ICT-SINE-WAVE-INVERTER-MIB: View SNMP OID List / Download MIB

VENDOR: INNOVATIVE CIRCUIT TECHNOLOGY


 Home MIB: ICT-SINE-WAVE-INVERTER-MIB
Download as:   

Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 ictPower 1.3.6.1.4.1.39145
             inverter 1.3.6.1.4.1.39145.12
                   deviceModel 1.3.6.1.4.1.39145.12.1 displaystring read-only
Model Number
                   deviceName 1.3.6.1.4.1.39145.12.2 displaystring read-only
Site Name
                   deviceHardware 1.3.6.1.4.1.39145.12.3 integer read-only
Hardware Version
                   deviceFirmware 1.3.6.1.4.1.39145.12.4 displaystring read-only
Firmware Version
                   deviceMacAddress 1.3.6.1.4.1.39145.12.5 displaystring read-only
MAC Address
                   batteryVoltage 1.3.6.1.4.1.39145.12.6 displaystring read-only
Battery Voltage (VDC)
                   inverterVoltage 1.3.6.1.4.1.39145.12.7 displaystring read-only
Inverter Output Voltage (VAC)
                   inverterPower 1.3.6.1.4.1.39145.12.8 displaystring read-only
Inverter Output Power (%)
                   inverterStatus 1.3.6.1.4.1.39145.12.9 integer read-only
Inverter Output Status ('1' indicates the Inverter Output is ENABLED, and '2' indicates the Inverter Output is DISABLED) Enumeration: 'disabled': 2, 'enabled': 1.
                   inverterControl 1.3.6.1.4.1.39145.12.10 integer read-write
Inverter Output Control (set to '1' to ENABLE the Inverter Output if no alarms are active, set to '2' to DISABLE the Inverter Output) Enumeration: 'disabled': 2, 'enabled': 1.
                   transferRelayStatus 1.3.6.1.4.1.39145.12.11 integer read-only
Transfer Relay Status ('1' indicates the Output is connected to the INVERTER, and '2' indicates the Output is connected to the GRID) Enumeration: 'inverter': 1, 'grid': 2.
                     undervoltageAlarmTrap 1.3.6.1.4.1.39145.120.101
Trap generated when the Battery Input Undervoltage Alarm is triggered
                     overvoltageAlarmTrap 1.3.6.1.4.1.39145.120.102
Trap generated when the Battery Input Overvoltage Alarm is triggered
                     overtemperatureAlarmTrap 1.3.6.1.4.1.39145.120.103
Trap generated when the Overtemperature Alarm is triggered
                     outputFaultAlarmTrap 1.3.6.1.4.1.39145.120.104
Trap generated when the Inverter Output Fault Alarm is triggered
                     systemFaultAlarmTrap 1.3.6.1.4.1.39145.120.105
Trap generated when the System Fault Alarm is triggered
                     remoteSwitchAlarmTrap 1.3.6.1.4.1.39145.120.106
Trap generated when the Remote Switch accessory is activated
                     undervoltageAlarmClear 1.3.6.1.4.1.39145.120.111
Trap generated when the Battery Input Undervoltage Alarm is cleared
                     overvoltageAlarmClear 1.3.6.1.4.1.39145.120.112
Trap generated when the Battery Input Overvoltage Alarm is cleared
                     overtemperatureAlarmClear 1.3.6.1.4.1.39145.120.113
Trap generated when the Overtemperature Alarm is cleared
                     outputFaultAlarmClear 1.3.6.1.4.1.39145.120.114
Trap generated when the Inverter Output Fault Alarm is cleared
                     systemFaultAlarmClear 1.3.6.1.4.1.39145.120.115
Trap generated when the System Fault Alarm is cleared
                     remoteSwitchAlarmClear 1.3.6.1.4.1.39145.120.116
Trap generated when the Remote Switch accessory is deactivated
                     inverterPowerTrap 1.3.6.1.4.1.39145.120.121
Trap generated when the Output switches to Inverter (Battery) Power
                     gridPowerTrap 1.3.6.1.4.1.39145.120.122
Trap generated when the Output switches to Grid Power