EPPC-MIB: View SNMP OID List / Download MIB

VENDOR: PHOENIXTEC POWER CO.


 Home MIB: EPPC-MIB
Download as:   

Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 ppc 1.3.6.1.4.1.935
         device 1.3.6.1.4.1.935.10
               upsAgent 1.3.6.1.4.1.935.10.1
                   upsE 1.3.6.1.4.1.935.10.1.1
                       upsEIdentity 1.3.6.1.4.1.935.10.1.1.1
                           upsEIdentityManufacturer 1.3.6.1.4.1.935.10.1.1.1.1 displaystring read-only
The name of the UPS manufacturer.
                           upsEIdentityModel 1.3.6.1.4.1.935.10.1.1.1.2 displaystring read-only
The UPS Model designation.
                           upsEIdentityUPSFirmwareVerison 1.3.6.1.4.1.935.10.1.1.1.3 displaystring read-only
The UPS firmware/software version(s).
                           upsEIndentityUPSSerialNumber 1.3.6.1.4.1.935.10.1.1.1.4 displaystring read-only
optional. Most UPS don't supply the value of UPS serial No.
                           upsEIdentityDescription 1.3.6.1.4.1.935.10.1.1.1.5 displaystring read-write
A string to identify the UPS. This object should be set by the administrator.
                           upsEIdentityAgentSoftwareVerison 1.3.6.1.4.1.935.10.1.1.1.6 displaystring read-only
The Network Management Card software/firmware version. This variable may or may not have the same value as upsEIdentGroupUPSSoftwareVersion in some implementations.
                           upsEIdentityAttachedDevices 1.3.6.1.4.1.935.10.1.1.1.7 displaystring read-write
A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator
                       upsESystemSummary 1.3.6.1.4.1.935.10.1.1.2
                           upsESystemStatus 1.3.6.1.4.1.935.10.1.1.2.1 integer read-only
The indication of UPS system status. Enumeration: 'by-pass': 3, 'converter': 8, 'battery': 5, 'fault': 7, 'stand-by': 2, 'power-on': 1, 'battery-test': 6, 'eco': 9, 'on-reducer': 12, 'other': 13, 'shutdown': 10, 'line': 4, 'on-booster': 11.
                           upsESystemTemperature 1.3.6.1.4.1.935.10.1.1.2.2 integer read-only
The temperature of UPS presented in 0.1 degree.
                           upsESystemWarningCode 1.3.6.1.4.1.935.10.1.1.2.3 displaystring read-only
The warning code of UPS. Please refer the warning table of 'Q6' for details.
                           upsESystemFaultCode 1.3.6.1.4.1.935.10.1.1.2.4 displaystring read-only
The fault code of UPS.Please refer the fault code of 'Q6' for details.
                           upsESystemConfigInputVoltage 1.3.6.1.4.1.935.10.1.1.2.5 nonnegativeinteger read-only
The magnitude of the nominal input voltage presented in 0.1 V. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.
                           upsESystemConfigInputFrequence 1.3.6.1.4.1.935.10.1.1.2.6 nonnegativeinteger read-only
The nominal input frequency presented in 0.1 Hz. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.
                           upsESystemConfigOutputVoltage 1.3.6.1.4.1.935.10.1.1.2.7 nonnegativeinteger read-only
The magnitude of the nominal output voltage presented in 0.1V. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2
                           upsESystemConfigOutputFrequency 1.3.6.1.4.1.935.10.1.1.2.8 nonnegativeinteger read-only
The nominal output frequency presented in 0.1Hz. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.
                           upsESystemConfigOutputVA 1.3.6.1.4.1.935.10.1.1.2.9 nonnegativeinteger read-only
The magnitude of the nominal Volt-Amp rating presented in VA.
                           upsESystemConfigOutputPower 1.3.6.1.4.1.935.10.1.1.2.10 nonnegativeinteger read-only
The magnitude of the nominal true power rating presented in W .
                           upsESystemConfigOutputLoadHighSetPoint 1.3.6.1.4.1.935.10.1.1.2.11 nonnegativeinteger read-write
The maximum output load allowed before the load is too high for UPS operation
                           upsESystemConfigOverTemperatureSetPoint 1.3.6.1.4.1.935.10.1.1.2.12 nonnegativeinteger read-write
The maximum temperature allowed before the UPS operation temperature is too high, presented in 0.1 degree.
                           upsESystemInputSourceNum 1.3.6.1.4.1.935.10.1.1.2.13 integer read-only
The present external source of input power.
                           upsESystemInputLineBads 1.3.6.1.4.1.935.10.1.1.2.14 counter read-only
The number of times the Input was out of tolerance in voltage or frequency. Its value should be initialized 0 after agent restarting.
                           upsESystemInputNumPhases 1.3.6.1.4.1.935.10.1.1.2.15 positiveinteger read-only
The number of input phase utilized is this device, serves as the table index. This value indicate the device initialized feature.
                           upsESystemInputTable 1.3.6.1.4.1.935.10.1.1.2.16 no-access
A list of input table entries. The number of entries is given by the value of upsESystemInputNumPhase.
                                 upsESystemInputEntry 1.3.6.1.4.1.935.10.1.1.2.16.1 no-access
An entry containing information applicable to a particular input line.
                                     upsESystemInputPhase 1.3.6.1.4.1.935.10.1.1.2.16.1.1 positiveinteger no-access
The number of the phase. Serves as index for input table
                                     upsESystemInputFrequency 1.3.6.1.4.1.935.10.1.1.2.16.1.2 nonnegativeinteger read-only
The measured input frquency from the UPS meters in 0.1Hz.
                                     upsESystemInputVoltage 1.3.6.1.4.1.935.10.1.1.2.16.1.3 nonnegativeinteger read-only
The measured input voltage from the UPS meters in 0.1 volts
                                     upsESystemInputCurrent 1.3.6.1.4.1.935.10.1.1.2.16.1.4 nonnegativeinteger read-only
The measured input mandatory from the UPS meters in 0.1 amps.
                                     upsESystemInputWatts 1.3.6.1.4.1.935.10.1.1.2.16.1.5 nonnegativeinteger read-only
The measured input real power in watts.
                           upsESystemOutputNumPhase 1.3.6.1.4.1.935.10.1.1.2.17 positiveinteger read-only
The number of metered output phases, serves as the table index. This value indicate the device initialized feature.
                           upsESystemOutputTable 1.3.6.1.4.1.935.10.1.1.2.18 no-access
A list of output table entries. The number of entries is given by the value of upsESystemOutputNumPhase.
                                 upsESystemOutputEntry 1.3.6.1.4.1.935.10.1.1.2.18.1 no-access
An entry containing information applicable to a particular line.
                                     upsESystemOutputPhase 1.3.6.1.4.1.935.10.1.1.2.18.1.1 positiveinteger no-access
The number of the phase. Serves as index for output table
                                     upsESystemOutputFrequency 1.3.6.1.4.1.935.10.1.1.2.18.1.2 nonnegativeinteger read-only
The measured output frequency from the UPS meters in 0.1Hz.
                                     upsESystemOutputVoltage 1.3.6.1.4.1.935.10.1.1.2.18.1.3 nonnegativeinteger read-only
The measured output voltage from the UPS meters in 0.1 volts
                                     upsESystemOutputCurrent 1.3.6.1.4.1.935.10.1.1.2.18.1.4 nonnegativeinteger read-only
The measured output mandatory from the UPS meters in 0.1 amps.
                                     upsESystemOutputWatts 1.3.6.1.4.1.935.10.1.1.2.18.1.5 nonnegativeinteger read-only
The measured output real power in watts.
                                     upsESystemOutputVA 1.3.6.1.4.1.935.10.1.1.2.18.1.6 nonnegativeinteger read-only
The measured output real complex power in VA.
                                     upsESystemOutputLoad 1.3.6.1.4.1.935.10.1.1.2.18.1.7 nonnegativeinteger read-only
The UPS output load in percent of rated capacity.
                           upsESystemBypassNumPhase 1.3.6.1.4.1.935.10.1.1.2.19 positiveinteger read-only
The number of bypass phases, serves as the table index. This value indicate the device initialized feature
                           upsESystemBypassTable 1.3.6.1.4.1.935.10.1.1.2.20 no-access
A list of bypass table entries. The number of entries is given by the value of upsESystemBypassNumPhase.
                                 upsESystemBypassEntry 1.3.6.1.4.1.935.10.1.1.2.20.1 no-access
An entry containing information applicable to a particular line.
                                     upsESystemBypassPhase 1.3.6.1.4.1.935.10.1.1.2.20.1.1 positiveinteger no-access
The number of the phase. Serves as index for bypass table
                                     upsESystemBypassFrequency 1.3.6.1.4.1.935.10.1.1.2.20.1.2 nonnegativeinteger read-only
The measured bypass frequency from the UPS meters in 0.1 Hz.
                                     upsESystemBypassVoltage 1.3.6.1.4.1.935.10.1.1.2.20.1.3 nonnegativeinteger read-only
The measured bypass voltage from the UPS meters in 0.1 volts
                                     upsESystemBypassCurrent 1.3.6.1.4.1.935.10.1.1.2.20.1.4 nonnegativeinteger read-only
The measured bypass mandatory from the UPS meters in 0.1 amps
                                     upsESystemBypassWatts 1.3.6.1.4.1.935.10.1.1.2.20.1.5 nonnegativeinteger read-only
The measured input real power in watts.
                           upsESystemConfigBelowCapacityLimit 1.3.6.1.4.1.935.10.1.1.2.21 nonnegativeinteger read-write
The UPS batteries capacity(%) limit for shutdown
                           upsESystemConfigBelowRemainTimeLimit 1.3.6.1.4.1.935.10.1.1.2.22 nonnegativeinteger read-write
The UPS batteries backup time(minute) limit for shutdown
                       upsEBatterySystem 1.3.6.1.4.1.935.10.1.1.3
                           upsEBatteryStatus 1.3.6.1.4.1.935.10.1.1.3.1 integer read-only
The status of UPS battery, a value of batteryLow indicates that the battery-low status bit has been set from device. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is mandatoryly absent and the UPS is unable to sustain the output) Enumeration: 'unknown': 1, 'batteryDepleted': 4, 'batteryFailure': 6, 'batteryNormal': 2, 'batteryLow': 3, 'batteryDischarging': 5.
                           upsESecondsOnBattery 1.3.6.1.4.1.935.10.1.1.3.2 nonnegativeinteger read-only
If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. 0 shall be returned if the unit is not on battery power
                           upsEBatteryEstimatedMinutesRemaining 1.3.6.1.4.1.935.10.1.1.3.3 positiveinteger read-only
An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.
                           upsEBatteryEstimatedChargeRemaining 1.3.6.1.4.1.935.10.1.1.3.4 integer32 read-only
An estimate of the battery charge remaining expressed as a percent of full charge
                           upsEPositiveBatteryVoltage 1.3.6.1.4.1.935.10.1.1.3.5 nonnegativeinteger read-only
The magnitude of the present positive battery voltage in 0.1 Volt DC
                           upsENegativeBatteryVoltage 1.3.6.1.4.1.935.10.1.1.3.6 nonnegativeinteger read-only
The magnitude of the present negative battery voltage in 0.1 Volt DC
                           upsEBatteryCellNumber 1.3.6.1.4.1.935.10.1.1.3.7 nonnegativeinteger read-only
This object indicate the cell number of each set.
                           upsEBatteryTemperature 1.3.6.1.4.1.935.10.1.1.3.8 integer read-only
The ambient temperature at or near the UPS Battery casing in 0.1 degree.
                           upsEBatteryLastReplacedDate 1.3.6.1.4.1.935.10.1.1.3.9 displaystring read-only
The date when the Batteries in this UPS were last replaced. The format should be DD/MM/YYYY.
                           upsEBatteryABMStatus 1.3.6.1.4.1.935.10.1.1.3.10 integer read-only
The status of ABM. Enumeration: 'discharge': 4, 'charge': 1, 'float': 2, 'disable': 5, 'rest': 3.
                           upsEChargerModulesNum 1.3.6.1.4.1.935.10.1.1.3.11 nonnegativeinteger read-only
The number of charger modules inserted to UPS systems. served as the index of the upsEChargerModulesTable. The default value 0 indicate that the UPS system don't have separate charger module.
                           upsEChargerModulesTable 1.3.6.1.4.1.935.10.1.1.3.12 no-access
A list of charger modules entries. The number of entries is given by the value of upsEchargerModulesNum.
                                 upsEChargerModulesEntry 1.3.6.1.4.1.935.10.1.1.3.12.1 no-access
An entry containing information applicable to a particular charger module.
                                     chargerModulesNum 1.3.6.1.4.1.935.10.1.1.3.12.1.1 positiveinteger no-access
The number of charger modules. Serves as index for charger module table
                                     chargerModulesAddress 1.3.6.1.4.1.935.10.1.1.3.12.1.2 nonnegativeinteger read-only
Charger Modules' address.
                                     positiveChargeVotlage 1.3.6.1.4.1.935.10.1.1.3.12.1.3 nonnegativeinteger read-only
The measured positive charger voltage from the UPS meters in 0.1 volts
                                     negativeChargeVoltage 1.3.6.1.4.1.935.10.1.1.3.12.1.4 nonnegativeinteger read-only
The measured nepositive charger voltage from the UPS meters in 0.1 volts
                                     positiveChargeCurrent 1.3.6.1.4.1.935.10.1.1.3.12.1.5 nonnegativeinteger read-only
The measured positive charger mandatory from the UPS meters in in 0.1 amps.
                                     negativeChargeCurrent 1.3.6.1.4.1.935.10.1.1.3.12.1.6 nonnegativeinteger read-only
The measured nepositive charger mandatory from the UPS meters in 0.1 amps.
                                     chargerModulesTemperature 1.3.6.1.4.1.935.10.1.1.3.12.1.7 integer read-only
The measured charger temperature from the UPS meters in 0.1 degree.
                                     chargerModulesMode 1.3.6.1.4.1.935.10.1.1.3.12.1.8 integer read-only
The working mode of charger modules. Enumeration: 'suicide': 6, 'fault': 3, 'running': 5, 'shutdown': 4, 'unknown': 7, 'standyby': 2, 'powerOn': 1.
                       upsEPowerConverterSystem 1.3.6.1.4.1.935.10.1.1.4
                           upsEUPSModulesNum 1.3.6.1.4.1.935.10.1.1.4.1 nonnegativeinteger read-only
The number of UPS modules inserted to UPS systems. served as the index of the upsEModulesTable. the default value 0 indicate that the UPS system do not have separate UPS module.
                           upsEModulesTable 1.3.6.1.4.1.935.10.1.1.4.2 no-access
A list of UPS modules entries. The number of entries is given by the value of upsEModulesNum.
                               upsEModulesEntry 1.3.6.1.4.1.935.10.1.1.4.2.1 no-access
An entry containing information applicable to a particular upsE module.
                                   upsEModulesNum 1.3.6.1.4.1.935.10.1.1.4.2.1.1 positiveinteger no-access
The number of UPS modules. Serves as index for UPS module table
                                   upsEModuleAddress 1.3.6.1.4.1.935.10.1.1.4.2.1.2 integer read-only
the address of UPS modules.
                                   upsEModulePositiveBusVolt 1.3.6.1.4.1.935.10.1.1.4.2.1.3 nonnegativeinteger read-only
The measured positive upsE module voltage from the UPS meters in 0.1 volts
                                   upsEModuleNegativeBusVolt 1.3.6.1.4.1.935.10.1.1.4.2.1.4 nonnegativeinteger read-only
The measured nepositive upsE module voltage from the UPS meters in 0.1 volts
                                   upsEModuleTemperature 1.3.6.1.4.1.935.10.1.1.4.2.1.5 integer read-only
The measured upsE module temperature from the UPS meters in 0.1 degree.
                                   upsEModuleWorkingMode 1.3.6.1.4.1.935.10.1.1.4.2.1.6 integer read-only
The working mode of UPS modules. Enumeration: 'by-pass': 3, 'converter': 8, 'battery': 5, 'fault': 7, 'stand-by': 2, 'power-on': 1, 'battery-test': 6, 'eco': 9, 'on-reducer': 12, 'other': 13, 'shutdown': 10, 'line': 4, 'on-booster': 11.
                                   upsEModuleOutputCurrentR 1.3.6.1.4.1.935.10.1.1.4.2.1.7 nonnegativeinteger read-only
The measured upsE module output mandatory from the UPS meters in 0.1 A.
                                   upsEModuleOutputWattR 1.3.6.1.4.1.935.10.1.1.4.2.1.8 nonnegativeinteger read-only
The measured upsE module output watts from the UPS meters in watts.
                                   upsEModuleOutputLoadR 1.3.6.1.4.1.935.10.1.1.4.2.1.9 integer read-only
The output load of UPS modules in %.
                                   upsEModuleWarningCode 1.3.6.1.4.1.935.10.1.1.4.2.1.10 displaystring read-only
The warning code of ups modules.Please refer the warning table of 'QU,XX' for details.
                                   upsEModuleFaultCode 1.3.6.1.4.1.935.10.1.1.4.2.1.11 displaystring read-only
The fault code of ups modules.Please refer command 'QU,XX' for details.
                                   upsEModuleTrapState 1.3.6.1.4.1.935.10.1.1.4.2.1.12 displaystring read-only
the values indicate the unrestored traps. For example, after AC fail, so the value of upsETrapState should be '1'. And then the AC restore, the value of upsEModuleTrapState should change to empty.
                                   upsEModuleConfigOutputVA 1.3.6.1.4.1.935.10.1.1.4.2.1.13 nonnegativeinteger read-only
The magnitude of the nominal Volt-Amp rating presented in VA.
                                   upsEModuleOutputCurrentS 1.3.6.1.4.1.935.10.1.1.4.2.1.14 nonnegativeinteger read-only
The measured upsE module output mandatory from the UPS meters in 0.1 A.
                                   upsEModuleOutputCurrentT 1.3.6.1.4.1.935.10.1.1.4.2.1.15 nonnegativeinteger read-only
The measured upsE module output mandatory from the UPS meters in 0.1 A.
                                   upsEModuleOutputWattS 1.3.6.1.4.1.935.10.1.1.4.2.1.16 nonnegativeinteger read-only
The measured upsE module output watts from the UPS meters in watts.
                                   upsEModuleOutputWattT 1.3.6.1.4.1.935.10.1.1.4.2.1.17 nonnegativeinteger read-only
The measured upsE module output watts from the UPS meters in watts.
                                   upsEModuleOutputLoadS 1.3.6.1.4.1.935.10.1.1.4.2.1.18 integer read-only
The output load of UPS modules in %.
                                   upsEModuleOutputLoadT 1.3.6.1.4.1.935.10.1.1.4.2.1.19 integer read-only
The output load of UPS modules in %.
                                   upsEModuleOutputVAR 1.3.6.1.4.1.935.10.1.1.4.2.1.20 nonnegativeinteger read-only
The magnitude of the nominal Volt-Amp rating presented in VA.
                                   upsEModuleOutputVAS 1.3.6.1.4.1.935.10.1.1.4.2.1.21 nonnegativeinteger read-only
The magnitude of the nominal Volt-Amp rating presented in VA.
                                   upsEModuleOutputVAT 1.3.6.1.4.1.935.10.1.1.4.2.1.22 nonnegativeinteger read-only
The magnitude of the nominal Volt-Amp rating presented in VA.
                       upsELoadSegment 1.3.6.1.4.1.935.10.1.1.5
                           upsELoadSegment1OffDelay 1.3.6.1.4.1.935.10.1.1.5.1 integer read-write
Setting this object will shutdown the UPS Load Segment output after the indicated number of seconds, or less. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. Read this object will get countdown value of the Load Segment.
                           upsELoadSegment1OnDelay 1.3.6.1.4.1.935.10.1.1.5.2 integer read-write
Setting this object will start the Load segment output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown.
                           upsELoadSegment1AutoOffTimer 1.3.6.1.4.1.935.10.1.1.5.3 integer read-write
The load segment turns automatically off after the delay while the unit operates on battery, but the shutdown is cancelled if the utility return before the delay has expired.
                           upsELoadSegment1AutoOnTimer 1.3.6.1.4.1.935.10.1.1.5.4 integer read-write
The load segment is automatically turned on after a selected delay if it has been shutdown due to on battery.
                           upsELoadSegment1State 1.3.6.1.4.1.935.10.1.1.5.5 integer read-only
Load segment output state. Enumeration: 'on': 2, 'off-pending': 3, 'off': 1, 'not-support': 5, 'on-pending': 4.
                           upsELoadSegment2OffDelay 1.3.6.1.4.1.935.10.1.1.5.6 integer read-write
Setting this object will shutdown the UPS Load Segment output after the indicated number of seconds, or less. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. Read this object will get countdown value of the Load Segment.
                           upsELoadSegment2OnDelay 1.3.6.1.4.1.935.10.1.1.5.7 integer read-write
Setting this object will start the Load segment output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown.
                           upsELoadSegment2AutoOffTimer 1.3.6.1.4.1.935.10.1.1.5.8 integer read-write
The load segment turns automatically off after the delay while the unit operates on battery, but the shutdown is cancelled if the utility return before the delay has expired.
                           upsELoadSegment2AutoOnTimer 1.3.6.1.4.1.935.10.1.1.5.9 integer read-write
The load segment is automatically turned on after a selected delay if it has been shutdown due to on battery.
                           upsELoadSegment2State 1.3.6.1.4.1.935.10.1.1.5.10 integer read-only
Load segment output state. Enumeration: 'on': 2, 'off-pending': 3, 'off': 1, 'not-support': 5, 'on-pending': 4.
                       upsEEnvironment 1.3.6.1.4.1.935.10.1.1.6
                           upsEEnvironmentTemperature 1.3.6.1.4.1.935.10.1.1.6.1
                               upsEEnvironmentCurrentTemperature 1.3.6.1.4.1.935.10.1.1.6.1.1 integer read-only
The measurement of temperature sensor, in 0.1 degree
                               upsEEnvironmentTemperatureHighSetPoint 1.3.6.1.4.1.935.10.1.1.6.1.2 integer read-write
The set point for high temperature warning, in 0.1 degrees. This value must be greater than upsEEnvironmentTemperatureLowSetPoint, and the least significant digit must be zero.
                               upsEEnvironmentTemperatureHighStatus 1.3.6.1.4.1.935.10.1.1.6.1.3 integer read-write
To enable/disable high set point check with sensor temperature. Enumeration: 'enable': 1, 'disable': 2.
                               upsEEnvironmentTemperatureLowSetPoint 1.3.6.1.4.1.935.10.1.1.6.1.4 integer read-write
The set point for low temperature warning, in 0.1 degrees. This value must be less than upsEEnvironmentTemperatureHighSetPoint, and the least significant digit must be zero.
                               upsEEnvironmentTemperatureLowStatus 1.3.6.1.4.1.935.10.1.1.6.1.5 integer read-write
To enable/disable low set point check with sensor temperature. Enumeration: 'enable': 1, 'disable': 2.
                               upsEEnvironmentTemperatureOffset 1.3.6.1.4.1.935.10.1.1.6.1.6 integer read-write
The offset to calibrate temperature of EMD, in 0.1 degrees
                           upsEEnvironmentHumidity 1.3.6.1.4.1.935.10.1.1.6.2
                               upsEEnvironmentCurrentHumidity 1.3.6.1.4.1.935.10.1.1.6.2.1 integer read-only
The measurement of sensor humidity present in %.
                               upsEEnvironmentHumidityHighSetPoint 1.3.6.1.4.1.935.10.1.1.6.2.2 integer read-write
The set point for high humidity warning, in %. This value must be greater than upsEEnvironmentHumidityLowSetPoint.
                               upsEEnvironmentHumidityHighStatus 1.3.6.1.4.1.935.10.1.1.6.2.3 integer read-write
To enable/disable high set point check with emd humidity. Enumeration: 'enable': 1, 'disable': 2.
                               upsEEnvironmentHumidityLowSetPoint 1.3.6.1.4.1.935.10.1.1.6.2.4 integer read-write
The set point for low humidity warning, in %. This value must be less than upsEEnvironmentHumidityHighSetPoint.
                               upsEEnvironmentHumidityLowStatus 1.3.6.1.4.1.935.10.1.1.6.2.5 integer read-write
To enable/disable high set point check with emd humidity. Enumeration: 'enable': 1, 'disable': 2.
                               upsEEnvironmentHumidityOffset 1.3.6.1.4.1.935.10.1.1.6.2.6 integer read-write
The offset to calibrate humidity of EMD, in %.
                           upsEEnvironmentContactsNum 1.3.6.1.4.1.935.10.1.1.6.3 nonnegativeinteger read-only
The number of environment contacts, serves as the table index.
                           upsEEnvironmentContactTable 1.3.6.1.4.1.935.10.1.1.6.4 no-access
A list of contacts table entries. The number of entries is given by the value of upsEEnvironmentContactsNum
                               upsEEnvironmentContactEntry 1.3.6.1.4.1.935.10.1.1.6.4.1 no-access
An entry containing information applicable to a particular contact
                                   upsEEnvironmentContactIndex 1.3.6.1.4.1.935.10.1.1.6.4.1.1 positiveinteger no-access
The number of environment contacts. Serves as index for environment contact table
                                   upsEEnvironmentContactType 1.3.6.1.4.1.935.10.1.1.6.4.1.2 integer read-write
operation type Enumeration: 'normallyOpen': 1, 'normallyClosed': 2, 'notUsed': 3.
                                   upsEEnvironmentContactState 1.3.6.1.4.1.935.10.1.1.6.4.1.3 integer read-only
The mandatory status. Enumeration: 'closedWithNotice': 4, 'openWithNotice': 3, 'open': 1, 'closed': 2.
                                   upsEEnvironmentContactDescription 1.3.6.1.4.1.935.10.1.1.6.4.1.4 displaystring read-write
Description of environment contact.
                       upsEBatteryTest 1.3.6.1.4.1.935.10.1.1.7
                           upsEBatteryTestStart 1.3.6.1.4.1.935.10.1.1.7.1 integer read-write
This object specify the battery test type and initiate battery test. If battTestWithTime selected, the test time is refer to upsEBatteryTestSettingTime. Enumeration: 'none': 1, 'batteryTestWithTime': 4, 'batteryTest10Sec': 2, 'cancelBatteryTest': 5, 'batteryTestUntilLow': 3, 'clearBatteryInfo': 6.
                           upsEBatteryTestSettingTime 1.3.6.1.4.1.935.10.1.1.7.2 nonnegativeinteger read-write
The object specify the test time for battery test in seconds.
                           upsEBatteryTestResult 1.3.6.1.4.1.935.10.1.1.7.3 integer read-only
This object indicate the test result of battery. Enumeration: 'notPossible': 5, 'failureOrWarning': 4, 'processing': 2, 'idle': 1, 'noFailure': 3, 'testCancel': 6.
                           upsEBatteryTestStartTime 1.3.6.1.4.1.935.10.1.1.7.4 displaystring read-only
The value of the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsETestBatteryTestResult is noTestsInitiated(6), upsETestStartTime has the value 01/01/1970 00:00:00.
                           upsEBatteryTestElapsedTime 1.3.6.1.4.1.935.10.1.1.7.5 displaystring read-only
The amount of time in format hh:mm:ss, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is idle(1), upsTestElapsedTime has the value 00:00:00.
                           upsEBatteryTestScheduleTable 1.3.6.1.4.1.935.10.1.1.7.6 no-access
This table describes the schedule for automatically battery test.
                               upsEBatteryTestScheduleEntry 1.3.6.1.4.1.935.10.1.1.7.6.1 no-access
An entry containing information applicable to schedule test.
                                   upsEBatteryTestScheduleIndex 1.3.6.1.4.1.935.10.1.1.7.6.1.1 positiveinteger no-access
The index of battery test scheduled.
                                   upsEBatteryTestScheduleDay 1.3.6.1.4.1.935.10.1.1.7.6.1.2 integer read-write
The weekday or specaial day on which the UPS should start battery test. Enumeration: 'wednsday': 3, 'none': 9, 'monday': 1, 'thusday': 4, 'tuesday': 2, 'friday': 5, 'sunday': 7, 'specialday': 8, 'saturday': 6.
                                   upsEBatteryTestScheduleTime 1.3.6.1.4.1.935.10.1.1.7.6.1.3 displaystring read-write
The time that the battery test will be initiated in hh:mm format.
                                   upsEBatteryTestScheduleType 1.3.6.1.4.1.935.10.1.1.7.6.1.5 integer read-write
The type of battery test. Enumeration: 'none': 1, 'batteryTest10sec': 2, 'batteryTestUntilLow': 3, 'batteryTestWithTime': 4.
                                   upsEBatteryTestScheduleTestWithTime 1.3.6.1.4.1.935.10.1.1.7.6.1.6 nonnegativeinteger read-write
The battery time of setting time test in seconds.
                                   upsEBatteryTestScheduleSpecialDay 1.3.6.1.4.1.935.10.1.1.7.6.1.7 displaystring read-write
The special day that the battery test will be initiated in dd/mm/yyyy format.
                       upsEControl 1.3.6.1.4.1.935.10.1.1.8
                           upsEControlOutputOffDelay 1.3.6.1.4.1.935.10.1.1.8.1 nonnegativeinteger read-write
Setting this value to other than zero will cause the UPS output to turn off after the number of seconds.
                           upsEControlOutputOnDelay 1.3.6.1.4.1.935.10.1.1.8.2 nonnegativeinteger read-write
Setting this value to other than zero will cause the UPS output to turn on after the number of seconds.
                           upsEControlOutputOnOffControl 1.3.6.1.4.1.935.10.1.1.8.3 integer read-write
upsEOutputOff ( 1 ) indicates the shutdown sequence, upsEOutputOffCancel ( 2 ) indicates cancel the shutdown sequence, upsESleep( 3 ) indicates shutdown UPS first, then switch on. Enumeration: 'upsESleep': 3, 'none': 4, 'upsEOutputOffCancel': 2, 'upsEOutputOff': 1.
                           upsEShutdownEventsTable 1.3.6.1.4.1.935.10.1.1.8.4 no-access
This table describes the parametes for shutdown process when shutdown event occurs
                               upsEShutdownEventsEntry 1.3.6.1.4.1.935.10.1.1.8.4.1 no-access
An entry containing information applicable to a particular shutdown event line
                                   upsEShutdownEvent 1.3.6.1.4.1.935.10.1.1.8.4.1.1 integer no-access
The shutdown event identification Enumeration: 'upsEOverTemperature': 4, 'upsEWeeklySchedule': 5, 'upsESpecialSchedule': 6, 'environmentTemperatureOverThreshold': 7, 'belowCapacityLimit': 11, 'belowRemainTimeLimit': 12, 'environmentHumidityOverThreshold': 8, 'upsEOverLoad': 3, 'batteryLow': 2, 'acFail': 1, 'environmentContact1Alarm': 9, 'environmentContact2Alarm': 10.
                                   upsEShutdownEventAction 1.3.6.1.4.1.935.10.1.1.8.4.1.2 integer read-write
Status of the corresponding shutdown Event. When set to disable(), shutdown process will not start when corresponding event occured. Enumeration: 'disable': 1, 'warning': 2, 'shutdownClient': 3, 'shutdownUPS': 4.
                                   upsEShutdownwarningPeriodTime 1.3.6.1.4.1.935.10.1.1.8.4.1.3 nonnegativeinteger read-write
The Delay in seconds after the occurance of the curresponding shutdown event, and warning message should be popped in this period.
                                   upsEShutdownWarningPeriodInterval 1.3.6.1.4.1.935.10.1.1.8.4.1.4 nonnegativeinteger read-write
The frequency of sending warning messages to the connected clients when the curresponding shutdown event occurs. The value is in units of seconds.
                           upsEControlWeeklyScheduleTable 1.3.6.1.4.1.935.10.1.1.8.5 no-access
The table to schedule shutting down the ups by weekly
                               upsEControlWeeklyScheduleEntry 1.3.6.1.4.1.935.10.1.1.8.5.1 no-access
An entry containing information applicable to a particular line
                                   upsEControlWeeklyScheduleIndex 1.3.6.1.4.1.935.10.1.1.8.5.1.1 positiveinteger no-access
the index of schedule events.
                                   upsEWeeklyScheduleShutdownDay 1.3.6.1.4.1.935.10.1.1.8.5.1.2 integer read-write
the weekday on which upsE shoud shutdown Enumeration: 'none': 8, 'monday': 1, 'tuesday': 2, 'friday': 5, 'wednesday': 3, 'thursday': 4, 'sunday': 7, 'saturday': 6.
                                   upsEWeeklyScheduleShutdownTime 1.3.6.1.4.1.935.10.1.1.8.5.1.3 displaystring read-write
The time that the process of shutting down the UPS will be initiated in hh:mm format.
                                   upsEWeeklyScheduleRestartDay 1.3.6.1.4.1.935.10.1.1.8.5.1.4 integer read-write
the weekday on which the UPS should restart. Enumeration: 'none': 8, 'monday': 1, 'tuesday': 2, 'friday': 5, 'wednesday': 3, 'thursday': 4, 'sunday': 7, 'saturday': 6.
                                   upsEWeeklyScheduleRestartTime 1.3.6.1.4.1.935.10.1.1.8.5.1.5 displaystring read-write
The time the UPS will restart in hh:mm format.
                           upsEControlSpecialDayScheduleTable 1.3.6.1.4.1.935.10.1.1.8.6 no-access
The table to schedule shutting down the ups.
                               upsEControlSpecialDayScheduleEntry 1.3.6.1.4.1.935.10.1.1.8.6.1 no-access
An entry containing information applicable to a particular line.
                                   upsEControlSpecialDayScheduleIndex 1.3.6.1.4.1.935.10.1.1.8.6.1.1 positiveinteger no-access
The index of special day schedule.
                                   upsESpecialDayScheduleShutdownDay 1.3.6.1.4.1.935.10.1.1.8.6.1.2 displaystring read-write
The special day on which UPS should shutdown with the format of DD/MM/YYYY.
                                   upsESpecialDayScheduleShutdownTime 1.3.6.1.4.1.935.10.1.1.8.6.1.3 displaystring read-write
The time that the process of shutting down the UPS will be initiated in hh:mm format.
                                   upsESpecialDayScheduleRestartDay 1.3.6.1.4.1.935.10.1.1.8.6.1.4 displaystring read-write
The special day on which the UPS should restart with the format of DD/MM/YYYY.
                                   upsESpecialDayScheduleRestartTime 1.3.6.1.4.1.935.10.1.1.8.6.1.5 displaystring read-write
The time the UPS will restart in hh:mm format.
                           upsESystemMasterOffDelay 1.3.6.1.4.1.935.10.1.1.8.7 integer read-only
The UPS output will shutdown after the indicated number of seconds, -1 indicate no action.
                           upsESystemMasterOnDelay 1.3.6.1.4.1.935.10.1.1.8.8 integer read-only
The UPS output will start on after the indicated number of seconds, -1 indicate no action.
                       upsETrapControl 1.3.6.1.4.1.935.10.1.1.9
                           upsETrapsReceiversTable 1.3.6.1.4.1.935.10.1.1.9.1 no-access
This table list the managers'IP to send traps to.
                               upsETrapsReceiversEntry 1.3.6.1.4.1.935.10.1.1.9.1.1 no-access
An entry containing information applicable to a particular input line.
                                   upsETrapsReceiversIndex 1.3.6.1.4.1.935.10.1.1.9.1.1.1 positiveinteger no-access
The index to a trap receiver entry
                                   upsETrapsReceiverAddress 1.3.6.1.4.1.935.10.1.1.9.1.1.2 displaystring read-write
The IP address of the manager to send a trap to.
                                   upsETrapReceiverCommunityString 1.3.6.1.4.1.935.10.1.1.9.1.1.3 displaystring read-write
The community name to use in the trap when sent to the manager.
                                   upsETrapType 1.3.6.1.4.1.935.10.1.1.9.1.1.4 integer read-write
The type of trap to be received by the manager. Enumeration: 'none': 1, 'rfc1628Trap': 2, 'eppcTrap': 3.
                                   upsETrapsSeverityLevel 1.3.6.1.4.1.935.10.1.1.9.1.1.5 integer read-write
The severity level of traps to be received by this manager. Enumeration: 'severe': 3, 'warning': 2, 'informational': 1.
                                   upsETrapReceiverDescription 1.3.6.1.4.1.935.10.1.1.9.1.1.6 displaystring read-write
Description of trap receivers
                           upsETrapState 1.3.6.1.4.1.935.10.1.1.9.2 displaystring read-only
the values indicate the unrestored traps. For example, after AC fail, the agent send the trap 1(AC Fail) and trap 7(battery on) to NMS. so the value of upsETrapState should be '1,7'. And then the AC restore, the value of upsETrapState should change to empty.
                   upsETraps 1.3.6.1.4.1.935.10.1.2
                         upsEPowerFail 1.3.6.1.4.1.935.10.1.20.1
WARNING: Utility power not available.
                         upsEPowerRestored 1.3.6.1.4.1.935.10.1.20.2
INFORMATION: Utility power has restored.
                         upsELowBattery 1.3.6.1.4.1.935.10.1.20.3
SEVERE: The UPS batteries are low and will soon be exhausted.
                         upsEReturnFromLowBattery 1.3.6.1.4.1.935.10.1.20.4
INFORMATION: The UPS has return from a low battery condition.
                         upsEFailed 1.3.6.1.4.1.935.10.1.20.5
SEVERE: The UPS is not working fine.
                         upsEOk 1.3.6.1.4.1.935.10.1.20.6
INFORMATION: The UPS is working fine.
                         upsEOnBattery 1.3.6.1.4.1.935.10.1.20.7
WARNING: The UPS has switched to battery backup power.
                         upsENotOnBattery 1.3.6.1.4.1.935.10.1.20.8
INFORMATION: The UPS is not on battery power.
                         upsETestInProgress 1.3.6.1.4.1.935.10.1.20.9
INFORMATION: The testing is going on ups.
                         upsETestOver 1.3.6.1.4.1.935.10.1.20.10
INFORMATION: The testing of UPS is completed.
                         upsEBypassOn 1.3.6.1.4.1.935.10.1.20.11
INFORMATION: The UPS has enabled bypass.
                         upsEOnline 1.3.6.1.4.1.935.10.1.20.12
INFORMATION: The UPS is not on Bypass and return to normal status.
                         upsECommunicationLost 1.3.6.1.4.1.935.10.1.20.13
SEVERE: Communication to the UPS has been lost.
                         upsECommunicationEstablished 1.3.6.1.4.1.935.10.1.20.14
INFORMATION: Communication with the UPS has been established.
                         upsEGoingShutdown 1.3.6.1.4.1.935.10.1.20.15
WARNING: The UPS is going to shutdown output.
                         upsEShutdownCancelled 1.3.6.1.4.1.935.10.1.20.16
INFORMATION: The UPS is not going to shutdown output.
                         upsEOutlet1GoingShutdown 1.3.6.1.4.1.935.10.1.20.17
WARNING: The UPS is going to shutdown outlet1.
                         upsEOutlet1ShutdownCancelled 1.3.6.1.4.1.935.10.1.20.18
INFORMATION: The UPS is not going to shutdown outlet1.
                         upsEOutlet2GoingShutdown 1.3.6.1.4.1.935.10.1.20.19
WARNING: The UPS is going to shutdown outlet2.
                         upsEOutlet2ShutdownCancelled 1.3.6.1.4.1.935.10.1.20.20
INFORMATION: The UPS is not going to shutdown outlet2.
                         upsESleeping 1.3.6.1.4.1.935.10.1.20.21
INFORMATION: UPS has entered sleep mode and power to load has been cut off.
                         upsEWokeUp 1.3.6.1.4.1.935.10.1.20.22
INFORMATION: The UPS woke up from sleep mode and power to load has been restored.
                         upsEOverTemperature 1.3.6.1.4.1.935.10.1.20.23
WARNING: The UPS temperature is over the setting limit.
                         upsENotOverTemperature 1.3.6.1.4.1.935.10.1.20.24
INFORMATION: The UPS temperature is not over the setting limit.
                         upsEOverLoad 1.3.6.1.4.1.935.10.1.20.25
WARNING: The UPS load is over the setting limit.
                         upsENotOverLoad 1.3.6.1.4.1.935.10.1.20.26
INFORMATION: The UPS load is not over the setting limit.
                         upsEModuleInserted 1.3.6.1.4.1.935.10.1.20.27
WARNING: UPS module or charger module plug-in.
                         upsEModuleRemoved 1.3.6.1.4.1.935.10.1.20.28
WARNING: UPS module or charger module unplugs.
                         sensorTemperatureTooHigh 1.3.6.1.4.1.935.10.1.20.29
WARNING: Sensor Temperature over high Set point.
                         sensorTemperatureNotHigh 1.3.6.1.4.1.935.10.1.20.30
INFORMATION: Sensor Temperature not over high Set point.
                         sensorTemperatureTooLow 1.3.6.1.4.1.935.10.1.20.31
WARNING: Sensor Temperature under low Set point.
                         sensorTemperatureNotLow 1.3.6.1.4.1.935.10.1.20.32
INFORMATION: Sensor Temperature not under low Set point.
                         sensorHumidityTooHigh 1.3.6.1.4.1.935.10.1.20.33
WARNING: Sensor Humidity over high Set point.
                         sensorHumidityNotHigh 1.3.6.1.4.1.935.10.1.20.34
INFORMATION: Sensor Humidity not over high Set point.
                         sensorHumidityTooLow 1.3.6.1.4.1.935.10.1.20.35
WARNING: Sensor Humidity under low Set point.
                         sensorHumidityNotLow 1.3.6.1.4.1.935.10.1.20.36
INFORMATION: Sensor Humidity not under low Set point.
                         contactAlarm1Active 1.3.6.1.4.1.935.10.1.20.37
WARNING: Contact Alarm-1 activated.
                         concactAlarm1Normal 1.3.6.1.4.1.935.10.1.20.38
INFORMATION: Contact Alarm-1 not active.
                         contactAlarm2Active 1.3.6.1.4.1.935.10.1.20.39
WARNING: Contact Alarm-2 activated.
                         contactAlarm2Normal 1.3.6.1.4.1.935.10.1.20.40
INFORMATION: Contact Alarm-2 not active.
                         upsEInternalwarning 1.3.6.1.4.1.935.10.1.20.41
WARNING: Internal warning.
                         upsEReturnFromInternalwarning 1.3.6.1.4.1.935.10.1.20.42
INFORMATION: Return from Internal warning.
                         upsEEPOActive 1.3.6.1.4.1.935.10.1.20.43
WARNING: EPO Active.
                         upsEReturnFromEPOActive 1.3.6.1.4.1.935.10.1.20.44
INFORMATION: Return from EPO Active.
                         upsEModuleUnlock 1.3.6.1.4.1.935.10.1.20.45
WARNING: Module Unlock.
                         upsEReturnFromModuleUnlock 1.3.6.1.4.1.935.10.1.20.46
INFORMATION: Return from Module Unlock.
                         upsEMain1Neutralloss 1.3.6.1.4.1.935.10.1.20.47
WARNING: Main 1 Neutral loss.
                         upsEReturnFromMain1Neutralloss 1.3.6.1.4.1.935.10.1.20.48
INFORMATION: Return from Main 1 Neutral loss.
                         upsEMain1phaseerror 1.3.6.1.4.1.935.10.1.20.49
WARNING: Main 1 phase error.
                         upsEReturnFromMain1phaseerror 1.3.6.1.4.1.935.10.1.20.50
INFORMATION: Return from Main 1 phase error.
                         upsESitefault 1.3.6.1.4.1.935.10.1.20.51
WARNING: Site fault.
                         upsEReturnFromSitefault 1.3.6.1.4.1.935.10.1.20.52
INFORMATION: Return from Site fault.
                         upsEBypassAbnormal 1.3.6.1.4.1.935.10.1.20.53
WARNING: Bypass Abnormal.
                         upsEReturnFromBypassAbnormal 1.3.6.1.4.1.935.10.1.20.54
INFORMATION: Return from Bypass Abnormal.
                         upsEBypassPhaseError 1.3.6.1.4.1.935.10.1.20.55
WARNING: Bypass Phase Error.
                         upsEReturnFromBypassPhaseError 1.3.6.1.4.1.935.10.1.20.56
INFORMATION: Return from Bypass Phase Error.
                         upsEBatteryOpen 1.3.6.1.4.1.935.10.1.20.57
WARNING: Battery Open.
                         upsEReturnFromBatteryOpen 1.3.6.1.4.1.935.10.1.20.58
INFORMATION: Return from Battery Open.
                         upsEBatteryOverCharge 1.3.6.1.4.1.935.10.1.20.59
WARNING: Battery Over Charge.
                         upsEReturnFromBatteryOverCharge 1.3.6.1.4.1.935.10.1.20.60
INFORMATION: Return from Battery Over Charge.
                         upsEBatteryReverse 1.3.6.1.4.1.935.10.1.20.61
WARNING: Battery Reverse.
                         upsEReturnFromBatteryReverse 1.3.6.1.4.1.935.10.1.20.62
INFORMATION: Return from Battery Reverse.
                         upsEOverloadforewarning 1.3.6.1.4.1.935.10.1.20.63
WARNING: Overload forewarning.
                         upsEReturnFromOverloadforewarning 1.3.6.1.4.1.935.10.1.20.64
INFORMATION: Return from Overload forewarning.
                         upsEOverloadWarning 1.3.6.1.4.1.935.10.1.20.65
WARNING: Overload Warning.
                         upsEReturnFromOverloadWarning 1.3.6.1.4.1.935.10.1.20.66
INFORMATION: Return from Overload Warning.
                         upsEFanLock 1.3.6.1.4.1.935.10.1.20.67
WARNING: Fan Lock.
                         upsEReturnFromFanLock 1.3.6.1.4.1.935.10.1.20.68
INFORMATION: Return from Fan Lock.
                         upsEMaintaincoverisopen 1.3.6.1.4.1.935.10.1.20.69
WARNING: Maintain cover is open.
                         upsEReturnFromMaintaincoverisopen 1.3.6.1.4.1.935.10.1.20.70
INFORMATION: Return from Maintain cover is open.
                         upsEChargerfault 1.3.6.1.4.1.935.10.1.20.71
WARNING: Charger fault.
                         upsEReturnFromChargerfault 1.3.6.1.4.1.935.10.1.20.72
INFORMATION: Return from Charger fault.
                         upsEModulelocationerror 1.3.6.1.4.1.935.10.1.20.73
WARNING: Module location error.
                         upsEReturnFromModulelocationerror 1.3.6.1.4.1.935.10.1.20.74
INFORMATION: Return from Module location error.
                         upsETurnonabnormal 1.3.6.1.4.1.935.10.1.20.75
WARNING: Turn on abnormal.
                         upsEReturnFromTurnonabnormal 1.3.6.1.4.1.935.10.1.20.76
INFORMATION: Return from Turn on abnormal.
                         upsERedundancyloss 1.3.6.1.4.1.935.10.1.20.77
WARNING: Redundancy loss.
                         upsEReturnFromRedundancyloss 1.3.6.1.4.1.935.10.1.20.78
INFORMATION: Return from Redundancy loss.
                         upsEHotSwapActived 1.3.6.1.4.1.935.10.1.20.79
WARNING: Hot Swap Active.
                         upsEReturnFromHotSwapActived 1.3.6.1.4.1.935.10.1.20.80
INFORMATION: Return from Hot Swap Active.
                         upsEBatteryInform 1.3.6.1.4.1.935.10.1.20.81
WARNING: Battery Inform.
                         upsEReturnFromBatteryInform 1.3.6.1.4.1.935.10.1.20.82
INFORMATION: Return from Battery Inform.
                         upsEInspectionInform 1.3.6.1.4.1.935.10.1.20.83
WARNING: Inspection Inform.
                         upsEReturnFromInspectionInform 1.3.6.1.4.1.935.10.1.20.84
INFORMATION: Return from Inspection Inform.
                         upsEGuaranteeInform 1.3.6.1.4.1.935.10.1.20.85
WARNING: Guarantee Inform.
                         upsEReturnFromGuaranteeInform 1.3.6.1.4.1.935.10.1.20.86
INFORMATION: Return from Guarantee Inform.
                         upsETemperatureLow 1.3.6.1.4.1.935.10.1.20.87
WARNING: Temperature Low.
                         upsEReturnFromTemperatureLow 1.3.6.1.4.1.935.10.1.20.88
INFORMATION: Return from Temperature Low.
                         upsETemperatureHigh 1.3.6.1.4.1.935.10.1.20.89
WARNING: Temperature High.
                         upsEReturnFromTemperatureHigh 1.3.6.1.4.1.935.10.1.20.90
INFORMATION: Return from Temperature High.
                         upsEBatteryOverTemperature 1.3.6.1.4.1.935.10.1.20.91
WARNING: Battery Over Temperature.
                         upsEReturnFromBatteryOverTemperature 1.3.6.1.4.1.935.10.1.20.92
INFORMATION: Return from Battery Over Temperature.
                         upsEFanMaintainInform 1.3.6.1.4.1.935.10.1.20.93
WARNING: Fan Maintain Inform.
                         upsEReturnFromFanMaintainInform 1.3.6.1.4.1.935.10.1.20.94
INFORMATION: Return from Fan Maintain Inform.
                         upsEBusCapacitanceMaintainInform 1.3.6.1.4.1.935.10.1.20.95
WARNING: Bus Capacitance Maintain Inform.
                         upsEReturnFromBusCapacitanceMaintainInform 1.3.6.1.4.1.935.10.1.20.96
INFORMATION: Return from Bus Capacitance Maintain Inform.
                         upsESystemOverCapacity 1.3.6.1.4.1.935.10.1.20.97
WARNING: System Over Capacity.
                         upsEReturnFromSystemOverCapacity 1.3.6.1.4.1.935.10.1.20.98
INFORMATION: Return from System Over Capacity.
                         upsEBelowCapacityLimit 1.3.6.1.4.1.935.10.1.20.123
SEVERE: The UPS batteries capacity is lower than setting limit.
                         upsENotBelowCapacityLimit 1.3.6.1.4.1.935.10.1.20.124
INFORMATION: The UPS batteries capacity is not lower than setting limit.
                         upsEBelowRemainTimeLimit 1.3.6.1.4.1.935.10.1.20.125
SEVERE: The UPS batteries backup time is below the setting limit.
                         upsENotBelowRemainTimeLimit 1.3.6.1.4.1.935.10.1.20.126
INFORMATION: The UPS batteries backup time is not below the setting limit.
                         upsELoadSegment1Off 1.3.6.1.4.1.935.10.1.20.127
WARNING: Load segment 1 is off.
                         upsELoadSegment1On 1.3.6.1.4.1.935.10.1.20.128
INFORMATION: Load segment 1 is on.
                         upsELoadSegment2Off 1.3.6.1.4.1.935.10.1.20.129
WARNING: Load segment 2 is off.
                         upsELoadSegment2On 1.3.6.1.4.1.935.10.1.20.130
INFORMATION: Load segment 2 is on.