Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 gudeads 1.3.6.1.4.1.28507
             gadsPDU8310 1.3.6.1.4.1.28507.27
                   events 1.3.6.1.4.1.28507.27.0
                       pdu8310AmperageEvt1 1.3.6.1.4.1.28507.27.0.1
Event is triggered when a measured current is crossing the entered limits
                   pdu8310Objects 1.3.6.1.4.1.28507.27.1
                       pdu8310CommonConfig 1.3.6.1.4.1.28507.27.1.1
                           pdu8310SNMPaccess 1.3.6.1.4.1.28507.27.1.1.1
                               pdu8310TrapCtrl 1.3.6.1.4.1.28507.27.1.1.1.1 integer32 read-write
0 = off 1 = Ver. 1 2 = Ver. 2c
                               pdu8310TrapIPTable 1.3.6.1.4.1.28507.27.1.1.1.2 no-access
list of all Trap receiver
                                   pdu8310TrapIPEntry 1.3.6.1.4.1.28507.27.1.1.1.2.1 no-access
an entry containing management informations regarding the list of trap receivers
                                       pdu8310TrapIPIndex 1.3.6.1.4.1.28507.27.1.1.1.2.1.1 integer32 no-access
A unique value, greater than zero, for each receiver slot.
                                       pdu8310TrapAddr 1.3.6.1.4.1.28507.27.1.1.1.2.1.2 octet string read-write
DNS name or IP address specifying one Trap receiver slot. A port can optionally be specified: 'name:port' An empty string disables this slot.
                       pdu8310DeviceConfig 1.3.6.1.4.1.28507.27.1.2
                       pdu8310IntActors 1.3.6.1.4.1.28507.27.1.3
                       pdu8310ExtActors 1.3.6.1.4.1.28507.27.1.4
                       pdu8310IntSensors 1.3.6.1.4.1.28507.27.1.5
                           pdu8310PowerChan 1.3.6.1.4.1.28507.27.1.5.1
                               pdu8310ActivePowerChan 1.3.6.1.4.1.28507.27.1.5.1.1 unsigned32 read-only
Number of suppported Power Channels.
                               pdu8310PowerTable 1.3.6.1.4.1.28507.27.1.5.1.2 no-access
All available Channel Interfaces.
                                   pdu8310PowerEntry 1.3.6.1.4.1.28507.27.1.5.1.2.1 no-access
An entry containing management information applicable to a particular Power Channel.
                                       pdu8310PowerIndex 1.3.6.1.4.1.28507.27.1.5.1.2.1.1 integer32 no-access
Index of Power Channel entries
                                       pdu8310ChanStatus 1.3.6.1.4.1.28507.27.1.5.1.2.1.2 integer32 read-only
0 = data not active, 1 = data valid
                                       pdu8310EnergyActive 1.3.6.1.4.1.28507.27.1.5.1.2.1.3 unsigned32 read-only
Total accumulated Active Energy of Power Channel.
                                       pdu8310PowerActive 1.3.6.1.4.1.28507.27.1.5.1.2.1.4 unsigned32 read-only
Active Power
                                       pdu8310Current 1.3.6.1.4.1.28507.27.1.5.1.2.1.5 unsigned32 read-only
Actual Curent on Power Channel.
                                       pdu8310Voltage 1.3.6.1.4.1.28507.27.1.5.1.2.1.6 unsigned32 read-only
Actual Voltage on Power Channel
                                       pdu8310Frequency 1.3.6.1.4.1.28507.27.1.5.1.2.1.7 unsigned32 read-only
Freqency of Power Channel
                                       pdu8310PowerFactor 1.3.6.1.4.1.28507.27.1.5.1.2.1.8 integer32 read-only
Power Factor of Channel between -1.0 and 1.00
                                       pdu8310Pangle 1.3.6.1.4.1.28507.27.1.5.1.2.1.9 integer32 read-only
Phase Angle between Voltage and L Line Current between -180.0 and 180.0
                                       pdu8310PowerApparent 1.3.6.1.4.1.28507.27.1.5.1.2.1.10 unsigned32 read-only
L Line Mean Apparent Power
                                       pdu8310PowerReactive 1.3.6.1.4.1.28507.27.1.5.1.2.1.11 unsigned32 read-only
L Line Mean Reactive Power
                                       pdu8310EnergyReactive 1.3.6.1.4.1.28507.27.1.5.1.2.1.12 unsigned32 read-only
Total accumulated Reactive Energy of Power Channel.
                                       pdu8310EnergyActiveResettable 1.3.6.1.4.1.28507.27.1.5.1.2.1.13 unsigned32 read-only
Resettable accumulated Active Energy of Power Channel.
                                       pdu8310EnergyReactiveResettable 1.3.6.1.4.1.28507.27.1.5.1.2.1.14 unsigned32 read-only
Resettable accumulated Reactive Energy of Power Channel.
                                       pdu8310ResetTime 1.3.6.1.4.1.28507.27.1.5.1.2.1.15 unsigned32 read-only
Time in seconds since last Energy Counter reset.
                       pdu8310ExtSensors 1.3.6.1.4.1.28507.27.1.6
                   pdu8310Conf 1.3.6.1.4.1.28507.27.2
                       pdu8310Groups 1.3.6.1.4.1.28507.27.2.1
                           pdu8310BasicGroup 1.3.6.1.4.1.28507.27.2.1.1
Basic objects.
                           pdu8310NotificationGroup 1.3.6.1.4.1.28507.27.2.1.2
                       pdu8310Compls 1.3.6.1.4.1.28507.27.2.2