GUDEADS-EPC2X6-MIB: View SNMP OID List / Download MIB
VENDOR: GUDE ANALOG- UND DIGITALSYSTEME GMBH
Home | MIB: GUDEADS-EPC2X6-MIB | |||
---|---|---|---|---|
Download as: |
Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
|
|||
Object Name | OID | Type | Access | Info |
gudeads | 1.3.6.1.4.1.28507 | |||
events | 1.3.6.1.4.1.28507.0 | |||
epc2x6witchEvt1 | 1.3.6.1.4.1.28507.0.1 |
Event is triggered when |
||
epc2x6witchEvt2 | 1.3.6.1.4.1.28507.0.2 |
Event is triggered when |
||
epc2x6witchEvt3 | 1.3.6.1.4.1.28507.0.3 |
Event is triggered when |
||
epc2x6witchEvt4 | 1.3.6.1.4.1.28507.0.4 |
Event is triggered when |
||
epc2x6witchEvt5 | 1.3.6.1.4.1.28507.0.5 |
Event is triggered when |
||
epc2x6witchEvt6 | 1.3.6.1.4.1.28507.0.6 |
Event is triggered when |
||
epc2x6witchEvt7 | 1.3.6.1.4.1.28507.0.7 |
Event is triggered when |
||
epc2x6witchEvt8 | 1.3.6.1.4.1.28507.0.8 |
Event is triggered when |
||
epc2x6witchEvt9 | 1.3.6.1.4.1.28507.0.9 |
Event is triggered when |
||
epc2x6witchEvt10 | 1.3.6.1.4.1.28507.0.10 |
Event is triggered when |
||
epc2x6witchEvt11 | 1.3.6.1.4.1.28507.0.11 |
Event is triggered when |
||
epc2x6witchEvt12 | 1.3.6.1.4.1.28507.0.12 |
Event is triggered when |
||
epc2x6FuseEvt | 1.3.6.1.4.1.28507.0.13 | |||
epc2x6TempEvt | 1.3.6.1.4.1.28507.0.14 |
change of temperature |
||
gadsEPC2x6 | 1.3.6.1.4.1.28507.6 | |||
epc2x6Objects | 1.3.6.1.4.1.28507.6.1 | |||
epc2x6SNMPaccess | 1.3.6.1.4.1.28507.6.1.1 | |||
epc2x6TrapCtrl | 1.3.6.1.4.1.28507.6.1.1.1 | integer32 | read-write |
0 = off 1 = Ver. 1 2 = Ver. 2c |
epc2x6TrapIPTable | 1.3.6.1.4.1.28507.6.1.1.2 | no-access |
list of all Trap receiver |
|
1.3.6.1.4.1.28507.6.1.1.2.1 | no-access |
an entry containing management informations regarding the list of trap receivers |
||
epc2x6TrapIPIndex | 1.3.6.1.4.1.28507.6.1.1.2.1.1 | integer32 | no-access |
A unique value, greater than zero, for each receiver slot. |
epc2x6TrapIPAddr | 1.3.6.1.4.1.28507.6.1.1.2.1.2 | ipaddress | read-write |
IP Address specifying one Trap receiver slot. A value of '00000000'H disables this slot. |
epc2x6TrapIPPort | 1.3.6.1.4.1.28507.6.1.1.2.1.3 | integer32 | read-write |
IP Port specifying one Trap receiver slot. A value of 0 disables this slot. |
epc2x6powerports | 1.3.6.1.4.1.28507.6.1.2 | |||
epc2x6portNumber | 1.3.6.1.4.1.28507.6.1.2.1 | integer32 | read-only |
The number of PowerPorts |
epc2x6portTable | 1.3.6.1.4.1.28507.6.1.2.2 | no-access |
list of all EPC Powerports |
|
1.3.6.1.4.1.28507.6.1.2.2.1 | no-access |
An entry containing management information applicable to a particular powerport. |
||
epc2x6PortIndex | 1.3.6.1.4.1.28507.6.1.2.2.1.1 | integer32 | no-access |
A unique value, greater than zero, for each PowerPort. |
epc2x6PortName | 1.3.6.1.4.1.28507.6.1.2.2.1.2 | octet string | read-only |
A textual string containing name of a PowerPort. |
epc2x6PortState | 1.3.6.1.4.1.28507.6.1.2.2.1.3 | integer | read-write |
current state a PowerPort Enumeration: 'on': 1, 'off': 0. |
epc2x6PortSwitchCount | 1.3.6.1.4.1.28507.6.1.2.2.1.4 | counter32 | read-only |
The total number of switch actions ocurred on a PowerPort. Does not count switch commands which will not switch the ralay state, so just real relay switches are displayed here. |
epc2x6PortStartupMode | 1.3.6.1.4.1.28507.6.1.2.2.1.5 | integer | read-write |
set Mode of startup sequence (off, on , remember last state) Enumeration: 'on': 1, 'off': 0, 'laststate': 2. |
epc2x6PortStartupDelay | 1.3.6.1.4.1.28507.6.1.2.2.1.6 | integer32 | read-write |
Delay in sec for startup action |
epc2x6PortRepowerTime | 1.3.6.1.4.1.28507.6.1.2.2.1.7 | integer32 | read-write |
Delay in sec for repower port after switching off |
epc2x6portFuses | 1.3.6.1.4.1.28507.6.1.2.3 | integer32 | read-only |
Bit State of Fuses (Bit 0 = Fuse1, Bit 1 = Fuse2) |
epc2x6Temperature | 1.3.6.1.4.1.28507.6.1.3 | integer32 | read-only |
actual Temperature, if sensor is not supported '9998', not connected '9999' is given back as result |
epc2x6Conf | 1.3.6.1.4.1.28507.6.3 | |||
epc2x6Groups | 1.3.6.1.4.1.28507.6.3.1 | |||
epc2x6BasicGroup | 1.3.6.1.4.1.28507.6.3.1.1 |
Basic objects. |
||
epc2x6NotificationGroup | 1.3.6.1.4.1.28507.6.3.1.2 | |||
epc2x6Compls | 1.3.6.1.4.1.28507.6.3.2 |