GEIST-IMD-MIB: View SNMP OID List / Download MIB

VENDOR: VERTIV


 Home MIB: GEIST-IMD-MIB
Download as:   

Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 geist 1.3.6.1.4.1.21239
The MIB for Geist Products
             blackbird 1.3.6.1.4.1.21239.5
                 imd 1.3.6.1.4.1.21239.5.2
                     deviceInfo 1.3.6.1.4.1.21239.5.2.1
                         productTitle 1.3.6.1.4.1.21239.5.2.1.1 displaystring read-only
Product name
                         productVersion 1.3.6.1.4.1.21239.5.2.1.2 displaystring read-only
Product version
                         productFriendlyName 1.3.6.1.4.1.21239.5.2.1.3 displaystring read-only
User-assigned name
                         productMacAddress 1.3.6.1.4.1.21239.5.2.1.4 octet string read-only
Product's unique MAC address
                         productUrl 1.3.6.1.4.1.21239.5.2.1.5 ipaddress read-only
Product's main URL access point
                         deviceCount 1.3.6.1.4.1.21239.5.2.1.6 integer32 read-only
Total number of devices on unit
                         temperatureUnits 1.3.6.1.4.1.21239.5.2.1.7 integer32 read-write
Current units for temperature values. 0 = Degrees Fahrenheit, 1 = Degrees Celsius
                     pdu 1.3.6.1.4.1.21239.5.2.3
                         pduMainTable 1.3.6.1.4.1.21239.5.2.3.1 no-access
PDU general information
                             pduMainEntry 1.3.6.1.4.1.21239.5.2.3.1.1 no-access
Entry in the pduMainTable table: each entry contains an index and other sensor details
                                 pduMainIndex 1.3.6.1.4.1.21239.5.2.3.1.1.1 integer32 read-only
Table entry index value
                                 pduMainSerial 1.3.6.1.4.1.21239.5.2.3.1.1.2 displaystring read-only
Serial Number
                                 pduMainName 1.3.6.1.4.1.21239.5.2.3.1.1.3 displaystring read-only
Name
                                 pduMainLabel 1.3.6.1.4.1.21239.5.2.3.1.1.4 displaystring read-only
Label
                                 pduMainAvail 1.3.6.1.4.1.21239.5.2.3.1.1.5 gauge32 read-only
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable
                                 pduMeterType 1.3.6.1.4.1.21239.5.2.3.1.1.6 integer32 read-only
Current meter type. 0 = Wye, 1 = Delta
                                 pduTotalName 1.3.6.1.4.1.21239.5.2.3.1.1.7 displaystring read-only
Total Name
                                 pduTotalLabel 1.3.6.1.4.1.21239.5.2.3.1.1.8 displaystring read-only
Total Label
                                 pduTotalRealPower 1.3.6.1.4.1.21239.5.2.3.1.1.9 gauge32 read-only
PDU Total Real Power
                                 pduTotalApparentPower 1.3.6.1.4.1.21239.5.2.3.1.1.10 gauge32 read-only
PDU Total Apparent Power
                                 pduTotalPowerFactor 1.3.6.1.4.1.21239.5.2.3.1.1.11 gauge32 read-only
PDU Total Power Factor
                                 pduTotalEnergy 1.3.6.1.4.1.21239.5.2.3.1.1.12 gauge32 read-only
PDU Total Accumulated Energy
                         pduPhaseTable 1.3.6.1.4.1.21239.5.2.3.2 no-access
PDU phases information
                             pduPhaseEntry 1.3.6.1.4.1.21239.5.2.3.2.1 no-access
Entry in the pduPhaseTable table: each entry contains an index and other sensor details
                                 pduPhaseIndex 1.3.6.1.4.1.21239.5.2.3.2.1.1 integer32 read-only
Table entry index value
                                 pduPhaseName 1.3.6.1.4.1.21239.5.2.3.2.1.2 displaystring read-only
PDU Phase Name
                                 pduPhaseLabel 1.3.6.1.4.1.21239.5.2.3.2.1.3 displaystring read-only
PDU Phase Label
                                 pduPhaseVoltage 1.3.6.1.4.1.21239.5.2.3.2.1.4 gauge32 read-only
PDU Phase Voltage in tenths of a volt
                                 pduPhaseVoltageMax 1.3.6.1.4.1.21239.5.2.3.2.1.5 gauge32 read-only
PDU Phase Voltage (Max) in tenths of a volt
                                 pduPhaseVoltageMin 1.3.6.1.4.1.21239.5.2.3.2.1.6 gauge32 read-only
PDU Phase Voltage (Min) in tenths of a volt
                                 pduPhaseVoltagePeak 1.3.6.1.4.1.21239.5.2.3.2.1.7 gauge32 read-only
PDU Phase Voltage (Peak) in tenths of a volt
                                 pduPhaseCurrent 1.3.6.1.4.1.21239.5.2.3.2.1.8 gauge32 read-only
PDU Phase Current reading in hundreths of an amp
                                 pduPhaseCurrentMax 1.3.6.1.4.1.21239.5.2.3.2.1.9 gauge32 read-only
PDU Phase Current (Max) reading in hundreths of an amp
                                 pduPhaseCurrentMin 1.3.6.1.4.1.21239.5.2.3.2.1.10 gauge32 read-only
PDU Phase Current (Min) reading in hundreths of an amp
                                 pduPhaseCurrentPeak 1.3.6.1.4.1.21239.5.2.3.2.1.11 gauge32 read-only
PDU Phase Current (Peak) reading in hundreths of an amp
                                 pduPhaseRealPower 1.3.6.1.4.1.21239.5.2.3.2.1.12 gauge32 read-only
PDU Phase Real Power
                                 pduPhaseApparentPower 1.3.6.1.4.1.21239.5.2.3.2.1.13 gauge32 read-only
PDU Phase Apparent Power
                                 pduPhasePowerFactor 1.3.6.1.4.1.21239.5.2.3.2.1.14 gauge32 read-only
PDU Phase Power Factor
                                 pduPhaseEnergy 1.3.6.1.4.1.21239.5.2.3.2.1.15 gauge32 read-only
PDU Phase Accumulated Energy
                         pduBreakerTable 1.3.6.1.4.1.21239.5.2.3.3 no-access
PDU information
                             pduBreakerEntry 1.3.6.1.4.1.21239.5.2.3.3.1 no-access
Entry in the pduBreakerTable table: each entry contains an index and other sensor details
                                 pduBreakerIndex 1.3.6.1.4.1.21239.5.2.3.3.1.1 integer32 read-only
Table entry index value
                                 pduBreakerName 1.3.6.1.4.1.21239.5.2.3.3.1.2 displaystring read-only
PDU Breaker Name
                                 pduBreakerLabel 1.3.6.1.4.1.21239.5.2.3.3.1.3 displaystring read-only
PDU Breaker Label
                                 pduBreakerCurrent 1.3.6.1.4.1.21239.5.2.3.3.1.4 gauge32 read-only
PDU Breaker Current reading in hundreths of an amp
                                 pduBreakerCurrentMax 1.3.6.1.4.1.21239.5.2.3.3.1.5 gauge32 read-only
PDU Breaker Current (Max) reading in hundreths of an amp
                                 pduBreakerCurrentMin 1.3.6.1.4.1.21239.5.2.3.3.1.6 gauge32 read-only
PDU Breaker Current (Min) reading in hundreths of an amp
                                 pduBreakerCurrentPeak 1.3.6.1.4.1.21239.5.2.3.3.1.7 gauge32 read-only
PDU Breaker Current (Peak) reading in hundreths of an amp
                         pduLineTable 1.3.6.1.4.1.21239.5.2.3.4 no-access
PDU line current information
                             pduLineEntry 1.3.6.1.4.1.21239.5.2.3.4.1 no-access
Entry in the pduLineTable table: each entry contains an index and other sensor details
                                 pduLineIndex 1.3.6.1.4.1.21239.5.2.3.4.1.1 integer32 read-only
Table entry index value
                                 pduLineName 1.3.6.1.4.1.21239.5.2.3.4.1.2 displaystring read-only
PDU Line Name
                                 pduLineLabel 1.3.6.1.4.1.21239.5.2.3.4.1.3 displaystring read-only
PDU Line Label
                                 pduLineCurrent 1.3.6.1.4.1.21239.5.2.3.4.1.4 gauge32 read-only
PDU Line Current reading in hundreths of an amp
                                 pduLineCurrentMax 1.3.6.1.4.1.21239.5.2.3.4.1.5 gauge32 read-only
PDU Line Current (Max) reading in hundreths of an amp
                                 pduLineCurrentMin 1.3.6.1.4.1.21239.5.2.3.4.1.6 gauge32 read-only
PDU Line Current (Min) reading in hundreths of an amp
                                 pduLineCurrentPeak 1.3.6.1.4.1.21239.5.2.3.4.1.7 gauge32 read-only
PDU Line Current (Peak) reading in hundreths of an amp
                     tempSensorTable 1.3.6.1.4.1.21239.5.2.4 no-access
Remote Temperature Sensor
                         tempSensorEntry 1.3.6.1.4.1.21239.5.2.4.1 no-access
Entry in the tempSensorTable table: each entry contains an index and other sensor details
                             tempSensorIndex 1.3.6.1.4.1.21239.5.2.4.1.1 integer32 read-only
Table entry index value
                             tempSensorSerial 1.3.6.1.4.1.21239.5.2.4.1.2 displaystring read-only
Serial Number
                             tempSensorName 1.3.6.1.4.1.21239.5.2.4.1.3 displaystring read-only
Friendly Name
                             tempSensorAvail 1.3.6.1.4.1.21239.5.2.4.1.4 gauge32 read-only
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable
                             tempSensorTemp 1.3.6.1.4.1.21239.5.2.4.1.5 integer32 read-only
Current reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInfo
                     airFlowSensorTable 1.3.6.1.4.1.21239.5.2.5 no-access
Remote Airflow, Humidity, Temperature and Dewpoint Sensor
                         airFlowSensorEntry 1.3.6.1.4.1.21239.5.2.5.1 no-access
Entry in the airFlowSensorTable table: each entry contains an index and other sensor details
                             airFlowSensorIndex 1.3.6.1.4.1.21239.5.2.5.1.1 integer32 read-only
Table entry index value
                             airFlowSensorSerial 1.3.6.1.4.1.21239.5.2.5.1.2 displaystring read-only
Serial Number
                             airFlowSensorName 1.3.6.1.4.1.21239.5.2.5.1.3 displaystring read-only
Friendly Name
                             airFlowSensorAvail 1.3.6.1.4.1.21239.5.2.5.1.4 gauge32 read-only
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable
                             airFlowSensorTemp 1.3.6.1.4.1.21239.5.2.5.1.5 integer32 read-only
Current reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInfo
                             airFlowSensorFlow 1.3.6.1.4.1.21239.5.2.5.1.6 integer32 read-only
AFHT3 Airflow reading
                             airFlowSensorHumidity 1.3.6.1.4.1.21239.5.2.5.1.7 integer32 read-only
AFHT3 Humidity reading
                             airFlowSensorDewPoint 1.3.6.1.4.1.21239.5.2.5.1.8 integer32 read-only
Current reading for Dew Point in tenths of degrees. Units are given by temperatureUnits field in deviceInfo
                     dewPointSensorTable 1.3.6.1.4.1.21239.5.2.6 no-access
Remote Dew Point sensor
                         dewPointSensorEntry 1.3.6.1.4.1.21239.5.2.6.1 no-access
Entry in the dewPointSensorTable table: each entry contains an index and other sensor details
                             dewPointSensorIndex 1.3.6.1.4.1.21239.5.2.6.1.1 integer32 read-only
Table entry index value
                             dewPointSensorSerial 1.3.6.1.4.1.21239.5.2.6.1.2 displaystring read-only
Serial Number
                             dewPointSensorName 1.3.6.1.4.1.21239.5.2.6.1.3 displaystring read-only
Friendly Name
                             dewPointSensorAvail 1.3.6.1.4.1.21239.5.2.6.1.4 gauge32 read-only
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable
                             dewPointSensorTemp 1.3.6.1.4.1.21239.5.2.6.1.5 integer32 read-only
Current reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInfo
                             dewPointSensorHumidity 1.3.6.1.4.1.21239.5.2.6.1.6 integer32 read-only
Humidity reading
                             dewPointSensorDewPoint 1.3.6.1.4.1.21239.5.2.6.1.7 integer32 read-only
Current reading for Dew-point in tenths of degrees. Units are given by temperatureUnits field in deviceInfo
                     ccatSensorTable 1.3.6.1.4.1.21239.5.2.7 no-access
Remote CCAT sensor
                         ccatSensorEntry 1.3.6.1.4.1.21239.5.2.7.1 no-access
Entry in the ccatSensorTable table: each entry contains an index and other sensor details
                             ccatSensorIndex 1.3.6.1.4.1.21239.5.2.7.1.1 integer32 read-only
Table entry index value
                             ccatSensorSerial 1.3.6.1.4.1.21239.5.2.7.1.2 displaystring read-only
Serial Number
                             ccatSensorName 1.3.6.1.4.1.21239.5.2.7.1.3 displaystring read-only
Friendly Name
                             ccatSensorAvail 1.3.6.1.4.1.21239.5.2.7.1.4 gauge32 read-only
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable
                             ccatSensorValue 1.3.6.1.4.1.21239.5.2.7.1.5 integer32 read-only
CCAT sensor reading
                             ccatSensorType 1.3.6.1.4.1.21239.5.2.7.1.6 displaystring read-only
CCAT sensor type
                             ccatSensorDescription 1.3.6.1.4.1.21239.5.2.7.1.7 displaystring read-only
CCAT sensor value description
                     t3hdSensorTable 1.3.6.1.4.1.21239.5.2.8 no-access
Remote Temperature x 3, Humidity and Dewpoint Sensor
                         t3hdSensorEntry 1.3.6.1.4.1.21239.5.2.8.1 no-access
Entry in the t3hdSensorTable table: each entry contains an index and other sensor details
                             t3hdSensorIndex 1.3.6.1.4.1.21239.5.2.8.1.1 integer32 read-only
Table entry index value
                             t3hdSensorSerial 1.3.6.1.4.1.21239.5.2.8.1.2 displaystring read-only
Serial Number
                             t3hdSensorName 1.3.6.1.4.1.21239.5.2.8.1.3 displaystring read-only
Friendly Name
                             t3hdSensorAvail 1.3.6.1.4.1.21239.5.2.8.1.4 gauge32 read-only
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable
                             t3hdSensorIntName 1.3.6.1.4.1.21239.5.2.8.1.5 displaystring read-only
T3HD Sensor Internal Friendly Name
                             t3hdSensorIntTemp 1.3.6.1.4.1.21239.5.2.8.1.6 integer32 read-only
Current reading for Internal Temperature in 0.1 degrees. Units are given by temperatureUnits field in deviceInfo
                             t3hdSensorIntHumidity 1.3.6.1.4.1.21239.5.2.8.1.7 integer32 read-only
T3HD Sensor Internal Humidity
                             t3hdSensorIntDewPoint 1.3.6.1.4.1.21239.5.2.8.1.8 integer32 read-only
Current reading for Internal DewPoint in 0.1 degrees. Units are given by temperatureUnits field in deviceInfo
                             t3hdSensorExtAAvail 1.3.6.1.4.1.21239.5.2.8.1.9 gauge32 read-only
T3HD External A status: 0 = Unavailable, 1 = Available
                             t3hdSensorExtAName 1.3.6.1.4.1.21239.5.2.8.1.10 displaystring read-only
T3HD External A Friendly Name
                             t3hdSensorExtATemp 1.3.6.1.4.1.21239.5.2.8.1.11 integer32 read-only
Current reading for External Temperature A in 0.1 degrees. Units are given by temperatureUnits field in deviceInfo
                             t3hdSensorExtBAvail 1.3.6.1.4.1.21239.5.2.8.1.12 gauge32 read-only
T3HD External B status: 0 = Unavailable, 1 = Available
                             t3hdSensorExtBName 1.3.6.1.4.1.21239.5.2.8.1.13 displaystring read-only
T3HD External B Friendly Name
                             t3hdSensorExtBTemp 1.3.6.1.4.1.21239.5.2.8.1.14 integer32 read-only
Current reading for External Temperature B in 0.1 degrees. Units are given by temperatureUnits field in deviceInfo
                     thdSensorTable 1.3.6.1.4.1.21239.5.2.9 no-access
Remote Temperature, Humidity and Dewpoint Sensor
                         thdSensorEntry 1.3.6.1.4.1.21239.5.2.9.1 no-access
Entry in the thdSensorTable table: each entry contains an index and other sensor details
                             thdSensorIndex 1.3.6.1.4.1.21239.5.2.9.1.1 integer32 read-only
Table entry index value
                             thdSensorSerial 1.3.6.1.4.1.21239.5.2.9.1.2 displaystring read-only
Serial Number
                             thdSensorName 1.3.6.1.4.1.21239.5.2.9.1.3 displaystring read-only
Friendly Name
                             thdSensorAvail 1.3.6.1.4.1.21239.5.2.9.1.4 gauge32 read-only
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable
                             thdSensorTemp 1.3.6.1.4.1.21239.5.2.9.1.5 integer32 read-only
Current reading for Temperature in 0.1 degrees. Units are given by temperatureUnits field in deviceInfo
                             thdSensorHumidity 1.3.6.1.4.1.21239.5.2.9.1.6 integer32 read-only
THD Sensor Humidity
                             thdSensorDewPoint 1.3.6.1.4.1.21239.5.2.9.1.7 integer32 read-only
Current reading for DewPoint in 0.1 degrees. Units are given by temperatureUnits field in deviceInfo
                     rpmSensorTable 1.3.6.1.4.1.21239.5.2.10 no-access
Remote Power Manager Sensor
                           rpmSensorEntry 1.3.6.1.4.1.21239.5.2.10.1 no-access
Entry in the rpmSensorTable table: each entry contains an index and other sensor details
                               rpmSensorIndex 1.3.6.1.4.1.21239.5.2.10.1.1 integer32 read-only
Table entry index value
                               rpmSensorSerial 1.3.6.1.4.1.21239.5.2.10.1.2 displaystring read-only
Serial Number
                               rpmSensorName 1.3.6.1.4.1.21239.5.2.10.1.3 displaystring read-only
Friendly Name
                               rpmSensorAvail 1.3.6.1.4.1.21239.5.2.10.1.4 gauge32 read-only
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable
                               rpmSensorEnergy 1.3.6.1.4.1.21239.5.2.10.1.5 gauge32 read-only
RPM Sensor Accumulated Energy
                               rpmSensorVoltage 1.3.6.1.4.1.21239.5.2.10.1.6 gauge32 read-only
RPM Sensor Voltage
                               rpmSensorVoltageMax 1.3.6.1.4.1.21239.5.2.10.1.7 gauge32 read-only
RPM Sensor Voltage (Max)
                               rpmSensorVoltageMin 1.3.6.1.4.1.21239.5.2.10.1.8 gauge32 read-only
RPM Sensor Voltage (Min)
                               rpmSensorVoltagePeak 1.3.6.1.4.1.21239.5.2.10.1.9 gauge32 read-only
RPM Sensor Voltage (Peak)
                               rpmSensorCurrent 1.3.6.1.4.1.21239.5.2.10.1.10 gauge32 read-only
RPM Sensor Current reading in deciAmps
                               rpmSensorRealPower 1.3.6.1.4.1.21239.5.2.10.1.11 gauge32 read-only
RPM Sensor Real Power
                               rpmSensorApparentPower 1.3.6.1.4.1.21239.5.2.10.1.12 gauge32 read-only
RPM Sensor Apparent Power
                               rpmSensorPowerFactor 1.3.6.1.4.1.21239.5.2.10.1.13 gauge32 read-only
RPM Sensor Power Factor
                               rpmSensorOutlet1 1.3.6.1.4.1.21239.5.2.10.1.14 gauge32 read-only
RPM Sensor Outlet 1 State: 0 = off, 1 = on
                               rpmSensorOutlet2 1.3.6.1.4.1.21239.5.2.10.1.15 gauge32 read-only
RPM Sensor Outlet 2 State: 0 = off, 1 = on
                     a2dSensorTable 1.3.6.1.4.1.21239.5.2.11 no-access
Analog Measurement Sensor (Voltage, Current, or Dry Contact)
                           a2DSensorEntry 1.3.6.1.4.1.21239.5.2.11.1 no-access
Entry in the a2dSensorTable table: each entry contains an index and other sensor details
                               a2dSensorIndex 1.3.6.1.4.1.21239.5.2.11.1.1 integer32 read-only
Table entry index value
                               a2dSensorSerial 1.3.6.1.4.1.21239.5.2.11.1.2 displaystring read-only
Serial Number
                               a2dSensorName 1.3.6.1.4.1.21239.5.2.11.1.3 displaystring read-only
Friendly Name
                               a2dSensorAvail 1.3.6.1.4.1.21239.5.2.11.1.4 gauge32 read-only
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable
                               a2dSensorValue 1.3.6.1.4.1.21239.5.2.11.1.5 integer32 read-only
Current analog measurement reading within either a user defined or preset range depending on device mode.
                     trap 1.3.6.1.4.1.21239.5.2.32767
                                 trapPrefix 1.3.6.1.4.1.21239.5.2.32767.0
                                     internalTestNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10101
Test SNMP Trap
                                     pduMainAvailNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10305
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap
                                     pduTotalRealPowerNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10309
PDU Total Real Power Trap
                                     pduTotalApparentPowerNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10310
PDU Total Apparent Power Trap
                                     pduTotalPowerFactorNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10311
PDU Total Power Factor Trap
                                     pduTotalEnergyNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10312
PDU Total Accumulated Energy Trap
                                     pduPhaseVoltageNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10324
PDU Phase Voltage in tenths of a volt Trap
                                     pduPhaseVoltageMaxNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10325
PDU Phase Voltage (Max) in tenths of a volt Trap
                                     pduPhaseVoltageMinNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10326
PDU Phase Voltage (Min) in tenths of a volt Trap
                                     pduPhaseVoltagePeakNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10327
PDU Phase Voltage (Peak) in tenths of a volt Trap
                                     pduPhaseCurrentNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10328
PDU Phase Current Trap
                                     pduPhaseCurrentMaxNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10329
PDU Phase Current (Max) Trap
                                     pduPhaseCurrentMinNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10330
PDU Phase Current (Min) Trap
                                     pduPhaseCurrentPeakNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10331
PDU Phase Current (Peak) Trap
                                     pduPhaseRealPowerNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10332
PDU Phase Real Power Trap
                                     pduPhaseApparentPowerNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10333
PDU Phase Apparent Power Trap
                                     pduPhasePowerFactorNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10334
PDU Phase Power Factor Trap
                                     pduPhaseEnergyNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10335
PDU Phase Accumulated Energy Trap
                                     pduBreakerCurrentNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10354
PDU Breaker Current Trap
                                     pduBreakerCurrentMaxNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10355
PDU Breaker Current (Max) Trap
                                     pduBreakerCurrentMinNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10356
PDU Breaker Current (Min) Trap
                                     pduBreakerCurrentPeakNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10357
PDU Breaker Current (Peak) Trap
                                     pduLineCurrentNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10374
PDU Line Current Trap
                                     pduLineCurrentMaxNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10375
PDU Line Current (Max) Trap
                                     pduLineCurrentMinNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10376
PDU Line Current (Min) Trap
                                     pduLineCurrentPeakNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10377
PDU Line Current (Peak) Trap
                                     tempSensorAvailNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10404
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap
                                     tempSensorTempNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10405
Remote Temperature Sensor Trap
                                     airFlowSensorAvailNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10504
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap
                                     airFlowSensorTempNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10505
AFHT3 Sensor Temperature Trap
                                     airFlowSensorFlowNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10506
AFHT3 Airflow reading Trap
                                     airFlowSensorHumidityNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10507
AFHT3 Humidity reading Trap
                                     airFlowSensorDewPointNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10508
AFHT3 Sensor Dew Point Trap
                                     dewPointSensorAvailNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10604
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap
                                     dewPointSensorTempNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10605
Remote Dew Point Sensor Temperature Trap
                                     dewPointSensorHumidityNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10606
Humidity reading Trap
                                     dewPointSensorDewPointNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10607
Remote Dew Point Sensor Dew Point Trap
                                     ccatSensorAvailNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10704
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap
                                     ccatSensorValueNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10705
CCAT sensor reading Trap
                                     t3hdSensorAvailNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10804
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap
                                     t3hdSensorIntTempNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10806
T3HD Sensor Temperature Trap
                                     t3hdSensorIntHumidityNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10807
T3HD Sensor Internal Humidity Trap
                                     t3hdSensorIntDewPointNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10808
T3HD Sensor Dew Point Trap
                                     t3hdSensorExtATempNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10811
T3HD Sensor External A Temperature Trap
                                     t3hdSensorExtBTempNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10814
T3HD Sensor External B Temperature Trap
                                     thdSensorAvailNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10904
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap
                                     thdSensorTempNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10905
THD Sensor Temperature Trap
                                     thdSensorHumidityNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10906
THD Sensor Humidity Trap
                                     thdSensorDewPointNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.10907
THD Sensor Dew Point Trap
                                     rpmSensorAvailNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.11004
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap
                                     rpmSensorEnergyNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.11005
RPM Sensor Accumulated Energy Trap
                                     rpmSensorVoltageNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.11006
RPM Sensor Voltage Trap
                                     rpmSensorVoltageMaxNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.11007
RPM Sensor Voltage (Max) Trap
                                     rpmSensorVoltageMinNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.11008
RPM Sensor Voltage (Min) Trap
                                     rpmSensorVoltagePeakNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.11009
RPM Sensor Voltage (Peak) Trap
                                     rpmSensorCurrentNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.11010
RPM Sensor Current Trap
                                     rpmSensorRealPowerNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.11011
RPM Sensor Real Power Trap
                                     rpmSensorApparentPowerNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.11012
RPM Sensor Apparent Power Trap
                                     rpmSensorPowerFactorNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.11013
RPM Sensor Power Factor Trap
                                     a2dSensorAvailNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.11104
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap
                                     a2dSensorValueNOTIFY 1.3.6.1.4.1.21239.5.2.32767.0.11105
A2D Analog Sensor Measurement Trap
                                     pduMainAvailCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20305
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap
                                     pduTotalRealPowerCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20309
PDU Total Real Power Clear Trap
                                     pduTotalApparentPowerCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20310
PDU Total Apparent Power Clear Trap
                                     pduTotalPowerFactorCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20311
PDU Total Power Factor Clear Trap
                                     pduTotalEnergyCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20312
PDU Total Accumulated Energy Clear Trap
                                     pduPhaseVoltageCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20324
PDU Phase Voltage in tenths of a volt Clear Trap
                                     pduPhaseVoltageMaxCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20325
PDU Phase Voltage (Max) in tenths of a volt Clear Trap
                                     pduPhaseVoltageMinCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20326
PDU Phase Voltage (Min) in tenths of a volt Clear Trap
                                     pduPhaseVoltagePeakCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20327
PDU Phase Voltage (Peak) in tenths of a volt Clear Trap
                                     pduPhaseCurrentCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20328
PDU Phase Current Clear Trap
                                     pduPhaseCurrentMaxCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20329
PDU Phase Current (Max) Clear Trap
                                     pduPhaseCurrentMinCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20330
PDU Phase Current (Min) Clear Trap
                                     pduPhaseCurrentPeakCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20331
PDU Phase Current (Peak) Clear Trap
                                     pduPhaseRealPowerCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20332
PDU Phase Real Power Clear Trap
                                     pduPhaseApparentPowerCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20333
PDU Phase Apparent Power Clear Trap
                                     pduPhasePowerFactorCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20334
PDU Phase Power Factor Clear Trap
                                     pduPhaseEnergyCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20335
PDU Phase Accumulated Energy Clear Trap
                                     pduBreakerCurrentCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20354
PDU Breaker Current Clear Trap
                                     pduBreakerCurrentMaxCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20355
PDU Breaker Current (Max) Clear Trap
                                     pduBreakerCurrentMinCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20356
PDU Breaker Current (Min) Clear Trap
                                     pduBreakerCurrentPeakCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20357
PDU Breaker Current (Peak) Clear Trap
                                     pduLineCurrentCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20374
PDU Line Current Clear Trap
                                     pduLineCurrentMaxCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20375
PDU Line Current (Max) Clear Trap
                                     pduLineCurrentMinCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20376
PDU Line Current (Min) Clear Trap
                                     pduLineCurrentPeakCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20377
PDU Line Current (Peak) Clear Trap
                                     tempSensorAvailCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20404
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap
                                     tempSensorTempCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20405
Remote Temperature Sensor Clear Trap
                                     airFlowSensorAvailCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20504
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap
                                     airFlowSensorTempCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20505
AFHT3 Sensor Temperature Clear Trap
                                     airFlowSensorFlowCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20506
AFHT3 Airflow reading Clear Trap
                                     airFlowSensorHumidityCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20507
AFHT3 Humidity reading Clear Trap
                                     airFlowSensorDewPointCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20508
AFHT3 Sensor Dew Point Clear Trap
                                     dewPointSensorAvailCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20604
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap
                                     dewPointSensorTempCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20605
Remote Dew Point Sensor Temperature Clear Trap
                                     dewPointSensorHumidityCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20606
Humidity reading Clear Trap
                                     dewPointSensorDewPointCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20607
Remote Dew Point Sensor Dew Point Clear Trap
                                     ccatSensorAvailCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20704
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap
                                     ccatSensorValueCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20705
CCAT sensor reading Clear Trap
                                     t3hdSensorAvailCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20804
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap
                                     t3hdSensorIntTempCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20806
T3HD Sensor Temperature Clear Trap
                                     t3hdSensorIntHumidityCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20807
T3HD Sensor Internal Humidity Clear Trap
                                     t3hdSensorIntDewPointCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20808
T3HD Sensor Dew Point Clear Trap
                                     t3hdSensorExtATempCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20811
T3HD Sensor External A Temperature Clear Trap
                                     t3hdSensorExtBTempCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20814
T3HD Sensor External B Temperature Clear Trap
                                     thdSensorAvailCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20904
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap
                                     thdSensorTempCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20905
THD Sensor Temperature Clear Trap
                                     thdSensorHumidityCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20906
THD Sensor Humidity Clear Trap
                                     thdSensorDewPointCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.20907
THD Sensor Dew Point Clear Trap
                                     rpmSensorAvailCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.21004
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap
                                     rpmSensorEnergyCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.21005
RPM Sensor Accumulated Energy Clear Trap
                                     rpmSensorVoltageCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.21006
RPM Sensor Voltage Clear Trap
                                     rpmSensorVoltageMaxCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.21007
RPM Sensor Voltage (Max) Clear Trap
                                     rpmSensorVoltageMinCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.21008
RPM Sensor Voltage (Min) Clear Trap
                                     rpmSensorVoltagePeakCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.21009
RPM Sensor Voltage (Peak) Clear Trap
                                     rpmSensorCurrentCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.21010
RPM Sensor Current Clear Trap
                                     rpmSensorRealPowerCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.21011
RPM Sensor Real Power Clear Trap
                                     rpmSensorApparentPowerCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.21012
RPM Sensor Apparent Power Clear Trap
                                     rpmSensorPowerFactorCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.21013
RPM Sensor Power Factor Clear Trap
                                     a2dSensorAvailCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.21104
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap
                                     a2dSensorValueCLEAR 1.3.6.1.4.1.21239.5.2.32767.0.21105
A2D Analog Sensor Measurement Clear Trap