LIEBERT-GP-ENVIRONMENTAL-MIB: View SNMP OID List / Download MIB

VENDOR: VERTIV


 Home MIB: LIEBERT-GP-ENVIRONMENTAL-MIB
Download as:   

Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 liebertGlobalProductsEnvironmentalModule 1.3.6.1.4.1.476.1.42.1.5.1
The MIB module used to register Liebert SNMP OIDs. Copyright 2000-2008 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
 lgpEnvTemperature 1.3.6.1.4.1.476.1.42.3.4.1
This sub-tree is used to register Liebert temperature object identifiers.
     lgpEnvTemperatureWellKnown 1.3.6.1.4.1.476.1.42.3.4.1.1
Liebert well known temperature objects are identified by OIDs that reside in this sub-tree.
         lgpEnvControlTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.1
Temperature measurement used as control feedback.
         lgpEnvReturnAirTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.2
Temperature measurement of return air.
         lgpEnvSupplyAirTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.3
Temperature measurement of supply air.
         lgpAmbientTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.4
Ambient temperature measurement.
         lgpInverterTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.5
Temperature measurement of the inverter.
         lgpBatteryTempterature 1.3.6.1.4.1.476.1.42.3.4.1.1.6
Temperature measurement of the battery.
         lgpAcDcConverterTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.7
Temperature measurement of the AC-to-DC Converter.
         lgpPfcTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.8
Temperature measurement of the power factor correction circuitry.
         lgpTransformerTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.9
Temperature measurement of the transformer.
         lgpLocalTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.10
Temperature measurement of local temperature sensor.
               lgpLocal1Temperature 1.3.6.1.4.1.476.1.42.3.4.1.1.10.1
Temperature and humidity measurements of Local Sensor 1.
               lgpLocal2Temperature 1.3.6.1.4.1.476.1.42.3.4.1.1.10.2
Temperature and humidity measurements of Local Sensor 2.
               lgpLocal3Temperature 1.3.6.1.4.1.476.1.42.3.4.1.1.10.3
Temperature and humidity measurements of Local Sensor 3.
         lgpDigitalScrollCompressorTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.11
Temperature and humidity measurements of a digital Scroll Compressor.
               lgpDigitalScrollCompressor1Temperature 1.3.6.1.4.1.476.1.42.3.4.1.1.11.1
Temperature and humidity measurements of a digital Scroll Compressor 1.
               lgpDigitalScrollCompressor2Temperature 1.3.6.1.4.1.476.1.42.3.4.1.1.11.2
Temperature and humidity measurements of a digital Scroll Compressor 2.
         lgpChillWaterTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.12
Temperature measurements of a chill water system.
         lgpCoolantTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.13
Temperature measurements of an environmental system's coolant.
         lgpEnvEnclosureTemperatureSensors 1.3.6.1.4.1.476.1.42.3.4.1.1.14
Enclosure temperature sensors
               lgpEnvEnclosureTemperatureSensor1 1.3.6.1.4.1.476.1.42.3.4.1.1.14.1
Enclosure temperature sensor 1
               lgpEnvEnclosureTemperatureSensor2 1.3.6.1.4.1.476.1.42.3.4.1.1.14.2
Enclosure temperature sensor 2
               lgpEnvEnclosureTemperatureSensor3 1.3.6.1.4.1.476.1.42.3.4.1.1.14.3
Enclosure temperature sensor 3
               lgpEnvEnclosureTemperatureSensor4 1.3.6.1.4.1.476.1.42.3.4.1.1.14.4
Enclosure temperature sensor 4
         lgpEnvValueAmbientRoomTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.15
Temperature outside enclosure.
         lgpEnvDewPointTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.16
The calculated temperature outside of the enclosure at which condensation is likely to occur.
         lgpEnvEnclosureTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.17
Temperature inside of enclosure.
         lgpEnvAdjustedTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.18
The current temperature set-point which is computed by the system and may be temporarily different from the user set-point because of external factors.
         lgpEnvExternalSensors 1.3.6.1.4.1.476.1.42.3.4.1.1.19
External sensors to monitor environmental variables such as temperature and humidity
               lgpEnvExternalAirSensorA 1.3.6.1.4.1.476.1.42.3.4.1.1.19.1
Temperature and humidity measurements from external air sensor A.
               lgpEnvExternalAirSensorADewPoint 1.3.6.1.4.1.476.1.42.3.4.1.1.19.2
Dewpoint temperature for External Air Sensor A.
               lgpEnvExternalAirSensorB 1.3.6.1.4.1.476.1.42.3.4.1.1.19.3
Temperature and humidity measurements from external air sensor B.
               lgpEnvExternalAirSensorBDewPoint 1.3.6.1.4.1.476.1.42.3.4.1.1.19.4
Dewpoint temperature for External Air Sensor B.
         lgpEnvSupplyFluidTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.20
The current temperature of the fluid being supplied.
         lgpEnvSupplyRefrigerantTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.21
The current temperature of the refrigerant being supplied.
         lgpEnvMinDesiredRoomAirTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.22
The minimum desired room air temperature. If the room air temperature falls below this set point, the unit will reduce the cooling.
         lgpEnvDewPointTemperatures 1.3.6.1.4.1.476.1.42.3.4.1.1.23
This sub-tree identifies well-known dew point temperatures in the system.
               lgpEnvInletDewPointTemperature 1.3.6.1.4.1.476.1.42.3.4.1.1.23.1
Dew point temperature measured at the inlet of the unit.
     lgpEnvTemperatureFahrenheit 1.3.6.1.4.1.476.1.42.3.4.1.2
This sub-tree contains OIDs that are used to control and monitor temperature using the Fahrenheit temperature scale.
         lgpEnvTemperatureSettingDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.1 integer32 read-write
The temperature setting used to control the well known temperature object 'lgpEnvControlTemperature'. This setting is cloned in 'lgpEnvTemperatureSettingDegC' with the value converted to Celsius.
         lgpEnvTemperatureToleranceDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.2 integer32 read-write
The acceptable variance from 'lgpEnvTemperatureSettingDegF', without initiating a control action. This setting is cloned in 'lgpEnvTemperatureToleranceDegC' with the value converted to Celsius.
         lgpEnvTemperatureTableDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3 no-access
A list of temperature table entries. The table contains zero, one, or many rows, depending upon the number of temperature objects available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device. The entries in this table are cloned in 'lgpEnvTemperatureTableDegC' where Fahrenheit values are converted to Celsius.
             lgpEnvTemperatureEntryDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1 no-access
This entry defines the contents of the rows for the table 'lgpEnvTemperatureTableDegF'.
                 lgpEnvTemperatureIdDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.1 unsigned32 read-only
This OID is used as an index to identify a row in the table 'lgpEnvTemperatureTableDegF'.
                 lgpEnvTemperatureDescrDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.2 object identifier read-only
A reference to a temperature description object. The object referenced should not be accessible, but rather be used to provide a unique description of the temperature.
                 lgpEnvTemperatureMeasurementDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.3 integer32 read-only
The measured temperature value.
                 lgpEnvTemperatureHighThresholdDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.4 integer32 read-write
The high temperature notification threshold. This is the maximum value of 'lgpEnvTemperatureMeasurementDegF' before the agent sends a notification.
                 lgpEnvTemperatureLowThresholdDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.5 integer32 read-write
The low temperature notification threshold. This is the minimum value of 'lgpEnvTemperatureMeasurementDegF' before the agent sends a notification.
                 lgpEnvTemperatureSetPointDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.6 integer32 read-write
The temperature setting for the well known 'lgpEnvTemperatureDescrDegF' point. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration.
                 lgpEnvTemperatureDailyHighDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.7 integer32 read-only
The daily high temperature measurement.
                 lgpEnvTemperatureDailyLowDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.8 integer32 read-only
The daily low temperature measurement.
                 lgpEnvTempDailyHighTimeHourDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.9 integer32 read-only
The hours digit of the time corresponding to the daily high temperature measurement.
                 lgpEnvTempDailyHighTimeMinuteDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.10 integer32 read-only
The minutes digit of the time corresponding to the daily high temperature measurement.
                 lgpEnvTempDailyHighTimeSecondDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.11 integer32 read-only
The seconds digit of the time corresponding to the daily high temperature measurement.
                 lgpEnvTempDailyLowTimeHourDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.12 integer32 read-only
The hours digit of the time corresponding to the daily low temperature measurement.
                 lgpEnvTempDailyLowTimeMinuteDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.13 integer32 read-only
The minutes digit of the time corresponding to the daily low temperature measurement.
                 lgpEnvTempDailyLowTimeSecondDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.14 integer32 read-only
The seconds digit of the time corresponding to the daily low temperature measurement.
                 lgpEnvTemperatureMeasurementTenthsDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.50 integer32 read-only
The measured temperature value.
                 lgpEnvTemperatureHighThresholdTenthsDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.51 integer32 read-write
The high temperature notification threshold. This is the maximum value of 'lgpEnvTemperatureMeasurementTenthsDegF' before the agent sends a notification.
                 lgpEnvTemperatureLowThresholdTenthsDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.52 integer32 read-write
The low temperature notification threshold. This is the minimum value of 'lgpEnvTemperatureMeasurementTenthsDegF' before the agent sends a notification.
                 lgpEnvTemperatureSetPointTenthsDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.53 integer32 read-write
The temperature setting for the well known 'lgpEnvTemperatureDescrDegF' point. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration.
                 lgpEnvTemperatureDeadBandTenthsDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.60 integer32 read-write
The deadband region around the setpoint value (lgpEnvTemperatureSetPointTenthsDegF) where no heating or cooling will occur.
                 lgpEnvTempHeatingPropBandTenthsDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.61 integer32 read-write
The proportional region below the setpoint value (lgpEnvTemperatureSetPointTenthsDegF) where heating will be proportionally controlled.
                 lgpEnvTempCoolingPropBandTenthsDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.62 integer32 read-write
The proportional region above the setpoint value (lgpEnvTemperatureSetPointTenthsDegF) where cooling will be proportionally controlled.
         lgpEnvTemperatureDeadbandRangeDegF 1.3.6.1.4.1.476.1.42.3.4.1.2.4 integer32 read-write
The allowable deviation above and below the temperature set point used to create a no control region, a dead-band, where heating and cooling control are disabled.
     lgpEnvTemperatureCelsius 1.3.6.1.4.1.476.1.42.3.4.1.3
This sub-tree contains OIDs that are used to control and monitor temperature using the Celsius temperature scale.
         lgpEnvTemperatureSettingDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.1 integer32 read-write
The temperature setting used to control the well known temperature object 'lgpEnvControlTemperature'. This setting is cloned in 'lgpEnvTemperatureSettingDegF' with the value converted to Fahrenheit.
         lgpEnvTemperatureToleranceDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.2 integer32 read-write
The acceptable variance from 'lgpEnvTemperatureSettingDegC', without initiating a control action. This setting is cloned in 'lgpEnvTemperatureToleranceDegF' with the value converted to Fahrenheit.
         lgpEnvTemperatureTableDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3 no-access
A list of temperature table entries. The table contains zero, one, or many rows, depending upon the number of temperature objects available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device. The entries in this table are cloned in 'lgpEnvTemperatureTableDegF' where Celsius values are converted to Fahrenheit.
             lgpEnvTemperatureEntryDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1 no-access
This entry defines the contents of the rows for the table 'lgpEnvTemperatureTableDegC'.
                 lgpEnvTemperatureIdDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.1 unsigned32 read-only
This OID is used as an index to identify a row in the table 'lgpEnvTemperatureTableDegC'.
                 lgpEnvTemperatureDescrDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.2 object identifier read-only
A reference to a temperature description object. The object referenced should not be accessible, but rather be used to provide a unique description of the temperature.
                 lgpEnvTemperatureMeasurementDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.3 integer32 read-only
The measured temperature value.
                 lgpEnvTemperatureHighThresholdDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.4 integer32 read-write
The high temperature notification threshold. This is the maximum value of 'lgpEnvTemperatureMeasurementDegC' before the agent sends a notification.
                 lgpEnvTemperatureLowThresholdDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.5 integer32 read-write
The low temperature notification threshold. This is the minimum value of 'lgpEnvTemperatureMeasurementDegC' before the agent sends a notification.
                 lgpEnvTemperatureSetPointDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.6 integer32 read-write
The temperature setting for the well known 'lgpEnvTemperatureDescrDegC' point. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration.
                 lgpEnvTemperatureDailyHighDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.7 integer32 read-only
The daily high temperature measurement.
                 lgpEnvTemperatureDailyLowDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.8 integer32 read-only
The daily low temperature measurement.
                 lgpEnvTempDailyHighTimeHourDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.9 integer32 read-only
The hours digit of the time corresponding to the daily high temperature measurement.
                 lgpEnvTempDailyHighTimeMinuteDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.10 integer32 read-only
The minutes digit of the time corresponding to the daily high temperature measurement.
                 lgpEnvTempDailyHighTimeSecondDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.11 integer32 read-only
The seconds digit of the time corresponding to the daily high temperature measurement.
                 lgpEnvTempDailyLowTimeHourDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.12 integer32 read-only
The hours digit of the time corresponding to the daily low temperature measurement.
                 lgpEnvTempDailyLowTimeMinuteDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.13 integer32 read-only
The minutes digit of the time corresponding to the daily low temperature measurement.
                 lgpEnvTempDailyLowTimeSecondDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.14 integer32 read-only
The seconds digit of the time corresponding to the daily low temperature measurement.
                 lgpEnvTemperatureMeasurementTenthsDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.50 integer32 read-only
The measured temperature value.
                 lgpEnvTemperatureHighThresholdTenthsDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.51 integer32 read-write
The high temperature notification threshold. This is the maximum value of 'lgpEnvTemperatureMeasurementTenthsDegC' before the agent sends a notification.
                 lgpEnvTemperatureLowThresholdTenthsDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.52 integer32 read-write
The low temperature notification threshold. This is the minimum value of 'lgpEnvTemperatureMeasurementTenthsDegC' before the agent sends a notification.
                 lgpEnvTemperatureSetPointTenthsDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.53 integer32 read-write
The temperature setting for the well known 'lgpEnvTemperatureDescrDegC' point. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration.
                 lgpEnvTemperatureDeadBandTenthsDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.60 integer32 read-write
The deadband region around the setpoint value (lgpEnvTemperatureSetPointTenthsDegC) where no heating or cooling will occur.
                 lgpEnvTempHeatingPropBandTenthsDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.61 integer32 read-write
The proportional region below the setpoint value (lgpEnvTemperatureSetPointTenthsDegC) where heating will be proportionally controlled.
                 lgpEnvTempCoolingPropBandTenthsDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.62 integer32 read-write
The proportional region above the setpoint value (lgpEnvTemperatureSetPointTenthsDegC) where cooling will be proportionally controlled.
         lgpEnvTemperatureDeadbandRangeDegC 1.3.6.1.4.1.476.1.42.3.4.1.3.4 integer32 read-write
The allowable deviation above and below the temperature set point used to create a no control region, a dead-band, where heating and cooling control are disabled.
     lgpEnvTemperatureControlMode 1.3.6.1.4.1.476.1.42.3.4.1.4 object identifier read-only
A reference to a temperature description object. The object referenced should not be accessible, but rather be used to provide a unique description of the temperature object that is used for control.
 lgpEnvHumidity 1.3.6.1.4.1.476.1.42.3.4.2
This sub-tree is used to register Liebert humidity object identifiers.
     lgpEnvHumidityWellKnown 1.3.6.1.4.1.476.1.42.3.4.2.1
Liebert well known humidity objects are defined by OIDs that reside in this sub-tree.
         lgpEnvControlHumidity 1.3.6.1.4.1.476.1.42.3.4.2.1.1
Humidity measurement used as control feedback.
         lgpEnvReturnAirHumidity 1.3.6.1.4.1.476.1.42.3.4.2.1.2
Humidity measurement of return air.
         lgpEnvSupplyAirHumidity 1.3.6.1.4.1.476.1.42.3.4.2.1.3
Humidity measurement of supply air.
         lgpEnvValueAmbientHumidity 1.3.6.1.4.1.476.1.42.3.4.2.1.4
Humidity outside enclosure.
     lgpEnvHumidityRelative 1.3.6.1.4.1.476.1.42.3.4.2.2
This sub-tree contains OIDs that are used to control and monitor relative humidity.
         lgpEnvHumiditySettingRel 1.3.6.1.4.1.476.1.42.3.4.2.2.1 integer32 read-write
The humidity setting used to control the well known humidity point.
         lgpEnvHumidityToleranceRel 1.3.6.1.4.1.476.1.42.3.4.2.2.2 integer32 read-write
Acceptable variance from lgpEnvHumiditySettingRel, without initiating a control action.
         lgpEnvHumidityTableRel 1.3.6.1.4.1.476.1.42.3.4.2.2.3 no-access
A list of humidity table entries. The table contains zero, one, or many rows, depending upon the number of humidity objects available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device.
             lgpEnvHumidityEntryRel 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1 no-access
This entry defines the contents of the rows for the table 'lgpEnvHumidityTableRel'.
                 lgpEnvHumidityIdRel 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.1 unsigned32 read-only
This OID is used as an index to identify a row in the table 'lgpEnvHumidityTableRel'.
                 lgpEnvHumidityDescrRel 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.2 object identifier read-only
A reference to a humidity description object. The object referenced should not be accessible, but rather be used to provide a unique description of the humidity.
                 lgpEnvHumidityMeasurementRel 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.3 integer32 read-only
The measured humidity value.
                 lgpEnvHumidityHighThresholdRel 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.4 integer32 read-write
The high humidity notification threshold. This is the maximum value of 'lgpEnvHumidityMeasurementRel' before the agent sends a notification.
                 lgpEnvHumidityLowThresholdRel 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.5 integer32 read-write
The low humidity notification threshold. This is the minimum value of 'lgpEnvHumidityMeasurementRel' before the agent sends a notification.
                 lgpEnvHumiditySetPoint 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.6 integer32 read-write
The humidity setting used to control the well known humidity object 'lgpEnvHumidityDescrRel'. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration.
                 lgpEnvHumidityDailyHigh 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.7 integer32 read-only
The daily high relative humidity measurement.
                 lgpEnvHumidityDailyLow 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.8 integer32 read-only
The daily low relative humidity measurement.
                 lgpEnvHumidityDailyHighTimeHour 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.9 integer32 read-only
The hours digit of the time corresponding to the daily high humidity measurement.
                 lgpEnvHumidityDailyHighTimeMinute 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.10 integer32 read-only
The minutes digit of the time corresponding to the daily high humidity measurement.
                 lgpEnvHumidityDailyHighTimeSecond 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.11 integer32 read-only
The seconds digit of the time corresponding to the daily high humidity measurement.
                 lgpEnvHumidityDailyLowTimeHour 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.12 integer32 read-only
The hours digit of the time corresponding to the daily low humidity measurement.
                 lgpEnvHumidityDailyLowTimeMinute 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.13 integer32 read-only
The minutes digit of the time corresponding to the daily low humidity measurement.
                 lgpEnvHumidityDailyLowTimeSecond 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.14 integer32 read-only
The seconds digit of the time corresponding to the daily low humidity measurement.
                 lgpEnvHumidityDeadBand 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.15 integer32 read-write
The deadband region around the setpoint value (lgpEnvHumiditySetPoint) where no humidifying or dehumidifying will occur.
                 lgpEnvHumidifyPropBand 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.16 integer32 read-write
The proportional region below the setpoint value (lgpEnvHumiditySetPoint) where humidifying will be proportionally controlled.
                 lgpEnvDehumidifyPropBand 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.17 integer32 read-write
The proportional region above the setpoint value (lgpEnvHumiditySetPoint) where dehumidifying will be proportionally controlled.
                 lgpEnvHumidityMeasurementRelTenths 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.50 integer32 read-only
The measured humidity value.
                 lgpEnvHumidityHighThresholdRelTenths 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.51 integer32 read-write
The high humidity notification threshold. This is the maximum value of 'lgpEnvHumidityMeasurementRelTenths' before the agent sends a notification.
                 lgpEnvHumidityLowThresholdRelTenths 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.52 integer32 read-write
The low humidity notification threshold. This is the minimum value of 'lgpEnvHumidityMeasurementRelTenths' before the agent sends a notification.
         lgpEnvHumidityDeadbandRange 1.3.6.1.4.1.476.1.42.3.4.2.2.4 integer32 read-write
The allowable deviation above and below the humidity set point used to create a no control region, a dead-band, where humidifying and dehumidifying control are disabled.
 lgpEnvState 1.3.6.1.4.1.476.1.42.3.4.3
This sub-tree is used to register Liebert environmental state object identifiers.
     lgpEnvStateSystem 1.3.6.1.4.1.476.1.42.3.4.3.1 integer read-only
The present state of the system. Enumeration: 'standby': 3, 'on': 1, 'off': 2.
     lgpEnvStateCooling 1.3.6.1.4.1.476.1.42.3.4.3.2 integer read-only
The present state of the cooling subsystem. Enumeration: 'on': 1, 'off': 2.
     lgpEnvStateHeating 1.3.6.1.4.1.476.1.42.3.4.3.3 integer read-only
The present state of the heating subsystem. Enumeration: 'on': 1, 'off': 2.
     lgpEnvStateHumidifying 1.3.6.1.4.1.476.1.42.3.4.3.4 integer read-only
The present state of the humidifier subsystem. Enumeration: 'on': 1, 'off': 2.
     lgpEnvStateDehumidifying 1.3.6.1.4.1.476.1.42.3.4.3.5 integer read-only
The present state of the dehumidifier subsystem Enumeration: 'on': 1, 'off': 2.
     lgpEnvStateEconoCycle 1.3.6.1.4.1.476.1.42.3.4.3.6 integer read-only
The present state of the Econ-o-cycle subsystem. Enumeration: 'on': 1, 'off': 2.
     lgpEnvStateFan 1.3.6.1.4.1.476.1.42.3.4.3.7 integer read-only
The present state of the system fan. Enumeration: 'on': 1, 'off': 2.
     lgpEnvStateGeneralAlarmOutput 1.3.6.1.4.1.476.1.42.3.4.3.8 integer read-only
The present state of the general alarm output. This indicates if an alarm is active in the system. Enumeration: 'on': 1, 'off': 2.
     lgpEnvStateCoolingCapacity 1.3.6.1.4.1.476.1.42.3.4.3.9 unsigned32 read-only
The percentage of the cooling capacity presently in use.
     lgpEnvStateHeatingCapacity 1.3.6.1.4.1.476.1.42.3.4.3.10 unsigned32 read-only
The percentage of the heating capacity presently in use.
     lgpEnvStateAudibleAlarm 1.3.6.1.4.1.476.1.42.3.4.3.11 integer read-only
The present state of the audible alarm output. Enumeration: 'on': 1, 'off': 2.
     lgpEnvStateCoolingUnits 1.3.6.1.4.1.476.1.42.3.4.3.12
This sub-tree contains OIDs that are used to indicate the status of cooling units.
           lgpEnvStateCoolingUnit1 1.3.6.1.4.1.476.1.42.3.4.3.12.2 integer read-only
The present state of cooling unit 1. Enumeration: 'on': 1, 'off': 2.
           lgpEnvStateCoolingUnit2 1.3.6.1.4.1.476.1.42.3.4.3.12.3 integer read-only
The present state of cooling unit 2. Enumeration: 'on': 1, 'off': 2.
           lgpEnvStateCoolingUnit3 1.3.6.1.4.1.476.1.42.3.4.3.12.4 integer read-only
The present state of cooling unit 3. Enumeration: 'on': 1, 'off': 2.
           lgpEnvStateCoolingUnit4 1.3.6.1.4.1.476.1.42.3.4.3.12.5 integer read-only
The present state of cooling unit 4. Enumeration: 'on': 1, 'off': 2.
     lgpEnvStateHeatingUnits 1.3.6.1.4.1.476.1.42.3.4.3.13
This sub-tree contains OIDs that are used to indicate the status of heating units.
           lgpEnvStateHeatingUnit1 1.3.6.1.4.1.476.1.42.3.4.3.13.2 integer read-only
The present state of heating unit 1. Enumeration: 'on': 1, 'off': 2.
           lgpEnvStateHeatingUnit2 1.3.6.1.4.1.476.1.42.3.4.3.13.3 integer read-only
The present state of heating unit 2. Enumeration: 'on': 1, 'off': 2.
           lgpEnvStateHeatingUnit3 1.3.6.1.4.1.476.1.42.3.4.3.13.4 integer read-only
The present state of heating unit 3. Enumeration: 'on': 1, 'off': 2.
           lgpEnvStateHeatingUnit4 1.3.6.1.4.1.476.1.42.3.4.3.13.5 integer read-only
The present state of heating unit 4. Enumeration: 'on': 1, 'off': 2.
     lgpEnvStateOperatingReason 1.3.6.1.4.1.476.1.42.3.4.3.14 integer read-only
The reason for the current operating state of the system. Enumeration: 'localUser': 2, 'none': 1, 'externalDevice': 6, 'remoteUser': 5, 'alarm': 3, 'schedule': 4, 'localDisplay': 7.
     lgpEnvStateOperatingMode 1.3.6.1.4.1.476.1.42.3.4.3.15 integer read-only
The present operating mode of the system. Enumeration: 'auto': 1, 'manual': 2.
     lgpEnvStateFanCapacity 1.3.6.1.4.1.476.1.42.3.4.3.16 unsigned32 read-only
The percentage of the fan capacity presently in use.
     lgpEnvStateFreeCoolingCapacity 1.3.6.1.4.1.476.1.42.3.4.3.17 unsigned32 read-only
The percentage of the free cooling capacity presently in use.
     lgpEnvStateDehumidifyingCapacity 1.3.6.1.4.1.476.1.42.3.4.3.18 unsigned32 read-only
The percentage of the dehumidifying capacity presently in use.
     lgpEnvStateHumidifyingCapacity 1.3.6.1.4.1.476.1.42.3.4.3.19 unsigned32 read-only
The percentage of the humidifying capacity presently in use.
     lgpEnvStateFreeCooling 1.3.6.1.4.1.476.1.42.3.4.3.20 integer read-only
The present state of the system free cooling process of heat exchange. When 'off', free cooling is not in use. When 'on' free cooling is in use. When 'start', free cooling is preparing to turn on. When 'unavailable', the state information is unavailable. Enumeration: 'on': 1, 'off': 2, 'unavailable': 4, 'start': 3.
     lgpEnvStateElectricHeater 1.3.6.1.4.1.476.1.42.3.4.3.21 integer read-only
The present state of the electric heaters. Enumeration: 'on': 1, 'off': 2.
     lgpEnvStateHotWater 1.3.6.1.4.1.476.1.42.3.4.3.22 integer read-only
The present state of hot water system. Enumeration: 'on': 1, 'off': 2.
     lgpEnvStateOperatingEfficiency 1.3.6.1.4.1.476.1.42.3.4.3.23 unsigned32 read-only
The ratio of cooling energy provided to the amount of total energy being used.
     lgpEnvComponentStateTable 1.3.6.1.4.1.476.1.42.3.4.3.50 no-access
This table contains a list of the units components that have a state associated with them. The table contains zero, one, or more rows, depending upon the number of components associated with the unit. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the units being monitored.
           lgpEnvComponentStateEntry 1.3.6.1.4.1.476.1.42.3.4.3.50.1 no-access
This entry defines the attributes to be populated in the various columns of the 'lgpEnvComponentStateTable'.
               lgpEnvComponentStateIndex 1.3.6.1.4.1.476.1.42.3.4.3.50.1.1 unsigned32 no-access
This is the index indicating the nth element of the table.
               lgpEnvComponentStateDescr 1.3.6.1.4.1.476.1.42.3.4.3.50.1.2 object identifier read-only
A reference to a component description object. The object referenced should not be accessible, but rather be used to provide a unique description of the component being described in the row of the table.
               lgpEnvComponentState 1.3.6.1.4.1.476.1.42.3.4.3.50.1.3 integer read-only
not-specified The state of the component is unknown. on The component is on. off The component is off. Enumeration: 'on': 1, 'off': 2, 'not-specified': 0.
     lgpEnvValveTable 1.3.6.1.4.1.476.1.42.3.4.3.70 no-access
This table contains a list of the unit valves that have information associated with them. The table contains zero, one, or more rows, depending upon the number of valves associated with the unit. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the units being monitored.
           lgpEnvValveEntry 1.3.6.1.4.1.476.1.42.3.4.3.70.1 no-access
This entry defines the attributes to be populated in the various columns of the 'lgpEnvValveTable'.
               lgpEnvValveIndex 1.3.6.1.4.1.476.1.42.3.4.3.70.1.1 unsigned32 no-access
This is the index indicating the nth element of the table.
               lgpEnvValveDescr 1.3.6.1.4.1.476.1.42.3.4.3.70.1.2 object identifier read-only
A reference to a valve description object. The object referenced should not be accessible, but rather be used to provide a unique description of the valve being described in the row of the table.
               lgpEnvValveState 1.3.6.1.4.1.476.1.42.3.4.3.70.1.3 integer read-only
not-specified The state of the component is unknown. open The valve is open. off The valve is closed. Enumeration: 'open': 1, 'closed': 2, 'not-specified': 0.
               lgpEnvValvePositionTenths 1.3.6.1.4.1.476.1.42.3.4.3.70.1.20 unsigned32 read-only
This gives a value describing the position of the valve.
 lgpEnvConfig 1.3.6.1.4.1.476.1.42.3.4.4
This sub-tree is used to register Liebert environmental configuration object identifiers.
     lgpEnvConfigReheatLockout 1.3.6.1.4.1.476.1.42.3.4.4.1 integer read-write
If locked-out the reheats will not operate even if controller calls for its operation. Enumeration: 'notLockedOut': 2, 'lockedOut': 1.
     lgpEnvConfigHumLockout 1.3.6.1.4.1.476.1.42.3.4.4.2 integer read-write
If locked-out the humidifier will not operate even if controller calls for its operation. Enumeration: 'notLockedOut': 2, 'lockedOut': 1.
     lgpEnvConfigRestartDelay 1.3.6.1.4.1.476.1.42.3.4.4.4 unsigned32 read-write
When utility power is disrupted, this is the delay interval to wait before restarting the system after the utility power is restored. A Restart Delay of zero denotes a manual restart, the unit will NOT automatically restart.
     lgpEnvConfigRemoteShutdown 1.3.6.1.4.1.476.1.42.3.4.4.7 integer read-write
When in the disabled state, the remote shutdown feature should be locked out. The enabled state is self-describing. Enumeration: 'disabled': 1, 'enabled': 2.
     lgpEnvConfigCoolingServiceInterval 1.3.6.1.4.1.476.1.42.3.4.4.8 unsigned32 read-write
The amount of time, in hours, between scheduled maintenance of the cooling system. When the cooling service timer reaches this value an lgpConditionServiceCooling will be activated. Once service has been completed the cooling service timer should be reset to 0.
     lgpEnvConfigHumidifierServiceInterval 1.3.6.1.4.1.476.1.42.3.4.4.9 unsigned32 read-write
The amount of time, in hours, between scheduled maintenance of the humidifier. When the humidifier service timer reaches this value an lgpConditionServiceHumidifier will be activated. Once service has been completed humidifier service timer should be reset to 0.
     lgpEnvConfigFilterServiceInterval 1.3.6.1.4.1.476.1.42.3.4.4.10 unsigned32 read-write
The amount of time, in hours, between scheduled maintenance of the system filter. When the filter service timer reaches this value an lgpConditionChangeFilter will be activated. Once service has been completed the filter service timer should be reset to 0.
     lgpEnvConfigSleepModeDeadbandRangeDegC 1.3.6.1.4.1.476.1.42.3.4.4.11 integer32 read-write
The allowable deviation above and below the temperature set point used to create a no control region, a dead-band, where heating and cooling control are disabled. This dead-band is applied only when the system's sleep mode function is in operation.
     lgpEnvConfigSleepModeDeadbandRangeDegF 1.3.6.1.4.1.476.1.42.3.4.4.12 integer32 read-write
The allowable deviation above and below the temperature set point used to create a no control region, a dead-band, where heating and cooling control are disabled. This dead-band is applied only when the system's sleep mode function is in operation.
     lgpEnvConfigSupplyTempLowLimitDegF 1.3.6.1.4.1.476.1.42.3.4.4.13 integer32 read-write
The minimum allowable supply temperature.
     lgpEnvConfigSupplyTempLowLimitDegC 1.3.6.1.4.1.476.1.42.3.4.4.14 integer32 read-write
The minimum allowable supply temperature.
     lgpEnvConfigTemperatureIntegTime 1.3.6.1.4.1.476.1.42.3.4.4.15 integer32 read-write
The value used as the integration factor in the proportional integral derivative (PID) temperature calculation.
     lgpEnvConfigLocalTemperatureUnit 1.3.6.1.4.1.476.1.42.3.4.4.16 integer read-write
The local temperature unit of the system. Enumeration: 'degC': 1, 'degF': 2.
     lgpEnvConfigSleepMode 1.3.6.1.4.1.476.1.42.3.4.4.17 integer read-write
The configured mode of the device's sleep function. If 'enabled', the device will sleep, or not operate, for each 'lgpEnvSleepDay' that is enabled and also during the periods defined in the 'lgpEnvSleepTimeTable' each day. If 'disabled', the device will operate continually and not sleep at all. If 'auto', the device will sleep, or not operate, for each 'lgpEnvSleepDay' that is enabled and also during the periods defined in the 'lgpEnvSleepTimeTable' each day unless the environmental conditions fall outside the desired operation ranges. Enumeration: 'disabled': 2, 'auto': 3, 'enabled': 1.
     lgpEnvConfigHumidityIntegTime 1.3.6.1.4.1.476.1.42.3.4.4.18 integer32 read-write
The value used as the integration factor in the proportional integral derivative (PID) humidity calculation.
     lgpEnvConfigFreecoolingDeltaDegF 1.3.6.1.4.1.476.1.42.3.4.4.19 integer32 read-write
The minimum temperature differential between the control temperature measurement and the coolant required to utilize free-cooling.
     lgpEnvConfigFreecoolingDeltaDegC 1.3.6.1.4.1.476.1.42.3.4.4.20 integer32 read-write
The minimum temperature differential between the control temperature measurement and the coolant required to utilize free-cooling.
     lgpEnvConfigSupplyTempLowLimit 1.3.6.1.4.1.476.1.42.3.4.4.21 integer read-write
The system configuration parameter to enable or disable the supply air low temperature limit. Enumeration: 'disabled': 1, 'enabled': 2.
     lgpEnvConfigSensorEventsStandard 1.3.6.1.4.1.476.1.42.3.4.4.22 integer read-write
The system configuration parameter to enable or disable the standard sensor events. Enumeration: 'disabled': 1, 'enabled': 2.
     lgpEnvConfigSensorEvents1 1.3.6.1.4.1.476.1.42.3.4.4.23 integer read-write
The system configuration parameter to enable or disable sensor 1 events. Enumeration: 'disabled': 1, 'enabled': 2.
     lgpEnvConfigSleepModeDeadbandRange 1.3.6.1.4.1.476.1.42.3.4.4.24 integer read-write
The system configuration parameter to enable or disable the use of the sleep interval dead-band range in the sleep mode temperature calculations and control algorithm. Enumeration: 'disabled': 1, 'enabled': 2.
     lgpEnvConfigAutoConfiguration 1.3.6.1.4.1.476.1.42.3.4.4.25 integer read-write
The system configuration parameter to enable or disable the auto configuration feature. This feature configures temperature and humidity control parameters. Enumeration: 'disabled': 1, 'enabled': 2.
     lgpEnvConfigDeltaGlycolType 1.3.6.1.4.1.476.1.42.3.4.4.26 integer read-write
The system configuration parameter that specifies how the system will determine if there is enough capacity to initiate free cooling. If 'disabled', the system will use the valve temperature to initiate free cooling. If 'contact', a input to the system will initiate free cooling. If 'valve', the system compares the room and glycol temperature differential with the valve temperature to initiate free cooling. If the temperature differential is greater than or equal to the valve temperature, free cooling will be initiated. Enumeration: 'disabled': 1, 'contact': 2, 'value': 3.
     lgpEnvConfigChillWaterControl 1.3.6.1.4.1.476.1.42.3.4.4.27 integer read-write
The system configuration parameter to enable or disable the minimum chill water temperature control. Enumeration: 'disabled': 1, 'enabled': 2.
     lgpEnvConfigInfaredFlushRate 1.3.6.1.4.1.476.1.42.3.4.4.28 unsigned32 read-write
The Infrared humidifier pan overfill rate. This parameter configures the amount of water that flows into the humidifier pan when the 'humidifier is in operation.
     lgpEnvConfigHumidityControl 1.3.6.1.4.1.476.1.42.3.4.4.29 integer read-write
The present configured state of the automatic humidity compensation algorithm. Enumeration: 'relative': 1, 'predictive': 3, 'compensated': 2.
     lgpEnvConfigCompressorLockout 1.3.6.1.4.1.476.1.42.3.4.4.30 integer read-write
The system as locked out the compressor(s). If locked-out, the compressor(s) will not operate even if the controller calls for their operation. Enumeration: 'notLockedOut': 2, 'lockedOut': 1.
     lgpEnvConfigReheatAndHumidifierLockout 1.3.6.1.4.1.476.1.42.3.4.4.31 integer read-write
The system as locked out the compressor(s). If locked-out, the electrical reheats and humidifier will not operate even if the controller calls for their operation. Enumeration: 'notLockedOut': 2, 'lockedOut': 1.
     lgpEnvOperationalTimeTable 1.3.6.1.4.1.476.1.42.3.4.4.32 no-access
A list of environmental operational time ranges for a given environmental unit. The entries in this table may be duplicated from values in the 'lgpEnvStatistics' group. This table contains zero, one, or many rows, depending upon the number of 'lgpEnvOperationTimePoint' and 'lgpEnvOperationTimeSubID' available in the table. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device.
           lgpEnvOperationalTimeEntry 1.3.6.1.4.1.476.1.42.3.4.4.32.1 no-access
This entry defines the contents of the columns for the table 'lgpEnvOperationalTimeTable'.
               lgpEnvOperationTimeIndex 1.3.6.1.4.1.476.1.42.3.4.4.32.1.1 unsigned32 no-access
This is the index indicating the nth element of the table.
               lgpEnvOperationTimePoint 1.3.6.1.4.1.476.1.42.3.4.4.32.1.2 object identifier read-only
An OID representing a well known operation point. These object identifiers can indicate a point, location, or mode of an operation for which a measurement is recorded. The OID's name usually implies a location of the measurement point such as 'fan', 'compressor', etc.
               lgpEnvOperationTimeSubID 1.3.6.1.4.1.476.1.42.3.4.4.32.1.3 integer32 read-only
This is a sub identifier for the 'lgpEnvOperationPoint'. It indicates the instance number of the well known operation point. For example, a system could have two fans installed. This variable would identify fan 1 with a lgpEnvOperationSubID equal to 1 and fan 2 with a lgpEnvOperationSubID equal to 2.
               lgpEnvOperationTimeUnit 1.3.6.1.4.1.476.1.42.3.4.4.32.1.4 object identifier read-only
An OID representing a well known operation time unit type. These object identifiers indicate the units of the operation time. The OID's name usually implies a measurement type such as 'lgpEnvHours', etc.
               lgpEnvOperationTimeValue 1.3.6.1.4.1.476.1.42.3.4.4.32.1.5 integer32 read-write
The actual operation time value of the 'lgpEnvOperationTimePoint'. If multiple operation times are available for a 'lgpEnvOperationTimePoint' the 'lgpEnvOperationTimeSubID' will differentiate between them.
               lgpEnvOperationTimeHighWarning 1.3.6.1.4.1.476.1.42.3.4.4.32.1.6 integer32 read-write
The high warning time of the operation designated by the 'lgpEnvOperationTimePoint'. If operation times are available at a single 'lgpEnvOperationTimePoint' the 'lgpEnvOperationTimeSubID' will differentiate between them.
     lgpEnvConfigTempControlAlgorithm 1.3.6.1.4.1.476.1.42.3.4.4.33 integer read-write
Selects the algorithm for controlling temperature. Enumeration: 'intelligent': 3, 'pi': 1, 'pid': 2, 'proportional': 4.
     lgpEnvConfigFanSpeedMode 1.3.6.1.4.1.476.1.42.3.4.4.34 integer read-write
Changes the function of the fan speed output. If auto, then the fan speed is modulated. If manual, the fan speed output follows lgpEnvConfigFanSpeedCapacity. Enumeration: 'auto': 2, 'manual': 1.
     lgpEnvConfigFanSpeedCapacity 1.3.6.1.4.1.476.1.42.3.4.4.35 unsigned32 read-write
Sets the fan speed output if lgpEnvConfigFanSpeedMode is set to 'manual'. Typical values range from 0 to 100% (actual valid ranges may differ from unit to unit).
     lgpEnvConfigBmsResetTimer 1.3.6.1.4.1.476.1.42.3.4.4.36 unsigned32 read-write
The current count-down time for a BMS to continue controlling the fan speed. If this value reaches 0, then the condition lgpConditionBmsResetTimerExpired will be generated. If a BMS wants to continue controlling the fan speed, it must reset this timer. Typical values range from 0 to 120 minutes (actual valid ranges may differ from unit to unit).
     lgpEnvConfigDisableSensorOffsetDegC 1.3.6.1.4.1.476.1.42.3.4.4.37 integer32 read-write
If any of the enclosure temperature sensors (lgpEnvEnclosureTemperatureSensors) are outside the average reading by this amount, that sensor's readings will not be used.
     lgpEnvConfigDisableSensorOffsetDegF 1.3.6.1.4.1.476.1.42.3.4.4.38 integer32 read-write
If any of the enclosure temperature sensors (lgpEnvEnclosureTemperatureSensors) are outside the average reading by this amount, that sensor's readings will not be used.
     lgpEnvConfigCabinetSensorAlarms 1.3.6.1.4.1.476.1.42.3.4.4.39 integer read-write
Enable or Disable Cabinet Sensor Alarms. Enumeration: 'disabled': 0, 'enabled': 1.
     lgpEnvConfigAirTemperatureControlSensor 1.3.6.1.4.1.476.1.42.3.4.4.42 integer read-write
Sensor from which air temperature measurements will be used for cooling and heating control. Enumeration: 'return': 3, 'remote': 2, 'supply': 1.
     lgpEnvConfigFanSpeedControlSensor 1.3.6.1.4.1.476.1.42.3.4.4.43 integer read-write
Sensor from which air temperature measurements will be used for fan speed control. Enumeration: 'return': 3, 'remote': 2, 'supply': 1.
     lgpEnvConfigMinFanSpeed 1.3.6.1.4.1.476.1.42.3.4.4.44 unsigned32 read-write
Sets the minimum fan speed output if lgpEnvConfigFanSpeedMode is set to 'Auto'.
     lgpEnvConfigMaxFanSpeed 1.3.6.1.4.1.476.1.42.3.4.4.45 unsigned32 read-write
Sets the maximum fan speed output if lgpEnvConfigFanSpeedMode is set to 'Auto'.
     lgpEnvConfigFanSpeedPropBandDegC 1.3.6.1.4.1.476.1.42.3.4.4.46 integer32 read-write
Temperature control band above the temperature set point calculated for proportional fan speed control. If measured air temperature is within this band, fan speed operations are proportionally controlled.
     lgpEnvConfigFanSpeedPropBandDegF 1.3.6.1.4.1.476.1.42.3.4.4.47 integer32 read-write
Temperature control band above the temperature set point calculated for proportional fan speed control. If measured air temperature is within this band, fan speed operations are proportionally controlled.
 lgpEnvControl 1.3.6.1.4.1.476.1.42.3.4.5
This sub-tree is used to register Liebert environmental control object identifiers.
     lgpEnvControlShutdownAfterDelay 1.3.6.1.4.1.476.1.42.3.4.5.1 integer32 read-write
Setting this object will shutdown (i.e., turn off) the system after the indicated number of seconds. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. When read, lgpEnvControlShutdownAfterDelay will return the number of seconds remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any lgpEnvControlShutdownAfterDelay already in effect.
     lgpEnvControlStartupAfterDelay 1.3.6.1.4.1.476.1.42.3.4.5.2 integer32 read-write
Setting this object will start the system after the indicated number of seconds. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. If the system is already on at the time the countdown reaches 0, then nothing will happen. Sets to this object override the effect of any lgpEnvControlStartupAfterDelay countdown in progress. When read, lgpEnvControlStartupAfterDelay will return the number of seconds until startup, or -1 if no startup countdown is in effect. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted.
     lgpEnvSleepIntervalTimeTable 1.3.6.1.4.1.476.1.42.3.4.5.3 no-access
A sleep time interval table containing a list of the start and stop times to be used to take a device online or offline. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device.
         lgpEnvSleepIntervalTimeEntry 1.3.6.1.4.1.476.1.42.3.4.5.3.1 no-access
This entry defines the contents of the columns for the table 'lgpEnvSleepIntervalTimeTable'.
             lgpEnvSleepTimeIndex 1.3.6.1.4.1.476.1.42.3.4.5.3.1.1 unsigned32 no-access
This is the index indicating the row of the table 'lgpEnvSleepIntervalTimeTable'.
             lgpEnvSleepTimeSubID 1.3.6.1.4.1.476.1.42.3.4.5.3.1.2 integer32 read-only
This is a sub identifier for each 'lgpEnvSleepIntervalTimeEntry'. It indicates the instance number of the 'lgpEnvSleepIntervalTimeEntry'. For example, a system could have two sleep intervals and the first interval's sub ID would be 1 and the second interval's sub ID would be 2.
             lgpEnvSleepTimeStartHour 1.3.6.1.4.1.476.1.42.3.4.5.3.1.3 integer32 read-write
This is the hours digit of the time when the system will be put online.
             lgpEnvSleepTimeStartMinute 1.3.6.1.4.1.476.1.42.3.4.5.3.1.4 integer32 read-write
This is the minutes digit of the time when the system will be put online.
             lgpEnvSleepTimeStopHour 1.3.6.1.4.1.476.1.42.3.4.5.3.1.5 integer32 read-write
This is the hours digit containing the time when the system will be taken offline.
             lgpEnvSleepTimeStopMinute 1.3.6.1.4.1.476.1.42.3.4.5.3.1.6 integer32 read-write
This is the minutes digit containing the time when the system will be taken offline.
     lgpEnvSleepDayTable 1.3.6.1.4.1.476.1.42.3.4.5.4 no-access
A sleep table containing a list of the days of the week the system will be offline. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device.
         lgpEnvSleepDayEntry 1.3.6.1.4.1.476.1.42.3.4.5.4.1 no-access
This entry defines the contents of the columns for the table 'lgpEnvSleepDayTable'.
             lgpEnvSleepDayIndex 1.3.6.1.4.1.476.1.42.3.4.5.4.1.1 unsigned32 no-access
This is the index indicating the row of the table 'lgpEnvSleepDayTable'.
             lgpEnvSleepDay 1.3.6.1.4.1.476.1.42.3.4.5.4.1.2 integer read-only
This is a sub identifier for the day of the week within 'lgpEnvSleepDayTable'. Enumeration: 'monday': 2, 'tuesday': 3, 'friday': 6, 'wednesday': 4, 'thursday': 5, 'sunday': 1, 'saturday': 7.
             lgpEnvSleepAllDayEnabled 1.3.6.1.4.1.476.1.42.3.4.5.4.1.3 integer read-write
The all day sleep functionality has been enabled for the corresponding 'lgpEnvSleepDay' in the 'lgpEnvSleepDayTable'. Enumeration: 'yes': 1, 'no': 2.
 lgpEnvStatistics 1.3.6.1.4.1.476.1.42.3.4.6
This sub-tree is used to register Liebert environmental statistic object identifiers.
     lgpEnvStatisticsComp1RunHr 1.3.6.1.4.1.476.1.42.3.4.6.1 unsigned32 read-only
Accumulated run hours of compressor 1. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
     lgpEnvStatisticsComp2RunHr 1.3.6.1.4.1.476.1.42.3.4.6.2 unsigned32 read-only
Accumulated run hours of compressor 2. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
     lgpEnvStatisticsFanRunHr 1.3.6.1.4.1.476.1.42.3.4.6.3 unsigned32 read-only
Accumulated run hours of the main fan. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
     lgpEnvStatisticsHumRunHr 1.3.6.1.4.1.476.1.42.3.4.6.4 unsigned32 read-only
Accumulated run hours of the humidifier. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
     lgpEnvStatisticsReheat1RunHr 1.3.6.1.4.1.476.1.42.3.4.6.7 unsigned32 read-only
Accumulated run hours of reheat element 1. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
     lgpEnvStatisticsReheat2RunHr 1.3.6.1.4.1.476.1.42.3.4.6.8 unsigned32 read-only
Accumulated run hours of reheat element 2. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
     lgpEnvStatisticsReheat3RunHr 1.3.6.1.4.1.476.1.42.3.4.6.9 unsigned32 read-only
Accumulated run hours of reheat element 3. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
     lgpEnvStatisticsCoolingModeHrs 1.3.6.1.4.1.476.1.42.3.4.6.10 unsigned32 read-only
Accumulated run hours while lgpEnvStateCooling is on(1). This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
     lgpEnvStatisticsHeatingModeHrs 1.3.6.1.4.1.476.1.42.3.4.6.11 unsigned32 read-only
Accumulated run hours while lgpEnvStateHeating is on(1). This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
     lgpEnvStatisticsHumidifyModeHrs 1.3.6.1.4.1.476.1.42.3.4.6.12 unsigned32 read-only
Accumulated run hours of the humidifying process of the system. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
     lgpEnvStatisticsDehumidifyModeHrs 1.3.6.1.4.1.476.1.42.3.4.6.13 unsigned32 read-only
Accumulated run hours of the dehumidifying process of the system. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
     lgpEnvStatisticsHotGasRunHr 1.3.6.1.4.1.476.1.42.3.4.6.14 unsigned32 read-only
Accumulated run hours of the hot gas system. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
     lgpEnvStatisticsHotWaterRunHr 1.3.6.1.4.1.476.1.42.3.4.6.15 unsigned32 read-only
Accumulated run hours of the hot water system. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
     lgpEnvStatisticsFreeCoolRunHr 1.3.6.1.4.1.476.1.42.3.4.6.16 unsigned32 read-only
Accumulated run hours of the free cooling process. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
     lgpEnvStatisticsComp3RunHr 1.3.6.1.4.1.476.1.42.3.4.6.17 unsigned32 read-only
Accumulated run hours of compressor 3.
     lgpEnvStatisticsComp4RunHr 1.3.6.1.4.1.476.1.42.3.4.6.18 unsigned32 read-only
Accumulated run hours of compressor 4.
 lgpEnvPoints 1.3.6.1.4.1.476.1.42.3.4.7
This sub-tree is used to register Liebert environmental point object identifiers.
     lgpEnvWellKnownPoints 1.3.6.1.4.1.476.1.42.3.4.7.1
This sub-tree registers well known Liebert Environmental Points. The object identifier names usually encompass a process, or location, where measurements are recorded or where values are applied.
         lgpEnvFanPoint 1.3.6.1.4.1.476.1.42.3.4.7.1.1
This identifier represents a well known fan measurement point.
         lgpEnvCompressorPoint 1.3.6.1.4.1.476.1.42.3.4.7.1.2
This identifier represents a well known compressor measurement point.
         lgpEnvElectricHeaterPoint 1.3.6.1.4.1.476.1.42.3.4.7.1.3
This identifier represents a well known electric heater measurement point.
         lgpEnvChilledWaterPoint 1.3.6.1.4.1.476.1.42.3.4.7.1.4
This identifier represents a well known chilled water measurement point.
         lgpEnvHumidifierPoint 1.3.6.1.4.1.476.1.42.3.4.7.1.5
This identifier represents a well known humidifier measurement point.
         lgpEnvDehumidifierPoint 1.3.6.1.4.1.476.1.42.3.4.7.1.6
This identifier represents a well known dehumidifier measurement point.
         lgpEnvFreeCoolingPoint 1.3.6.1.4.1.476.1.42.3.4.7.1.7
This identifier represents a well known free-cooling measurement process.
         lgpEnvHotWaterPoint 1.3.6.1.4.1.476.1.42.3.4.7.1.8
This identifier represents a well known hot water measurement point.
         lgpEnvHotGasPoint 1.3.6.1.4.1.476.1.42.3.4.7.1.9
This identifier represents a well known hot gas measurement point.
         lgpEnvBatteryCabinetPoint 1.3.6.1.4.1.476.1.42.3.4.7.1.10
This identifier represents a well known cabinet point. To determine the cabinet being described in a multi-cabinet system, this point implements two additional indexes. The first index describes the module being supplied with battery power. The second index identifies the number of the battery cabinet, which is typically a sequential number. Example: lgpPwrMeasBatteryCabinet.2.4 'lgpEnvBatteryCabinetPoint' = Point is a battery cabinet. '.2' = Cabinet is in the second module. '.4' = Cabinet number 4
         lgpEnvPumpPoints 1.3.6.1.4.1.476.1.42.3.4.7.1.11
This sub-tree identifies well-known pumps in the system.
               lgpEnvPump1Point 1.3.6.1.4.1.476.1.42.3.4.7.1.11.1
This identifier represents pump 1.
               lgpEnvPump2Point 1.3.6.1.4.1.476.1.42.3.4.7.1.11.2
This identifier represents pump 2.
         lgpEnvCompressorPoints 1.3.6.1.4.1.476.1.42.3.4.7.1.12
This sub-tree identifies well-known compressors in the system.
               lgpEnvCompressor1Point 1.3.6.1.4.1.476.1.42.3.4.7.1.12.1
This identifier represents compressor 1.
                   lgpEnvCompressor1APoint 1.3.6.1.4.1.476.1.42.3.4.7.1.12.1.1
This identifier represents compressor 1A.
                   lgpEnvCompressor1BPoint 1.3.6.1.4.1.476.1.42.3.4.7.1.12.1.2
This identifier represents compressor 1B.
               lgpEnvCompressor2Point 1.3.6.1.4.1.476.1.42.3.4.7.1.12.2
This identifier represents compressor 2.
                   lgpEnvCompressor2APoint 1.3.6.1.4.1.476.1.42.3.4.7.1.12.2.1
This identifier represents compressor 2A.
                   lgpEnvCompressor2BPoint 1.3.6.1.4.1.476.1.42.3.4.7.1.12.2.2
This identifier represents compressor 2B.
         lgpEnvValvePoints 1.3.6.1.4.1.476.1.42.3.4.7.1.13
This sub-tree identifies well-known valves in the system.
               lgpEnvHotGasValve1Point 1.3.6.1.4.1.476.1.42.3.4.7.1.13.1
This identifier represents hot gas valve 1.
               lgpEnvHotGasValve2Point 1.3.6.1.4.1.476.1.42.3.4.7.1.13.2
This identifier represents hot gas valve 2.
         lgpEnvRemoteSensorStatisticPoints 1.3.6.1.4.1.476.1.42.3.4.7.1.14
This sub-tree identifies well-known remote sensor statistics in the system.
               lgpEnvRemoteSensorMinimumPoint 1.3.6.1.4.1.476.1.42.3.4.7.1.14.1
This identifier represents the minimum value for remote sensor readings.
               lgpEnvRemoteSensorMaximumPoint 1.3.6.1.4.1.476.1.42.3.4.7.1.14.2
This identifier represents the maximum value for remote sensor readings.
               lgpEnvRemoteSensorAveragePoint 1.3.6.1.4.1.476.1.42.3.4.7.1.14.3
This identifier represents the average value for remote sensor readings.
 lgpEnvUnits 1.3.6.1.4.1.476.1.42.3.4.8
This sub-tree is used to register Liebert environmental unit object identifiers.
     lgpEnvWellKnownUnits 1.3.6.1.4.1.476.1.42.3.4.8.1
This sub-tree registers well known Liebert Environmental Units. The object identifier names usually encompass a process, or location, where measurements are recorded or where values are applied.
         lgpEnvHours 1.3.6.1.4.1.476.1.42.3.4.8.1.1
This identifier represents well known time unit of hours.
 lgpEnvRemoteSensors 1.3.6.1.4.1.476.1.42.3.4.9
This sub-tree is used to register Liebert environmental remote sensor object identifiers.
     lgpEnvRemoteSensorCalc 1.3.6.1.4.1.476.1.42.3.4.9.1 integer read-write
Calculation method applied to temperature readings from the remote sensors to determine a single temperature measurement value for cooling and heating control. Enumeration: 'average': 1, 'maximum': 2.
     lgpEnvRemoteSensorTable 1.3.6.1.4.1.476.1.42.3.4.9.10 no-access
This table contains a list of remote sensors attached to the environmental unit. The table contains zero, one, or more rows, depending upon the number of sensors attached to the unit.
           lgpEnvRemoteSensorEntry 1.3.6.1.4.1.476.1.42.3.4.9.10.1 no-access
This entry defines the attributes to be populated in the various columns of the 'lgpEnvRemoteSensorTable'.
               lgpEnvRemoteSensorIndex 1.3.6.1.4.1.476.1.42.3.4.9.10.1.1 unsigned32 no-access
This is the index indicating the nth element of the table.
               lgpEnvRemoteSensorId 1.3.6.1.4.1.476.1.42.3.4.9.10.1.2 unsigned32 read-only
This is the sensor number identifying the sensor.
               lgpEnvRemoteSensorMode 1.3.6.1.4.1.476.1.42.3.4.9.10.1.3 integer read-write
Function assigned to remote sensor. When set to control(2) the sensor will be used in calculation of remote sensor temperature which may be used for heating and cooling control. When set to disable(0) the remote sensor reading is not available. When set to reference(1) the remote sensor reading is available but not used for control. Enumeration: 'control': 2, 'disable': 0, 'reference': 1.
               lgpEnvRemoteSensorUsrLabel 1.3.6.1.4.1.476.1.42.3.4.9.10.1.4 displaystring read-write
User assigned remote sensor label.
               lgpEnvRemoteSensorTempMeasurementDegF 1.3.6.1.4.1.476.1.42.3.4.9.10.1.5 integer32 read-only
Temperature measured at the temperature sensor reported in degrees Fahrenheit.
               lgpEnvRemoteSensorTempMeasurementDegC 1.3.6.1.4.1.476.1.42.3.4.9.10.1.6 integer32 read-only
Temperature measured at the temperature sensor reported in degrees Celsius.