ICT-MODULAR-POWER-SYSTEM-MIB: View SNMP OID List / Download MIB
VENDOR: INNOVATIVE CIRCUIT TECHNOLOGY
Home | MIB: ICT-MODULAR-POWER-SYSTEM-MIB | |||
---|---|---|---|---|
Download as: |
Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
|
|||
Object Name | OID | Type | Access | Info |
ictPower | 1.3.6.1.4.1.39145 | |||
powerSystem | 1.3.6.1.4.1.39145.13 | |||
deviceModel | 1.3.6.1.4.1.39145.13.1 | displaystring | read-only |
Model Number |
deviceName | 1.3.6.1.4.1.39145.13.2 | displaystring | read-only |
Device Name |
deviceHardware | 1.3.6.1.4.1.39145.13.3 | integer | read-only |
Hardware Version |
deviceFirmware | 1.3.6.1.4.1.39145.13.4 | displaystring | read-only |
Firmware Version |
deviceMacAddress | 1.3.6.1.4.1.39145.13.5 | displaystring | read-only |
MAC Address |
inputVoltage | 1.3.6.1.4.1.39145.13.6 | displaystring | read-only |
Input Voltage (VAC) |
outputVoltage | 1.3.6.1.4.1.39145.13.7 | displaystring | read-only |
Output Voltage (VDC) |
outputCurrent | 1.3.6.1.4.1.39145.13.8 | displaystring | read-only |
Total System Current (Amps) |
outputEnable | 1.3.6.1.4.1.39145.13.9 | integer | read-write |
Output Enable Status (a value of '1' indicates Output is Enabled, and a value of '2' indicates Output is Disabled. Output cannot be disabled during an AC Failure) Enumeration: 'disabled': 2, 'enabled': 1. |
moduleTable | 1.3.6.1.4.1.39145.13.10 | no-access |
Module Table |
|
1.3.6.1.4.1.39145.13.10.1 | no-access | |||
moduleNumber | 1.3.6.1.4.1.39145.13.10.1.1 | integer | read-only |
Module Number |
moduleStatus | 1.3.6.1.4.1.39145.13.10.1.2 | integer | read-only |
Module Status Enumeration: 'alarm': 3, 'notInstalled': 1, 'ok': 2. |
moduleType | 1.3.6.1.4.1.39145.13.10.1.3 | integer | read-only |
Module Type ('1' indicates Module is NOT INSTALLED,'2' indicates POWER Module,'3' indicates BATTERY Module, and '4' indicates DISTRIBUTION Module) Enumeration: 'battery': 3, 'distribution': 4, 'notInstalled': 1, 'power': 2. |
moduleVoltage | 1.3.6.1.4.1.39145.13.10.1.4 | displaystring | read-only |
Module Voltage (VDC) |
moduleCurrentA | 1.3.6.1.4.1.39145.13.10.1.5 | displaystring | read-only |
Channel 1 Current (Amps) |
moduleCurrentB | 1.3.6.1.4.1.39145.13.10.1.6 | displaystring | read-only |
Channel 2 Current (Amps) |
moduleCurrentC | 1.3.6.1.4.1.39145.13.10.1.7 | displaystring | read-only |
Channel 3 Current (Amps) |
moduleCurrentD | 1.3.6.1.4.1.39145.13.10.1.8 | displaystring | read-only |
Channel 4 Current (Amps) |
moduleControlA | 1.3.6.1.4.1.39145.13.10.1.9 | integer | read-write |
Channel 1 Control (a value of '1' indicates Channel is Enabled, and a value of '2' indicates Channel is Disabled) Enumeration: 'disabled': 2, 'enabled': 1. |
moduleControlB | 1.3.6.1.4.1.39145.13.10.1.10 | integer | read-write |
Channel 2 Control (a value of '1' indicates Channel is Enabled, and a value of '2' indicates Channel is Disabled) Enumeration: 'disabled': 2, 'enabled': 1. |
moduleControlC | 1.3.6.1.4.1.39145.13.10.1.11 | integer | read-write |
Channel 3 Control (a value of '1' indicates Channel is Enabled, and a value of '2' indicates Channel is Disabled) Enumeration: 'disabled': 2, 'enabled': 1. |
moduleControlD | 1.3.6.1.4.1.39145.13.10.1.12 | integer | read-write |
Channel 4 Control (a value of '1' indicates Channel is Enabled, and a value of '2' indicates Channel is Disabled) Enumeration: 'disabled': 2, 'enabled': 1. |
alarmTable | 1.3.6.1.4.1.39145.13.11 | no-access |
Alarm Input Table |
|
1.3.6.1.4.1.39145.13.11.1 | no-access | |||
alarmNumber | 1.3.6.1.4.1.39145.13.11.1.1 | integer | read-only |
Alarm Input Number |
alarmName | 1.3.6.1.4.1.39145.13.11.1.2 | displaystring | read-only |
Alarm Input Name |
alarmStatus | 1.3.6.1.4.1.39145.13.11.1.3 | integer | read-only |
Alarm Input Status ('1' indicates Alarm is INACTIVE,'2' indicates Alarm is READY, and '3' indicates Alarm is in an ALARM condition) Enumeration: 'ready': 2, 'alarm': 3, 'inactive': 1. |
moduleAlarmTrap | 1.3.6.1.4.1.39145.130.101 |
Trap generated when a Module Alarm is triggered |
||
alarmInputTrap | 1.3.6.1.4.1.39145.130.102 |
Trap generated when an Alarm Input is activated |
||
acFailAlarmTrap | 1.3.6.1.4.1.39145.130.103 |
Trap generated when the AC Failure Alarm is triggered |
||
sysCurrentLimitTrap | 1.3.6.1.4.1.39145.130.104 |
Trap generated when the System Current Limit Alarm is triggered |
||
moduleAlarmClear | 1.3.6.1.4.1.39145.130.111 |
Trap generated when a Module Alarm is cleared |
||
alarmInputClear | 1.3.6.1.4.1.39145.130.112 |
Trap generated when an Alarm Input is cleared |
||
acFailAlarmClear | 1.3.6.1.4.1.39145.130.113 |
Trap generated when the AC Failure Alarm is cleared |
||
sysCurrentLimitClear | 1.3.6.1.4.1.39145.130.114 |
Trap generated when the System Current Limit Alarm is cleared |
||
batteryTestStart | 1.3.6.1.4.1.39145.130.121 |
Trap generated when a Battery Discharge Test is started |
||
batteryTestComplete | 1.3.6.1.4.1.39145.130.122 |
Trap generated when a Battery Discharge Test completes successfully |
||
batteryTestFail | 1.3.6.1.4.1.39145.130.123 |
Trap generated when a Battery Discharge Test fails |
||
batteryEqualiseStart | 1.3.6.1.4.1.39145.130.124 |
Trap generated when a Battery Equalise Charge is started |
||
batteryEqualiseComplete | 1.3.6.1.4.1.39145.130.125 |
Trap generated when a Battery Equalise Charge completes |