Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 eltek 1.3.6.1.4.1.12148
An ongoing effort toward a generic MIB for all ELTEK products. This iteration is based on Nextel spec as of May 2005 and is meant tp be a common basic mib for smartpack, aeon gold and mcu control units.
             eltekDistributedPlant 1.3.6.1.4.1.12148.8
                 controlSystem 1.3.6.1.4.1.12148.8.1
                     systemTime 1.3.6.1.4.1.12148.8.1.1
                         systemTimeTime 1.3.6.1.4.1.12148.8.1.1.1 displaystring read-only
The system date and time. Used for event timestamps and logging
                     systemInfoRefresh 1.3.6.1.4.1.12148.8.1.2 integer read-write
This object will re-initialize the agent, updating MIB data values. Enumeration: 'pushbutton': 0, 'refreshdata': 1.
                     systemTrapRepeatRate 1.3.6.1.4.1.12148.8.1.3 integer32 read-write
This object sets the repeat rate of any active traps, in seconds. Entering 0 (zero) will prevent repeating traps - one trap only will be sent per alarm event.
                     systemSendOffTrap 1.3.6.1.4.1.12148.8.1.4 integer read-write
A separate off-trap will be issued when an alarm condition goes off, if this flag is set to 1. Entering 0 (zero) will prevent OFF traps from being transmitted. Enumeration: 'on': 1, 'off': 0.
                     systemNumOfControlUnits 1.3.6.1.4.1.12148.8.1.5 integer32 read-only
The number of expected system controllers (smartpacks, smartnodes stc.) in a distributed system
                     systemControlUnitIndex 1.3.6.1.4.1.12148.8.1.6 integer32 no-access
Index used for navigating int the table of 1 to 8 system controller input groups
                     systemControlUnitTable 1.3.6.1.4.1.12148.8.1.7 no-access
                         systemControlUnitEntry 1.3.6.1.4.1.12148.8.1.7.1 no-access
                             inputControlUnitID 1.3.6.1.4.1.12148.8.1.7.1.1 integer32 read-only
                             inputUserConfigurable1 1.3.6.1.4.1.12148.8.1.7.1.2 integer read-only
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. Enumeration: 'alarm': 1, 'normal': 0.
                             inputUserConfigurable2 1.3.6.1.4.1.12148.8.1.7.1.3 integer read-only
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. Enumeration: 'alarm': 1, 'normal': 0.
                             inputUserConfigurable3 1.3.6.1.4.1.12148.8.1.7.1.4 integer read-only
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. Enumeration: 'alarm': 1, 'normal': 0.
                             inputUserConfigurable4 1.3.6.1.4.1.12148.8.1.7.1.5 integer read-only
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. Enumeration: 'alarm': 1, 'normal': 0.
                             inputUserConfigurable5 1.3.6.1.4.1.12148.8.1.7.1.6 integer read-only
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. Enumeration: 'alarm': 1, 'normal': 0.
                             inputUserConfigurable6 1.3.6.1.4.1.12148.8.1.7.1.7 integer read-only
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. Enumeration: 'alarm': 1, 'normal': 0.
                             inputUserConfigurable7 1.3.6.1.4.1.12148.8.1.7.1.8 integer read-only
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. Enumeration: 'alarm': 1, 'normal': 0.
                             inputUserConfigurable8 1.3.6.1.4.1.12148.8.1.7.1.9 integer read-only
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. Enumeration: 'alarm': 1, 'normal': 0.
                             inputUserConfigurable9 1.3.6.1.4.1.12148.8.1.7.1.10 integer read-only
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. Enumeration: 'alarm': 1, 'normal': 0.
                             inputUserConfigurable10 1.3.6.1.4.1.12148.8.1.7.1.11 integer read-only
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. Enumeration: 'alarm': 1, 'normal': 0.
                     systemLinkStatus 1.3.6.1.4.1.12148.8.1.8 integer read-only
A flag showing the status of the serial port used between the Webpower adapter and the Control system. If this flag shows status linkdown, the propable cause is that the wrong baudrate is set, which again is likely to happen when booting a brand new board. Execute a 'systemInitiateEEPROM' command to fix. Enumeration: 'linkup': 1, 'linkdown': 0.
                     systemInitiateEEPROM 1.3.6.1.4.1.12148.8.1.9 integer read-write
pushbutton function that initiates a forced write of baudrate of 38400bps for the serial port. It also writes default data to the eeprom. This function is used for productiontest only. The 3rd party OS used in this application are not able to write default data to EEPROM at boot time. A minimum set of configuration is thus created in RAM. A production test facility must therefore run this command as a part of the production test for the unit to function properly. Enumeration: 'start': 1, 'pushbutton': 0.
                 dcSystem 1.3.6.1.4.1.12148.8.2
                     dcPlant 1.3.6.1.4.1.12148.8.2.1
                         systemSiteInfo 1.3.6.1.4.1.12148.8.2.1.3
                             systemSiteInfoCustomer 1.3.6.1.4.1.12148.8.2.1.3.1 displaystring read-only
The Customer name (as stored in the Smartpack Control Unit)
                             systemSiteInfoLocation 1.3.6.1.4.1.12148.8.2.1.3.2 displaystring read-only
The system/site Location details (as stored in the Smartpack Control Unit).
                             systemSiteInfoMessage1 1.3.6.1.4.1.12148.8.2.1.3.3 displaystring read-only
The system/site Info Message record #1 (as stored in the Smartpack Control Unit). 31 Bytes.
                             systemSiteInfoMessage2 1.3.6.1.4.1.12148.8.2.1.3.4 displaystring read-only
The system/site Info Message record #2 (as stored in the Smartpack Control Unit). 31 Bytes.
                             systemSiteInfoInstalledDate 1.3.6.1.4.1.12148.8.2.1.3.5 displaystring read-only
The system's Installed Date text string (as stored in the Smartpack Control Unit) 16bytes.
                             systemSiteInfoControllerType 1.3.6.1.4.1.12148.8.2.1.3.6 integer read-only
The system Controller Module currently connected. AL175/MCU=0; AEON Gold=1; AL6000=2; Smartpack=3 Enumeration: 'al175': 0, 'al6000': 2, 'smartpack': 3, 'al4000': 1.
                             systemSiteInfoSystemSeriaNum 1.3.6.1.4.1.12148.8.2.1.3.7 displaystring read-only
The serial number for the complete system
                             systemSiteInfoControllerSeriaNum 1.3.6.1.4.1.12148.8.2.1.3.8 displaystring read-only
The serial number for the system controller
                         systemNominalVoltage 1.3.6.1.4.1.12148.8.2.1.4 integer read-only
The nominal voltage rating. 12V/24V/48V/60V systems 0=48V 1=24V 2=12V 3=26V 4=60V Enumeration: 'prs12v': 2, 'prs24v': 1, 'prs48v': 0, 'prs26v': 3, 'prs60v': 4.
                     systemOperationalStatus 1.3.6.1.4.1.12148.8.2.2 integer read-only
A summary status showing if the system is testing, boosting, floating etc. 0=Float, voltage regulated 1=Float, temperature comp. regulated; 2=equalize 3=battery test Enumeration: 'floattempcomp': 1, 'batteryboost': 2, 'batterytest': 3, 'floatvoltreg': 0.
                 battery 1.3.6.1.4.1.12148.8.3
                     batteryName 1.3.6.1.4.1.12148.8.3.1 displaystring read-only
A descriptive name of the battery installed in the system
                     batteryVoltage 1.3.6.1.4.1.12148.8.3.2 integer32 read-only
The measured battery voltage.
                     batteryCurrent 1.3.6.1.4.1.12148.8.3.3 integer32 read-only
The measured battery current.
                     batteryTemp 1.3.6.1.4.1.12148.8.3.4 integer32 read-only
The battery temperature
                     batteryBreakerStatus 1.3.6.1.4.1.12148.8.3.5 integer read-only
The state of the battery fuse/breaker can be either closed(0) or open(1) Enumeration: 'open': 1, 'closed': 0.
                     batteryChargeCurrentLimitCtrl 1.3.6.1.4.1.12148.8.3.6 integer read-write
Control field for the battery charge limitation feature; 0=inactive, 1=active. Enumeration: 'deactivate': 0, 'activate': 1.
                     batteryChargeCurrentLimitValue 1.3.6.1.4.1.12148.8.3.7 integer32 read-write
Battery charging current limit value
                     batteryTempCompEnable 1.3.6.1.4.1.12148.8.3.8 integer read-write
Enable (0) or Disable (1) Battery Temperature Compensated output regulation mode Enumeration: 'enable': 1, 'disable': 0.
                     batteryFloatVoltConfig 1.3.6.1.4.1.12148.8.3.9 integer32 read-write
The Voltage at which the DC System float charges.
                     batteryEqualizeVoltConfig 1.3.6.1.4.1.12148.8.3.10 integer32 read-write
The Voltage at which the DC System boost charges the batteries.
                     batteryHighMajorAlarmVoltageConfig 1.3.6.1.4.1.12148.8.3.11 integer32 read-write
The High Battery Voltage alarm limit set voltage
                     batteryHighMinorAlarmVoltageConfig 1.3.6.1.4.1.12148.8.3.12 integer32 read-write
The High Battery Voltage alarm limit set voltage
                     batteryLowMajorAlarmVoltageConfig 1.3.6.1.4.1.12148.8.3.13 integer32 read-write
The Low Battery Voltage Alarm limit set voltage
                     batteryLowMinorAlarmVoltageConfig 1.3.6.1.4.1.12148.8.3.14 integer32 read-write
The Very Low Battery Voltage Alarm limit set voltage
                     batteryStartManualTest 1.3.6.1.4.1.12148.8.3.15 integer read-write
This pushbutton will start a manual battery test if otherwise the system allows it. Enumeration: 'starttest': 1, 'pushbutton': 0, 'stoptest': 2.
                     batteryStartManualBoost 1.3.6.1.4.1.12148.8.3.16 integer read-write
This pushbutton will start a manual battery boost if otherwise the system allows it. Enumeration: 'stopboost': 2, 'pushbutton': 0, 'startboost': 1.
                     batteryLVD 1.3.6.1.4.1.12148.8.3.17
                           batteryLVDStatus 1.3.6.1.4.1.12148.8.3.17.1 integer read-only
Contactor is closed(0) or open(1) Enumeration: 'disable': 2, 'disconnect': 1, 'connect': 0.
                           batteryLVDDisconnectVoltage 1.3.6.1.4.1.12148.8.3.17.2 integer32 read-write
The Contactor Disconnect Voltage
                           batteryLVDConnectVoltage 1.3.6.1.4.1.12148.8.3.17.3 integer32 read-write
The Contactor Reconnect Voltage
                     batteryBanksNumofBanks 1.3.6.1.4.1.12148.8.3.18 integer32 read-only
                     batteryBanks 1.3.6.1.4.1.12148.8.3.19
                           batterySymmetryDeltaLimitVoltage 1.3.6.1.4.1.12148.8.3.19.1 integer32 read-write
The allowable deviation of the midpoint battery voltage from the theoretical. Exceeding this value in either direction (+/-) causes an alarm state
                           batteryBanksIndex 1.3.6.1.4.1.12148.8.3.19.2 integer32 no-access
Index used for navigating int the table of 1 to 8 batterybank symmetry groups
                           batteryBanksTable 1.3.6.1.4.1.12148.8.3.19.3 no-access
A table of up to 8 battery banks. Each bank may have up to 8 symmetry or midpoint measuments
                               batteryBanksEntry 1.3.6.1.4.1.12148.8.3.19.3.1 no-access
a distributed control system may contain up to 8 battery banks.
                                   batteryBankID 1.3.6.1.4.1.12148.8.3.19.3.1.1 integer32 read-only
                                   batteryBanksSymmetry1enable 1.3.6.1.4.1.12148.8.3.19.3.1.2 integer read-write
When set to 'on' the the symmetry input is activated. when turned off, measuments for this input is turned off and the correcponding value will read 0 volts and the alarm flag will be turned off Enumeration: 'enable': 1, 'disable': 0.
                                   batteryBanksSymmetry1status 1.3.6.1.4.1.12148.8.3.19.3.1.3 integer read-only
Status (0=Normal; 1=Alarm) of the Battery Monitor channel which corresponds to the batteryMidpointIndex value Enumeration: 'minorAlarm': 1, 'ok': 0, 'majorAlarm': 2, 'disabled': 3, 'error': 4.
                                   batteryBanksSymmetry1deltaVoltage 1.3.6.1.4.1.12148.8.3.19.3.1.4 integer32 read-only
The measured battery voltage deviation from midpoint of the Battery Monitor channel which corresponds to the batteryMidpointIndex value.
                                   batteryBanksSymmetry2enable 1.3.6.1.4.1.12148.8.3.19.3.1.5 integer read-write
When set to 'on' the the symmetry input is activated. when turned off, measuments for this input is turned off and the correcponding value will read 0 volts and the alarm flag will be turned off Enumeration: 'enable': 1, 'disable': 0.
                                   batteryBanksSymmetry2status 1.3.6.1.4.1.12148.8.3.19.3.1.6 integer read-only
Status (0=Normal; 1=Alarm) of the Battery Monitor channel which corresponds to the batteryMidpointIndex value Enumeration: 'minorAlarm': 1, 'ok': 0, 'majorAlarm': 2, 'disabled': 3, 'error': 4.
                                   batteryBanksSymmetry2deltaVoltage 1.3.6.1.4.1.12148.8.3.19.3.1.7 integer32 read-only
The measured battery voltage deviation from midpoint of the Battery Monitor channel which corresponds to the batteryMidpointIndex value.
                                   batteryBanksSymmetry3enable 1.3.6.1.4.1.12148.8.3.19.3.1.8 integer read-write
When set to 'on' the the symmetry input is activated. when turned off, measuments for this input is turned off and the correcponding value will read 0 volts and the alarm flag will be turned off Enumeration: 'enable': 1, 'disable': 0.
                                   batteryBanksSymmetry3status 1.3.6.1.4.1.12148.8.3.19.3.1.9 integer read-only
Status (0=Normal; 1=Alarm) of the Battery Monitor channel which corresponds to the batteryMidpointIndex value Enumeration: 'minorAlarm': 1, 'ok': 0, 'majorAlarm': 2, 'disabled': 3, 'error': 4.
                                   batteryBanksSymmetry3deltaVoltage 1.3.6.1.4.1.12148.8.3.19.3.1.10 integer32 read-only
The measured battery voltage deviation from midpoint of the Battery Monitor channel which corresponds to the batteryMidpointIndex value.
                                   batteryBanksSymmetry4enable 1.3.6.1.4.1.12148.8.3.19.3.1.11 integer read-write
When set to 'on' the the symmetry input is activated. when turned off, measuments for this input is turned off and the correcponding value will read 0 volts and the alarm flag will be turned off Enumeration: 'enable': 1, 'disable': 0.
                                   batteryBanksSymmetry4status 1.3.6.1.4.1.12148.8.3.19.3.1.12 integer read-only
Status (0=Normal; 1=Alarm) of the Battery Monitor channel which corresponds to the batteryMidpointIndex value Enumeration: 'minorAlarm': 1, 'ok': 0, 'majorAlarm': 2, 'disabled': 3, 'error': 4.
                                   batteryBanksSymmetry4deltaVoltage 1.3.6.1.4.1.12148.8.3.19.3.1.13 integer32 read-only
The measured battery voltage deviation from midpoint of the Battery Monitor channel which corresponds to the batteryMidpointIndex value.
                                   batteryBanksSymmetry5enable 1.3.6.1.4.1.12148.8.3.19.3.1.14 integer read-write
When set to 'on' the the symmetry input is activated. when turned off, measuments for this input is turned off and the correcponding value will read 0 volts and the alarm flag will be turned off Enumeration: 'enable': 1, 'disable': 0.
                                   batteryBanksSymmetry5status 1.3.6.1.4.1.12148.8.3.19.3.1.15 integer read-only
Status (0=Normal; 1=Alarm) of the Battery Monitor channel which corresponds to the batteryMidpointIndex value Enumeration: 'minorAlarm': 1, 'ok': 0, 'majorAlarm': 2, 'disabled': 3, 'error': 4.
                                   batteryBanksSymmetry5deltaVoltage 1.3.6.1.4.1.12148.8.3.19.3.1.16 integer32 read-only
The measured battery voltage deviation from midpoint of the Battery Monitor channel which corresponds to the batteryMidpointIndex value.
                                   batteryBanksSymmetry6enable 1.3.6.1.4.1.12148.8.3.19.3.1.17 integer read-write
When set to 'on' the the symmetry input is activated. when turned off, measuments for this input is turned off and the correcponding value will read 0 volts and the alarm flag will be turned off Enumeration: 'enable': 1, 'disable': 0.
                                   batteryBanksSymmetry6status 1.3.6.1.4.1.12148.8.3.19.3.1.18 integer read-only
Status (0=Normal; 1=Alarm) of the Battery Monitor channel which corresponds to the batteryMidpointIndex value Enumeration: 'minorAlarm': 1, 'ok': 0, 'majorAlarm': 2, 'disabled': 3, 'error': 4.
                                   batteryBanksSymmetry6deltaVoltage 1.3.6.1.4.1.12148.8.3.19.3.1.19 integer32 read-only
The measured battery voltage deviation from midpoint of the Battery Monitor channel which corresponds to the batteryMidpointIndex value.
                                   batteryBanksSymmetry7enable 1.3.6.1.4.1.12148.8.3.19.3.1.20 integer read-write
When set to 'on' the the symmetry input is activated. when turned off, measuments for this input is turned off and the correcponding value will read 0 volts and the alarm flag will be turned off Enumeration: 'enable': 1, 'disable': 0.
                                   batteryBanksSymmetry7status 1.3.6.1.4.1.12148.8.3.19.3.1.21 integer read-only
Status (0=Normal; 1=Alarm) of the Battery Monitor channel which corresponds to the batteryMidpointIndex value Enumeration: 'minorAlarm': 1, 'ok': 0, 'majorAlarm': 2, 'disabled': 3, 'error': 4.
                                   batteryBanksSymmetry7deltaVoltage 1.3.6.1.4.1.12148.8.3.19.3.1.22 integer32 read-only
The measured battery voltage deviation from midpoint of the Battery Monitor channel which corresponds to the batteryMidpointIndex value.
                                   batteryBanksSymmetry8enable 1.3.6.1.4.1.12148.8.3.19.3.1.23 integer read-write
When set to 'on' the the symmetry input is activated. when turned off, measuments for this input is turned off and the correcponding value will read 0 volts and the alarm flag will be turned off Enumeration: 'enable': 1, 'disable': 0.
                                   batteryBanksSymmetry8status 1.3.6.1.4.1.12148.8.3.19.3.1.24 integer read-only
Status (0=Normal; 1=Alarm) of the Battery Monitor channel which corresponds to the batteryMidpointIndex value Enumeration: 'minorAlarm': 1, 'ok': 0, 'majorAlarm': 2, 'disabled': 3, 'error': 4.
                                   batteryBanksSymmetry8deltaVoltage 1.3.6.1.4.1.12148.8.3.19.3.1.25 integer32 read-only
The measured battery voltage deviation from midpoint of the Battery Monitor channel which corresponds to the batteryMidpointIndex value.
                 loadDistribution 1.3.6.1.4.1.12148.8.4
                     loadDistributionCurrent 1.3.6.1.4.1.12148.8.4.1 integer32 read-only
The total load current
                     loadDistributionBreakerStatus 1.3.6.1.4.1.12148.8.4.2 integer read-only
The state of the load fuse/breaker can be either closed(0) or open(1) Enumeration: 'open': 1, 'closed': 0.
                     loadDistributionLVDStatus 1.3.6.1.4.1.12148.8.4.3
                         loadLVD1EnableStatus 1.3.6.1.4.1.12148.8.4.3.1 integer read-only
The status of contactors configuration. 'enabled' means that the contactor is i n use. 'disabled' means that the contactor is disconfigured and not in use. Enumeration: 'disabled': 0, 'enabled': 1.
                         loadLVD1Status 1.3.6.1.4.1.12148.8.4.3.2 integer read-only
The primary load Contactor is closed(0) or open(1) Enumeration: 'disable': 2, 'disconnect': 1, 'connect': 0.
                         loadLVD1ConnectVoltage 1.3.6.1.4.1.12148.8.4.3.3 integer32 read-write
The primary loads Contactor Connect Voltage
                         loadLVD1DisconnectVoltage 1.3.6.1.4.1.12148.8.4.3.4 integer32 read-write
The primary load Contactor Disconnect Voltage
                         loadLVD2EnableStatus 1.3.6.1.4.1.12148.8.4.3.5 integer read-only
The status of contactors configuration. 'enabled' means that the contactor is i n use. 'disabled' means that the contactor is disconfigured and not in use. Enumeration: 'disabled': 0, 'enabled': 1.
                         loadLVD2Status 1.3.6.1.4.1.12148.8.4.3.6 integer read-only
The secondary load Contactor is closed(0) or open(1) Enumeration: 'disable': 2, 'disconnect': 1, 'connect': 0.
                         loadLVD2ConnectVoltage 1.3.6.1.4.1.12148.8.4.3.7 integer32 read-write
The secondary load Contactor Connect Voltage
                         loadLVD2DisconnectVoltage 1.3.6.1.4.1.12148.8.4.3.8 integer32 read-write
The secondary loads Contactor Disconnect Voltage
                         loadLVD3EnableStatus 1.3.6.1.4.1.12148.8.4.3.9 integer read-only
The status of contactors configuration. 'enabled' means that the contactor is i n use. 'disabled' means that the contactor is disconfigured and not in use. Enumeration: 'disabled': 0, 'enabled': 1.
                         loadLVD3Status 1.3.6.1.4.1.12148.8.4.3.10 integer read-only
The third critical loads Contactor is closed(0) or open(1) Enumeration: 'disable': 2, 'disconnect': 1, 'connect': 0.
                         loadLVD3ConnectVoltage 1.3.6.1.4.1.12148.8.4.3.11 integer32 read-write
The third critical load Contactor Connect Voltage
                         loadLVD3DisconnectVoltage 1.3.6.1.4.1.12148.8.4.3.12 integer32 read-write
The third critical loads Contactor Disconnect Voltage
                 rectifier 1.3.6.1.4.1.12148.8.5
                     rectifierInstalledRectifiers 1.3.6.1.4.1.12148.8.5.1 integer32 read-only
The installed number of rectifiers for this DC Power System.
                     rectifierRectifiersActive 1.3.6.1.4.1.12148.8.5.2 integer32 read-only
The actual number of active rectifiers in this DC Power System.
                     rectifierTotalCurrent 1.3.6.1.4.1.12148.8.5.3 integer32 read-only
The DC system's total available current
                     rectifierUtilization 1.3.6.1.4.1.12148.8.5.4 integer32 read-only
Utilization in % of available rectifier capacity
                     rectifierStatus 1.3.6.1.4.1.12148.8.5.5
                         rectifierStatusNoIndex 1.3.6.1.4.1.12148.8.5.5.1 integer32 read-write
A starting index for the rectifierStatusTable array
                         rectifierStatusTable 1.3.6.1.4.1.12148.8.5.5.2 no-access
A table listing up to sixteen sequential recifiers, starting from the rectifier number specified by rectifierStatusNoIndex
                             rectifierStatusEntry 1.3.6.1.4.1.12148.8.5.5.2.1 no-access
A row of rectifier status data corresponding to the rectifierStatusNoIndex value
                                 rectifierStatusID 1.3.6.1.4.1.12148.8.5.5.2.1.1 integer32 read-only
The rectifier ID number of the rectifier record.
                                 rectifierStatusStatus 1.3.6.1.4.1.12148.8.5.5.2.1.2 integer read-only
The operational status of the rectifier record. absent (0), active (1), failed (2), walkin (3), disabledbycommand (4) Enumeration: 'active': 1, 'absent': 0, 'walkin': 3, 'failed': 2, 'disabledbycommand': 4.
                                 rectifierStatusOutputCurrent 1.3.6.1.4.1.12148.8.5.5.2.1.3 integer32 read-only
The rectifier current of the rectifier record.
                                 rectifierStatusOutputVoltage 1.3.6.1.4.1.12148.8.5.5.2.1.4 integer32 read-only
The rectifier voltage of the rectifier record.
                                 rectifierStatusTemp 1.3.6.1.4.1.12148.8.5.5.2.1.5 integer32 read-only
The heatsink temperature of the rectifier record.
                                 rectifierStatusType 1.3.6.1.4.1.12148.8.5.5.2.1.6 displaystring read-only
The rectifier article number string of the rectifier record.
                                 rectifierStatusSKU 1.3.6.1.4.1.12148.8.5.5.2.1.7 displaystring read-only
The rectifier Stock Keeping Unit number or other user-defined ID of the rectifier record.
                                 rectifierStatusSerialNo 1.3.6.1.4.1.12148.8.5.5.2.1.8 displaystring read-only
The rectifier serial number string of the rectifier record.
                                 rectifierStatusRevisionLevel 1.3.6.1.4.1.12148.8.5.5.2.1.9 displaystring read-only
The rectifier version number string of the rectifier record.
                 acDistribution 1.3.6.1.4.1.12148.8.6
                     acVoltage1 1.3.6.1.4.1.12148.8.6.1 integer32 read-only
The AC Voltage of phase 1
                     acVoltage2 1.3.6.1.4.1.12148.8.6.2 integer32 read-only
The AC Voltage of phase 2
                     acVoltage3 1.3.6.1.4.1.12148.8.6.3 integer32 read-only
The AC Voltage of phase 3
                 alarmGroup 1.3.6.1.4.1.12148.8.7
                     alarmWellknownAlarms 1.3.6.1.4.1.12148.8.7.1
                         alarmMajorHighBattVolt 1.3.6.1.4.1.12148.8.7.1.1 integer read-only
The Very High Battery Voltage Alarm Enumeration: 'alarm': 1, 'normal': 0.
                         alarmMinorHighBattVolt 1.3.6.1.4.1.12148.8.7.1.2 integer read-only
The High Battery Voltage alarm Enumeration: 'alarm': 1, 'normal': 0.
                         alarmMajorLowBattVolt 1.3.6.1.4.1.12148.8.7.1.3 integer read-only
The Very Low Battery Voltage Alarm Enumeration: 'alarm': 1, 'normal': 0.
                         alarmMinorLowBattVolt 1.3.6.1.4.1.12148.8.7.1.4 integer read-only
The Low Battery Voltage Alarm Enumeration: 'alarm': 1, 'normal': 0.
                         alarmMajorBatteryHighTemp 1.3.6.1.4.1.12148.8.7.1.5 integer read-only
Temperature much too high alarm, or temperature compensation circuit / probe failure alarm Enumeration: 'alarm': 1, 'normal': 0.
                         alarmMinorBatteryHighTemp 1.3.6.1.4.1.12148.8.7.1.6 integer read-only
Temperature much too high alarm Enumeration: 'alarm': 1, 'normal': 0.
                         alarmBatteryDisconnectOpen 1.3.6.1.4.1.12148.8.7.1.7 integer read-only
The Battery Disconnect Contactor alarm Enumeration: 'alarm': 1, 'normal': 0.
                         alarmLVD1open 1.3.6.1.4.1.12148.8.7.1.8 integer read-only
The A Bus (primary loads) Contactor alarm. The contactor dropout voltage has been reached and the contactor will release. Enumeration: 'alarm': 1, 'normal': 0.
                         alarmLVD2open 1.3.6.1.4.1.12148.8.7.1.9 integer read-only
The B Bus (secondary loads) Contactor alarm. The contactor dropout voltage has been reached and the contactor will release. Enumeration: 'alarm': 1, 'normal': 0.
                         alarmLVD3open 1.3.6.1.4.1.12148.8.7.1.10 integer read-only
The C Bus (critical loads) Contactor alarm. The contactor dropout voltage has been reached and the contactor will release. Enumeration: 'alarm': 1, 'normal': 0.
                         alarmACmains 1.3.6.1.4.1.12148.8.7.1.11 integer read-only
The AC voltage has dropped below critical level, or one or more AC input phases was lost. Enumeration: 'alarm': 1, 'normal': 0.
                         alarmBatteryBreakerOpen 1.3.6.1.4.1.12148.8.7.1.12 integer read-only
Battery string disconnect breaker/fuse alarm Enumeration: 'alarm': 1, 'normal': 0.
                         alarmDistributionBreakerOpen 1.3.6.1.4.1.12148.8.7.1.13 integer read-only
The Load Distribution breaker/fuse alarm Enumeration: 'alarm': 1, 'normal': 0.
                         alarmMajorRectifier 1.3.6.1.4.1.12148.8.7.1.14 integer read-only
This is a 'multiple rectifiers have failed' alarm Enumeration: 'alarm': 1, 'normal': 0.
                         alarmMinorRectifier 1.3.6.1.4.1.12148.8.7.1.15 integer read-only
This is a 'one rectifier has failed' alarm Enumeration: 'alarm': 1, 'normal': 0.
                         alarmMajorBatteryMidpoint 1.3.6.1.4.1.12148.8.7.1.16 integer read-only
Battery Symmetry (midpoint) Delta Voltage is badly out of limits alarm Enumeration: 'alarm': 1, 'normal': 0.
                         alarmMinorBatteryMidpoint 1.3.6.1.4.1.12148.8.7.1.17 integer read-only
Battery Symmetry (midpoint) Delta Voltage out of limits alarm Enumeration: 'alarm': 1, 'normal': 0.
                         alarmBatteryLifeEnded 1.3.6.1.4.1.12148.8.7.1.18 integer read-only
The battery capacity has dropped below critical level. A battery test has measured the fully charged capacity to be too low, and thus probably the battery lifecycle to be near expired. Enumeration: 'alarm': 1, 'normal': 0.
                         alarmBatteryTestmodeEntered 1.3.6.1.4.1.12148.8.7.1.19 integer read-only
The system has lowered the battery charge voltage in order to discharge the batteries to a predefinend level. When the criteria for stopping the battery testing is reached, the charge voltage is increased to commence normal charging. Enumeration: 'alarm': 1, 'normal': 0.
                         alarmBatteryBoostmodeEntered 1.3.6.1.4.1.12148.8.7.1.20 integer read-only
The system has increased the battery charge voltage in order to equalize the battery cells charging. When the criteria for stopping the battery equalizing is reached, the charge voltage is lowered to commence normal charging. Enumeration: 'alarm': 1, 'normal': 0.
                 dcSystemTraps 1.3.6.1.4.1.12148.8.8
This branch contains the Alarm Notification Traps, which duplicate the alarmGroup OIDs. Each alarm condition is represented by a Alarm Condition Trap and an associated OFF Trap, which is optionally transmitted according to the state of OID systemSendOffTrap
                     alarmMajorHighBattVoltTrap 1.3.6.1.4.1.12148.8.8.1
The Very High Battery Voltage alarm
                     alarmMinorHighBattVoltTrap 1.3.6.1.4.1.12148.8.8.2
The High Battery Voltage alarm
                     alarmMajorLowBattVoltTrap 1.3.6.1.4.1.12148.8.8.3
The Very Low Battery Voltage Alarm
                     alarmMinorLowBattVoltTrap 1.3.6.1.4.1.12148.8.8.4
The Low Battery Voltage Alarm
                     alarmMajorBatteryHighTempTrap 1.3.6.1.4.1.12148.8.8.5
High Battery temperature alarm or Temperature Compensation circuit / probe failure alarm
                     alarmMinorBatteryHighTempTrap 1.3.6.1.4.1.12148.8.8.6
High Battery temperature alarm
                     alarmBatteryDisconnectOpenTrap 1.3.6.1.4.1.12148.8.8.7
The Battery Disconnect Contactor alarm
                     alarmLVD1openTrap 1.3.6.1.4.1.12148.8.8.8
The A Bus (primary loads) Contactor is open alarm
                     alarmLVD2openTrap 1.3.6.1.4.1.12148.8.8.9
The B Bus (secondary loads) Contactor is open alarm
                     alarmLVD3openTrap 1.3.6.1.4.1.12148.8.8.10
The C Bus (critical loads) Contactor alarm. The contactor dropout voltage has been reached and the contactor is released.
                     alarmACmainsTrap 1.3.6.1.4.1.12148.8.8.11
The AC voltage has dropped below critical level, or one or more AC input phases was lost.
                     alarmBatteryBreakerOpenTrap 1.3.6.1.4.1.12148.8.8.12
Battery string disconnect breaker/fuse alarm
                     alarmDistributionBreakerOpenTrap 1.3.6.1.4.1.12148.8.8.13
The Load Distribution breaker/fuse alarm
                     alarmMajorRectifierTrap 1.3.6.1.4.1.12148.8.8.14
This is a 'multiple rectifiers have failed' alarm
                     alarmMinorRectifierTrap 1.3.6.1.4.1.12148.8.8.15
This is a 'one rectifier has failed' alarm
                     alarmMajorBatteryMidpointTrap 1.3.6.1.4.1.12148.8.8.16
Battery Symmetry (midpoint) Delta Voltage out of 'major fault' limits alarm
                     alarmMinorBatteryMidpointTrap 1.3.6.1.4.1.12148.8.8.17
Battery Symmetry (midpoint) Delta Voltage out of limits alarm
                     alarmBatteryLifeEndedTrap 1.3.6.1.4.1.12148.8.8.18
The battery capacity has dropped below critical level. A battery test has measured the fully charged capacity to be too low, and thus probably the battery lifecycle to be near expired.
                     alarmBatteryTestmodeEnteredTrap 1.3.6.1.4.1.12148.8.8.19
The system has lowered the battery charge voltage in order to discharge the batteries to a predefinend level. When the criteria for stopping the battery testing is reached, the charge voltage is increased to commence normal charging.
                     alarmBatteryBoostmodeEnteredTrap 1.3.6.1.4.1.12148.8.8.20
The system has increased the battery charge voltage in order to equalize the battery cells charging. When the criteria for stopping the battery equalizing is reached, the charge voltage is lowered to commence normal charging.
                     alarmController1proginputTrap 1.3.6.1.4.1.12148.8.8.21
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
                     alarmController2proginputTrap 1.3.6.1.4.1.12148.8.8.22
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
                     alarmController3proginputTrap 1.3.6.1.4.1.12148.8.8.23
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
                     alarmController4proginputTrap 1.3.6.1.4.1.12148.8.8.24
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
                     alarmController5proginputTrap 1.3.6.1.4.1.12148.8.8.25
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
                     alarmController6proginputTrap 1.3.6.1.4.1.12148.8.8.26
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
                     alarmController7proginputTrap 1.3.6.1.4.1.12148.8.8.27
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
                     alarmController8proginputTrap 1.3.6.1.4.1.12148.8.8.28
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.