.1.4.1.476.1.42.3.2.7.1.4235
Inverter is operating with an overload on phase B.
       lgpCondId4236InverterOverloadPhaseC 1.3.6.1.4.1.476.1.42.3.2.7.1.4236
Inverter is operating with an overload on phase C.
       lgpCondId4237InverterInhibitExternal 1.3.6.1.4.1.476.1.42.3.2.7.1.4237
Restart of the inverter is inhibited by an external signal.
       lgpCondId4238InverterOutBreakerOpenFail 1.3.6.1.4.1.476.1.42.3.2.7.1.4238
Inverter output breaker failed to open.
       lgpCondId4239InverterOutBreakerCloseFail 1.3.6.1.4.1.476.1.42.3.2.7.1.4239
Inverter output breaker failed to close.
       lgpCondId4270InputContact01 1.3.6.1.4.1.476.1.42.3.2.7.1.4270
The external input contact 1.
       lgpCondId4271InputContact02 1.3.6.1.4.1.476.1.42.3.2.7.1.4271
The external input contact 2.
       lgpCondId4272InputContact03 1.3.6.1.4.1.476.1.42.3.2.7.1.4272
The external input contact 3.
       lgpCondId4273InputContact04 1.3.6.1.4.1.476.1.42.3.2.7.1.4273
The external input contact 4.
       lgpCondId4274InputContact05 1.3.6.1.4.1.476.1.42.3.2.7.1.4274
The external input contact 5.
       lgpCondId4275InputContact06 1.3.6.1.4.1.476.1.42.3.2.7.1.4275
The external input contact 6.
       lgpCondId4276InputContact07 1.3.6.1.4.1.476.1.42.3.2.7.1.4276
The external input contact 7.
       lgpCondId4277InputContact08 1.3.6.1.4.1.476.1.42.3.2.7.1.4277
The external input contact 8.
       lgpCondId4278InputContact09 1.3.6.1.4.1.476.1.42.3.2.7.1.4278
The external input contact 9.
       lgpCondId4279InputContact10 1.3.6.1.4.1.476.1.42.3.2.7.1.4279
The external input contact 10.
       lgpCondId4280InputContact11 1.3.6.1.4.1.476.1.42.3.2.7.1.4280
The external input contact 11.
       lgpCondId4281InputContact12 1.3.6.1.4.1.476.1.42.3.2.7.1.4281
The external input contact 12.
       lgpCondId4282InputContact13 1.3.6.1.4.1.476.1.42.3.2.7.1.4282
The external input contact 13.
       lgpCondId4283InputContact14 1.3.6.1.4.1.476.1.42.3.2.7.1.4283
The external input contact 14.
       lgpCondId4284InputContact15 1.3.6.1.4.1.476.1.42.3.2.7.1.4284
The external input contact 15.
       lgpCondId4285InputContact16 1.3.6.1.4.1.476.1.42.3.2.7.1.4285
The external input contact 16.
       lgpCondId4286OutputAmpOverUserLimitPhsA 1.3.6.1.4.1.476.1.42.3.2.7.1.4286
The phase A output has exceeded the user amperage threshold.
       lgpCondId4287OutputAmpOverUserLimitPhsB 1.3.6.1.4.1.476.1.42.3.2.7.1.4287
The phase B output has exceeded the user amperage threshold.
       lgpCondId4288OutputAmpOverUserLimitPhsC 1.3.6.1.4.1.476.1.42.3.2.7.1.4288
The phase C output has exceeded the user amperage threshold.
       lgpCondId4289InverterTransferInhibitExt 1.3.6.1.4.1.476.1.42.3.2.7.1.4289
Transfer of critical bus source to inverter is inhibited by an external signal.
       lgpCondId4290InverterShutdownOverload 1.3.6.1.4.1.476.1.42.3.2.7.1.4290
The inverter has shutdown due to a sustained overload.
       lgpCondId4294InletAirOverTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.4294
The inlet air exceeds the maximum temperature threshold.
       lgpCondId4295RectifierFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.4295
Rectifier failure - rectifier is off.
       lgpCondId4296RectifierOperationInhibitExt 1.3.6.1.4.1.476.1.42.3.2.7.1.4296
The operation of the rectifier is inhibited by an external signal.
       lgpCondId4297UPSOutputonInverter 1.3.6.1.4.1.476.1.42.3.2.7.1.4297
The output power is supplied by the inverter.
       lgpCondId4298UPSOutputonBypass 1.3.6.1.4.1.476.1.42.3.2.7.1.4298
The output power is supplied by the bypass.
       lgpCondId4299OutputLoadonMaintBypass 1.3.6.1.4.1.476.1.42.3.2.7.1.4299
The output power is supplied by the maintenance bypass.
       lgpCondId4300InternalCommunicationsFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.4300
The control has detected a communication failure of a component on the internal communication bus.
       lgpCondId4308DCBusGroundFaultPositive 1.3.6.1.4.1.476.1.42.3.2.7.1.4308
A ground fault has been detected on the positive DC Bus link.
       lgpCondId4309DCBusGroundFaultNegative 1.3.6.1.4.1.476.1.42.3.2.7.1.4309
A ground fault has been detected on the negative DC Bus link.
       lgpCondId4310EquipmentOverTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.4310
Equipment over temperature summary event.
       lgpCondId4311SystemFanFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.4311
System fan failure - one or more fans have failed.
       lgpCondId4313PasswordChanged 1.3.6.1.4.1.476.1.42.3.2.7.1.4313
Password changed.
       lgpCondId4314PowerSupplyFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.4314
Power supply failure.
       lgpCondId4315OnGenerator 1.3.6.1.4.1.476.1.42.3.2.7.1.4315
A generator is supplying the power to the system.
       lgpCondId4316AutoRestartInProgress 1.3.6.1.4.1.476.1.42.3.2.7.1.4316
Auto restart is in progress.
       lgpCondId4317AutoRestartInhibitedExt 1.3.6.1.4.1.476.1.42.3.2.7.1.4317
Auto restart inhibited due to an external signal.
       lgpCondId4320InitiatedTransfertoBypass 1.3.6.1.4.1.476.1.42.3.2.7.1.4320
User initiated manual transfer to bypass.
       lgpCondId4321InitiatedTransfertoInverter 1.3.6.1.4.1.476.1.42.3.2.7.1.4321
User initiated manual transfer to inverter.
       lgpCondId4322BatteryTestPassed 1.3.6.1.4.1.476.1.42.3.2.7.1.4322
Battery test passed.
       lgpCondId4323BatteryTestFailed 1.3.6.1.4.1.476.1.42.3.2.7.1.4323
Battery test failed.
       lgpCondId4324BatteryTestManuallyStopped 1.3.6.1.4.1.476.1.42.3.2.7.1.4324
The battery test was manually stopped prior to completion.
       lgpCondId4325BackfeedBreakerOpen 1.3.6.1.4.1.476.1.42.3.2.7.1.4325
The backfeed breaker is in the open position.
       lgpCondId4341VelocityAuthenticationFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.4341
Notification of a message rejected by Velocity due to an authentication failure.
       lgpCondId4360ReceptacleOverCurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.4360
The system has detected a receptacle over current condition.
       lgpCondId4361ReceptacleUnderCurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.4361
The system has detected a receptacle under current condition.
       lgpCondId4382SystemInputCurrentImbalance 1.3.6.1.4.1.476.1.42.3.2.7.1.4382
System Input Currents are Imbalanced.
       lgpCondId4383BypassStaticSwitchOffExtrnl 1.3.6.1.4.1.476.1.42.3.2.7.1.4383
Bypass static switch is off due to the state of an external signal.
       lgpCondId4384BatteryEoDDisconnect 1.3.6.1.4.1.476.1.42.3.2.7.1.4384
Battery disconnect due to end-of-discharge.
       lgpCondId4389SystemOutputFault 1.3.6.1.4.1.476.1.42.3.2.7.1.4389
A fault has been detected in the system output.
       lgpCondId4390InverterOffExternal 1.3.6.1.4.1.476.1.42.3.2.7.1.4390
Inverter is off (operation is inhibited) due to external signal state.
       lgpCondId4391InverterStaticSwitchSCRShort 1.3.6.1.4.1.476.1.42.3.2.7.1.4391
The system has detected a short across one or more inverter static switch Silicon Controlled Rectifiers (SCR).
       lgpCondId4392TemperatureSensorError 1.3.6.1.4.1.476.1.42.3.2.7.1.4392
One or more temperature sensors cannot provide a valid temperature reading (i.e. sensor failure, wiring failure, sense circuit failure, etc).
       lgpCondId4406BranchOverCurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.4406
The system has detected a module over current condition.
       lgpCondId4407BranchUnderCurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.4407
The system has detected a module under current condition.
       lgpCondId4416BranchOverCurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.4416
The system has detected a module over current condition.
       lgpCondId4417BranchUnderCurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.4417
The system has detected a module under current condition.
       lgpCondId4421BranchFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.4421
One or more conditions indicate a Branch Receptacle Module failure , service is required.
       lgpCondId4436PDUOverCurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.4436
The system has detected a module over current condition.
       lgpCondId4437PDUUnderCurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.4437
The system has detected a module under current condition.
       lgpCondId4438SystemInternalTemperatureRise 1.3.6.1.4.1.476.1.42.3.2.7.1.4438
Excessive temperature rise internal to the system (i.e. difference between the output versus input temperature is too large).
       lgpCondId4439AutomaticRestartFailed 1.3.6.1.4.1.476.1.42.3.2.7.1.4439
Automatic restart failed.
       lgpCondId4440FuseFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.4440
A summary event indicating one or more fuse failures.
       lgpCondId4441SystemControllerError 1.3.6.1.4.1.476.1.42.3.2.7.1.4441
System controller internal error.
       lgpCondId4442SystemBreakersOpenFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.4442
One or more breakers in the system failed to open.
       lgpCondId4448PDUOverCurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.4448
The system has detected a module over current condition.
       lgpCondId4449PDUUnderCurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.4449
The system has detected a module under current condition.
       lgpCondId4468PDUOverCurrentL1 1.3.6.1.4.1.476.1.42.3.2.7.1.4468
The system has detected a module over current condition on line 1.
       lgpCondId4469PDUOverCurrentL2 1.3.6.1.4.1.476.1.42.3.2.7.1.4469
The system has detected a module over current condition on line 2.
       lgpCondId4470PDUOverCurrentL3 1.3.6.1.4.1.476.1.42.3.2.7.1.4470
The system has detected a module over current condition on line 3.
       lgpCondId4471PDUUnderCurrentL1 1.3.6.1.4.1.476.1.42.3.2.7.1.4471
The system has detected a module under current condition on line 1.
       lgpCondId4472PDUUnderCurrentL2 1.3.6.1.4.1.476.1.42.3.2.7.1.4472
The system has detected a module under current condition on line 2.
       lgpCondId4473PDUUnderCurrentL3 1.3.6.1.4.1.476.1.42.3.2.7.1.4473
The system has detected a module under current condition on line 3.
       lgpCondId4492ReceptaclePowerStateOn 1.3.6.1.4.1.476.1.42.3.2.7.1.4492
The receptacle power state changed to the ON state.
       lgpCondId4493ReceptaclePowerStateOff 1.3.6.1.4.1.476.1.42.3.2.7.1.4493
The receptacle power state changed to the OFF state.
       lgpCondId4494BranchBreakerOpen 1.3.6.1.4.1.476.1.42.3.2.7.1.4494
The Branch Receptacle Module's input breaker is open.
       lgpCondId4495DeviceConfigurationChange 1.3.6.1.4.1.476.1.42.3.2.7.1.4495
Device Configuration Change.
       lgpCondId4496BasicDisplayModuleRemoved 1.3.6.1.4.1.476.1.42.3.2.7.1.4496
Basic Display Module Removed.
       lgpCondId4497BasicDisplayModuleDiscovered 1.3.6.1.4.1.476.1.42.3.2.7.1.4497
Basic Display Module Discovered.
       lgpCondId4500PDUOverCurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.4500
The system has detected a power module over current condition.
       lgpCondId4501PDUUnderCurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.4501
The system has detected a power module under current condition.
       lgpCondId4502PDUFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.4502
One or more conditions indicate a power module failure, service is required.
       lgpCondId4503PDUCommunicationFail 1.3.6.1.4.1.476.1.42.3.2.7.1.4503
Internal communications failure with the Power Module.
       lgpCondId4504BranchRemoved 1.3.6.1.4.1.476.1.42.3.2.7.1.4504
Branch Receptacle Module Removed.
       lgpCondId4505BranchDiscovered 1.3.6.1.4.1.476.1.42.3.2.7.1.4505
Branch Receptacle Module Discovered.
       lgpCondId4506BranchOverCurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.4506
The system has detected a Branch Receptacle Module over current condition.
       lgpCondId4507BranchCurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.4507
The system has detected a Branch Receptacle Module under current condition.
       lgpCondId4508ReceptacleLoadRemoved 1.3.6.1.4.1.476.1.42.3.2.7.1.4508
The receptacle's load stopped drawing power.
       lgpCondId4509ReceptacleLoadAdded 1.3.6.1.4.1.476.1.42.3.2.7.1.4509
The receptacle's load started to draw power.
       lgpCondId4523ModuleRemoved 1.3.6.1.4.1.476.1.42.3.2.7.1.4523
Module Removed.
       lgpCondId4524ModuleAdded 1.3.6.1.4.1.476.1.42.3.2.7.1.4524
Module Added.
       lgpCondId4550FirmwareUpdateRequired 1.3.6.1.4.1.476.1.42.3.2.7.1.4550
Module compatibility error requires a system firmware update to resolve.
       lgpCondId4551GenericTestEvent 1.3.6.1.4.1.476.1.42.3.2.7.1.4551
A generic test event designed to evaluate system handling of events.
       lgpCondId4580OverTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.4580
An over temperature condition was detected.
       lgpCondId4581UnderTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.4581
An under temperature condition was detected.
       lgpCondId4588OverRelativeHumidity 1.3.6.1.4.1.476.1.42.3.2.7.1.4588
An over relative humidity condition was detected.
       lgpCondId4589UnderRelativeHumidity 1.3.6.1.4.1.476.1.42.3.2.7.1.4589
An under relative humidity condition was detected.
       lgpCondId4601ExternalAirSensorAOverTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.4601
[Ext Air Sensor A Temperature] has exceeded [External Air Over Temp Threshold].
       lgpCondId4604ExternalAirSensorBOverTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.4604
[Ext Air Sensor B Temperature] has exceeded [External Air Over Temp Threshold].
       lgpCondId4608ExtAirSensorAUnderTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.4608
[Ext Air Sensor A Temperature] has dropped below [Ext Air Under Temp Threshold].
       lgpCondId4611ExtAirSensorBUnderTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.4611
[Ext Air Sensor B Temperature] has dropped below [Ext Air Under Temp Threshold].
       lgpCondId4615ExtDewPointOverTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.4615
At least one dew point temperature reading ([Ext Air Sensor A Dew Point Temp], [Ext Air Sensor B Dew Point Temp]...) has exceeded [Ext Dew Point Over Temp Threshold].
       lgpCondId4618ExternalAirSensorAIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.4618
The external air sensor A is disconnected or the signal is out of range.
       lgpCondId4621ExternalAirSensorBIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.4621
The external air sensor B is disconnected or the signal is out of range.
       lgpCondId4626SupplyChilledWaterOverTemp 1.3.6.1.4.1.476.1.42.3.2.7.1.4626
[Supply Fluid Temperature] has exceeded [High Supply Fluid Temperature Threshold].
       lgpCondId4629SupplyChilledWaterTempSensorIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.4629
The supply chilled water temperature sensor is disconnected or the signal is out of range.
       lgpCondId4634SupplyRefrigerantOverTemp 1.3.6.1.4.1.476.1.42.3.2.7.1.4634
Event that is activated when [Supply Refrigerant Temperature] exceeds [Supply Refrig Over Temp Threshold]. The event is deactivated when the temperature drops below the threshold.
       lgpCondId4637SupplyRefrigerantUnderTemp 1.3.6.1.4.1.476.1.42.3.2.7.1.4637
[Supply Refrigerant Temperature] has dropped below a specified threshold.
       lgpCondId4640SupplyRefrigerantTempSensorIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.4640
The supply refrigeramt temperature sensor is disconnected or the signal is out of range.
       lgpCondId4645SupplyFluidOverTemp 1.3.6.1.4.1.476.1.42.3.2.7.1.4645
[Supply Fluid Temperature] has exceeded [Supply Fluid Over Temp Threshold].
       lgpCondId4648SupplyFluidUnderTemp 1.3.6.1.4.1.476.1.42.3.2.7.1.4648
[Supply Fluid Temperature] has dropped below a specified threshold.
       lgpCondId4651SupplyFluidTempSensorIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.4651
The supply fluid temperature sensor is disconnected or the signal is out of range.
       lgpCondId4656Pump1LossofFlow 1.3.6.1.4.1.476.1.42.3.2.7.1.4656
Loss of flow is detected in pump 1. The loss of flow condition occurs when no differential pressure is detected across the pump.
       lgpCondId4659Pump2LossofFlow 1.3.6.1.4.1.476.1.42.3.2.7.1.4659
Loss of flow is detected in pump 2. The loss of flow condition occurs when no differential pressure is detected across the pump.
       lgpCondId4662PumpShortCycle 1.3.6.1.4.1.476.1.42.3.2.7.1.4662
Pumps have short cycled. A short cycle is defined as turning on and off a number of times over a set time period.
       lgpCondId4669Compressor1AHighHeadPressure 1.3.6.1.4.1.476.1.42.3.2.7.1.4669
Compressor 1A high head pressure.
       lgpCondId4672Compressor1BHighHeadPressure 1.3.6.1.4.1.476.1.42.3.2.7.1.4672
Compressor 1B high head pressure.
       lgpCondId4675Compressor2AHighHeadPressure 1.3.6.1.4.1.476.1.42.3.2.7.1.4675
Compressor 2A high head pressure.
       lgpCondId4678Compressor2BHighHeadPressure 1.3.6.1.4.1.476.1.42.3.2.7.1.4678
Compressor 2B high head pressure.
       lgpCondId4681Compressor1AShortCycle 1.3.6.1.4.1.476.1.42.3.2.7.1.4681
Compressor 1A short cycle. A short cycle is defined as turning on and off a number of times over a set time period.
       lgpCondId4684Compressor1BShortCycle 1.3.6.1.4.1.476.1.42.3.2.7.1.4684
Compressor 1B short cycle. A short cycle is defined as turning on and off a number of times over a set time period.
       lgpCondId4687Compressor2AShortCycle 1.3.6.1.4.1.476.1.42.3.2.7.1.4687
Compressor 2A short cycle. A short cycle is defined as turning on and off a number of times over a set time period.
       lgpCondId4690Compressor2BShortCycle 1.3.6.1.4.1.476.1.42.3.2.7.1.4690
Compressor 2B short cycle. A short cycle is defined as turning on and off a number of times over a set time period.
       lgpCondId4693Tandem1LowSuctionPressure 1.3.6.1.4.1.476.1.42.3.2.7.1.4693
'Tandem compressors' 1 low suction pressure.
       lgpCondId4696Tandem2LowSuctionPressure 1.3.6.1.4.1.476.1.42.3.2.7.1.4696
'Tandem compressors' 2 low suction pressure.
       lgpCondId4703ChilledWaterControlValvePosition 1.3.6.1.4.1.476.1.42.3.2.7.1.4703
Chilled water valve out of position. Chilled water control valve position does not match expected value.
       lgpCondId4711SystemCondensationDetected 1.3.6.1.4.1.476.1.42.3.2.7.1.4711
System condensation detected.
       lgpCondId4714ShutdownLossOfPower 1.3.6.1.4.1.476.1.42.3.2.7.1.4714
System lost power. This event becomes active when the unit is powered on following an unexpected loss of power.
       lgpCondId4720SmokeDetected 1.3.6.1.4.1.476.1.42.3.2.7.1.4720
Smoke detected.
       lgpCondId4723WaterUnderFloor 1.3.6.1.4.1.476.1.42.3.2.7.1.4723
Water under the floor is detected.
       lgpCondId4726ServiceRequired 1.3.6.1.4.1.476.1.42.3.2.7.1.4726
Unit requires servicing.
       lgpCondId4729FanIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.4729
One or more fans are not operating within their operational parameters.
       lgpCondId4732ReceptacleLoadDropped 1.3.6.1.4.1.476.1.42.3.2.7.1.4732
The receptacle's load is not drawing power.
       lgpCondId4740BatteryAutomaticTestInhibited 1.3.6.1.4.1.476.1.42.3.2.7.1.4740
Automatic (scheduled) battery tests are inhibited.
       lgpCondId4741BatterySelfTest 1.3.6.1.4.1.476.1.42.3.2.7.1.4741
Battery self test is in progress.
       lgpCondId4742BatteryLowShutdown 1.3.6.1.4.1.476.1.42.3.2.7.1.4742
Battery disconnect due to end-of-discharge.
       lgpCondId4747EquipmentTemperatureSensorFail 1.3.6.1.4.1.476.1.42.3.2.7.1.4747
One or more temperature sensors report a temperature outside of the range of expected operation.
       lgpCondId4749SystemFanFailureRedundant 1.3.6.1.4.1.476.1.42.3.2.7.1.4749
Redundant system fan failure.
       lgpCondId4750MultipleFanFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.4750
Multiple fan failure.
       lgpCondId4753MainControllerFault 1.3.6.1.4.1.476.1.42.3.2.7.1.4753
A Main Controller fault has been detected.
       lgpCondId4754SystemBreakersCloseFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.4754
One or more breakers in the system failed to close.
       lgpCondId4755InputFilterCycleLock 1.3.6.1.4.1.476.1.42.3.2.7.1.4755
The input filter disconnect is open due to exceeding the maximum number of cycles.
       lgpCondId4756ServiceCodeActive 1.3.6.1.4.1.476.1.42.3.2.7.1.4756
Service code is running.
       lgpCondId4757LBSActive 1.3.6.1.4.1.476.1.42.3.2.7.1.4757
The Load Bus Sync option is active.
       lgpCondId4758LBSInhibited 1.3.6.1.4.1.476.1.42.3.2.7.1.4758
The system has detected that conditions to perform Load Bus Sync are not satisfied.
       lgpCondId4759LeadingPowerFactor 1.3.6.1.4.1.476.1.42.3.2.7.1.4759
The leading output Power Factor has fallen below a specified value.
       lgpCondId4760ControlsResetRequired 1.3.6.1.4.1.476.1.42.3.2.7.1.4760
A controls reset is required due to one or more critical settings changing.
       lgpCondId4823ParallelCommWarning 1.3.6.1.4.1.476.1.42.3.2.7.1.4823
Parallel communication bus warning.
       lgpCondId4824SystemCommFail 1.3.6.1.4.1.476.1.42.3.2.7.1.4824
Failure of a device on the multi-module system communication bus.
       lgpCondId4825LossofRedundancy 1.3.6.1.4.1.476.1.42.3.2.7.1.4825
The multi-module collection doesn't have enough modules to satisfy the redundancy configuration.
       lgpCondId4826BPSSStartupInhibit 1.3.6.1.4.1.476.1.42.3.2.7.1.4826
The Bypass Static Switch startup is inhibited.
       lgpCondId4827MMSTransferInhibit 1.3.6.1.4.1.476.1.42.3.2.7.1.4827
The critical load can not be manually transferred from inverter to bypass.
       lgpCondId4828MMSRetransferInhibit 1.3.6.1.4.1.476.1.42.3.2.7.1.4828
The critical load can not be manually retransferred from bypass to inverter.
       lgpCondId4830MMSLossofSyncPulse 1.3.6.1.4.1.476.1.42.3.2.7.1.4830
Multi-module system loss of sync pulse.
       lgpCondId4831MMSOverload 1.3.6.1.4.1.476.1.42.3.2.7.1.4831
Multi-module system overload.
       lgpCondId4834MMSOnBattery 1.3.6.1.4.1.476.1.42.3.2.7.1.4834
The multi-module system is on battery.
       lgpCondId4835MMSLowBatteryWarning 1.3.6.1.4.1.476.1.42.3.2.7.1.4835
Multi-module system low battery warning.
       lgpCondId4906LowAmbientTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.4906
The system has detected a low ambient temperature condition.
       lgpCondId4907HighAmbientTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.4907
The system has detected a high ambient temperature condition.
       lgpCondId4908LowOverallVoltage 1.3.6.1.4.1.476.1.42.3.2.7.1.4908
The system has detected a low battery string overall voltage condition.
       lgpCondId4909HighOverallVoltage 1.3.6.1.4.1.476.1.42.3.2.7.1.4909
The system has detected a high battery string overall voltage condition.
       lgpCondId4910HighBatteryStringCurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.4910
The system has detected a high battery string current condition.
       lgpCondId4911LowBatteryStringFloatCurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.4911
The system has detected a low battery string float current condition.
       lgpCondId4912HighBatteryStringFloatCurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.4912
The system has detected a high battery string float current condition.
       lgpCondId4913HighBatteryStringRippleCurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.4913
The system has detected a high battery string ripple current condition.
       lgpCondId4914BatteryStringDischargeDetected 1.3.6.1.4.1.476.1.42.3.2.7.1.4914
The system has detected a battery string discharge condition.
       lgpCondId4915MaximumDischargeTimeExceeded 1.3.6.1.4.1.476.1.42.3.2.7.1.4915
The system has detected an excessive discharge time condition.
       lgpCondId4916DischargeLowOverallVoltage 1.3.6.1.4.1.476.1.42.3.2.7.1.4916
The system has detected a low battery string overall voltage condition during a discharge.
       lgpCondId4917DischargeLowCellVoltage 1.3.6.1.4.1.476.1.42.3.2.7.1.4917
The system has detected a low cell voltage condition during a discharge.
       lgpCondId4918DischargeHighBatteryStringCurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.4918
The system has detected a high battery string current condition during a discharge.
       lgpCondId4919ExcessiveCelltoCellTemperatureDeviation 1.3.6.1.4.1.476.1.42.3.2.7.1.4919
The system has detected an excessive cell to cell temperature deviation condition.
       lgpCondId4920ExcessiveCelltoAmbientTemperatureDeviation 1.3.6.1.4.1.476.1.42.3.2.7.1.4920
The system has detected an excessive cell to ambient temperature deviation condition.
       lgpCondId4964LowCellVoltage 1.3.6.1.4.1.476.1.42.3.2.7.1.4964
The system has detected a low cell voltage condition.
       lgpCondId4965HighCellVoltage 1.3.6.1.4.1.476.1.42.3.2.7.1.4965
The system has detected a high cell voltage condition.
       lgpCondId4966LowCellTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.4966
The system has detected a low cell temperature condition.
       lgpCondId4967HighCellTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.4967
The system has detected a high cell temperature condition.
       lgpCondId4968LowInternalResistance 1.3.6.1.4.1.476.1.42.3.2.7.1.4968
The system has detected a low internal resistance condition.
       lgpCondId4969HighInternalResistance 1.3.6.1.4.1.476.1.42.3.2.7.1.4969
The system has detected a high internal resistance condition.
       lgpCondId4970HighIntercellResistance 1.3.6.1.4.1.476.1.42.3.2.7.1.4970
The system has detected a high intercell resistance condition.
       lgpCondId4978IntertierResistanceHigh 1.3.6.1.4.1.476.1.42.3.2.7.1.4978
The system has detected a high intertier resistance condition.
       lgpCondId4980SupplyChilledWaterLossofFlow 1.3.6.1.4.1.476.1.42.3.2.7.1.4980
Supply chilled water or glycol flow is too low.
       lgpCondId4983SupplyRefrigOverTempBand1 1.3.6.1.4.1.476.1.42.3.2.7.1.4983
[Supply Refrigerant Temperature] is above the upper threshold specified by [Supply Refrig Temp Band 1].
       lgpCondId4986SupplyRefrigUnderTempBand1 1.3.6.1.4.1.476.1.42.3.2.7.1.4986
[Supply Refrigerant Temperature] is below the lower threshold specified by [Supply Refrig Temp Band 1].
       lgpCondId4990SupplyRefrigOverTempBand2 1.3.6.1.4.1.476.1.42.3.2.7.1.4990
[Supply Refrigerant Temperature] is above the upper threshold specified by [Supply Refrig Temp Band 2].
       lgpCondId4993SupplyRefrigUnderTempBand2 1.3.6.1.4.1.476.1.42.3.2.7.1.4993
[Supply Refrigerant Temperature] is below the lower threshold specified by [Supply Refrig Temp Band 2].
       lgpCondId4996Inverter1ShortCycle 1.3.6.1.4.1.476.1.42.3.2.7.1.4996
Inverter for pump 1 has short cycled and is temporarily locked out from further operation to protect from thermal overload. A short cycle is defined as powering on and off a number of times over a set time period.
       lgpCondId4999Inverter2ShortCycle 1.3.6.1.4.1.476.1.42.3.2.7.1.4999
Inverter for pump 2 has short cycled and is temporarily locked out from further operation to protect from thermal overload. A short cycle is defined as powering on and off a number of times over a set time period.
       lgpCondId5015SupplyAirOverTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.5015
[Supply Air Temperature] has exceeded [High Supply Air Temperature Threshold].
       lgpCondId5019SupplyAirUnderTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.5019
[Supply Air Temperature] has dropped below [Low Supply Air Temperature Threshold].
       lgpCondId5023ReturnAirOverTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.5023
[Return Air Temperature] has exceeded [High Return Air Temperature Threshold].
       lgpCondId5026SupplyAirSensorIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5026
The air sensor at the outlet of the unit is disconnected or the signal is out of range.
       lgpCondId5034HighReturnHumidity 1.3.6.1.4.1.476.1.42.3.2.7.1.5034
[Return Humidity] has exceeded [High Return Humidity Threshold].
       lgpCondId5036LowReturnHumidity 1.3.6.1.4.1.476.1.42.3.2.7.1.5036
[Return Humidity] has dropped below [Low Return Humidity Threshold].
       lgpCondId5037HumidifierHoursExceeded 1.3.6.1.4.1.476.1.42.3.2.7.1.5037
Operating hours for the humidifier have exceeded the threshold.
       lgpCondId5038DehumidifierHoursExceeded 1.3.6.1.4.1.476.1.42.3.2.7.1.5038
Operating hours for the dehumidifier have exceeded the threshold.
       lgpCondId5039HumidifierUnderCurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.5039
The electrical current to the humidifier has dropped below its lower threshold.
       lgpCondId5040HumidifierOverCurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.5040
The electrical current to the humidifier has exceeded its upper threshold.
       lgpCondId5041HumidifierLowWater 1.3.6.1.4.1.476.1.42.3.2.7.1.5041
The water level in the humidifier has dropped below its threshold.
       lgpCondId5042HumidifierCylinderWorn 1.3.6.1.4.1.476.1.42.3.2.7.1.5042
Humidifier cylinder is not operating properly and needs to be replaced.
       lgpCondId5043HumidifierIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5043
Humidifier issue detected, causing it to be locked out.
       lgpCondId5044ExtHumidifierLockout 1.3.6.1.4.1.476.1.42.3.2.7.1.5044
The humidifier is shut down and disabled by an external input signal.
       lgpCondId5045HumidifierControlBoardNotDetected 1.3.6.1.4.1.476.1.42.3.2.7.1.5045
Humidifier control board is required to be connected, but no signal is detected.
       lgpCondId5046ReturnHumidityOutOfProportionalBand 1.3.6.1.4.1.476.1.42.3.2.7.1.5046
[Return Humidity] has exceeded the upper limit of [Dehumidification Proportional Band], or has dropped below the lower limit of [Humidification Proportional Band] ], for an extended period of time.
       lgpCondId5053LossofAirFlow 1.3.6.1.4.1.476.1.42.3.2.7.1.5053
No air flow through the unit due to failure of all fans.
       lgpCondId5054FanHoursExceeded 1.3.6.1.4.1.476.1.42.3.2.7.1.5054
Operating hours for the unit blower fan have exceeded the threshold.
       lgpCondId5055TopFanIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5055
The top fan is not operating within its normal parameters.
       lgpCondId5056BottomFanIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5056
The bottom fan is not operating within its normal parameters.
       lgpCondId5060RemoteSensorIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5060
Remote sensor is disconnected or the signal is out of range.
       lgpCondId5062Compressor1LowSuctionPressure 1.3.6.1.4.1.476.1.42.3.2.7.1.5062
Compressor 1 low suction pressure.
       lgpCondId5063Compressor1HoursExceeded 1.3.6.1.4.1.476.1.42.3.2.7.1.5063
Operating hours for compressor 1 have exceeded the threshold.
       lgpCondId5064DigScrollComp1TempSensorIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5064
Digital scroll compressor 1 temperature sensor is disconnected or the signal is out of range.
       lgpCondId5065DigScrollComp1OverTemp 1.3.6.1.4.1.476.1.42.3.2.7.1.5065
Digital scroll compressor 1 shut off because its head temperature has exceeded the upper threshold.
       lgpCondId5066Compressor1LowPressureTransducerIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5066
Compressor 1 low pressure transducer is disconnected or the signal is out of range.
       lgpCondId5067ExtCompressorLockout 1.3.6.1.4.1.476.1.42.3.2.7.1.5067
The compressor is shut down and disabled by an external input signal.
       lgpCondId5068ReheaterOverTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.5068
The temperature of the reheater has exceeded its threshold.
       lgpCondId5069ElectricReheater1HoursExceeded 1.3.6.1.4.1.476.1.42.3.2.7.1.5069
Operating hours for electric reheater 1 have exceeded the threshold.
       lgpCondId5070ExtReheatLockout 1.3.6.1.4.1.476.1.42.3.2.7.1.5070
The reheater is shut down and disabled by an external input signal.
       lgpCondId5071Condenser1Issue 1.3.6.1.4.1.476.1.42.3.2.7.1.5071
Condenser 1 is not operating within its normal parameters.
       lgpCondId5072CondenserVFDIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5072
The condenser fan Variable Frequency Drive is offline.
       lgpCondId5073CondenserTVSSIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5073
The condenser Transient Voltage Surge Suppressor or Surge Protection Device has failed.
       lgpCondId5104ExtOverTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.5104
A temperature has exceeded its threshold, as indicated by an external input signal.
       lgpCondId5105ExtLossofFlow 1.3.6.1.4.1.476.1.42.3.2.7.1.5105
Loss of flow is detected, as indicated by an external input signal.
       lgpCondId5106ExtCondenserPumpHighWater 1.3.6.1.4.1.476.1.42.3.2.7.1.5106
High water is detected in the condensate pump by the auxiliary float, as indicated by an external input signal.
       lgpCondId5107ExtStandbyGlycolPumpOn 1.3.6.1.4.1.476.1.42.3.2.7.1.5107
The standby glycol pump is on, as indicated by an external input signal.
       lgpCondId5108ExternalFireDetected 1.3.6.1.4.1.476.1.42.3.2.7.1.5108
Fire detected, as indicated by an external input signal.
       lgpCondId5109UnitOn 1.3.6.1.4.1.476.1.42.3.2.7.1.5109
Unit was turned on.
       lgpCondId5110UnitOff 1.3.6.1.4.1.476.1.42.3.2.7.1.5110
Unit was turned off.
       lgpCondId5111UnitStandby 1.3.6.1.4.1.476.1.42.3.2.7.1.5111
Unit was placed in standby mode.
       lgpCondId5112UnitPartialShutdown 1.3.6.1.4.1.476.1.42.3.2.7.1.5112
An event has occurred requiring some system components to be shutdown and disabled.
       lgpCondId5113UnitShutdown 1.3.6.1.4.1.476.1.42.3.2.7.1.5113
An event has occurred requiring the unit to be shutdown and disabled to prevent damage to the system.
       lgpCondId5114WaterLeakageDetectorSensorIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5114
The water leakage detector sensor is disconnected or the signal is out of range.
       lgpCondId5115BMSCommunicationsTimeout 1.3.6.1.4.1.476.1.42.3.2.7.1.5115
Building Management System (or external monitoring system) has not communicated with the system within the expected timeframe.
       lgpCondId5116MaintenanceDue 1.3.6.1.4.1.476.1.42.3.2.7.1.5116
The calculated maintenance date has been reached.
       lgpCondId5117MaintenanceCompleted 1.3.6.1.4.1.476.1.42.3.2.7.1.5117
Maintenance has been completed on the unit.
       lgpCondId5118CloggedAirFilter 1.3.6.1.4.1.476.1.42.3.2.7.1.5118
Air filter is dirty and needs to be (cleaned or) replaced.
       lgpCondId5119RAMBatteryIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5119
RAM or RAM backup battery is not operating correctly.
       lgpCondId5120MasterUnitCommunicationLost 1.3.6.1.4.1.476.1.42.3.2.7.1.5120
Communication with master unit has been lost.
       lgpCondId5121HighPowerShutdown 1.3.6.1.4.1.476.1.42.3.2.7.1.5121
Supply to high power components has been shutdown.
       lgpCondId5126DigScrollComp2OverTemp 1.3.6.1.4.1.476.1.42.3.2.7.1.5126
Digital scroll compressor 2 shut off because its head temperature has exceeded the upper threshold.
       lgpCondId5144OutputOfUf 1.3.6.1.4.1.476.1.42.3.2.7.1.5144
The output frequency has exceeded a specified range for a specified period of time.
       lgpCondId5145MMSModuleAlarmActive 1.3.6.1.4.1.476.1.42.3.2.7.1.5145
Active alarm or fault of any module in a multi-module system.
       lgpCondId5146CompressorPumpDownIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5146
Unable to pump down suction-side pressure during compressor shutdown.
       lgpCondId5147ReturnAirSensorIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5147
The air sensor at the inlet of the unit is disconnected or the signal is out of range.
       lgpCondId5148CompressorHighPressureTransducerIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5148
Compressor high pressure transducer is disconnected or the signal is out of range.
       lgpCondId5149BatteryNotQualified 1.3.6.1.4.1.476.1.42.3.2.7.1.5149
The UPS battery voltage is not qualified. This event will be detected even in the absence of battery disconnect or when it is open.
       lgpCondId5150BatteryTerminalsReversed 1.3.6.1.4.1.476.1.42.3.2.7.1.5150
The measured battery voltage is a negative value due to reverse battery terminal connections.
       lgpCondId5151BatteryConverterFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.5151
Battery converter failure. This is a summary event caused by one or more power sub-modules in a UPS module.
       lgpCondId5152InverterSCROpen 1.3.6.1.4.1.476.1.42.3.2.7.1.5152
The system has detected an open across one or more inverter static switch Silicon Controlled Rectifiers.
       lgpCondId5153LoadSharingFault 1.3.6.1.4.1.476.1.42.3.2.7.1.5153
Difference between any phase inverter current of unit and the relevant average output current of parallel system is more than a specific percent of nominal current.
       lgpCondId5154DCBusAbnormal 1.3.6.1.4.1.476.1.42.3.2.7.1.5154
The system has detected an abnormal DC Bus Voltage.
       lgpCondId5155MainsInputNeutralLost 1.3.6.1.4.1.476.1.42.3.2.7.1.5155
Loss of neutral in the input source is detected.
       lgpCondId5156LoadImpactTransfer 1.3.6.1.4.1.476.1.42.3.2.7.1.5156
On bypass as result of load impact.
       lgpCondId5157UserOperationInvalid 1.3.6.1.4.1.476.1.42.3.2.7.1.5157
User attempted an invalid operation.
       lgpCondId5158PowerSubModuleFault 1.3.6.1.4.1.476.1.42.3.2.7.1.5158
One or more failures detected in power module, inverter or rectifier.
       lgpCondId5178OutputOvervoltage 1.3.6.1.4.1.476.1.42.3.2.7.1.5178
One or more of the output phase voltages has exceeded the limit.
       lgpCondId5179OutputUndervoltage 1.3.6.1.4.1.476.1.42.3.2.7.1.5179
One or more of the output phase voltages has dropped below the limit.
       lgpCondId5180OutputOvercurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.5180
One or more of the phase currents has exceeded the limit.
       lgpCondId5181NeutralOvercurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.5181
The system's neutral current has exceeded the limit.
       lgpCondId5182GroundOvercurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.5182
System ground current has exceeded the limit.
       lgpCondId5183OutputVoltageTHD 1.3.6.1.4.1.476.1.42.3.2.7.1.5183
The Total Harmonic Distortion of the voltage on one or more of the output phases has exceeded the limit.
       lgpCondId5184OutputFrequencyError 1.3.6.1.4.1.476.1.42.3.2.7.1.5184
The output frequency is outside a specified range.
       lgpCondId5185TransformerOvertemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.5185
Indicates a unit transformer overtemperature condition.
       lgpCondId5212PanelSummaryStatus 1.3.6.1.4.1.476.1.42.3.2.7.1.5212
The status for the panel. Detects and annunciates upon occurrence of any branch or panelboard main breaker active event.
       lgpCondId5213PanelOvervoltage 1.3.6.1.4.1.476.1.42.3.2.7.1.5213
One or more of the phase voltages of this panel has exceeded the limit.
       lgpCondId5214PanelUndervoltage 1.3.6.1.4.1.476.1.42.3.2.7.1.5214
One or more of the phase voltages of this panel is less than the limit.
       lgpCondId5215PanelOvercurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.5215
One or more of the phase currents of this panel has exceeded the limit.
       lgpCondId5216PanelNeutralOvercurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.5216
The Neutral current of this panel has exceeded the limit.
       lgpCondId5217PanelGroundOvercurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.5217
The Ground current of this panel has exceeded the limit.
       lgpCondId5226BranchOvercurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.5226
The current in one or more phases of this branch exceeds the limit.
       lgpCondId5227BranchUndercurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.5227
The current in one or more phases of this branch is less than the limit.
       lgpCondId5245SubfeedPhaseOvercurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.5245
One or more of the phase currents in this subfeed has exceeded the limit.
       lgpCondId5246SubfeedNeutralOvercurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.5246
The Neutral current in this subfeed has exceeded the limit.
       lgpCondId5247SubfeedGroundOvercurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.5247
The Ground current of this subfeed has exceeded the limit.
       lgpCondId5249EventState 1.3.6.1.4.1.476.1.42.3.2.7.1.5249
The present state of this digital event input.
       lgpCondId5263CompressorNotStopping 1.3.6.1.4.1.476.1.42.3.2.7.1.5263
Compressor commanded to stop, but continues to run.
       lgpCondId5269CompressorHoursExceeded 1.3.6.1.4.1.476.1.42.3.2.7.1.5269
[Compressor Hours] has exceeded [Compressor Hours Threshold].
       lgpCondId5270CompressorHighHeadPressure 1.3.6.1.4.1.476.1.42.3.2.7.1.5270
Compressor is shut down due to high head pressure.
       lgpCondId5271CompressorLowSuctionPressure 1.3.6.1.4.1.476.1.42.3.2.7.1.5271
Compressor is shut down due to low suction pressure.
       lgpCondId5272CompressorThermalOverload 1.3.6.1.4.1.476.1.42.3.2.7.1.5272
Compressor is shut down due to thermal overload.
       lgpCondId5273CompressorLowOilPressure 1.3.6.1.4.1.476.1.42.3.2.7.1.5273
Compressor low oil pressure.
       lgpCondId5274CompressorHeadPressureOverThreshold 1.3.6.1.4.1.476.1.42.3.2.7.1.5274
Compressor head pressure has exceeded an upper threshold.
       lgpCondId5275CompressorLossofDifferentialPressure 1.3.6.1.4.1.476.1.42.3.2.7.1.5275
Compressor is shut down due to low differential pressure.
       lgpCondId5277CondenserFanIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5277
Condenser fan is not operating within its operational parameters.
       lgpCondId5278LowCondenserRefrigerantPressure 1.3.6.1.4.1.476.1.42.3.2.7.1.5278
Refrigerant pressure in condenser coil is too low.
       lgpCondId5280LowFluidPressure 1.3.6.1.4.1.476.1.42.3.2.7.1.5280
[Fluid Pressure] has dropped below a specified threshold.
       lgpCondId5293ReturnFluidOverTemp 1.3.6.1.4.1.476.1.42.3.2.7.1.5293
[Return Fluid Temperature] has exceeded a specified threshold.
       lgpCondId5294ReturnFluidUnderTemp 1.3.6.1.4.1.476.1.42.3.2.7.1.5294
[Return Fluid Temperature] has dropped below a specified threshold.
       lgpCondId5295ReturnFluidTempSensorIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5295
The return fluid temperature sensor is disconnected or the signal is out of range.
       lgpCondId5296TeamworkReturnFluidTempSensorIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5296
The return fluid temperature sensors for all Teamwork units are disconnected or the signals are out of range.
       lgpCondId5297AllPumpsLossofFlow 1.3.6.1.4.1.476.1.42.3.2.7.1.5297
System is shut down due to loss of flow in all available pumps.
       lgpCondId5300PumpHoursExceeded 1.3.6.1.4.1.476.1.42.3.2.7.1.5300
[Pump Hours] has exceeded [Pump Hours Threshold].
       lgpCondId5306FreeCoolingValveHoursExceeded 1.3.6.1.4.1.476.1.42.3.2.7.1.5306
[Free Cooling Valve Hours] has exceeded [Free Cooling Valve Hours Threshold].
       lgpCondId5308EvaporatorInletTempSensorIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5308
The evaporator inlet temperature sensor is disconnected or the signal is out of range.
       lgpCondId5309TeamworkEvaporatorInletTempSensorIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5309
The evaporator inlet temperature sensors for all Teamwork units are disconnected or the signals are out of range.
       lgpCondId5310EvaporatorFluidFreezeAutoReset 1.3.6.1.4.1.476.1.42.3.2.7.1.5310
Evaporator outlet fluid temperature has dropped below the freeze threshold. Evaporator has been shut down, but will restart when the temperature rises above the threshold.
       lgpCondId5311EvaporatorFluidFreezeManualResetRequired 1.3.6.1.4.1.476.1.42.3.2.7.1.5311
Evaporator outlet fluid temperature has dropped below the freeze threshold. Evaporator has been shut down and requires a manual reset.
       lgpCondId5315SubgroupEventOccurredDuringCommunicationLoss 1.3.6.1.4.1.476.1.42.3.2.7.1.5315
While subgroup unit communication was lost, an event occurred on the subgroup unit. Please check subgroup unit event log.
       lgpCondId5335ReturnAirUnderTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.5335
[Return Air Temperature] has dropped below [Low Return Air Temperature Threshold].
       lgpCondId5349ExtAirSensorAHighHumidity 1.3.6.1.4.1.476.1.42.3.2.7.1.5349
[Ext Air Sensor A Humidity] has exceeded [Ext Air Sensor A High Humidity Threshold].
       lgpCondId5351ExtAirSensorALowHumidity 1.3.6.1.4.1.476.1.42.3.2.7.1.5351
[Ext Air Sensor A Humidity] has dropped below [Ext Air Sensor A Low Humidity Threshold].
       lgpCondId5352CompressorShortCycle 1.3.6.1.4.1.476.1.42.3.2.7.1.5352
Compressor short cycle. A short cycle is defined as turning on and off a number of times over a set time period.
       lgpCondId5354DigScrollCompDischargeTempSensorIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5354
Digital scroll compressor discharge temperature sensor is disconnected or the signal is out of range.
       lgpCondId5355DigScrollCompOverTemp 1.3.6.1.4.1.476.1.42.3.2.7.1.5355
Digital scroll compressor is shut down due to head temperature exceeding an upper threshold.
       lgpCondId5361ExtFreeCoolingLockout 1.3.6.1.4.1.476.1.42.3.2.7.1.5361
Free cooling is disabled by an external input signal.
       lgpCondId5362FreeCoolingTempSensorIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5362
The free cooling fluid temperature sensor is disconnected or the signal is out of range.
       lgpCondId5365HotWaterHotGasValveHoursExceeded 1.3.6.1.4.1.476.1.42.3.2.7.1.5365
[Hot Water / Hot Gas Valve Hours] has exceeded [Hot Water / Hot Gas Valve Hours Threshold].
       lgpCondId5368ElectricReheaterHoursExceeded 1.3.6.1.4.1.476.1.42.3.2.7.1.5368
[Electric Reheater Hours] has exceeded [Electric Reheaters Hours Threshold].
       lgpCondId5376MainFanOverload 1.3.6.1.4.1.476.1.42.3.2.7.1.5376
Main fan is shut down due to thermal overload.
       lgpCondId5377Condenser 1.3.6.1.4.1.476.1.42.3.2.7.1.5377
Condenser is not operating within its operational parameters.
       lgpCondId5415ExtLossofAirBlower 1.3.6.1.4.1.476.1.42.3.2.7.1.5415
Loss of air blower is detected, as indicated by an external input signal.
       lgpCondId5416ExtStandbyUnitOn 1.3.6.1.4.1.476.1.42.3.2.7.1.5416
Standby unit is on, as indicated by an external input signal.
       lgpCondId5417DigitalOutputBoardNotDetected 1.3.6.1.4.1.476.1.42.3.2.7.1.5417
Digital output board is required to be connected, but no signal is detected.
       lgpCondId5418UnitCodeMissing 1.3.6.1.4.1.476.1.42.3.2.7.1.5418
Unit code has not been entered and saved.
       lgpCondId5419UnitCommunicationLost 1.3.6.1.4.1.476.1.42.3.2.7.1.5419
Master has lost communication with one or more networked units.
       lgpCondId5422OvertemperaturePowerOff 1.3.6.1.4.1.476.1.42.3.2.7.1.5422
Power turned off because equipment over temperature limit.
       lgpCondId5423TooManySensors 1.3.6.1.4.1.476.1.42.3.2.7.1.5423
The number of sensors connected to the PDU exceeds the allowable limit.
       lgpCondId5432TransformerOvertemperaturePowerOff 1.3.6.1.4.1.476.1.42.3.2.7.1.5432
Output power shutdown due to high transformer temperature.
       lgpCondId5433TransformerOvertemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.5433
Transformer temperature has exceeded the limit.
       lgpCondId5434TransformerTemperatureSensorFail 1.3.6.1.4.1.476.1.42.3.2.7.1.5434
Transformer temperature sensor has failed.
       lgpCondId5436LowAmbientTemperatureProbeTwo 1.3.6.1.4.1.476.1.42.3.2.7.1.5436
The system has detected a low ambient temperature condition on temperature probe 2.
       lgpCondId5437HighAmbientTemperatureProbeTwo 1.3.6.1.4.1.476.1.42.3.2.7.1.5437
The system has detected a high ambient temperature condition on temperature probe 2.
       lgpCondId5438ThermalRunawayDetected 1.3.6.1.4.1.476.1.42.3.2.7.1.5438
The system has detected a thermal runaway condition.
       lgpCondId5439BatteryStringEqualize 1.3.6.1.4.1.476.1.42.3.2.7.1.5439
The system has detected a battery string equalize condition.
       lgpCondId5440BatteryStringOffline 1.3.6.1.4.1.476.1.42.3.2.7.1.5440
The system has detected the battery string is offline.
       lgpCondId5442DischargeLowCellVoltage 1.3.6.1.4.1.476.1.42.3.2.7.1.5442
The system has detected a low cell voltage condition during a discharge.
       lgpCondId5447MMSPowerSharing 1.3.6.1.4.1.476.1.42.3.2.7.1.5447
A module is not sharing power with the other modules in a multi -module system.
       lgpCondId5453ModuleInStandbyIntelligentParalleling 1.3.6.1.4.1.476.1.42.3.2.7.1.5453
Module is placed into standby operation per Intelligent Paralleling.
       lgpCondId5456ECOModeActive 1.3.6.1.4.1.476.1.42.3.2.7.1.5456
Conditions for Activation or Automatic Reactivation have been satisfied.
       lgpCondId5457ECOModeSuspended 1.3.6.1.4.1.476.1.42.3.2.7.1.5457
ECO Mode session is suspended.
       lgpCondId5458ExcessECOSuspends 1.3.6.1.4.1.476.1.42.3.2.7.1.5458
Number of automatic suspensions has exceeded the ECO Mode - Maximum Auto Suspensions setting.
       lgpCondId5471DoorOpen 1.3.6.1.4.1.476.1.42.3.2.7.1.5471
An open door was detected.
       lgpCondId5472DoorSensorDisconnected 1.3.6.1.4.1.476.1.42.3.2.7.1.5472
Door sensor disconnect detected.
       lgpCondId5479ContactClosureOpen 1.3.6.1.4.1.476.1.42.3.2.7.1.5479
An open circuit was detected.
       lgpCondId5480ContactClosureClosed 1.3.6.1.4.1.476.1.42.3.2.7.1.5480
A closed circuit was detected.
       lgpCondId5492ExtSystemCondensationDetected 1.3.6.1.4.1.476.1.42.3.2.7.1.5492
External system condensation detected.
       lgpCondId5495ExtFanIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5495
One or more fans are not operating within their operational parameters.
       lgpCondId5500ExtRemoteShutdown 1.3.6.1.4.1.476.1.42.3.2.7.1.5500
Unit is shut down by a remote signal.
       lgpCondId5505HotAisleTempOutofRange 1.3.6.1.4.1.476.1.42.3.2.7.1.5505
The air temperature in the Hot aisle is either above [Hot Aisle Over Temp Threshold] or below [Hot Aisle Under Temp Threshold].
       lgpCondId5508ColdAisleTempOutofRange 1.3.6.1.4.1.476.1.42.3.2.7.1.5508
The air temperature in the cold aisle is either above [Cold Aisle Over Temp Threshold] or below [Cold Aisle Under Temp Threshold].
       lgpCondId5512RemoteShutdown 1.3.6.1.4.1.476.1.42.3.2.7.1.5512
Unit is shut down by a remote signal.
       lgpCondId5513CompressorCapacityReduced 1.3.6.1.4.1.476.1.42.3.2.7.1.5513
Compressor capacity has been reduced.
       lgpCondId5514CompressorLowPressureTransducerIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5514
Compressor low pressure transducer is disconnected or the signal is out of range.
       lgpCondId5524PDUNeutralOverCurrent 1.3.6.1.4.1.476.1.42.3.2.7.1.5524
The system has detected a neutral over current condition.
       lgpCondId5531CondenserCommunicationLost 1.3.6.1.4.1.476.1.42.3.2.7.1.5531
Communication with condenser unit has been lost.
       lgpCondId5535CondenserOutsideAirTempSensorIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5535
Condenser outside air temperature sensor is disconnected or the signal is out of range.
       lgpCondId5536CondenserOutsideAirTempOutofOperatingRange 1.3.6.1.4.1.476.1.42.3.2.7.1.5536
[Condenser Outside Air Temperature] is either above an upper threshold or below a lower threshold.
       lgpCondId5537CondenserControlBoardIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5537
The condenser control board is reporting an issue.
       lgpCondId5539CondenserRefrigerantPressureOverThreshold 1.3.6.1.4.1.476.1.42.3.2.7.1.5539
Condenser refrigerant pressure has exceeded a threshold.
       lgpCondId5540CondenserRefrigerantPressureUnderThreshold 1.3.6.1.4.1.476.1.42.3.2.7.1.5540
Condenser refrigerant pressure has dropped below a threshold.
       lgpCondId5541CondenserRefrigerantPressureSensorIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5541
Condenser refrigerant pressure sensor is disconnected or the signal is out of range.
       lgpCondId5542CondenserSupplyRefrigerantOverTemp 1.3.6.1.4.1.476.1.42.3.2.7.1.5542
Condenser supply refrigerant temperature has exceeded a threshold.
       lgpCondId5543CondenserSupplyRefrigerantUnderTemp 1.3.6.1.4.1.476.1.42.3.2.7.1.5543
Condenser supply refrigerant temperature has dropped below a specified threshold.
       lgpCondId5544CondenserSupplyRefrigerantTempSensorIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5544
Condenser supply refrigerant temperature sensor is disconnected or the signal is out of range.
       lgpCondId5545CondenserMaxFanSpeedOverride 1.3.6.1.4.1.476.1.42.3.2.7.1.5545
Fan speed exceeding the maximum set point in order to alleviate a high temperature or pressure condition.
       lgpCondId5559EvaporatorReturnFluidOverTemp 1.3.6.1.4.1.476.1.42.3.2.7.1.5559
[Evaporator Return Fluid Temperature] has exceeded a threshold. The event is deactivated when the temperature drops below the threshold.
       lgpCondId5560EvaporatorReturnFluidUnderTemp 1.3.6.1.4.1.476.1.42.3.2.7.1.5560
[Evaporator Return Fluid Temperature] has dropped below a threshold. The event is deactivated when the temperature rises above the threshold.
       lgpCondId5561LBSActiveMaster 1.3.6.1.4.1.476.1.42.3.2.7.1.5561
This UPS system has been selected as the functional Master Load Bus Synchronization (LBS) system.
       lgpCondId5562LBSActiveSlave 1.3.6.1.4.1.476.1.42.3.2.7.1.5562
This UPS system is synchronized to the output bus of the UPS system that has been selected as the Master Load Bus Synchronization (LBS) system.
       lgpCondId5563DCBusLowFault 1.3.6.1.4.1.476.1.42.3.2.7.1.5563
The DC Bus voltage has reached a critical low level.
       lgpCondId5564FanContactorOpen 1.3.6.1.4.1.476.1.42.3.2.7.1.5564
The fan contactor is open.
       lgpCondId5565FanContactorOpenFail 1.3.6.1.4.1.476.1.42.3.2.7.1.5565
The fan contactor failed to open.
       lgpCondId5566FanContactorCloseFail 1.3.6.1.4.1.476.1.42.3.2.7.1.5566
The fan contactor failed to close.
       lgpCondId5567IPInhibit 1.3.6.1.4.1.476.1.42.3.2.7.1.5567
The intelligent paralleling operation is inhibited.
       lgpCondId5568InputUndervoltage 1.3.6.1.4.1.476.1.42.3.2.7.1.5568
One or more of the input phase voltages has dropped below the limit.
       lgpCondId5569InputOvervoltage 1.3.6.1.4.1.476.1.42.3.2.7.1.5569
One or more of the input phase voltages has exceeded the limit.
       lgpCondId5573AmbientAirSensorIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5573
Ambient air sensor is disconnected or the signal is out of range.
       lgpCondId5577ExtDewPointUnderTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.5577
At least one dew point temperature reading ([Ext Air Sensor A Dew Point Temp], [Ext Air Sensor B Dew Point Temp]...) has dropped below [Ext Dew Point Under Temp Threshold].
       lgpCondId5578DewPointOverTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.5578
Dew point temperature reading has exceeded the upper threshold.
       lgpCondId5579DewPointUnderTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.5579
Dew point temperature reading has dropped below the lower threshold.
       lgpCondId5588UnspecifiedGeneralEvent 1.3.6.1.4.1.476.1.42.3.2.7.1.5588
One or more unspecified events active. See local unit display for further details.
       lgpCondId5593RemoteSensorAverageOverTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.5593
[Remote Sensor Average Temperature] has exceeded [Remote Sensor Over Temp Threshold].
       lgpCondId5594RemoteSensorAverageUnderTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.5594
[Remote Sensor Average Temperature] has dropped below [Remote Sensor Under Temp Threshold].
       lgpCondId5595RemoteSensorSystemAverageOverTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.5595
[Remote Sensor System Average Temperature] has exceeded [Remote Sensor Over Temp Threshold].
       lgpCondId5596RemoteSensorSystemAverageUnderTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.5596
[Remote Sensor System Average Temperature] has dropped below [Remote Sensor Under Temp Threshold].
       lgpCondId5597RemoteSensorOverTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.5597
[Remote Sensor Temperature] has exceeded [Remote Sensor Over Temp Threshold].
       lgpCondId5598RemoteSensorUnderTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.5598
[Remote Sensor Temperature] has dropped below [Remote Sensor Under Temp Threshold].
       lgpCondId5600AirEconomizerEmergencyOverride 1.3.6.1.4.1.476.1.42.3.2.7.1.5600
Indoor room temperature has exceeded its upper threshold and the outdoor air damper has been opened for emergency cooling.
       lgpCondId5601AirEconomizerReducedAirflow 1.3.6.1.4.1.476.1.42.3.2.7.1.5601
Air economizer filter is dirty and needs to be cleaned or replaced.
       lgpCondId5604CompressorSuperheatOverThreshold 1.3.6.1.4.1.476.1.42.3.2.7.1.5604
Compressor discharge refrigerant superheat temperature has exceeded an upper threshold.
       lgpCondId5609ThermalRunawayCelltoAmbientTemperatureEvent 1.3.6.1.4.1.476.1.42.3.2.7.1.5609
The delta temperature between a cell temperature and the ambient temperature has exceeded the thermal runaway cell to ambient temperature threshold.
       lgpCondId5610ThermalRunawayCelltoCellTemperatureEvent 1.3.6.1.4.1.476.1.42.3.2.7.1.5610
The delta temperature between two cells has exceeded the thermal runaway cell to cell temperature threshold.
       lgpCondId5611ThermalRunawayChargerCurrentLevelOneEvent 1.3.6.1.4.1.476.1.42.3.2.7.1.5611
The Battery-String charger current has exceeded the thermal runaway charger current level one threshold.
       lgpCondId5612ThermalRunawayChargerCurrentLevelTwoEvent 1.3.6.1.4.1.476.1.42.3.2.7.1.5612
The Battery-String charger current has exceeded the thermal runaway charger current level two threshold.
       lgpCondId5617TemperatureControlSensorIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5617
The air sensor selected for cooling control is disconnected or the signal is out of range.
       lgpCondId5621EEVSuperheatBelowThreshold 1.3.6.1.4.1.476.1.42.3.2.7.1.5621
Electronic expansion valve refrigerant low superheat event.
       lgpCondId5622EEVDischargeTempAboveThreshold 1.3.6.1.4.1.476.1.42.3.2.7.1.5622
Electronic expansion valve refrigerant high discharge temperature event.
       lgpCondId5623EEVBatteryIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5623
Electronic expansion valve battery cannot be recharged and needs to be replaced.
       lgpCondId5624EEVPowerIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5624
Electronic expansion valve lost power and is running on battery backup.
       lgpCondId5625EEVUnspecifiedGeneralEvent 1.3.6.1.4.1.476.1.42.3.2.7.1.5625
One or more unspecified electronic expansion valve events active. See local unit display for further details.
       lgpCondId5629StaticPressureSensorIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5629
The static pressure sensor is disconnected or the signal is out of range.
       lgpCondId5630HighStaticPressure 1.3.6.1.4.1.476.1.42.3.2.7.1.5630
High static pressure event.
       lgpCondId5631LowStaticPressure 1.3.6.1.4.1.476.1.42.3.2.7.1.5631
Low static pressure event.
       lgpCondId5636PumpUnspecifiedGeneralEvent 1.3.6.1.4.1.476.1.42.3.2.7.1.5636
One or more unspecified pump events active. See local unit display for further details.
       lgpCondId5637CondenserUnitUnspecifiedGeneralEvent 1.3.6.1.4.1.476.1.42.3.2.7.1.5637
One or more unspecified condenser unit events active. See local unit display for further details.
       lgpCondId5638CondenserCircuitUnspecifiedGeneralEvent 1.3.6.1.4.1.476.1.42.3.2.7.1.5638
One or more unspecified condenser circuit events active. See local unit display for further details.
       lgpCondId5642SFAReservedEvent1 1.3.6.1.4.1.476.1.42.3.2.7.1.5642
Reserved event for SFA use.
       lgpCondId5643SFAReservedEvent2 1.3.6.1.4.1.476.1.42.3.2.7.1.5643
Reserved event for SFA use.
       lgpCondId5644SFAReservedEvent3 1.3.6.1.4.1.476.1.42.3.2.7.1.5644
Reserved event for SFA use.
       lgpCondId5645SFAReservedEvent4 1.3.6.1.4.1.476.1.42.3.2.7.1.5645
Reserved event for SFA use.
       lgpCondId5646SFAReservedEvent5 1.3.6.1.4.1.476.1.42.3.2.7.1.5646
Reserved event for SFA use.
       lgpCondId5647SFAReservedEvent6 1.3.6.1.4.1.476.1.42.3.2.7.1.5647
Reserved event for SFA use.
       lgpCondId5648SFAReservedEvent7 1.3.6.1.4.1.476.1.42.3.2.7.1.5648
Reserved event for SFA use.
       lgpCondId5649SFAReservedEvent8 1.3.6.1.4.1.476.1.42.3.2.7.1.5649
Reserved event for SFA use.
       lgpCondId5650SFAReservedEvent9 1.3.6.1.4.1.476.1.42.3.2.7.1.5650
Reserved event for SFA use.
       lgpCondId5651SFAReservedEvent10 1.3.6.1.4.1.476.1.42.3.2.7.1.5651
Reserved event for SFA use.
       lgpCondId5652SFAReservedEvent11 1.3.6.1.4.1.476.1.42.3.2.7.1.5652
Reserved event for SFA use.
       lgpCondId5653SFAReservedEvent12 1.3.6.1.4.1.476.1.42.3.2.7.1.5653
Reserved event for SFA use.
       lgpCondId5654SFAReservedEvent13 1.3.6.1.4.1.476.1.42.3.2.7.1.5654
Reserved event for SFA use.
       lgpCondId5655SFAReservedEvent14 1.3.6.1.4.1.476.1.42.3.2.7.1.5655
Reserved event for SFA use.
       lgpCondId5656SFAReservedEvent15 1.3.6.1.4.1.476.1.42.3.2.7.1.5656
Reserved event for SFA use.
       lgpCondId5657SFAReservedEvent16 1.3.6.1.4.1.476.1.42.3.2.7.1.5657
Reserved event for SFA use.
       lgpCondId5658SFAReservedEvent17 1.3.6.1.4.1.476.1.42.3.2.7.1.5658
Reserved event for SFA use.
       lgpCondId5659SFAReservedEvent18 1.3.6.1.4.1.476.1.42.3.2.7.1.5659
Reserved event for SFA use.
       lgpCondId5660SFAReservedEvent19 1.3.6.1.4.1.476.1.42.3.2.7.1.5660
Reserved event for SFA use.
       lgpCondId5661SFAReservedEvent20 1.3.6.1.4.1.476.1.42.3.2.7.1.5661
Reserved event for SFA use.
       lgpCondId5662SFAReservedEvent21 1.3.6.1.4.1.476.1.42.3.2.7.1.5662
Reserved event for SFA use.
       lgpCondId5663SFAReservedEvent22 1.3.6.1.4.1.476.1.42.3.2.7.1.5663
Reserved event for SFA use.
       lgpCondId5664SFAReservedEvent23 1.3.6.1.4.1.476.1.42.3.2.7.1.5664
Reserved event for SFA use.
       lgpCondId5665SFAReservedEvent24 1.3.6.1.4.1.476.1.42.3.2.7.1.5665
Reserved event for SFA use.
       lgpCondId5666SFAReservedEvent25 1.3.6.1.4.1.476.1.42.3.2.7.1.5666
Reserved event for SFA use.
       lgpCondId5768OutletAirOvertemperatureLimit 1.3.6.1.4.1.476.1.42.3.2.7.1.5768
The difference between the outlet air temperature and inlet air temperature exceeds a specified maximum temperature.
       lgpCondId5769EMOShutdown 1.3.6.1.4.1.476.1.42.3.2.7.1.5769
An Emergency Module Off command has been detected.
       lgpCondId5770TopOutletFanFault 1.3.6.1.4.1.476.1.42.3.2.7.1.5770
Top outlet fan fault - one or more top outlet fans have failed.
       lgpCondId5771MMSOverCapacity 1.3.6.1.4.1.476.1.42.3.2.7.1.5771
The multi-module system load is larger than the apparent power limit setting.
       lgpCondId5773CompressorCapacityNormal 1.3.6.1.4.1.476.1.42.3.2.7.1.5773
Compressor has returned to normal load capacity.
       lgpCondId5774CompressorContactorIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5774
Compressor contactor is not closing during compressor startup or is not opening during compressor shutdown.
       lgpCondId5775UnitShutdownUnspecifiedGeneralEvent 1.3.6.1.4.1.476.1.42.3.2.7.1.5775
One or more unspecified unit shutdown events active. See local unit display for further details.
       lgpCondId5776PDULowVoltageLN 1.3.6.1.4.1.476.1.42.3.2.7.1.5776
The system has detected a module under voltage condition (LN).
       lgpCondId5777PDULowVoltageLL 1.3.6.1.4.1.476.1.42.3.2.7.1.5777
The system has detected a module under voltage condition (LL).
       lgpCondId5778PDULowVoltageL1L2 1.3.6.1.4.1.476.1.42.3.2.7.1.5778
The system has detected a line-to-line under voltage condition (L1 -L2).
       lgpCondId5779PDULowVoltageL2L3 1.3.6.1.4.1.476.1.42.3.2.7.1.5779
The system has detected a line-to-line under voltage condition (L2 -L3).
       lgpCondId5780PDULowVoltageL3L1 1.3.6.1.4.1.476.1.42.3.2.7.1.5780
The system has detected a line-to-line under voltage condition (L3 -L1).
       lgpCondId5781PDULowVoltageL1N 1.3.6.1.4.1.476.1.42.3.2.7.1.5781
The system has detected a line to neutral under voltage condition (L1-N).
       lgpCondId5782PDULowVoltageL2N 1.3.6.1.4.1.476.1.42.3.2.7.1.5782
The system has detected a line to neutral under voltage condition (L2-N).
       lgpCondId5783PDULowVoltageL3N 1.3.6.1.4.1.476.1.42.3.2.7.1.5783
The system has detected a line to neutral under voltage condition (L3-N).
       lgpCondId5784BranchLowVoltageLN 1.3.6.1.4.1.476.1.42.3.2.7.1.5784
The system has detected a module under voltage condition (LN).
       lgpCondId5785BranchLowVoltageLL 1.3.6.1.4.1.476.1.42.3.2.7.1.5785
The system has detected a module under voltage condition (LL).
       lgpCondId5786BranchLowVoltage 1.3.6.1.4.1.476.1.42.3.2.7.1.5786
The system has detected a module under voltage condition.
       lgpCondId5788ContTieActive 1.3.6.1.4.1.476.1.42.3.2.7.1.5788
Continuous Power Tie Active.
       lgpCondId5792UserkWhReset 1.3.6.1.4.1.476.1.42.3.2.7.1.5792
The user kWh accumulator was reset to zero by the operator.
       lgpCondId5796PeakkWReset 1.3.6.1.4.1.476.1.42.3.2.7.1.5796
The Peak kW was reset.
       lgpCondId5798BypassOverload 1.3.6.1.4.1.476.1.42.3.2.7.1.5798
Bypass overloaded, reduce load immediately.
       lgpCondId5801LowBatteryShutdownImminent 1.3.6.1.4.1.476.1.42.3.2.7.1.5801
If active and guaranteed shutdown is enabled, a low battery reserve condition exists that will shutdown the UPS.
       lgpCondId5806OutputOverload 1.3.6.1.4.1.476.1.42.3.2.7.1.5806
An overload exists on the output.
       lgpCondId5807OutputOffPending 1.3.6.1.4.1.476.1.42.3.2.7.1.5807
Output off pending - shutdown imminent.
       lgpCondId5808SystemShutdownOutputShort 1.3.6.1.4.1.476.1.42.3.2.7.1.5808
Shutdown was due to a short on the output.
       lgpCondId5809SystemShutdownLowBattery 1.3.6.1.4.1.476.1.42.3.2.7.1.5809
Shutdown was due to a low battery condition.
       lgpCondId5810SystemShutdownRemoteShutdown 1.3.6.1.4.1.476.1.42.3.2.7.1.5810
Shutdown was due to a remote communications shutdown command.
       lgpCondId5811SystemShutdownHardwareFault 1.3.6.1.4.1.476.1.42.3.2.7.1.5811
Shutdown was due to an externally applied hardware control signal.
       lgpCondId5817LossofRedundancy 1.3.6.1.4.1.476.1.42.3.2.7.1.5817
The system has an insufficient number of power modules to provide redundancy.
       lgpCondId5818PowerModuleFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.5818
One or more conditions indicate a power module failure, service is required.
       lgpCondId5819PowerModuleWarning 1.3.6.1.4.1.476.1.42.3.2.7.1.5819
One or more power modules is reporting a warning condition.
       lgpCondId5838PowerModuleFanFault 1.3.6.1.4.1.476.1.42.3.2.7.1.5838
The Power Module has detected a fan fault.
       lgpCondId5839PowerModuleOverTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.5839
The Power Module has detected an over temperature condition.
       lgpCondId5840PowerModuleShutdownOverTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.5840
Power Module has shutdown due to over temperature.
       lgpCondId5842ChargerModuleFanFault 1.3.6.1.4.1.476.1.42.3.2.7.1.5842
The Charger Module has detected a fan fault.
       lgpCondId5847BatteryModuleTemperatureSensorFault 1.3.6.1.4.1.476.1.42.3.2.7.1.5847
A Battery Module temperature sensor fault has been detected.
       lgpCondId5848BatteryModuleOverTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.5848
The Battery Module has detected an over temperature condition.
       lgpCondId5849ReplaceBatteryModule 1.3.6.1.4.1.476.1.42.3.2.7.1.5849
The Battery Module needs to be replaced.
       lgpCondId5850SystemShutdownTransformerOverTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.5850
System shutdown due to transformer over temperature.
       lgpCondId5851MaximumLoadAlarm 1.3.6.1.4.1.476.1.42.3.2.7.1.5851
Maximum load alarm indicating load setting has been exceeded.
       lgpCondId5856BatteryModuleFault 1.3.6.1.4.1.476.1.42.3.2.7.1.5856
One or more battery modules are reporting a fault condition.
       lgpCondId5857BatteryModuleWarning 1.3.6.1.4.1.476.1.42.3.2.7.1.5857
One or more battery modules are reporting a warning condition.
       lgpCondId5862CheckAirFilter 1.3.6.1.4.1.476.1.42.3.2.7.1.5862
Please check air filter, it may need to be cleaned or replaced.
       lgpCondId5863TransformerFanFault 1.3.6.1.4.1.476.1.42.3.2.7.1.5863
The transformer fan has failed.
       lgpCondId5865NoLoadWarning 1.3.6.1.4.1.476.1.42.3.2.7.1.5865
Indicates the UPS has output voltage but the output current is below a set threshold [No Load Warning Current Threshold] for a set period of time [No Load Warning Delay].
       lgpCondId5871BatteryOverTemperatureLimit 1.3.6.1.4.1.476.1.42.3.2.7.1.5871
A battery temperature sensor is reporting a value above a predetermined limit.
       lgpCondId5873UnexpectedMainBatteryDisconnectClosure 1.3.6.1.4.1.476.1.42.3.2.7.1.5873
The main battery disconnect has closed unexpectedly.
       lgpCondId5874BatteryOverVoltage 1.3.6.1.4.1.476.1.42.3.2.7.1.5874
The system has detected that the battery voltage has exceeded a predetermined limit.
       lgpCondId5875BatteryFuseFault 1.3.6.1.4.1.476.1.42.3.2.7.1.5875
One or more battery fuse faults has occurred.
       lgpCondId5878MainBatteryDisconnectForcedToUnlock 1.3.6.1.4.1.476.1.42.3.2.7.1.5878
The main battery disconnect is forced to the unlocked state.
       lgpCondId5879VdcBackfeed 1.3.6.1.4.1.476.1.42.3.2.7.1.5879
The voltage between battery and DC bus measurements is out of tolerance.
       lgpCondId5880RectifierConfigurationChangeRequest 1.3.6.1.4.1.476.1.42.3.2.7.1.5880
This event indicates that the battery is not configured and PFC is not enabled.
       lgpCondId5881RegenerationActive 1.3.6.1.4.1.476.1.42.3.2.7.1.5881
Regeneration operation is active.
       lgpCondId5882RegenerationOperationTerminated 1.3.6.1.4.1.476.1.42.3.2.7.1.5882
Regeneration operation is not active.
       lgpCondId5883RegenerationOperationFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.5883
Regeneration operation has been terminated due to bypass source instability or unit misoperation.
       lgpCondId5884ProgramInputContact01 1.3.6.1.4.1.476.1.42.3.2.7.1.5884
When the signal from [Program Input Contact 01] is active the function assigned to this contact is executed.
       lgpCondId5885ProgramInputContact02 1.3.6.1.4.1.476.1.42.3.2.7.1.5885
When the signal from [Program Input Contact 02] is active the function assigned to this contact is executed.
       lgpCondId5886ProgramInputContact03 1.3.6.1.4.1.476.1.42.3.2.7.1.5886
When the signal from [Program Input Contact 03] is active the function assigned to this contact is executed.
       lgpCondId5887ProgramInputContact04 1.3.6.1.4.1.476.1.42.3.2.7.1.5887
When the signal from [Program Input Contact 04] is active the function assigned to this contact is executed.
       lgpCondId5888ProgramInputContact05 1.3.6.1.4.1.476.1.42.3.2.7.1.5888
When the signal from [Program Input Contact 05] is active the function assigned to this contact is executed.
       lgpCondId5889ProgramInputContact06 1.3.6.1.4.1.476.1.42.3.2.7.1.5889
When the signal from [Program Input Contact 06] is active the function assigned to this contact is executed.
       lgpCondId5890ProgramInputContact07 1.3.6.1.4.1.476.1.42.3.2.7.1.5890
When the signal from [Program Input Contact 07] is active the function assigned to this contact is executed.
       lgpCondId5891ProgramInputContact08 1.3.6.1.4.1.476.1.42.3.2.7.1.5891
When the signal from [Program Input Contact 08] is active the function assigned to this contact is executed.
       lgpCondId5892ProgramInputContact09 1.3.6.1.4.1.476.1.42.3.2.7.1.5892
When the signal from [Program Input Contact 09] is active the function assigned to this contact is executed.
       lgpCondId5893ProgramInputContact10 1.3.6.1.4.1.476.1.42.3.2.7.1.5893
When the signal from [Program Input Contact 10] is active the function assigned to this contact is executed.
       lgpCondId5894ProgramInputContact11 1.3.6.1.4.1.476.1.42.3.2.7.1.5894
When the signal from [Program Input Contact 11] is active the function assigned to this contact is executed.
       lgpCondId5895ProgramInputContact12 1.3.6.1.4.1.476.1.42.3.2.7.1.5895
When the signal from [Program Input Contact 12] is active the function assigned to this contact is executed.
       lgpCondId5896GroundFaultDetected 1.3.6.1.4.1.476.1.42.3.2.7.1.5896
The system has detected a ground fault on a Battery-String.
       lgpCondId5902ReturnHumiditySensorIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5902
The humidity sensor at the inlet of the unit is disconnected or the signal is out of range.
       lgpCondId5903CompressorLowDifferentialPressureLockout 1.3.6.1.4.1.476.1.42.3.2.7.1.5903
Compressor exceeded maximum startup attempts due to low differential pressure. Compressor is shutdown and has been disabled.
       lgpCondId5906AirflowSensorIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5906
Airflow sensor is disconnected or the signal is out of range.
       lgpCondId5907ExtAirDamperPositionIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5907
Air damper position does not match expected value, as indicated by an external input signal.
       lgpCondId5908ExtPowerSourceAFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.5908
Unit main power source A failure, as indicated by an external input signal.
       lgpCondId5909ExtPowerSourceBFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.5909
Unit main power source B failure, as indicated by an external input signal.
       lgpCondId5910StaticPressureSensorOutofRange 1.3.6.1.4.1.476.1.42.3.2.7.1.5910
Static pressure sensor signal is out of its configured range.
       lgpCondId5911FluidTemperatureSensorIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5911
The fluid temperature sensor is disconnected or the signal is out of range.
       lgpCondId5912FluidFlowSensorIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.5912
The fluid flow sensor is disconnected or the signal is out of range.
       lgpCondId5914OverDifferentialPressure 1.3.6.1.4.1.476.1.42.3.2.7.1.5914
An over differential pressure condition was detected.
       lgpCondId5915UnderDifferentialPressure 1.3.6.1.4.1.476.1.42.3.2.7.1.5915
An under differential pressure condition was detected.
       lgpCondId5924MixedModeLockout 1.3.6.1.4.1.476.1.42.3.2.7.1.5924
Mixed mode has been entered too many times over a rolling time period and has been temporarily disabled. Mixed mode is defined as the use of a compressor on one refrigeration circuit and the use of a refrigerant pump on the other circuit.
       lgpCondId5928UnbalancedLoadCondition 1.3.6.1.4.1.476.1.42.3.2.7.1.5928
The system has detected a line-to-line unbalanced load condition.
       lgpCondId5939BranchOverCurrentProtection 1.3.6.1.4.1.476.1.42.3.2.7.1.5939
The Branch Receptacle Module's over current protection is triggered.
       lgpCondId5948BranchLowVoltageLL 1.3.6.1.4.1.476.1.42.3.2.7.1.5948
The system has detected a module under voltage condition (LL).
       lgpCondId5957BypassInputVoltageFault 1.3.6.1.4.1.476.1.42.3.2.7.1.5957
The system has detected the bypass voltage is unqualified.
       lgpCondId5958BatteryTemperatureOutofRange 1.3.6.1.4.1.476.1.42.3.2.7.1.5958
Battery temperature is outside of acceptable range.
       lgpCondId5960InverterOverload 1.3.6.1.4.1.476.1.42.3.2.7.1.5960
Inverter in overload fault.
       lgpCondId5966AuxAirTempDeviceCommunicationLost 1.3.6.1.4.1.476.1.42.3.2.7.1.5966
Communication with external auxiliary device providing an air temperature value has been lost.
       lgpCondId5967ModbusPowerMeterCommunicationLost 1.3.6.1.4.1.476.1.42.3.2.7.1.5967
Communication with Modbus power meter has been lost.
       lgpCondId5968InverterDesaturation 1.3.6.1.4.1.476.1.42.3.2.7.1.5968
Inverter Desaturation.
       lgpCondId5969GenericDICFault 1.3.6.1.4.1.476.1.42.3.2.7.1.5969
The control board reports a fault - Service required.
       lgpCondId5970GroundFault 1.3.6.1.4.1.476.1.42.3.2.7.1.5970
An AC phase to ground fault or three phase fault to ground exists on the output of the UPS.
       lgpCondId5973InputBreakerOpen 1.3.6.1.4.1.476.1.42.3.2.7.1.5973
The main input breaker is open.
       lgpCondId5974NeutralBreakerOpen 1.3.6.1.4.1.476.1.42.3.2.7.1.5974
The neutral breaker is open.
       lgpCondId5975OutputBreakerOpen 1.3.6.1.4.1.476.1.42.3.2.7.1.5975
The output breaker is open.
       lgpCondId5976MaintenanceBypassBreakerClosed 1.3.6.1.4.1.476.1.42.3.2.7.1.5976
The maintenance bypass breaker is closed.
       lgpCondId5977BatteryBreakerOpen 1.3.6.1.4.1.476.1.42.3.2.7.1.5977
The battery circuit is open.
       lgpCondId5978RectifierIsolationBreakerRFBOpen 1.3.6.1.4.1.476.1.42.3.2.7.1.5978
The rectifier isolation breaker (RFB) indicates that it is in the open position.
       lgpCondId5982BypassBreakerSBBOpen 1.3.6.1.4.1.476.1.42.3.2.7.1.5982
The bypass circuit breaker (SBB) indicates that it is in the open position.
       lgpCondId5983BypassIsolationBreakerBIBOpen 1.3.6.1.4.1.476.1.42.3.2.7.1.5983
The bypass isolation breaker (BIB) indicates that it is in the open position.
       lgpCondId5984BypassUndervoltageWarning 1.3.6.1.4.1.476.1.42.3.2.7.1.5984
The voltage on one or more bypass phases is less than a specified percentage of the nominal voltage.
       lgpCondId5985BypassStaticSwitchBPSSOn 1.3.6.1.4.1.476.1.42.3.2.7.1.5985
The Bypass Static Switch has been turned on.
       lgpCondId5998BattOvtempWarning 1.3.6.1.4.1.476.1.42.3.2.7.1.5998
A battery temperature sensor is reporting a value above the setpoint.
       lgpCondId6009InverterOutputBreakerOpen 1.3.6.1.4.1.476.1.42.3.2.7.1.6009
The inverter output breaker indicates that it is in the open position.
       lgpCondId6011EquipmentOverTempWarning 1.3.6.1.4.1.476.1.42.3.2.7.1.6011
Equipment over temperature warning is a summary event based on the detection of at least one measured temperature exceeding a threshold.
       lgpCondId6012EquipmentOvertemperatureLimit 1.3.6.1.4.1.476.1.42.3.2.7.1.6012
The equipment air temperature has exceeded its maximum set point.
       lgpCondId6045RectifierInputBreakerOpen 1.3.6.1.4.1.476.1.42.3.2.7.1.6045
The rectifier isolation breaker indicates that it is in the open position.
       lgpCondId6046LoadonUPS 1.3.6.1.4.1.476.1.42.3.2.7.1.6046
The output is being supplied power from the inverter.
       lgpCondId6047Core2CoreFuseFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.6047
Core-2-core fuse failure.
       lgpCondId6052SystemOutputBreakerOpen 1.3.6.1.4.1.476.1.42.3.2.7.1.6052
The system output breaker is open.
       lgpCondId6059InverterRelayFault 1.3.6.1.4.1.476.1.42.3.2.7.1.6059
The inverter relay has malfunctioned.
       lgpCondId6060TransfertoBypassSystemOverload 1.3.6.1.4.1.476.1.42.3.2.7.1.6060
The UPS System has transferred to bypass because the active power modules cannot support the critical load.
       lgpCondId6061InputSourceBackfeed 1.3.6.1.4.1.476.1.42.3.2.7.1.6061
The battery is backfeeding the input source.
       lgpCondId6062LossofSynchronization 1.3.6.1.4.1.476.1.42.3.2.7.1.6062
The inverter and bypass are no longer synchronized. .
       lgpCondId6063BatteryConverterCurrentLimit 1.3.6.1.4.1.476.1.42.3.2.7.1.6063
The battery converter has reached is maximum current limit. .
       lgpCondId6064LBSCableFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.6064
Load Bus Sync communications is abnormal. A problem with the LBS cable may exist.
       lgpCondId6065BatteryChargeEqualizationTimeout 1.3.6.1.4.1.476.1.42.3.2.7.1.6065
The battery equalizing is time out.
       lgpCondId6066ParallelCableFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.6066
The UPS parallel system communications is abnormal. A problem with the parallel cable may exist.
       lgpCondId6067BatteryFault 1.3.6.1.4.1.476.1.42.3.2.7.1.6067
A short circuit exists in the battery system.
       lgpCondId6068BatteryRoomAlarm 1.3.6.1.4.1.476.1.42.3.2.7.1.6068
The ambient temperature of the battery room is abnormal.
       lgpCondId6080UPSCCommunicationFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.6080
The UPSC has failed to communicate in a designated time period.
       lgpCondId6092Compressor1BThermalOverload 1.3.6.1.4.1.476.1.42.3.2.7.1.6092
Fixed compressor 1B is shut down due to thermal overload.
       lgpCondId6093Compressor2BThermalOverload 1.3.6.1.4.1.476.1.42.3.2.7.1.6093
Fixed compressor 2B is shut down due to thermal overload.
       lgpCondId6094Compressor1BHoursExceeded 1.3.6.1.4.1.476.1.42.3.2.7.1.6094
Fixed compressor 1B run hours have exceeded the threshold.
       lgpCondId6095Compressor2BHoursExceeded 1.3.6.1.4.1.476.1.42.3.2.7.1.6095
Fixed compressor 2B run hours have exceeded the threshold.
       lgpCondId6100CondenserRemoteShutdown 1.3.6.1.4.1.476.1.42.3.2.7.1.6100
Condenser is shut down by a remote signal.
       lgpCondId6105ExternalCondenserTVSSIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.6105
The condenser Transient Voltage Surge Suppressor or Surge Protection Device has failed, as indicated by an external input signal.
       lgpCondId6106ExternalCondenserVFDIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.6106
The condenser fan Variable Frequency Drive is offline, as indicated by an external input signal.
       lgpCondId6107ExternalCondenserIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.6107
Condenser is not operating within its operational parameters, as indicated by an external input signal.
       lgpCondId6119Slotsnotavailable 1.3.6.1.4.1.476.1.42.3.2.7.1.6119
The number of sensors exceeds the number of allocated slots and cannot be displayed.
       lgpCondId6180BatteryUnderVoltage 1.3.6.1.4.1.476.1.42.3.2.7.1.6180
Battery voltage is too low.
       lgpCondId6182ReplaceBattery 1.3.6.1.4.1.476.1.42.3.2.7.1.6182
The battery is due for replacement.
       lgpCondId6186InputFrequencyDeviation 1.3.6.1.4.1.476.1.42.3.2.7.1.6186
The input frequency is outside of the normal range.
       lgpCondId6187ShutdownPending 1.3.6.1.4.1.476.1.42.3.2.7.1.6187
Shutdown is pending.
       lgpCondId6194SystemRebootCommandIssued 1.3.6.1.4.1.476.1.42.3.2.7.1.6194
Reboot command issued to the system.
       lgpCondId6203SensorAdded 1.3.6.1.4.1.476.1.42.3.2.7.1.6203
Sensor Added.
       lgpCondId6204SensorRemoved 1.3.6.1.4.1.476.1.42.3.2.7.1.6204
Sensor Removed.
       lgpCondId6205WaterLeakDetected 1.3.6.1.4.1.476.1.42.3.2.7.1.6205
Water leak detected.
       lgpCondId6210FirmwareUpdateInProgress 1.3.6.1.4.1.476.1.42.3.2.7.1.6210
Firmware update has started and is in progress.
       lgpCondId6211FirmwareUpdateCompletedSuccessfully 1.3.6.1.4.1.476.1.42.3.2.7.1.6211
Firmware update has completed successfully.
       lgpCondId6212FirmwareUpdateCompletedUnsuccessfully 1.3.6.1.4.1.476.1.42.3.2.7.1.6212
Firmware update has completed, but was not successful.
       lgpCondId6216PrechargeCircuitFailed 1.3.6.1.4.1.476.1.42.3.2.7.1.6216
DC Bus precharge/discharge didn't reach specified level within a specified time.
       lgpCondId6217MemoryCardRemoved 1.3.6.1.4.1.476.1.42.3.2.7.1.6217
The memory card on the control board has been removed.
       lgpCondId6218AutoCalibrationActive 1.3.6.1.4.1.476.1.42.3.2.7.1.6218
The system is automatically calibrating ADC channels.
       lgpCondId6219AutoCalibrationFailed 1.3.6.1.4.1.476.1.42.3.2.7.1.6219
ADC channel calibration has failed.
       lgpCondId6220ModuleOutputBreakerOpen 1.3.6.1.4.1.476.1.42.3.2.7.1.6220
The module output breaker is open.
       lgpCondId6221NeutralVoltageFault 1.3.6.1.4.1.476.1.42.3.2.7.1.6221
Voltage observed on neutral line.
       lgpCondId6222BranchLoadLoss 1.3.6.1.4.1.476.1.42.3.2.7.1.6222
Loss of load on branch detected. Branch circuit breaker might be open.
       lgpCondId6225RemoteSensorLowHumidity 1.3.6.1.4.1.476.1.42.3.2.7.1.6225
Remote sensor humidity has dropped below a lower threshold. The event is deactivated when the humidity rises above the threshold.
       lgpCondId6226RemoteSensorHighHumidity 1.3.6.1.4.1.476.1.42.3.2.7.1.6226
Remote sensor humidity has exceeded an upper threshold. The event is deactivated when the humidity drops below the threshold.
       lgpCondId6227RemoteSensorAverageLowHumidity 1.3.6.1.4.1.476.1.42.3.2.7.1.6227
The average humidity of multiple remote sensors on the cooling unit has dropped below a lower threshold. The event is deactivated when the humidity rises above the threshold.
       lgpCondId6228RemoteSensorAverageHighHumidity 1.3.6.1.4.1.476.1.42.3.2.7.1.6228
The average humidity of multiple remote sensors on the cooling unit has exceeded an upper threshold. The event is deactivated when the humidity drops below the threshold.
       lgpCondId6229RemoteSensorSystemAverageLowHumidity 1.3.6.1.4.1.476.1.42.3.2.7.1.6229
The average humidity of multiple remote sensors on interconnected cooling units in a single system has dropped below a lower threshold. The event is deactivated when the humidity rises above the threshold.
       lgpCondId6230RemoteSensorSystemAverageHighHumidity 1.3.6.1.4.1.476.1.42.3.2.7.1.6230
The average humidity of multiple remote sensors on interconnected cooling units in a single system has exceeded an upper threshold. The event is deactivated when the humidity drops below the threshold.
       lgpCondId6231LowCompressorSuperheat 1.3.6.1.4.1.476.1.42.3.2.7.1.6231
Compressor suction superheat has dropped below a lower threshold.
       lgpCondId6232SECUnspecifiedGeneralEvent 1.3.6.1.4.1.476.1.42.3.2.7.1.6232
One or more unspecified events active for the Superheat and Envelope Controller. See local unit display for further details.
       lgpCondId6233SECCommunicationLost 1.3.6.1.4.1.476.1.42.3.2.7.1.6233
Communication with the Superheat and Envelope Controller has been lost. The event is deactivated when communication is re -established.
       lgpCondId6236PowerSourceAIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.6236
No power is detected at power source input 'A'.
       lgpCondId6237PowerSourceBIssue 1.3.6.1.4.1.476.1.42.3.2.7.1.6237
No power is detected at power source input 'B'.
       lgpCondId6239FluidValveHoursExceeded 1.3.6.1.4.1.476.1.42.3.2.7.1.6239
Operating hours for the fluid valve have exceeded the threshold.
       lgpCondId6253BoosterFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.6253
Booster failure - boost is off.
       lgpCondId6254ChargerFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.6254
Charger Failure - Charger is off.
       lgpCondId6274UnitTopReturnAirSensorFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.6274
Return air sensor at the top of the unit is disconnected or the signal is out of range.
       lgpCondId6275UnitMiddleReturnAirSensorFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.6275
Return air sensor in the middle of the unit is disconnected or the signal is out of range.
       lgpCondId6276UnitBottomReturnAirSensorFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.6276
Return air sensor at the bottom of the unit is disconnected or the signal is out of range.
       lgpCondId6277UnitTopSupplyAirSensorFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.6277
Supply air sensor at the top of the unit is disconnected or the signal is out of range.
       lgpCondId6278UnitMiddleFirstSupplyAirSensorFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.6278
First supply air sensor in the middle of the unit is disconnected or the signal is out of range.
       lgpCondId6279UnitBottomSupplyAirSensorFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.6279
Supply air sensor at the bottom of the unit is disconnected or the signal is out of range.
       lgpCondId6284UnitMiddleSecondSupplyAirSensorFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.6284
Second supply air sensor in the middle of the unit is disconnected or the signal is out of range.
       lgpCondId6293ChilledWaterControlActive 1.3.6.1.4.1.476.1.42.3.2.7.1.6293
Chilled water inlet temperature control function is enabled due to 'bad' water.
       lgpCondId6294ChilledWaterFlowTransducerFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.6294
Chilled water flow transducer is disconnected or the signal is out of range.
       lgpCondId6295ChilledWaterInletTemperatureSensorFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.6295
Chilled water inlet temperature sensor is disconnected or the signal is out of range. The sensor is mandatory for the chilled water flow function.
       lgpCondId6296ChilledWaterHighInletTemperature 1.3.6.1.4.1.476.1.42.3.2.7.1.6296
Chilled water inlet temperature has exceeded an upper threshold.
       lgpCondId6297Modbus010VModuleCommunicationFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.6297
Modbus 0-10V module for managing the second Chilled Water circuit valve is disconnected or the signal is out of range.
       lgpCondId6299RackDoorsOpen 1.3.6.1.4.1.476.1.42.3.2.7.1.6299
Rack doors opened due to supply air temperature exceeding the [Rack Door Open High Supply Air Temperature Threshold].
       lgpCondId6303TeamStaticPressureSensorFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.6303
The team static pressure sensor is disconnected or the signal is out of range.
       lgpCondId6304HeatingLockout 1.3.6.1.4.1.476.1.42.3.2.7.1.6304
Heating is shut down and disabled.
       lgpCondId6305FreeCoolingStoppedHighRoomTemp 1.3.6.1.4.1.476.1.42.3.2.7.1.6305
Free cooling is temporarily disabled due to room temperature exceeding a preset delta above the the set point.
       lgpCondId6306ColdAisleTemperatureHumidityTeamSensorFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.6306
Cold aisle team sensor measuring air temperature and humidity is disconnected or the signal is out of range.
       lgpCondId6309ColdAisleAirSensorFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.6309
Cold aisle sensor measuring air temperature and humidity is disconnected or the signal is out of range.
       lgpCondId6310ChilledWaterInletTemperatureControlActive 1.3.6.1.4.1.476.1.42.3.2.7.1.6310
Chilled water inlet temperature control is active.
       lgpCondId6313ChilledWaterInletTemperatureSensorFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.6313
Chilled water inlet temperature sensor is disconnected or the signal is out of range.
       lgpCondId6314ChilledWaterOutletTemperatureSensorFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.6314
Chilled water outlet temperature sensor is disconnected or the signal is out of range.
       lgpCondId6315ChilledWaterFlowMeterSensorFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.6315
Chilled water flow meter sensor is disconnected or the signal is out of range.
       lgpCondId6333Bypassoutofsync 1.3.6.1.4.1.476.1.42.3.2.7.1.6333
Bypass and Inverter inputs are not in sync.
       lgpCondId6348SystemOutputoffasrequested 1.3.6.1.4.1.476.1.42.3.2.7.1.6348
The UPS has shutdown as requested, i.e., the output is off.
       lgpCondId6349SystemOffasrequested 1.3.6.1.4.1.476.1.42.3.2.7.1.6349
The entire UPS has shutdown as commanded.
       lgpCondId6350GeneralFault 1.3.6.1.4.1.476.1.42.3.2.7.1.6350
A general fault in the UPS has been detected.
       lgpCondId6351UPSAwaitingPower 1.3.6.1.4.1.476.1.42.3.2.7.1.6351
The UPS output is off and the UPS is awaiting the return of input power.
       lgpCondId6352AutonomyCalibration 1.3.6.1.4.1.476.1.42.3.2.7.1.6352
Calibration test occurred.
       lgpCondId6353GeneralWarning 1.3.6.1.4.1.476.1.42.3.2.7.1.6353
A warning in the UPS has been detected.
       lgpCondId6354BatteryCharging 1.3.6.1.4.1.476.1.42.3.2.7.1.6354
The UPS battery is charging (battery charge percentage lower than 98).
       lgpCondId6355BackfeedRelayFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.6355
Bypass SCR is wrongly on or commutated.
       lgpCondId6356BatteryCircuitOpen 1.3.6.1.4.1.476.1.42.3.2.7.1.6356
Battery Circuit Open.
       lgpCondId6357SystemRestartPending 1.3.6.1.4.1.476.1.42.3.2.7.1.6357
A request for UPS restart has been received.
       lgpCondId6358PipeTemperatureSensorFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.6358
Air temperature sensor located in the pipe is not sending a valid value.
       lgpCondId6362SFAReservedEvent26 1.3.6.1.4.1.476.1.42.3.2.7.1.6362
Reserved event for SFA use.
       lgpCondId6363SFAReservedEvent27 1.3.6.1.4.1.476.1.42.3.2.7.1.6363
Reserved event for SFA use.
       lgpCondId6364SFAReservedEvent28 1.3.6.1.4.1.476.1.42.3.2.7.1.6364
Reserved event for SFA use.
       lgpCondId6365SFAReservedEvent29 1.3.6.1.4.1.476.1.42.3.2.7.1.6365
Reserved event for SFA use.
       lgpCondId6366SFAReservedEvent30 1.3.6.1.4.1.476.1.42.3.2.7.1.6366
Reserved event for SFA use.
       lgpCondId6367SFAReservedEvent31 1.3.6.1.4.1.476.1.42.3.2.7.1.6367
Reserved event for SFA use.
       lgpCondId6368SFAReservedEvent32 1.3.6.1.4.1.476.1.42.3.2.7.1.6368
Reserved event for SFA use.
       lgpCondId6369SFAReservedEvent33 1.3.6.1.4.1.476.1.42.3.2.7.1.6369
Reserved event for SFA use.
       lgpCondId6370SFAReservedEvent34 1.3.6.1.4.1.476.1.42.3.2.7.1.6370
Reserved event for SFA use.
       lgpCondId6371SFAReservedEvent35 1.3.6.1.4.1.476.1.42.3.2.7.1.6371
Reserved event for SFA use.
       lgpCondId6372SFAReservedEvent36 1.3.6.1.4.1.476.1.42.3.2.7.1.6372
Reserved event for SFA use.
       lgpCondId6373SFAReservedEvent37 1.3.6.1.4.1.476.1.42.3.2.7.1.6373
Reserved event for SFA use.
       lgpCondId6374SFAReservedEvent38 1.3.6.1.4.1.476.1.42.3.2.7.1.6374
Reserved event for SFA use.
       lgpCondId6375SFAReservedEvent39 1.3.6.1.4.1.476.1.42.3.2.7.1.6375
Reserved event for SFA use.
       lgpCondId6376SFAReservedEvent40 1.3.6.1.4.1.476.1.42.3.2.7.1.6376
Reserved event for SFA use.
       lgpCondId6377SFAReservedEvent41 1.3.6.1.4.1.476.1.42.3.2.7.1.6377
Reserved event for SFA use.
       lgpCondId6378SFAReservedEvent42 1.3.6.1.4.1.476.1.42.3.2.7.1.6378
Reserved event for SFA use.
       lgpCondId6379SFAReservedEvent43 1.3.6.1.4.1.476.1.42.3.2.7.1.6379
Reserved event for SFA use.
       lgpCondId6380SFAReservedEvent44 1.3.6.1.4.1.476.1.42.3.2.7.1.6380
Reserved event for SFA use.
       lgpCondId6381SFAReservedEvent45 1.3.6.1.4.1.476.1.42.3.2.7.1.6381
Reserved event for SFA use.
       lgpCondId6382SFAReservedEvent46 1.3.6.1.4.1.476.1.42.3.2.7.1.6382
Reserved event for SFA use.
       lgpCondId6383SFAReservedEvent47 1.3.6.1.4.1.476.1.42.3.2.7.1.6383
Reserved event for SFA use.
       lgpCondId6384SFAReservedEvent48 1.3.6.1.4.1.476.1.42.3.2.7.1.6384
Reserved event for SFA use.
       lgpCondId6385SFAReservedEvent49 1.3.6.1.4.1.476.1.42.3.2.7.1.6385
Reserved event for SFA use.
       lgpCondId6386SFAReservedEvent50 1.3.6.1.4.1.476.1.42.3.2.7.1.6386
Reserved event for SFA use.
       lgpCondId6438PowerModuleInputCurrentAbnormal 1.3.6.1.4.1.476.1.42.3.2.7.1.6438
Input current of the power module is abnormal.
       lgpCondId6439PowerModuleBalancerofDCBusFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.6439
Balancer of DC Bus in the power module has failed.
       lgpCondId6440PowerModuleFuseFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.6440
A summary event indicating one or more fuse failures in the power module.
       lgpCondId6441PowerModulePowerSupplyFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.6441
Power module power supply failure.
       lgpCondId6450PDUPoweredOn 1.3.6.1.4.1.476.1.42.3.2.7.1.6450
The PDU was powered on.
       lgpCondId6453InputWiringFault 1.3.6.1.4.1.476.1.42.3.2.7.1.6453
The neutral/ground conductors on the input wiring are not properly bonded, or the line/neutral conductors have been swapped.
       lgpCondId6454DCtoDCConverterFault 1.3.6.1.4.1.476.1.42.3.2.7.1.6454
A failure has occurred in the battery discharge circuit.
       lgpCondId6455LeakSensorCableFault 1.3.6.1.4.1.476.1.42.3.2.7.1.6455
A fault is detected in the 'Leak Sensor' cable.
       lgpCondId6518StandbyUnitActivatedDuetoChillerFailure 1.3.6.1.4.1.476.1.42.3.2.7.1.6518
External chiller unit has failed for this unit, so the standby cooling unit has been activated.