GUDEADS-PDU8110-MIB: View SNMP OID List / Download MIB
VENDOR: GUDE ANALOG- UND DIGITALSYSTEME GMBH
Home | MIB: GUDEADS-PDU8110-MIB | |||
---|---|---|---|---|
Download as: |
Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
|
|||
Object Name | OID | Type | Access | Info |
gudeads | 1.3.6.1.4.1.28507 | |||
gadsPDU8110 | 1.3.6.1.4.1.28507.23 | |||
events | 1.3.6.1.4.1.28507.23.0 | |||
pdu8110TempEvtSen1 | 1.3.6.1.4.1.28507.23.0.1 |
temperature limits exceeded |
||
pdu8110TempEvtSen2 | 1.3.6.1.4.1.28507.23.0.2 |
temperature limits exceeded |
||
pdu8110HygroEvtSen1 | 1.3.6.1.4.1.28507.23.0.3 |
hygro limits exceeded |
||
pdu8110HygroEvtSen2 | 1.3.6.1.4.1.28507.23.0.4 |
hygro limits exceeded |
||
pdu8110Objects | 1.3.6.1.4.1.28507.23.1 | |||
pdu8110CommonConfig | 1.3.6.1.4.1.28507.23.1.1 | |||
pdu8110SNMPaccess | 1.3.6.1.4.1.28507.23.1.1.1 | |||
pdu8110TrapCtrl | 1.3.6.1.4.1.28507.23.1.1.1.1 | integer32 | read-write |
0 = off 1 = Ver. 1 2 = Ver. 2c |
pdu8110TrapIPTable | 1.3.6.1.4.1.28507.23.1.1.1.2 | no-access |
list of all Trap receiver |
|
1.3.6.1.4.1.28507.23.1.1.1.2.1 | no-access |
an entry containing management informations regarding the list of trap receivers |
||
pdu8110TrapIPIndex | 1.3.6.1.4.1.28507.23.1.1.1.2.1.1 | integer32 | no-access |
A unique value, greater than zero, for each receiver slot. |
pdu8110TrapAddr | 1.3.6.1.4.1.28507.23.1.1.1.2.1.2 | octet string | read-write |
DNS name or IP address specifying one Trap receiver slot. A port can optionally be specified: 'name:port' An empty string disables this slot. |
pdu8110DeviceConfig | 1.3.6.1.4.1.28507.23.1.2 | |||
pdu8110IntActors | 1.3.6.1.4.1.28507.23.1.3 | |||
pdu8110ExtActors | 1.3.6.1.4.1.28507.23.1.4 | |||
pdu8110IntSensors | 1.3.6.1.4.1.28507.23.1.5 | |||
pdu8110PowerChan | 1.3.6.1.4.1.28507.23.1.5.1 | |||
pdu8110ActivePowerChan | 1.3.6.1.4.1.28507.23.1.5.1.1 | unsigned32 | read-only |
Number of suppported Power Channels. |
pdu8110PowerTable | 1.3.6.1.4.1.28507.23.1.5.1.2 | no-access |
All available Channel Interfaces. |
|
1.3.6.1.4.1.28507.23.1.5.1.2.1 | no-access |
An entry containing management information applicable to a particular Power Channel. |
||
pdu8110PowerIndex | 1.3.6.1.4.1.28507.23.1.5.1.2.1.1 | integer32 | no-access |
Index of Power Channel entries |
pdu8110ChanStatus | 1.3.6.1.4.1.28507.23.1.5.1.2.1.2 | integer32 | read-only |
0 = data not active, 1 = data valid |
pdu8110Current | 1.3.6.1.4.1.28507.23.1.5.1.2.1.5 | unsigned32 | read-only |
Actual Curent on Power Channel. |
pdu8110ExtSensors | 1.3.6.1.4.1.28507.23.1.6 | |||
pdu8110SensorTable | 1.3.6.1.4.1.28507.23.1.6.1 | no-access | ||
1.3.6.1.4.1.28507.23.1.6.1.1 | no-access | |||
pdu8110SensorIndex | 1.3.6.1.4.1.28507.23.1.6.1.1.1 | integer32 | no-access | |
pdu8110TempSensor | 1.3.6.1.4.1.28507.23.1.6.1.1.2 | integer32 | read-only |
actual temperature, a value of -9999 indicates that data is not available |
pdu8110HygroSensor | 1.3.6.1.4.1.28507.23.1.6.1.1.3 | integer32 | read-only |
actual humidity, a value of -9999 indicates that data is not available |
pdu8110Conf | 1.3.6.1.4.1.28507.23.2 | |||
pdu8110Groups | 1.3.6.1.4.1.28507.23.2.1 | |||
pdu8110BasicGroup | 1.3.6.1.4.1.28507.23.2.1.1 |
Basic objects. |
||
pdu8110NotificationGroup | 1.3.6.1.4.1.28507.23.2.1.2 | |||
pdu8110Compls | 1.3.6.1.4.1.28507.23.2.2 |