ELTEK-DISTRIBUTEDV4-MIB: View SNMP OID List / Download MIB
VENDOR: ELTEK ENERGY AS
Home | MIB: ELTEK-DISTRIBUTEDV4-MIB | |||
---|---|---|---|---|
Download as: |
Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
|
|||
Object Name | OID | Type | Access | Info |
eltek | 1.3.6.1.4.1.12148 |
An ongoing effort toward a generic MIB for all ELTEK products. Branch overview: Aeongold branch will be 1 AL175 branch will be 2 AL6000 branch will be 3 Internal used branch will be 4 Internal used branch will be 5 OEM Smartpack branch will be 6 ELTEK Common branch will be 7 (SmartPack, MCU, AEON w/WebPower sw V2.x) ELTEK Distributed branch will be 8 (SmartPack w/WebPower sw V3.x) ELTEK Distributed V2 branch will be 9 (SmartPack w/WebPower sw V4.0) ELTEK Distributed V3 branch will be 9 (SmartPack w/WebPower sw V4.1) |
||
eltekDistributedPlantV3 | 1.3.6.1.4.1.12148.9 | |||
controlSystem | 1.3.6.1.4.1.12148.9.1 | |||
systemTime | 1.3.6.1.4.1.12148.9.1.1 | |||
systemTimeTime | 1.3.6.1.4.1.12148.9.1.1.1 | displaystring | read-only |
The system date and time. Used for event timestamps and logging |
systemInfoRefresh | 1.3.6.1.4.1.12148.9.1.2 | integer | read-write |
This is a push button function that will rebuild all the dynamic SNMP tables. When control units are removed or added this function must be executed to make sure the tables are updated. Enumeration: 'pushbutton': 0, 'refreshdata': 1. |
systemTrapRepeatRate | 1.3.6.1.4.1.12148.9.1.3 | integer32 | read-write |
This object sets the repeat rate of any active traps, in minutes. Entering 0 (zero) will prevent repeating traps - one trap only will be sent per alarm event. |
systemSendOffTrap | 1.3.6.1.4.1.12148.9.1.4 | integer | read-write |
A separate off-trap will be issued when an alarm condition goes off, if this flag is set to 1. Entering 0 (zero) will prevent OFF traps from being transmitted. Enumeration: 'on': 1, 'off': 0. |
systemNumOfControlUnits | 1.3.6.1.4.1.12148.9.1.5 | integer32 | read-only |
The number of SmartPacks in a distributed system. |
systemControlUnitIndex | 1.3.6.1.4.1.12148.9.1.6 | integer32 | no-access |
Index used for navigating in the table for configurable inputs. |
systemControlUnitTable | 1.3.6.1.4.1.12148.9.1.7 | no-access |
This table contains the status of the programmable inputs. There is one row for each SmartPack. |
|
1.3.6.1.4.1.12148.9.1.7.1 | no-access | |||
inputControlUnitID | 1.3.6.1.4.1.12148.9.1.7.1.1 | integer32 | read-only |
The ID of which SmartPack to be read. |
inputUserConfigurable1 | 1.3.6.1.4.1.12148.9.1.7.1.2 | integer | read-only |
Programmable input status. The description of the input is found in the systemControlUnitInputTable Enumeration: 'alarm': 1, 'normal': 0. |
inputUserConfigurable2 | 1.3.6.1.4.1.12148.9.1.7.1.3 | integer | read-only |
Programmable input status. The description of the input is found in the systemControlUnitInputTable Enumeration: 'alarm': 1, 'normal': 0. |
inputUserConfigurable3 | 1.3.6.1.4.1.12148.9.1.7.1.4 | integer | read-only |
Programmable input status. The description of the input is found in the systemControlUnitInputTable Enumeration: 'alarm': 1, 'normal': 0. |
inputUserConfigurable4 | 1.3.6.1.4.1.12148.9.1.7.1.5 | integer | read-only |
Programmable input status. The description of the input is found in the systemControlUnitInputTable Enumeration: 'alarm': 1, 'normal': 0. |
inputUserConfigurable5 | 1.3.6.1.4.1.12148.9.1.7.1.6 | integer | read-only |
Programmable input status. The description of the input is found in the systemControlUnitInputTable Enumeration: 'alarm': 1, 'normal': 0. |
inputUserConfigurable6 | 1.3.6.1.4.1.12148.9.1.7.1.7 | integer | read-only |
Programmable input status. The description of the input is found in the systemControlUnitInputTable Enumeration: 'alarm': 1, 'normal': 0. |
inputUserConfigurable7 | 1.3.6.1.4.1.12148.9.1.7.1.8 | integer | read-only |
Programmable input status. The description of the input is found in the systemControlUnitInputTable Enumeration: 'alarm': 1, 'normal': 0. |
inputUserConfigurable8 | 1.3.6.1.4.1.12148.9.1.7.1.9 | integer | read-only |
Programmable input status. The description of the input is found in the systemControlUnitInputTable Enumeration: 'alarm': 1, 'normal': 0. |
inputUserConfigurable9 | 1.3.6.1.4.1.12148.9.1.7.1.10 | integer | read-only |
Programmable input status. The description of the input is found in the systemControlUnitInputTable Enumeration: 'alarm': 1, 'normal': 0. |
inputUserConfigurable10 | 1.3.6.1.4.1.12148.9.1.7.1.11 | integer | read-only |
Programmable input status. The description of the input is found in the systemControlUnitInputTable Enumeration: 'alarm': 1, 'normal': 0. |
systemLinkStatus | 1.3.6.1.4.1.12148.9.1.8 | integer | read-only |
A flag showing the status of the serial port used between the HEIDI Webpower adapter or embedded WEB/SNMP card and the Smartpack Control system. If this flag shows status linkdown, the propable cause is that the wrong baudrate is set, which again is likely to happen when booting a brand new board. Execute a 'systemInitiateEEPROM' command to fix. Enumeration: 'linkup': 1, 'linkdown': 0. |
systemInitiateEEPROM | 1.3.6.1.4.1.12148.9.1.9 | integer | read-write |
Pushbutton function that initiates a forced write of default data to the SB70/SB72 eeprom. This function is used for productiontest only. The 3rd party OS used in this application are not able to write default data to EEPROM at boot time. A minimum set of configuration is thus created in RAM. A production test facility must therefore run this command as a part of the production test for the unit to function properly. Enumeration: 'start': 1, 'pushbutton': 0. |
systemLastDigInput | 1.3.6.1.4.1.12148.9.1.10 | integer32 | no-access |
The last Prog.Input that generated a trap. Used by Traps only. |
systemTrapCounter | 1.3.6.1.4.1.12148.9.1.11 | counter32 | no-access |
The number of times a trap has been repeated.. Only acessible for Traps. |
systemHeartBeatTrapRepeatRate | 1.3.6.1.4.1.12148.9.1.12 | integer32 | read-write |
The repeat rate for the systemHeartBeatTrap. Setting this value to zero will disable the HeartBeatTrap. |
systemResetManualAlarms | 1.3.6.1.4.1.12148.9.1.13 | integer | read-write |
A pushutton that resets all manually resettable alarms in the controlsystem. Alarms that is not manually resettable will not be affected by this. Enumeration: 'apply': 1, 'pushbutton': 0. |
systemControlUnitInputIndex | 1.3.6.1.4.1.12148.9.1.14 | integer32 | no-access |
Index used for navigating in the table for configurable inputs. |
systemControlUnitInputTable | 1.3.6.1.4.1.12148.9.1.15 | no-access |
This table contains the description of the programmable inputs. There is one row for each SmartPack. Programmable input alarms will have description attached to the traps that explains the alarm. Default description is: ProgInput |
|
1.3.6.1.4.1.12148.9.1.15.1 | no-access | |||
inputUnitID | 1.3.6.1.4.1.12148.9.1.15.1.1 | integer32 | read-only |
The ID of which SmartPack to be read. |
inputUserConfigurableText1 | 1.3.6.1.4.1.12148.9.1.15.1.2 | displaystring | read-only |
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput |
inputUserConfigurableText2 | 1.3.6.1.4.1.12148.9.1.15.1.3 | displaystring | read-only |
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput |
inputUserConfigurableText3 | 1.3.6.1.4.1.12148.9.1.15.1.4 | displaystring | read-only |
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput |
inputUserConfigurableText4 | 1.3.6.1.4.1.12148.9.1.15.1.5 | displaystring | read-only |
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput |
inputUserConfigurableText5 | 1.3.6.1.4.1.12148.9.1.15.1.6 | displaystring | read-only |
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput |
inputUserConfigurableText6 | 1.3.6.1.4.1.12148.9.1.15.1.7 | displaystring | read-only |
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput |
inputUserConfigurableText7 | 1.3.6.1.4.1.12148.9.1.15.1.8 | displaystring | read-only |
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput |
inputUserConfigurableText8 | 1.3.6.1.4.1.12148.9.1.15.1.9 | displaystring | read-only |
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput |
inputUserConfigurableText9 | 1.3.6.1.4.1.12148.9.1.15.1.10 | displaystring | read-only |
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput |
inputUserConfigurableText10 | 1.3.6.1.4.1.12148.9.1.15.1.11 | displaystring | read-only |
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput |
systemResetCtrlSystem | 1.3.6.1.4.1.12148.9.1.16 | integer | read-write |
A pushbutton function that resets the control system. Configuration data will be kept. Enumeration: 'pushbutton': 0, 'reboot': 1. |
dcSystem | 1.3.6.1.4.1.12148.9.2 | |||
dcPlant | 1.3.6.1.4.1.12148.9.2.1 | |||
systemSiteInfo | 1.3.6.1.4.1.12148.9.2.1.3 | |||
systemSiteInfoCustomer | 1.3.6.1.4.1.12148.9.2.1.3.1 | displaystring | read-only |
The Customer name (as stored in the Smartpack Control Unit). |
systemSiteInfoLocation | 1.3.6.1.4.1.12148.9.2.1.3.2 | displaystring | read-only |
The system/site Location details (as stored in the Smartpack Control Unit). |
systemSiteInfoMessage1 | 1.3.6.1.4.1.12148.9.2.1.3.3 | displaystring | read-only |
The system/site Info Message record #1 (as stored in the Smartpack Control Unit). 31 Bytes. |
systemSiteInfoMessage2 | 1.3.6.1.4.1.12148.9.2.1.3.4 | displaystring | read-only |
The system/site Info Message record #2 (as stored in the Smartpack Control Unit). 31 Bytes. |
systemSiteInfoInstalledDate | 1.3.6.1.4.1.12148.9.2.1.3.5 | displaystring | read-only |
The system's Installed Date text string (as stored in the Smartpack Control Unit) 16bytes. |
systemSiteInfoControllerType | 1.3.6.1.4.1.12148.9.2.1.3.6 | integer | read-only |
The system Controller Module currently connected. Smartpack=3 Enumeration: 'al175': 0, 'smartpack': 3, 'al4000': 1, 'al6000': 2. |
systemSiteInfoSystemSeriaNum | 1.3.6.1.4.1.12148.9.2.1.3.7 | displaystring | read-only |
The serial number for the complete system. |
systemSiteInfoControllerSeriaNum | 1.3.6.1.4.1.12148.9.2.1.3.8 | displaystring | read-only |
The serial number for the SmartPack 1. |
systemNominalVoltage | 1.3.6.1.4.1.12148.9.2.1.4 | integer | read-only |
The nominal voltage rating. 24V/48V/60V systems. 0=48V 1=24V 2=Not used 3=Not used 4=60V Enumeration: 'prs12v': 2, 'prs24v': 1, 'prs48v': 0, 'prs26v': 3, 'prs60v': 4. |
systemOperationalStatus | 1.3.6.1.4.1.12148.9.2.2 | integer | read-only |
A summary status showing if the system is testing, boosting, floating etc. 0=Float, voltage regulated 1=Float, temperature comp. regulated; 2=boost 3=battery test Enumeration: 'floattempcomp': 1, 'batteryboost': 2, 'batterytest': 3, 'floatvoltreg': 0. |
battery | 1.3.6.1.4.1.12148.9.3 | |||
batteryName | 1.3.6.1.4.1.12148.9.3.1 | displaystring | read-only |
A descriptive name of the battery installed in the system. |
batteryVoltage | 1.3.6.1.4.1.12148.9.3.2 | integer32 | read-only |
The measured battery voltage. |
batteryCurrent | 1.3.6.1.4.1.12148.9.3.3 | integer32 | read-only |
The measured total battery current. This is the sum of all the enabled shunt measurements in the system. Negative battery current indicates discharging of the batteries. Positive battery current indicates charging of the batteries. |
batteryTemp | 1.3.6.1.4.1.12148.9.3.4 | integer32 | read-only |
The highest value of the enabled battery temperature measurements. Depending on the global setting in the SmartPack, this value will be presented in Celsius or Fahrenheit. |
batteryBreakerStatus | 1.3.6.1.4.1.12148.9.3.5 | integer | read-only |
The state of the battery fuses/breakers can be either normal(0) or alarm(1). Enumeration: 'alarm': 1, 'normal': 0. |
batteryChargeCurrentLimitCtrl | 1.3.6.1.4.1.12148.9.3.6 | integer | read-write |
Enable/disable of the battery charge current limitation feature; 0=disable, 1=enable. Enumeration: 'enable': 1, 'disable': 0. |
batteryChargeCurrentLimitValue | 1.3.6.1.4.1.12148.9.3.7 | integer32 | read-write |
Battery charging current limit value. Used only when AC source is mains feed. |
batteryTempCompEnable | 1.3.6.1.4.1.12148.9.3.8 | integer | read-write |
Enable (0) or Disable (1) of Battery Temperature Compensated output regulation mode Enumeration: 'enable': 1, 'disable': 0. |
batteryFloatVoltConfig | 1.3.6.1.4.1.12148.9.3.9 | integer32 | read-write |
The Voltage at which the DC System float charges. Acts as reference voltage when running temperature compensated charging. |
batteryBoostVoltConfig | 1.3.6.1.4.1.12148.9.3.10 | integer32 | read-write |
The Voltage at which the DC System boost charges the batteries. |
batteryHighMajorAlarmVoltageConfig | 1.3.6.1.4.1.12148.9.3.11 | integer32 | read-write |
The Major High Battery Voltage alarm limit set voltage |
batteryHighMinorAlarmVoltageConfig | 1.3.6.1.4.1.12148.9.3.12 | integer32 | read-write |
The Minor High Battery Voltage alarm limit set voltage |
batteryLowMajorAlarmVoltageConfig | 1.3.6.1.4.1.12148.9.3.13 | integer32 | read-write |
The Major Low Battery Voltage Alarm limit set voltage |
batteryLowMinorAlarmVoltageConfig | 1.3.6.1.4.1.12148.9.3.14 | integer32 | read-write |
The Minor Low Battery Voltage Alarm limit set voltage |
batteryStartManualTest | 1.3.6.1.4.1.12148.9.3.15 | integer | read-write |
This pushbutton will start or stop a manual battery test if the system allows it. Enumeration: 'starttest': 1, 'pushbutton': 0, 'stoptest': 2. |
batteryStartManualBoost | 1.3.6.1.4.1.12148.9.3.16 | integer | read-write |
This pushbutton will start or stop a manual battery boost if the system allows it. Enumeration: 'stopboost': 2, 'pushbutton': 0, 'startboost': 1. |
batteryLVD | 1.3.6.1.4.1.12148.9.3.17 | |||
batteryLVDStatus | 1.3.6.1.4.1.12148.9.3.17.1 | integer | read-only |
The Battery Contactor is connected(0), disconnected(1) or disabled(2) Enumeration: 'disabled': 2, 'connected': 0, 'disconnected': 1. |
batteryLVDDisconnectVoltage | 1.3.6.1.4.1.12148.9.3.17.2 | integer32 | read-write |
The Battery Contactors Disconnect Voltage |
batteryLVDConnectVoltage | 1.3.6.1.4.1.12148.9.3.17.3 | integer32 | read-write |
The Battery Contactors Reconnect Voltage |
batteryBanksNumofBanks | 1.3.6.1.4.1.12148.9.3.18 | integer32 | read-only |
The number of Smartpacks that is used to measure battery parameters. |
batteryBanks | 1.3.6.1.4.1.12148.9.3.19 | |||
batterySymmetryDeltaLimitVoltage | 1.3.6.1.4.1.12148.9.3.19.1 | integer32 | read-write |
The allowable deviation of the symmetry voltage from the theoretical. Exceeding this value in either direction (+/-) causes an alarm state. |
batteryBanksIndex | 1.3.6.1.4.1.12148.9.3.19.2 | integer32 | no-access |
Index used for navigating the rows 1..8 of batteryBanksTable |
batteryBanksTable | 1.3.6.1.4.1.12148.9.3.19.3 | no-access |
A table of up to 8 battery banks. Each banks may have up to 8 symmetry measuments. |
|
1.3.6.1.4.1.12148.9.3.19.3.1 | no-access | |||
batteryBankID | 1.3.6.1.4.1.12148.9.3.19.3.1.1 | integer32 | read-only |
The ID of the selected row in the table. i.e. the battery bank. |
batteryBanksSymmetry1enable | 1.3.6.1.4.1.12148.9.3.19.3.1.2 | integer | read-write |
Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off. Enumeration: 'enable': 1, 'disable': 0. |
batteryBanksSymmetry1status | 1.3.6.1.4.1.12148.9.3.19.3.1.3 | integer | read-only |
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error Enumeration: 'minorAlarm': 1, 'majorAlarm': 2, 'ok': 0, 'disabled': 3, 'error': 4. |
batteryBanksSymmetry1deltaVoltage | 1.3.6.1.4.1.12148.9.3.19.3.1.4 | integer32 | read-only |
The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block. |
batteryBanksSymmetry2enable | 1.3.6.1.4.1.12148.9.3.19.3.1.5 | integer | read-write |
Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off. Enumeration: 'enable': 1, 'disable': 0. |
batteryBanksSymmetry2status | 1.3.6.1.4.1.12148.9.3.19.3.1.6 | integer | read-only |
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error Enumeration: 'minorAlarm': 1, 'majorAlarm': 2, 'ok': 0, 'disabled': 3, 'error': 4. |
batteryBanksSymmetry2deltaVoltage | 1.3.6.1.4.1.12148.9.3.19.3.1.7 | integer32 | read-only |
The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block. |
batteryBanksSymmetry3enable | 1.3.6.1.4.1.12148.9.3.19.3.1.8 | integer | read-write |
Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off. Enumeration: 'enable': 1, 'disable': 0. |
batteryBanksSymmetry3status | 1.3.6.1.4.1.12148.9.3.19.3.1.9 | integer | read-only |
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error Enumeration: 'minorAlarm': 1, 'majorAlarm': 2, 'ok': 0, 'disabled': 3, 'error': 4. |
batteryBanksSymmetry3deltaVoltage | 1.3.6.1.4.1.12148.9.3.19.3.1.10 | integer32 | read-only |
The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block. |
batteryBanksSymmetry4enable | 1.3.6.1.4.1.12148.9.3.19.3.1.11 | integer | read-write |
Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off. Enumeration: 'enable': 1, 'disable': 0. |
batteryBanksSymmetry4status | 1.3.6.1.4.1.12148.9.3.19.3.1.12 | integer | read-only |
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error Enumeration: 'minorAlarm': 1, 'majorAlarm': 2, 'ok': 0, 'disabled': 3, 'error': 4. |
batteryBanksSymmetry4deltaVoltage | 1.3.6.1.4.1.12148.9.3.19.3.1.13 | integer32 | read-only |
The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block. |
batteryBanksSymmetry5enable | 1.3.6.1.4.1.12148.9.3.19.3.1.14 | integer | read-write |
Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off. Enumeration: 'enable': 1, 'disable': 0. |
batteryBanksSymmetry5status | 1.3.6.1.4.1.12148.9.3.19.3.1.15 | integer | read-only |
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error Enumeration: 'minorAlarm': 1, 'majorAlarm': 2, 'ok': 0, 'disabled': 3, 'error': 4. |
batteryBanksSymmetry5deltaVoltage | 1.3.6.1.4.1.12148.9.3.19.3.1.16 | integer32 | read-only |
The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block. |
batteryBanksSymmetry6enable | 1.3.6.1.4.1.12148.9.3.19.3.1.17 | integer | read-write |
Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off. Enumeration: 'enable': 1, 'disable': 0. |
batteryBanksSymmetry6status | 1.3.6.1.4.1.12148.9.3.19.3.1.18 | integer | read-only |
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error Enumeration: 'minorAlarm': 1, 'majorAlarm': 2, 'ok': 0, 'disabled': 3, 'error': 4. |
batteryBanksSymmetry6deltaVoltage | 1.3.6.1.4.1.12148.9.3.19.3.1.19 | integer32 | read-only |
The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block. |
batteryBanksSymmetry7enable | 1.3.6.1.4.1.12148.9.3.19.3.1.20 | integer | read-write |
Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off. Enumeration: 'enable': 1, 'disable': 0. |
batteryBanksSymmetry7status | 1.3.6.1.4.1.12148.9.3.19.3.1.21 | integer | read-only |
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error Enumeration: 'minorAlarm': 1, 'majorAlarm': 2, 'ok': 0, 'disabled': 3, 'error': 4. |
batteryBanksSymmetry7deltaVoltage | 1.3.6.1.4.1.12148.9.3.19.3.1.22 | integer32 | read-only |
The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block. |
batteryBanksSymmetry8enable | 1.3.6.1.4.1.12148.9.3.19.3.1.23 | integer | read-write |
Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off. Enumeration: 'enable': 1, 'disable': 0. |
batteryBanksSymmetry8status | 1.3.6.1.4.1.12148.9.3.19.3.1.24 | integer | read-only |
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error Enumeration: 'minorAlarm': 1, 'majorAlarm': 2, 'ok': 0, 'disabled': 3, 'error': 4. |
batteryBanksSymmetry8deltaVoltage | 1.3.6.1.4.1.12148.9.3.19.3.1.25 | integer32 | read-only |
The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block. |
batteryBanksNumberOfStrings | 1.3.6.1.4.1.12148.9.3.19.4 | integer32 | read-only |
Number of strings in the power system. |
batteryBanksExtensionIndex | 1.3.6.1.4.1.12148.9.3.19.5 | integer32 | no-access |
Index used for navigating the rows 1..8 of batteryBanksExtensionTable |
batteryBanksExtensionTable | 1.3.6.1.4.1.12148.9.3.19.6 | no-access |
This table shows the measured value on the symmetry inputs. |
|
1.3.6.1.4.1.12148.9.3.19.6.1 | no-access | |||
batteryBanksExtensionID | 1.3.6.1.4.1.12148.9.3.19.6.1.1 | integer32 | read-only |
The ID of the selected row in the table. i.e. the battery bank. |
batteryBanksExtensionSymmetryInputValue1 | 1.3.6.1.4.1.12148.9.3.19.6.1.2 | integer32 | read-only |
The measured voltage on the symmetry input. |
batteryBanksExtensionSymmetryInputValue2 | 1.3.6.1.4.1.12148.9.3.19.6.1.3 | integer32 | read-only |
The measured voltage on the symmetry input. |
batteryBanksExtensionSymmetryInputValue3 | 1.3.6.1.4.1.12148.9.3.19.6.1.4 | integer32 | read-only |
The measured voltage on the symmetry input. |
batteryBanksExtensionSymmetryInputValue4 | 1.3.6.1.4.1.12148.9.3.19.6.1.5 | integer32 | read-only |
The measured voltage on the symmetry input. |
batteryBanksExtensionSymmetryInputValue5 | 1.3.6.1.4.1.12148.9.3.19.6.1.6 | integer32 | read-only |
The measured voltage on the symmetry input. |
batteryBanksExtensionSymmetryInputValue6 | 1.3.6.1.4.1.12148.9.3.19.6.1.7 | integer32 | read-only |
The measured voltage on the symmetry input. |
batteryBanksExtensionSymmetryInputValue7 | 1.3.6.1.4.1.12148.9.3.19.6.1.8 | integer32 | read-only |
The measured voltage on the symmetry input. |
batteryBanksExtensionSymmetryInputValue8 | 1.3.6.1.4.1.12148.9.3.19.6.1.9 | integer32 | read-only |
The measured voltage on the symmetry input. |
batteryCapacityData | 1.3.6.1.4.1.12148.9.3.20 | |||
batteryTimeToDisconnect | 1.3.6.1.4.1.12148.9.3.20.1 | integer32 | read-only |
Remaining time to low voltage battery disconnect. |
batteryCapacityLeft | 1.3.6.1.4.1.12148.9.3.20.2 | integer32 | read-only |
Ampere hours left in the battery. |
batteryCapacityUsed | 1.3.6.1.4.1.12148.9.3.20.3 | integer32 | read-only |
Ampere hours consumed. |
batteryCapacityTotal | 1.3.6.1.4.1.12148.9.3.20.4 | integer32 | read-only |
This is the total Ampere hours of the battery. This value is the installed capacity compensated with the last battery tests quality level |
batteryQuality | 1.3.6.1.4.1.12148.9.3.20.5 | integer32 | read-only |
This is the battery quality (%) of the latest battery test. |
batteryMonitorUnits | 1.3.6.1.4.1.12148.9.3.21 | |||
battmonNumberOfUnits | 1.3.6.1.4.1.12148.9.3.21.1 | integer32 | read-only |
Number of battery monitor units in the power system. |
battmonUnitsIndex | 1.3.6.1.4.1.12148.9.3.21.2 | integer32 | no-access |
Index used for navigating the rows 1..14 of battmonUnitsTable |
battmonUnitsTable | 1.3.6.1.4.1.12148.9.3.21.3 | no-access |
A table of up to 14 battery monitor control units. |
|
1.3.6.1.4.1.12148.9.3.21.3.1 | no-access | |||
batteryMonitorID | 1.3.6.1.4.1.12148.9.3.21.3.1.1 | integer32 | read-only |
The ID of the selected row |
batteryMonitorSymmetry1status | 1.3.6.1.4.1.12148.9.3.21.3.1.2 | integer | read-only |
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error Enumeration: 'minorAlarm': 1, 'majorAlarm': 2, 'ok': 0, 'disabled': 3, 'error': 4. |
batteryMonitorSymmetry1InputValue | 1.3.6.1.4.1.12148.9.3.21.3.1.3 | integer32 | read-only |
The measured voltage on the symmetry input. |
batteryMonitorSymmetry2status | 1.3.6.1.4.1.12148.9.3.21.3.1.4 | integer | read-only |
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error Enumeration: 'minorAlarm': 1, 'majorAlarm': 2, 'ok': 0, 'disabled': 3, 'error': 4. |
batteryMonitorSymmetry2InputValue | 1.3.6.1.4.1.12148.9.3.21.3.1.5 | integer32 | read-only |
The measured voltage on the symmetry input. |
batteryMonitorSymmetry3status | 1.3.6.1.4.1.12148.9.3.21.3.1.6 | integer | read-only |
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error Enumeration: 'minorAlarm': 1, 'majorAlarm': 2, 'ok': 0, 'disabled': 3, 'error': 4. |
batteryMonitorSymmetry3InputValue | 1.3.6.1.4.1.12148.9.3.21.3.1.7 | integer32 | read-only |
The measured voltage on the symmetry input. |
batteryMonitorSymmetry4status | 1.3.6.1.4.1.12148.9.3.21.3.1.8 | integer | read-only |
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error Enumeration: 'minorAlarm': 1, 'majorAlarm': 2, 'ok': 0, 'disabled': 3, 'error': 4. |
batteryMonitorSymmetry4InputValue | 1.3.6.1.4.1.12148.9.3.21.3.1.9 | integer32 | read-only |
The measured voltage on the symmetry input. |
batteryMonitorCurrentValue | 1.3.6.1.4.1.12148.9.3.21.3.1.10 | integer32 | read-only |
The measured current to/from the battery. |
batteryMonitorFuseStatus | 1.3.6.1.4.1.12148.9.3.21.3.1.11 | integer | read-only |
The state of the battery fuse/breaker can be either normal(0) or alarm(1). Enumeration: 'alarm': 1, 'normal': 0. |
batteryMonitorTemperature | 1.3.6.1.4.1.12148.9.3.21.3.1.12 | integer32 | read-only |
The battery temperature. |
batteryHighMajorTempAlarmLevel | 1.3.6.1.4.1.12148.9.3.22 | integer32 | read-write |
This is the Major High Temperature Alarm level. |
batteryHighMinorTempAlarmLevel | 1.3.6.1.4.1.12148.9.3.23 | integer32 | read-write |
This is the Minor High Temperature Alarm level. |
loadDistribution | 1.3.6.1.4.1.12148.9.4 | |||
loadDistributionCurrent | 1.3.6.1.4.1.12148.9.4.1 | integer32 | read-only |
The total load current |
loadDistributionBreakerStatus | 1.3.6.1.4.1.12148.9.4.2 | integer | read-only |
The state of the load fuses/breakers can be either normal(0) or alarm(1) Enumeration: 'alarm': 1, 'normal': 0. |
loadDistributionLVDStatus | 1.3.6.1.4.1.12148.9.4.3 | |||
loadLVD1Enable | 1.3.6.1.4.1.12148.9.4.3.1 | integer | read-only |
The status of contactors configuration. 'enabled' means that the contactor is in use. 'disabled' means that the contactor is disconfigured and not in use. Enumeration: 'disabled': 0, 'enabled': 1. |
loadLVD1Status | 1.3.6.1.4.1.12148.9.4.3.2 | integer | read-only |
The load Contactor 1 is connected(0), disconnected(1) or disabled(2) Enumeration: 'disabled': 2, 'connected': 0, 'disconnected': 1. |
loadLVD1ConnectVoltage | 1.3.6.1.4.1.12148.9.4.3.3 | integer32 | read-write |
LVLD1 Connect Voltage |
loadLVD1DisconnectVoltage | 1.3.6.1.4.1.12148.9.4.3.4 | integer32 | read-write |
LVLD1 Disconnect Voltage |
loadLVD2Enable | 1.3.6.1.4.1.12148.9.4.3.5 | integer | read-only |
The status of contactors configuration. 'enabled' means that the contactor is in use. 'disabled' means that the contactor is disconfigured and not in use. Enumeration: 'disabled': 0, 'enabled': 1. |
loadLVD2Status | 1.3.6.1.4.1.12148.9.4.3.6 | integer | read-only |
The load Contactor 2 is connected(0), disconnected(1) or disabled(2) Enumeration: 'disabled': 2, 'connected': 0, 'disconnected': 1. |
loadLVD2ConnectVoltage | 1.3.6.1.4.1.12148.9.4.3.7 | integer32 | read-write |
LVLD2 Connect Voltage |
loadLVD2DisconnectVoltage | 1.3.6.1.4.1.12148.9.4.3.8 | integer32 | read-write |
LVLD2 Disconnect Voltage |
loadLVD3Enable | 1.3.6.1.4.1.12148.9.4.3.9 | integer | read-only |
The status of contactors configuration. 'enabled' means that the contactor is in use. 'disabled' means that the contactor is disconfigured and not in use. Enumeration: 'disabled': 0, 'enabled': 1. |
loadLVD3Status | 1.3.6.1.4.1.12148.9.4.3.10 | integer | read-only |
The load Contactor 3 is connected(0), disconnected(1) or disabled(2) Enumeration: 'disabled': 2, 'connected': 0, 'disconnected': 1. |
loadLVD3ConnectVoltage | 1.3.6.1.4.1.12148.9.4.3.11 | integer32 | read-write |
LVLD3 Connect Voltage |
loadLVD3DisconnectVoltage | 1.3.6.1.4.1.12148.9.4.3.12 | integer32 | read-write |
LVLD3 Disconnect Voltage |
rectifier | 1.3.6.1.4.1.12148.9.5 | |||
rectifierInstalledRectifiers | 1.3.6.1.4.1.12148.9.5.1 | integer32 | read-only |
The number of installed rectifiers for this DC Power System. |
rectifierRectifiersActive | 1.3.6.1.4.1.12148.9.5.2 | integer32 | read-only |
Not Used! |
rectifierTotalCurrent | 1.3.6.1.4.1.12148.9.5.3 | integer32 | read-only |
The DC system's total delivered rectifier current |
rectifierUtilization | 1.3.6.1.4.1.12148.9.5.4 | integer32 | read-only |
Utilization in % of available rectifier capacity |
rectifierStatus | 1.3.6.1.4.1.12148.9.5.5 | |||
rectifierStatusNoIndex | 1.3.6.1.4.1.12148.9.5.5.1 | integer32 | read-write |
An offset for the rectifierStatusTable array. The rectifier status table has a fixed number of 20 rows. This OID sets the offset for the rectifier in the first row i.e. setting the index to 11 will give a range from rectifier ID12 to ID31. Setting the index to 0 will give a range from rectifier ID1 to ID20. |
rectifierStatusTable | 1.3.6.1.4.1.12148.9.5.5.2 | no-access |
A table listing up to 20 recifiers, starting from the rectifier number specified by rectifierStatusNoIndex |
|
1.3.6.1.4.1.12148.9.5.5.2.1 | no-access |
A row of rectifier status data corresponding to the rectifierStatusNoIndex value |
||
rectifierStatusID | 1.3.6.1.4.1.12148.9.5.5.2.1.1 | integer32 | read-only |
The rectifier ID number of the rectifier. |
rectifierStatusStatus | 1.3.6.1.4.1.12148.9.5.5.2.1.2 | integer | read-only |
The operational status of the rectifier record. Not Present (0), normal (1), alarm (2), notUsed (3), disabled (4) Enumeration: 'disabled': 4, 'notPresent': 0, 'notUsed': 3, 'alarm': 2, 'normal': 1. |
rectifierStatusOutputCurrent | 1.3.6.1.4.1.12148.9.5.5.2.1.3 | integer32 | read-only |
The output current of the rectifier |
rectifierStatusOutputVoltage | 1.3.6.1.4.1.12148.9.5.5.2.1.4 | integer32 | read-only |
The rectifier voltage of the rectifier record. |
rectifierStatusTemp | 1.3.6.1.4.1.12148.9.5.5.2.1.5 | integer32 | read-only |
The input air temperature of the rectifier. |
rectifierStatusType | 1.3.6.1.4.1.12148.9.5.5.2.1.6 | displaystring | read-only |
The rectifier article number string of the rectifier record. |
rectifierStatusSKU | 1.3.6.1.4.1.12148.9.5.5.2.1.7 | displaystring | read-only |
The rectifier part number. |
rectifierStatusSerialNo | 1.3.6.1.4.1.12148.9.5.5.2.1.8 | displaystring | read-only |
The rectifier serial number string of the rectifier record. |
rectifierStatusRevisionLevel | 1.3.6.1.4.1.12148.9.5.5.2.1.9 | displaystring | read-only |
The rectifier HW revision number string of the rectifier record. |
acDistribution | 1.3.6.1.4.1.12148.9.6 | |||
acVoltage1 | 1.3.6.1.4.1.12148.9.6.1 | integer32 | read-only |
The AC Voltage of phase 1 |
acVoltage2 | 1.3.6.1.4.1.12148.9.6.2 | integer32 | read-only |
The AC Voltage of phase 2 |
acVoltage3 | 1.3.6.1.4.1.12148.9.6.3 | integer32 | read-only |
The AC Voltage of phase 3 |
alarmGroup | 1.3.6.1.4.1.12148.9.7 | |||
alarmWellknownAlarms | 1.3.6.1.4.1.12148.9.7.1 | |||
alarmMajorHighBattVolt | 1.3.6.1.4.1.12148.9.7.1.1 | integer | read-only |
The Major High Battery Voltage Alarm Enumeration: 'alarm': 1, 'normal': 0. |
alarmMinorHighBattVolt | 1.3.6.1.4.1.12148.9.7.1.2 | integer | read-only |
The Minor High Battery Voltage alarm Enumeration: 'alarm': 1, 'normal': 0. |
alarmMajorLowBattVolt | 1.3.6.1.4.1.12148.9.7.1.3 | integer | read-only |
The Major Low Battery Voltage Alarm Enumeration: 'alarm': 1, 'normal': 0. |
alarmMinorLowBattVolt | 1.3.6.1.4.1.12148.9.7.1.4 | integer | read-only |
The Minor Low Battery Voltage Alarm Enumeration: 'alarm': 1, 'normal': 0. |
alarmMajorBatteryHighTemp | 1.3.6.1.4.1.12148.9.7.1.5 | integer | read-only |
The Major High Battery Temperature alarm. Enumeration: 'alarm': 1, 'normal': 0. |
alarmMinorBatteryHighTemp | 1.3.6.1.4.1.12148.9.7.1.6 | integer | read-only |
The Minor High Battery Temperature alarm. Enumeration: 'alarm': 1, 'normal': 0. |
alarmBatteryDisconnectOpen | 1.3.6.1.4.1.12148.9.7.1.7 | integer | read-only |
The Battery Disconnect Contactor alarm Enumeration: 'alarm': 1, 'normal': 0. |
alarmLVD1open | 1.3.6.1.4.1.12148.9.7.1.8 | integer | read-only |
The load Contactor 1 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected. Enumeration: 'alarm': 1, 'normal': 0. |
alarmLVD2open | 1.3.6.1.4.1.12148.9.7.1.9 | integer | read-only |
The load Contactor 2 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected. Enumeration: 'alarm': 1, 'normal': 0. |
alarmLVD3open | 1.3.6.1.4.1.12148.9.7.1.10 | integer | read-only |
The load Contactor 3 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected. Enumeration: 'alarm': 1, 'normal': 0. |
alarmACmains | 1.3.6.1.4.1.12148.9.7.1.11 | integer | read-only |
The AC voltage has dropped below critical level, or one or more AC input phases was lost. Enumeration: 'alarm': 1, 'normal': 0. |
alarmBatteryBreakerOpen | 1.3.6.1.4.1.12148.9.7.1.12 | integer | read-only |
A battery breaker/fuse alarm. Enumeration: 'alarm': 1, 'normal': 0. |
alarmDistributionBreakerOpen | 1.3.6.1.4.1.12148.9.7.1.13 | integer | read-only |
A Load Distribution breaker/fuse alarm. Enumeration: 'alarm': 1, 'normal': 0. |
alarmMajorRectifier | 1.3.6.1.4.1.12148.9.7.1.14 | integer | read-only |
This is a Major Rectifier alarm. Enumeration: 'alarm': 1, 'normal': 0. |
alarmMinorRectifier | 1.3.6.1.4.1.12148.9.7.1.15 | integer | read-only |
This is a Minor Rectifier alarm. Enumeration: 'alarm': 1, 'normal': 0. |
alarmMajorBatterySymmetry | 1.3.6.1.4.1.12148.9.7.1.16 | integer | read-only |
Battery Symmetry Delta Voltage Major alarm. Enumeration: 'alarm': 1, 'normal': 0. |
alarmMinorBatterySymmetry | 1.3.6.1.4.1.12148.9.7.1.17 | integer | read-only |
Battery Symmetry Delta Voltage Minor alarm Enumeration: 'alarm': 1, 'normal': 0. |
alarmBatteryLifeEnded | 1.3.6.1.4.1.12148.9.7.1.18 | integer | read-only |
The battery quality has dropped below critical level. A battery test has measured the fully charged capacity to be too low, and thus probably the battery lifecycle to be near expired. Enumeration: 'alarm': 1, 'normal': 0. |
alarmBatteryTestmodeEntered | 1.3.6.1.4.1.12148.9.7.1.19 | integer | read-only |
The system has lowered the battery charge voltage in order to discharge the batteries to a predefined level. When the criteria for stopping the battery testing is reached, the charge voltage is increased to commence normal charging. Enumeration: 'alarm': 1, 'normal': 0. |
alarmBatteryBoostmodeEntered | 1.3.6.1.4.1.12148.9.7.1.20 | integer | read-only |
The system has increased the battery charge voltage in order to boost the battery. When the criteria for stopping the battery boost is reached, the charge voltage is lowered to commence normal charging. Enumeration: 'alarm': 1, 'normal': 0. |
dcSystemTraps | 1.3.6.1.4.1.12148.9.8 |
This branch contains the Alarm Notification Traps, which duplicate the alarmGroup OIDs. Each alarm condition is represented by a Alarm Condition Trap and an associated OFF Trap, which is optionally transmitted according to the state of OID systemSendOffTrap |
||
alarmMajorHighBattVoltTrap | 1.3.6.1.4.1.12148.9.8.1 |
The Major High Battery Voltage alarm |
||
alarmMinorHighBattVoltTrap | 1.3.6.1.4.1.12148.9.8.2 |
The Minor High Battery Voltage alarm |
||
alarmMajorLowBattVoltTrap | 1.3.6.1.4.1.12148.9.8.3 |
The Major Low Battery Voltage Alarm |
||
alarmMinorLowBattVoltTrap | 1.3.6.1.4.1.12148.9.8.4 |
The Minor Low Battery Voltage Alarm |
||
alarmMajorBatteryHighTempTrap | 1.3.6.1.4.1.12148.9.8.5 |
The Major High Battery Temperature alarm. |
||
alarmMinorBatteryHighTempTrap | 1.3.6.1.4.1.12148.9.8.6 |
The Minor High Battery Temperature alarm. |
||
alarmBatteryDisconnectOpenTrap | 1.3.6.1.4.1.12148.9.8.7 |
The Battery Disconnect Contactor alarm |
||
alarmLVD1openTrap | 1.3.6.1.4.1.12148.9.8.8 |
The load Contactor 1 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected. |
||
alarmLVD2openTrap | 1.3.6.1.4.1.12148.9.8.9 |
The load Contactor 2 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected. |
||
alarmLVD3openTrap | 1.3.6.1.4.1.12148.9.8.10 |
The load Contactor 3 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected. |
||
alarmACmainsTrap | 1.3.6.1.4.1.12148.9.8.11 |
The AC voltage has dropped below critical level, or one or more AC input phases was lost. |
||
alarmBatteryBreakerOpenTrap | 1.3.6.1.4.1.12148.9.8.12 |
A battery breaker/fuse alarm. |
||
alarmDistributionBreakerOpenTrap | 1.3.6.1.4.1.12148.9.8.13 |
A Load Distribution breaker/fuse alarm. |
||
alarmMajorRectifierTrap | 1.3.6.1.4.1.12148.9.8.14 |
This is a Major Rectifier alarm. |
||
alarmMinorRectifierTrap | 1.3.6.1.4.1.12148.9.8.15 |
This is a Minor Rectifier alarm. |
||
alarmMajorBatterySymmetryTrap | 1.3.6.1.4.1.12148.9.8.16 |
Battery Symmetry Delta Voltage Major alarm |
||
alarmMinorBatterySymmetryTrap | 1.3.6.1.4.1.12148.9.8.17 |
Battery Symmetry Delta Voltage Minor alarm |
||
alarmBatteryLifeEndedTrap | 1.3.6.1.4.1.12148.9.8.18 |
The battery quality has dropped below critical level. A battery test has measured the fully charged capacity to be too low, and thus probably the battery lifecycle to be near expired. |
||
alarmBatteryTestmodeEnteredTrap | 1.3.6.1.4.1.12148.9.8.19 |
The system has lowered the battery charge voltage in order to discharge the batteries to a predefined level. When the criteria for stopping the battery testing is reached, the charge voltage is increased to commence normal charging. |
||
alarmBatteryBoostmodeEnteredTrap | 1.3.6.1.4.1.12148.9.8.20 |
The system has increased the battery charge voltage in order to boost the battery. When the criteria for stopping the battery boost is reached, the charge voltage is lowered to commence normal charging. |
||
alarmController1proginputTrap | 1.3.6.1.4.1.12148.9.8.21 |
Programmable input alarm for Smartpack 1. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput |
||
alarmController2proginputTrap | 1.3.6.1.4.1.12148.9.8.22 |
Programmable input alarm for Smartpack 2. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput |
||
alarmController3proginputTrap | 1.3.6.1.4.1.12148.9.8.23 |
Programmable input alarm for Smartpack 3. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput |
||
alarmController4proginputTrap | 1.3.6.1.4.1.12148.9.8.24 |
Programmable input alarm for Smartpack 4. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput |
||
alarmController5proginputTrap | 1.3.6.1.4.1.12148.9.8.25 |
Programmable input alarm for Smartpack 5. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput |
||
alarmController6proginputTrap | 1.3.6.1.4.1.12148.9.8.26 |
Programmable input alarm for Smartpack 6. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput |
||
alarmController7proginputTrap | 1.3.6.1.4.1.12148.9.8.27 |
Programmable input alarm for Smartpack 7. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput |
||
alarmController8proginputTrap | 1.3.6.1.4.1.12148.9.8.28 |
Programmable input alarm for Smartpack 8. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput |
||
infoHeartBeatTrap | 1.3.6.1.4.1.12148.9.8.29 |
When enabled, this trap will be transmitted at regular inervals. This trap is not intended to be an alarm but more like some information that the system is alive and the link is up. |