ELTEK-DISTRIBUTED-PLANTV4-MIB: View SNMP OID List / Download MIB

VENDOR: ELTEK ENERGY AS


 Home MIB: ELTEK-DISTRIBUTED-PLANTV4-MIB
Download as:   

Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 eltekDistributedPlantV4 1.3.6.1.4.1.12148.9
     controlSystem 1.3.6.1.4.1.12148.9.1
         systemTime 1.3.6.1.4.1.12148.9.1.1
             systemTimeTime 1.3.6.1.4.1.12148.9.1.1.1 displaystring read-only
The system date and time. Used for event timestamps and logging
         systemInfoRefresh 1.3.6.1.4.1.12148.9.1.2 integer read-write
This is a push button function that will rebuild all the dynamic SNMP tables. When control units are removed or added this function must be executed to make sure the tables are updated. Enumeration: 'pushbutton': 0, 'refreshdata': 1.
         systemTrapRepeatRate 1.3.6.1.4.1.12148.9.1.3 integer32 read-write
This object sets the repeat rate of any active traps, in minutes. Entering 0 (zero) will prevent repeating traps - one trap only will be sent per alarm event.
         systemSendOffTrap 1.3.6.1.4.1.12148.9.1.4 integer read-write
A separate off-trap will be issued when an alarm condition goes off, if this flag is set to 1. Entering 0 (zero) will prevent OFF traps from being transmitted. Enumeration: 'on': 1, 'off': 0.
         systemNumOfControlUnits 1.3.6.1.4.1.12148.9.1.5 integer32 read-only
The number of Control units in a distributed system.
         systemControlUnitIndex 1.3.6.1.4.1.12148.9.1.6 integer32 no-access
Index used for navigating in the table for configurable inputs.
         systemControlUnitTable 1.3.6.1.4.1.12148.9.1.7 no-access
This table contains the status of the programmable inputs. There is one row for each Control unit.
             systemControlUnitEntry 1.3.6.1.4.1.12148.9.1.7.1 no-access
                 inputControlUnitID 1.3.6.1.4.1.12148.9.1.7.1.1 integer32 read-only
The ID of which Control unit to be read.
                 inputUserConfigurable1 1.3.6.1.4.1.12148.9.1.7.1.2 integer read-only
Programmable input status. The description of the input is found in the systemControlUnitInputTable Enumeration: 'alarm': 1, 'normal': 0.
                 inputUserConfigurable2 1.3.6.1.4.1.12148.9.1.7.1.3 integer read-only
Programmable input status. The description of the input is found in the systemControlUnitInputTable Enumeration: 'alarm': 1, 'normal': 0.
                 inputUserConfigurable3 1.3.6.1.4.1.12148.9.1.7.1.4 integer read-only
Programmable input status. The description of the input is found in the systemControlUnitInputTable Enumeration: 'alarm': 1, 'normal': 0.
                 inputUserConfigurable4 1.3.6.1.4.1.12148.9.1.7.1.5 integer read-only
Programmable input status. The description of the input is found in the systemControlUnitInputTable Enumeration: 'alarm': 1, 'normal': 0.
                 inputUserConfigurable5 1.3.6.1.4.1.12148.9.1.7.1.6 integer read-only
Programmable input status. The description of the input is found in the systemControlUnitInputTable Enumeration: 'alarm': 1, 'normal': 0.
                 inputUserConfigurable6 1.3.6.1.4.1.12148.9.1.7.1.7 integer read-only
Programmable input status. The description of the input is found in the systemControlUnitInputTable Enumeration: 'alarm': 1, 'normal': 0.
                 inputUserConfigurable7 1.3.6.1.4.1.12148.9.1.7.1.8 integer read-only
Programmable input status. The description of the input is found in the systemControlUnitInputTable Enumeration: 'alarm': 1, 'normal': 0.
                 inputUserConfigurable8 1.3.6.1.4.1.12148.9.1.7.1.9 integer read-only
Programmable input status. The description of the input is found in the systemControlUnitInputTable Enumeration: 'alarm': 1, 'normal': 0.
                 inputUserConfigurable9 1.3.6.1.4.1.12148.9.1.7.1.10 integer read-only
Programmable input status. The description of the input is found in the systemControlUnitInputTable Enumeration: 'alarm': 1, 'normal': 0.
                 inputUserConfigurable10 1.3.6.1.4.1.12148.9.1.7.1.11 integer read-only
Programmable input status. The description of the input is found in the systemControlUnitInputTable Enumeration: 'alarm': 1, 'normal': 0.
         systemLinkStatus 1.3.6.1.4.1.12148.9.1.8 integer read-only
A flag showing the status of the serial port used between the HEIDI Webpower adapter or embedded WEB/SNMP card and the Smartpack Control system. If this flag shows status linkdown, the propable cause is that the wrong baudrate is set, which again is likely to happen when booting a brand new board. Execute a 'systemInitiateEEPROM' command to fix. Not applicable for ComPack control unit Enumeration: 'linkup': 1, 'linkdown': 0.
         systemInitiateEEPROM 1.3.6.1.4.1.12148.9.1.9 integer read-write
Pushbutton function that initiates a forced write of default data to the SB70/SB72 eeprom. This function is used for productiontest only. The 3rd party OS used in this application are not able to write default data to EEPROM at boot time. A minimum set of configuration is thus created in RAM. A production test facility must therefore run this command as a part of the production test for the unit to function properly. Enumeration: 'start': 1, 'pushbutton': 0.
         systemLastDigInput 1.3.6.1.4.1.12148.9.1.10 integer32 no-access
The last Prog.Input that generated a trap. Used by Traps only.
         systemTrapCounter 1.3.6.1.4.1.12148.9.1.11 counter32 no-access
The number of times a trap has been repeated.. Only acessible for Traps.
         systemHeartBeatTrapRepeatRate 1.3.6.1.4.1.12148.9.1.12 integer32 read-write
The repeat rate for the systemHeartBeatTrap. Setting this value to zero will disable the HeartBeatTrap.
         systemResetManualAlarms 1.3.6.1.4.1.12148.9.1.13 integer read-write
A pushutton that resets all manually resettable alarms in the controlsystem. Alarms that is not manually resettable will not be affected by this. Enumeration: 'apply': 1, 'pushbutton': 0.
         systemControlUnitInputIndex 1.3.6.1.4.1.12148.9.1.14 integer32 no-access
Index used for navigating in the table for configurable inputs.
         systemControlUnitInputTable 1.3.6.1.4.1.12148.9.1.15 no-access
This table contains the description of the programmable inputs. There is one row for each Control unit. Programmable input alarms will have description attached to the traps that explains the alarm. Default description is: ProgInput .x
               systemControlUnitInputEntry 1.3.6.1.4.1.12148.9.1.15.1 no-access
                   inputUnitID 1.3.6.1.4.1.12148.9.1.15.1.1 integer32 read-only
The ID of which Control unit to be read.
                   inputUserConfigurableText1 1.3.6.1.4.1.12148.9.1.15.1.2 displaystring read-only
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .1.
                   inputUserConfigurableText2 1.3.6.1.4.1.12148.9.1.15.1.3 displaystring read-only
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .2.
                   inputUserConfigurableText3 1.3.6.1.4.1.12148.9.1.15.1.4 displaystring read-only
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .3.
                   inputUserConfigurableText4 1.3.6.1.4.1.12148.9.1.15.1.5 displaystring read-only
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .4.
                   inputUserConfigurableText5 1.3.6.1.4.1.12148.9.1.15.1.6 displaystring read-only
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .5.
                   inputUserConfigurableText6 1.3.6.1.4.1.12148.9.1.15.1.7 displaystring read-only
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .6.
                   inputUserConfigurableText7 1.3.6.1.4.1.12148.9.1.15.1.8 displaystring read-only
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .7.
                   inputUserConfigurableText8 1.3.6.1.4.1.12148.9.1.15.1.9 displaystring read-only
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .8.
                   inputUserConfigurableText9 1.3.6.1.4.1.12148.9.1.15.1.10 displaystring read-only
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .9.
                   inputUserConfigurableText10 1.3.6.1.4.1.12148.9.1.15.1.11 displaystring read-only
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .10.
         systemResetCtrlSystem 1.3.6.1.4.1.12148.9.1.16 integer read-write
A pushbutton function that resets the control system. Configuration data will be kept. Enumeration: 'pushbutton': 0, 'reboot': 1.
         ioUnits 1.3.6.1.4.1.12148.9.1.17
               ioUnitNumberOfUnits 1.3.6.1.4.1.12148.9.1.17.1 integer32 read-only
               ioUnitsIndex 1.3.6.1.4.1.12148.9.1.17.2 integer32 no-access
               ioUnitsTable 1.3.6.1.4.1.12148.9.1.17.3 no-access
                   ioUnitsEntry 1.3.6.1.4.1.12148.9.1.17.3.1 no-access
                       ioUnitID 1.3.6.1.4.1.12148.9.1.17.3.1.1 integer32 read-only
                       ioUnitOutDoorTemp1 1.3.6.1.4.1.12148.9.1.17.3.1.2 integer32 read-only
The measured value of the temperature input. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit.
                       ioUnitOutDoorTemp2 1.3.6.1.4.1.12148.9.1.17.3.1.3 integer32 read-only
The measured value of the temperature input. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit.
                       ioUnitFanSpeed1 1.3.6.1.4.1.12148.9.1.17.3.1.4 integer32 read-only
The speed of the cooling/ circulation fan. The speed is a percentage of max RPM.
                       ioUnitFanSpeedDeltaValue1 1.3.6.1.4.1.12148.9.1.17.3.1.5 integer32 read-only
The deviation of the cooling/circulation fans speed set value. Is a percentage of the desired value.
                       ioUnitFanSpeed2 1.3.6.1.4.1.12148.9.1.17.3.1.6 integer32 read-only
The speed of the cooling/ circulation fan. The speed is a percentage of max RPM.
                       ioUnitFanSpeedDeltaValue2 1.3.6.1.4.1.12148.9.1.17.3.1.7 integer32 read-only
The deviation of the cooling/circulation fans speed set value. Is a percentage of the desired value.
                       ioUnitProgInputText1 1.3.6.1.4.1.12148.9.1.17.3.1.8 displaystring read-only
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .1
                       ioUnitProgInputStatus1 1.3.6.1.4.1.12148.9.1.17.3.1.9 integer read-only
Programmable input status. Enumeration: 'alarm': 1, 'normal': 0.
                       ioUnitProgInputText2 1.3.6.1.4.1.12148.9.1.17.3.1.10 displaystring read-only
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .2
                       ioUnitProgInputStatus2 1.3.6.1.4.1.12148.9.1.17.3.1.11 integer read-only
Programmable input status. Enumeration: 'alarm': 1, 'normal': 0.
                       ioUnitProgInputText3 1.3.6.1.4.1.12148.9.1.17.3.1.12 displaystring read-only
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .3
                       ioUnitProgInputStatus3 1.3.6.1.4.1.12148.9.1.17.3.1.13 integer read-only
Programmable input status. Enumeration: 'alarm': 1, 'normal': 0.
                       ioUnitProgInputText4 1.3.6.1.4.1.12148.9.1.17.3.1.14 displaystring read-only
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .4
                       ioUnitProgInputStatus4 1.3.6.1.4.1.12148.9.1.17.3.1.15 integer read-only
Programmable input status. Enumeration: 'alarm': 1, 'normal': 0.
                       ioUnitProgInputText5 1.3.6.1.4.1.12148.9.1.17.3.1.16 displaystring read-only
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .5
                       ioUnitProgInputStatus5 1.3.6.1.4.1.12148.9.1.17.3.1.17 integer read-only
Programmable input status. Enumeration: 'alarm': 1, 'normal': 0.
                       ioUnitProgInputText6 1.3.6.1.4.1.12148.9.1.17.3.1.18 displaystring read-only
Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .6
                       ioUnitProgInputStatus6 1.3.6.1.4.1.12148.9.1.17.3.1.19 integer read-only
Programmable input status. Enumeration: 'alarm': 1, 'normal': 0.
     dcSystem 1.3.6.1.4.1.12148.9.2
         dcPlant 1.3.6.1.4.1.12148.9.2.1
             systemSiteInfo 1.3.6.1.4.1.12148.9.2.1.3
                 systemSiteInfoCustomer 1.3.6.1.4.1.12148.9.2.1.3.1 displaystring read-only
The Customer name (as stored in the Control Unit).
                 systemSiteInfoLocation 1.3.6.1.4.1.12148.9.2.1.3.2 displaystring read-only
The system/site Location details (as stored in the Control Unit).
                 systemSiteInfoMessage1 1.3.6.1.4.1.12148.9.2.1.3.3 displaystring read-only
The system/site Info Message record #1 (as stored in the Control Unit). 31 Bytes.
                 systemSiteInfoMessage2 1.3.6.1.4.1.12148.9.2.1.3.4 displaystring read-only
The system/site Info Message record #2 (as stored in the Control Unit). 31 Bytes.
                 systemSiteInfoInstalledDate 1.3.6.1.4.1.12148.9.2.1.3.5 displaystring read-only
The system's Installed Date text string (as stored in the Control Unit) 16bytes.
                 systemSiteInfoControllerType 1.3.6.1.4.1.12148.9.2.1.3.6 integer read-only
The system Controller Module currently connected. 0 = AL175 1 = AL4000 (Aeon Gold) 2 = AL6000 3 = AL175OEM 4 = MCU 5 = SmartPack 6 = ComPack Enumeration: 'smartpack': 5, 'al6000': 2, 'al4000': 1, 'al175oem': 3, 'al175': 0, 'mc': 4, 'compack': 6.
                 systemSiteInfoSystemSeriaNum 1.3.6.1.4.1.12148.9.2.1.3.7 displaystring read-only
The serial number for the complete system.
                 systemSiteInfoControllerSeriaNum 1.3.6.1.4.1.12148.9.2.1.3.8 displaystring read-only
The serial number for Control unit 1.
             systemNominalVoltage 1.3.6.1.4.1.12148.9.2.1.4 integer read-only
The nominal voltage rating. 24V/48V/60V systems. 0=48V 1=24V 2=Not used 3=Not used 4=60V Enumeration: 'prs12v': 2, 'prs24v': 1, 'prs48v': 0, 'prs26v': 3, 'prs60v': 4.
         systemOperationalStatus 1.3.6.1.4.1.12148.9.2.2 integer read-only
A summary status showing if the system is testing, boosting, floating etc. 0=Float, voltage regulated 1=Float, temperature comp. regulated; 2=boost 3=battery test Enumeration: 'floattempcomp': 1, 'batteryboost': 2, 'batterytest': 3, 'floatvoltreg': 0.
     battery 1.3.6.1.4.1.12148.9.3
         batteryName 1.3.6.1.4.1.12148.9.3.1 displaystring read-only
A descriptive name of the battery installed in the system.
         batteryVoltage 1.3.6.1.4.1.12148.9.3.2 integer32 read-only
The measured battery voltage.
         batteryCurrent 1.3.6.1.4.1.12148.9.3.3 integer32 read-only
The measured total battery current. This is the sum of all the enabled shunt measurements in the system. Negative battery current indicates discharging of the batteries. Positive battery current indicates charging of the batteries. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
         batteryTemp 1.3.6.1.4.1.12148.9.3.4 integer32 read-only
The highest value of the enabled battery temperature measurements. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit.
         batteryBreakerStatus 1.3.6.1.4.1.12148.9.3.5 integer read-only
The state of the battery fuses/breakers can be either normal(0) or alarm(1). Enumeration: 'alarm': 1, 'normal': 0.
         batteryChargeCurrentLimitCtrl 1.3.6.1.4.1.12148.9.3.6 integer read-write
Enable/disable of the battery charge current limitation feature; 0=disable, 1=enable. Enumeration: 'enable': 1, 'disable': 0.
         batteryChargeCurrentLimitValue 1.3.6.1.4.1.12148.9.3.7 integer32 read-write
Battery charging current limit value. Used only when AC source is mains feed. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
         batteryTempCompEnable 1.3.6.1.4.1.12148.9.3.8 integer read-write
Enable (0) or Disable (1) of Battery Temperature Compensated output regulation mode Enumeration: 'enable': 1, 'disable': 0.
         batteryFloatVoltConfig 1.3.6.1.4.1.12148.9.3.9 integer32 read-write
The Voltage at which the DC System float charges. Acts as reference voltage when running temperature compensated charging.
         batteryBoostVoltConfig 1.3.6.1.4.1.12148.9.3.10 integer32 read-write
The Voltage at which the DC System boost charges the batteries.
         batteryHighMajorAlarmVoltageConfig 1.3.6.1.4.1.12148.9.3.11 integer32 read-write
The Major High Battery Voltage alarm limit set voltage
         batteryHighMinorAlarmVoltageConfig 1.3.6.1.4.1.12148.9.3.12 integer32 read-write
The Minor High Battery Voltage alarm limit set voltage
         batteryLowMajorAlarmVoltageConfig 1.3.6.1.4.1.12148.9.3.13 integer32 read-write
The Major Low Battery Voltage Alarm limit set voltage
         batteryLowMinorAlarmVoltageConfig 1.3.6.1.4.1.12148.9.3.14 integer32 read-write
The Minor Low Battery Voltage Alarm limit set voltage
         batteryStartManualTest 1.3.6.1.4.1.12148.9.3.15 integer read-write
This pushbutton will start or stop a manual battery test if the system allows it. Enumeration: 'starttest': 1, 'pushbutton': 0, 'stoptest': 2.
         batteryStartManualBoost 1.3.6.1.4.1.12148.9.3.16 integer read-write
This pushbutton will start or stop a manual battery boost if the system allows it. Enumeration: 'stopboost': 2, 'pushbutton': 0, 'startboost': 1.
         batteryLVD 1.3.6.1.4.1.12148.9.3.17
               batteryLVDStatus 1.3.6.1.4.1.12148.9.3.17.1 integer read-only
The Battery Contactor is connected(0), disconnected(1) or disabled(2) Enumeration: 'disabled': 2, 'connected': 0, 'disconnected': 1.
               batteryLVDDisconnectVoltage 1.3.6.1.4.1.12148.9.3.17.2 integer32 read-write
The Battery Contactors Disconnect Voltage
               batteryLVDConnectVoltage 1.3.6.1.4.1.12148.9.3.17.3 integer32 read-write
The Battery Contactors Reconnect Voltage
         batteryBanksNumofBanks 1.3.6.1.4.1.12148.9.3.18 integer32 read-only
The number of Control units that is used to measure battery parameters.
         batteryBanks 1.3.6.1.4.1.12148.9.3.19
               batterySymmetryDeltaLimitVoltage 1.3.6.1.4.1.12148.9.3.19.1 integer32 read-write
The allowable deviation of the symmetry voltage from the theoretical. Exceeding this value in either direction (+/-) causes an alarm state.
               batteryBanksIndex 1.3.6.1.4.1.12148.9.3.19.2 integer32 no-access
Index used for navigating the rows 1..8 of batteryBanksTable
               batteryBanksTable 1.3.6.1.4.1.12148.9.3.19.3 no-access
A table of up to 8 battery banks. Each banks may have up to 8 symmetry measuments.
                   batteryBanksEntry 1.3.6.1.4.1.12148.9.3.19.3.1 no-access
                       batteryBankID 1.3.6.1.4.1.12148.9.3.19.3.1.1 integer32 read-only
The ID of the selected row in the table. i.e. the battery bank.
                       batteryBanksSymmetry1enable 1.3.6.1.4.1.12148.9.3.19.3.1.2 integer read-write
Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off. Enumeration: 'enable': 1, 'disable': 0.
                       batteryBanksSymmetry1status 1.3.6.1.4.1.12148.9.3.19.3.1.3 integer read-only
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error Enumeration: 'minorAlarm': 1, 'ok': 0, 'majorAlarm': 2, 'disabled': 3, 'error': 4.
                       batteryBanksSymmetry1deltaVoltage 1.3.6.1.4.1.12148.9.3.19.3.1.4 integer32 read-only
The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.
                       batteryBanksSymmetry2enable 1.3.6.1.4.1.12148.9.3.19.3.1.5 integer read-write
Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off. Enumeration: 'enable': 1, 'disable': 0.
                       batteryBanksSymmetry2status 1.3.6.1.4.1.12148.9.3.19.3.1.6 integer read-only
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error Enumeration: 'minorAlarm': 1, 'ok': 0, 'majorAlarm': 2, 'disabled': 3, 'error': 4.
                       batteryBanksSymmetry2deltaVoltage 1.3.6.1.4.1.12148.9.3.19.3.1.7 integer32 read-only
The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.
                       batteryBanksSymmetry3enable 1.3.6.1.4.1.12148.9.3.19.3.1.8 integer read-write
Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off. Enumeration: 'enable': 1, 'disable': 0.
                       batteryBanksSymmetry3status 1.3.6.1.4.1.12148.9.3.19.3.1.9 integer read-only
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error Enumeration: 'minorAlarm': 1, 'ok': 0, 'majorAlarm': 2, 'disabled': 3, 'error': 4.
                       batteryBanksSymmetry3deltaVoltage 1.3.6.1.4.1.12148.9.3.19.3.1.10 integer32 read-only
The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.
                       batteryBanksSymmetry4enable 1.3.6.1.4.1.12148.9.3.19.3.1.11 integer read-write
Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off. Enumeration: 'enable': 1, 'disable': 0.
                       batteryBanksSymmetry4status 1.3.6.1.4.1.12148.9.3.19.3.1.12 integer read-only
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error Enumeration: 'minorAlarm': 1, 'ok': 0, 'majorAlarm': 2, 'disabled': 3, 'error': 4.
                       batteryBanksSymmetry4deltaVoltage 1.3.6.1.4.1.12148.9.3.19.3.1.13 integer32 read-only
The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.
                       batteryBanksSymmetry5enable 1.3.6.1.4.1.12148.9.3.19.3.1.14 integer read-write
Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off. Enumeration: 'enable': 1, 'disable': 0.
                       batteryBanksSymmetry5status 1.3.6.1.4.1.12148.9.3.19.3.1.15 integer read-only
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error Enumeration: 'minorAlarm': 1, 'ok': 0, 'majorAlarm': 2, 'disabled': 3, 'error': 4.
                       batteryBanksSymmetry5deltaVoltage 1.3.6.1.4.1.12148.9.3.19.3.1.16 integer32 read-only
The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.
                       batteryBanksSymmetry6enable 1.3.6.1.4.1.12148.9.3.19.3.1.17 integer read-write
Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off. Enumeration: 'enable': 1, 'disable': 0.
                       batteryBanksSymmetry6status 1.3.6.1.4.1.12148.9.3.19.3.1.18 integer read-only
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error Enumeration: 'minorAlarm': 1, 'ok': 0, 'majorAlarm': 2, 'disabled': 3, 'error': 4.
                       batteryBanksSymmetry6deltaVoltage 1.3.6.1.4.1.12148.9.3.19.3.1.19 integer32 read-only
The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.
                       batteryBanksSymmetry7enable 1.3.6.1.4.1.12148.9.3.19.3.1.20 integer read-write
Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off. Enumeration: 'enable': 1, 'disable': 0.
                       batteryBanksSymmetry7status 1.3.6.1.4.1.12148.9.3.19.3.1.21 integer read-only
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error Enumeration: 'minorAlarm': 1, 'ok': 0, 'majorAlarm': 2, 'disabled': 3, 'error': 4.
                       batteryBanksSymmetry7deltaVoltage 1.3.6.1.4.1.12148.9.3.19.3.1.22 integer32 read-only
The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.
                       batteryBanksSymmetry8enable 1.3.6.1.4.1.12148.9.3.19.3.1.23 integer read-write
Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off. Enumeration: 'enable': 1, 'disable': 0.
                       batteryBanksSymmetry8status 1.3.6.1.4.1.12148.9.3.19.3.1.24 integer read-only
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error Enumeration: 'minorAlarm': 1, 'ok': 0, 'majorAlarm': 2, 'disabled': 3, 'error': 4.
                       batteryBanksSymmetry8deltaVoltage 1.3.6.1.4.1.12148.9.3.19.3.1.25 integer32 read-only
The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.
               batteryBanksNumberOfStrings 1.3.6.1.4.1.12148.9.3.19.4 integer32 read-only
Number of strings in the power system.
               batteryBanksExtensionIndex 1.3.6.1.4.1.12148.9.3.19.5 integer32 no-access
Index used for navigating the rows 1..14 of batteryBanksExtensionTable
               batteryBanksExtensionTable 1.3.6.1.4.1.12148.9.3.19.6 no-access
This table shows the measured value on the symmetry inputs.
                   batteryBanksExtensionEntry 1.3.6.1.4.1.12148.9.3.19.6.1 no-access
                       batteryBanksExtensionID 1.3.6.1.4.1.12148.9.3.19.6.1.1 integer32 read-only
The ID of the selected row in the table. i.e. the battery bank.
                       batteryBanksExtensionSymmetryInputValue1 1.3.6.1.4.1.12148.9.3.19.6.1.2 integer32 read-only
The measured voltage on the symmetry input.
                       batteryBanksExtensionSymmetryInputValue2 1.3.6.1.4.1.12148.9.3.19.6.1.3 integer32 read-only
The measured voltage on the symmetry input.
                       batteryBanksExtensionSymmetryInputValue3 1.3.6.1.4.1.12148.9.3.19.6.1.4 integer32 read-only
The measured voltage on the symmetry input.
                       batteryBanksExtensionSymmetryInputValue4 1.3.6.1.4.1.12148.9.3.19.6.1.5 integer32 read-only
The measured voltage on the symmetry input.
                       batteryBanksExtensionSymmetryInputValue5 1.3.6.1.4.1.12148.9.3.19.6.1.6 integer32 read-only
The measured voltage on the symmetry input.
                       batteryBanksExtensionSymmetryInputValue6 1.3.6.1.4.1.12148.9.3.19.6.1.7 integer32 read-only
The measured voltage on the symmetry input.
                       batteryBanksExtensionSymmetryInputValue7 1.3.6.1.4.1.12148.9.3.19.6.1.8 integer32 read-only
The measured voltage on the symmetry input.
                       batteryBanksExtensionSymmetryInputValue8 1.3.6.1.4.1.12148.9.3.19.6.1.9 integer32 read-only
The measured voltage on the symmetry input.
         batteryCapacityData 1.3.6.1.4.1.12148.9.3.20
               batteryTimeToDisconnect 1.3.6.1.4.1.12148.9.3.20.1 integer32 read-only
Remaining time to low voltage battery disconnect.
               batteryCapacityLeft 1.3.6.1.4.1.12148.9.3.20.2 integer32 read-only
Capacity left in the battery.
               batteryCapacityUsed 1.3.6.1.4.1.12148.9.3.20.3 integer32 read-only
Capacity consumed.
               batteryCapacityTotal 1.3.6.1.4.1.12148.9.3.20.4 integer32 read-only
This is the total Capacity of the battery. This value is the installed capacity compensated with the last battery tests quality level
               batteryQuality 1.3.6.1.4.1.12148.9.3.20.5 integer32 read-only
This is the battery quality (%) of the latest battery test.
         batteryMonitorUnits 1.3.6.1.4.1.12148.9.3.21
               battmonNumberOfUnits 1.3.6.1.4.1.12148.9.3.21.1 integer32 read-only
Number of battery monitor units in the power system.
               battmonUnitsIndex 1.3.6.1.4.1.12148.9.3.21.2 integer32 no-access
Index used for navigating the rows 1..14 of battmonUnitsTable
               battmonUnitsTable 1.3.6.1.4.1.12148.9.3.21.3 no-access
A table of up to 14 battery monitor control units.
                   battmonUnitsEntry 1.3.6.1.4.1.12148.9.3.21.3.1 no-access
                       batteryMonitorID 1.3.6.1.4.1.12148.9.3.21.3.1.1 integer32 read-only
The ID of the selected row
                       batteryMonitorSymmetry1status 1.3.6.1.4.1.12148.9.3.21.3.1.2 integer read-only
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error Enumeration: 'minorAlarm': 1, 'ok': 0, 'majorAlarm': 2, 'disabled': 3, 'error': 4.
                       batteryMonitorSymmetry1InputValue 1.3.6.1.4.1.12148.9.3.21.3.1.3 integer32 read-only
The measured voltage on the symmetry input.
                       batteryMonitorSymmetry2status 1.3.6.1.4.1.12148.9.3.21.3.1.4 integer read-only
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error Enumeration: 'minorAlarm': 1, 'ok': 0, 'majorAlarm': 2, 'disabled': 3, 'error': 4.
                       batteryMonitorSymmetry2InputValue 1.3.6.1.4.1.12148.9.3.21.3.1.5 integer32 read-only
The measured voltage on the symmetry input.
                       batteryMonitorSymmetry3status 1.3.6.1.4.1.12148.9.3.21.3.1.6 integer read-only
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error Enumeration: 'minorAlarm': 1, 'ok': 0, 'majorAlarm': 2, 'disabled': 3, 'error': 4.
                       batteryMonitorSymmetry3InputValue 1.3.6.1.4.1.12148.9.3.21.3.1.7 integer32 read-only
The measured voltage on the symmetry input.
                       batteryMonitorSymmetry4status 1.3.6.1.4.1.12148.9.3.21.3.1.8 integer read-only
Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error Enumeration: 'minorAlarm': 1, 'ok': 0, 'majorAlarm': 2, 'disabled': 3, 'error': 4.
                       batteryMonitorSymmetry4InputValue 1.3.6.1.4.1.12148.9.3.21.3.1.9 integer32 read-only
The measured voltage on the symmetry input.
                       batteryMonitorCurrentValue 1.3.6.1.4.1.12148.9.3.21.3.1.10 integer32 read-only
The measured current to/from the battery. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
                       batteryMonitorFuseStatus 1.3.6.1.4.1.12148.9.3.21.3.1.11 integer read-only
The state of the battery fuse/breaker can be either normal(0) or alarm(1). Enumeration: 'alarm': 1, 'normal': 0.
                       batteryMonitorTemperature 1.3.6.1.4.1.12148.9.3.21.3.1.12 integer32 read-only
The battery temperature.
         batteryHighMajorTempAlarmLevel 1.3.6.1.4.1.12148.9.3.22 integer32 read-write
This is the Major High Temperature Alarm level.
         batteryHighMinorTempAlarmLevel 1.3.6.1.4.1.12148.9.3.23 integer32 read-write
This is the Minor High Temperature Alarm level.
     loadDistribution 1.3.6.1.4.1.12148.9.4
         loadDistributionCurrent 1.3.6.1.4.1.12148.9.4.1 integer32 read-only
The total load current Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
         loadDistributionBreakerStatus 1.3.6.1.4.1.12148.9.4.2 integer read-only
The state of the load fuses/breakers can be either normal(0) or alarm(1) Enumeration: 'alarm': 1, 'normal': 0.
         loadDistributionLVDStatus 1.3.6.1.4.1.12148.9.4.3
             loadLVD1Enable 1.3.6.1.4.1.12148.9.4.3.1 integer read-only
The status of contactors configuration. 'enabled' means that the contactor is in use. 'disabled' means that the contactor is disconfigured and not in use. Enumeration: 'disabled': 0, 'enabled': 1.
             loadLVD1Status 1.3.6.1.4.1.12148.9.4.3.2 integer read-only
The load Contactor 1 is connected(0), disconnected(1) or disabled(2) Enumeration: 'disabled': 2, 'connected': 0, 'disconnected': 1.
             loadLVD1ConnectVoltage 1.3.6.1.4.1.12148.9.4.3.3 integer32 read-write
LVLD1 Connect Voltage
             loadLVD1DisconnectVoltage 1.3.6.1.4.1.12148.9.4.3.4 integer32 read-write
LVLD1 Disconnect Voltage
             loadLVD2Enable 1.3.6.1.4.1.12148.9.4.3.5 integer read-only
The status of contactors configuration. 'enabled' means that the contactor is in use. 'disabled' means that the contactor is disconfigured and not in use. Enumeration: 'disabled': 0, 'enabled': 1.
             loadLVD2Status 1.3.6.1.4.1.12148.9.4.3.6 integer read-only
The load Contactor 2 is connected(0), disconnected(1) or disabled(2) Enumeration: 'disabled': 2, 'connected': 0, 'disconnected': 1.
             loadLVD2ConnectVoltage 1.3.6.1.4.1.12148.9.4.3.7 integer32 read-write
LVLD2 Connect Voltage
             loadLVD2DisconnectVoltage 1.3.6.1.4.1.12148.9.4.3.8 integer32 read-write
LVLD2 Disconnect Voltage
             loadLVD3Enable 1.3.6.1.4.1.12148.9.4.3.9 integer read-only
The status of contactors configuration. 'enabled' means that the contactor is in use. 'disabled' means that the contactor is disconfigured and not in use. Enumeration: 'disabled': 0, 'enabled': 1.
             loadLVD3Status 1.3.6.1.4.1.12148.9.4.3.10 integer read-only
The load Contactor 3 is connected(0), disconnected(1) or disabled(2) Enumeration: 'disabled': 2, 'connected': 0, 'disconnected': 1.
             loadLVD3ConnectVoltage 1.3.6.1.4.1.12148.9.4.3.11 integer32 read-write
LVLD3 Connect Voltage
             loadLVD3DisconnectVoltage 1.3.6.1.4.1.12148.9.4.3.12 integer32 read-write
LVLD3 Disconnect Voltage
         loadMonitorUnits 1.3.6.1.4.1.12148.9.4.4
             loadmonitorNumberOfUnits 1.3.6.1.4.1.12148.9.4.4.1 integer32 read-only
             loadMonitorUnitsIndex 1.3.6.1.4.1.12148.9.4.4.2 integer32 no-access
             loadMonitorUnitsTable 1.3.6.1.4.1.12148.9.4.4.3 no-access
                 loadMonitorUnitsEntry 1.3.6.1.4.1.12148.9.4.4.3.1 no-access
                     loadMonitorID 1.3.6.1.4.1.12148.9.4.4.3.1.1 integer32 read-only
                     loadMonitorFuseStatus1 1.3.6.1.4.1.12148.9.4.4.3.1.2 integer read-only
The state of the load fuses/breakers can be either normal(0) or alarm(1) Enumeration: 'alarm': 1, 'normal': 0.
                     loadMonitorCurrent1 1.3.6.1.4.1.12148.9.4.4.3.1.3 integer32 read-only
The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
                     loadMonitorFuseStatus2 1.3.6.1.4.1.12148.9.4.4.3.1.4 integer read-only
The state of the load fuses/breakers can be either normal(0) or alarm(1) Enumeration: 'alarm': 1, 'normal': 0.
                     loadMonitorCurrent2 1.3.6.1.4.1.12148.9.4.4.3.1.5 integer32 read-only
The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
                     loadMonitorFuseStatus3 1.3.6.1.4.1.12148.9.4.4.3.1.6 integer read-only
The state of the load fuses/breakers can be either normal(0) or alarm(1) Enumeration: 'alarm': 1, 'normal': 0.
                     loadMonitorCurrent3 1.3.6.1.4.1.12148.9.4.4.3.1.7 integer32 read-only
The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
                     loadMonitorFuseStatus4 1.3.6.1.4.1.12148.9.4.4.3.1.8 integer read-only
The state of the load fuses/breakers can be either normal(0) or alarm(1) Enumeration: 'alarm': 1, 'normal': 0.
                     loadMonitorCurrent4 1.3.6.1.4.1.12148.9.4.4.3.1.9 integer32 read-only
The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
                     loadMonitorFuseStatus5 1.3.6.1.4.1.12148.9.4.4.3.1.10 integer read-only
The state of the load fuses/breakers can be either normal(0) or alarm(1) Enumeration: 'alarm': 1, 'normal': 0.
                     loadMonitorCurrent5 1.3.6.1.4.1.12148.9.4.4.3.1.11 integer32 read-only
The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
                     loadMonitorFuseStatus6 1.3.6.1.4.1.12148.9.4.4.3.1.12 integer read-only
The state of the load fuses/breakers can be either normal(0) or alarm(1) Enumeration: 'alarm': 1, 'normal': 0.
                     loadMonitorCurrent6 1.3.6.1.4.1.12148.9.4.4.3.1.13 integer32 read-only
The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
                     loadMonitorFuseStatus7 1.3.6.1.4.1.12148.9.4.4.3.1.14 integer read-only
The state of the load fuses/breakers can be either normal(0) or alarm(1) Enumeration: 'alarm': 1, 'normal': 0.
                     loadMonitorCurrent7 1.3.6.1.4.1.12148.9.4.4.3.1.15 integer32 read-only
The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
                     loadMonitorFuseStatus8 1.3.6.1.4.1.12148.9.4.4.3.1.16 integer read-only
The state of the load fuses/breakers can be either normal(0) or alarm(1) Enumeration: 'alarm': 1, 'normal': 0.
                     loadMonitorCurrent8 1.3.6.1.4.1.12148.9.4.4.3.1.17 integer32 read-only
The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
     rectifier 1.3.6.1.4.1.12148.9.5
         rectifierInstalledRectifiers 1.3.6.1.4.1.12148.9.5.1 integer32 read-only
The number of installed rectifiers for this DC Power System.
         rectifierRectifiersActive 1.3.6.1.4.1.12148.9.5.2 integer32 read-only
Not Used!
         rectifierTotalCurrent 1.3.6.1.4.1.12148.9.5.3 integer32 read-only
The DC system's total delivered rectifier current
         rectifierUtilization 1.3.6.1.4.1.12148.9.5.4 integer32 read-only
Utilization in % of available rectifier capacity
         rectifierStatus 1.3.6.1.4.1.12148.9.5.5
             rectifierStatusNoIndex 1.3.6.1.4.1.12148.9.5.5.1 integer32 read-write
An offset for the rectifierStatusTable array. The rectifier status table has a fixed number of 20 rows. This OID sets the offset for the rectifier in the first row i.e. setting the index to 11 will give a range from rectifier ID12 to ID31. Setting the index to 0 will give a range from rectifier ID1 to ID20.
             rectifierStatusTable 1.3.6.1.4.1.12148.9.5.5.2 no-access
A table listing up to 20 recifiers, starting from the rectifier number specified by rectifierStatusNoIndex
                 rectifierStatusEntry 1.3.6.1.4.1.12148.9.5.5.2.1 no-access
A row of rectifier status data corresponding to the rectifierStatusNoIndex value
                     rectifierStatusID 1.3.6.1.4.1.12148.9.5.5.2.1.1 integer32 read-only
The rectifier ID number of the rectifier.
                     rectifierStatusStatus 1.3.6.1.4.1.12148.9.5.5.2.1.2 integer read-only
The operational status of the rectifier record. Not Present (0), normal (1), alarm (2), notUsed (3), disabled (4) Enumeration: 'disabled': 4, 'notPresent': 0, 'notUsed': 3, 'alarm': 2, 'normal': 1.
                     rectifierStatusOutputCurrent 1.3.6.1.4.1.12148.9.5.5.2.1.3 integer32 read-only
The output current of the rectifier.
                     rectifierStatusOutputVoltage 1.3.6.1.4.1.12148.9.5.5.2.1.4 integer32 read-only
The rectifier voltage of the rectifier record.
                     rectifierStatusTemp 1.3.6.1.4.1.12148.9.5.5.2.1.5 integer32 read-only
The input air temperature of the rectifier.
                     rectifierStatusType 1.3.6.1.4.1.12148.9.5.5.2.1.6 displaystring read-only
The rectifier article number string of the rectifier record.
                     rectifierStatusSKU 1.3.6.1.4.1.12148.9.5.5.2.1.7 displaystring read-only
The rectifier part number.
                     rectifierStatusSerialNo 1.3.6.1.4.1.12148.9.5.5.2.1.8 displaystring read-only
The rectifier serial number string of the rectifier record.
                     rectifierStatusRevisionLevel 1.3.6.1.4.1.12148.9.5.5.2.1.9 displaystring read-only
The rectifier HW revision number string of the rectifier record.
     acDistribution 1.3.6.1.4.1.12148.9.6
         acVoltage1 1.3.6.1.4.1.12148.9.6.1 integer32 read-only
The AC Voltage of phase 1
         acVoltage2 1.3.6.1.4.1.12148.9.6.2 integer32 read-only
The AC Voltage of phase 2
         acVoltage3 1.3.6.1.4.1.12148.9.6.3 integer32 read-only
The AC Voltage of phase 3
     alarmGroup 1.3.6.1.4.1.12148.9.7
         alarmWellknownAlarms 1.3.6.1.4.1.12148.9.7.1
             alarmMajorHighBattVolt 1.3.6.1.4.1.12148.9.7.1.1 integer read-only
The Major High Battery Voltage Alarm Enumeration: 'alarm': 1, 'normal': 0.
             alarmMinorHighBattVolt 1.3.6.1.4.1.12148.9.7.1.2 integer read-only
The Minor High Battery Voltage alarm Enumeration: 'alarm': 1, 'normal': 0.
             alarmMajorLowBattVolt 1.3.6.1.4.1.12148.9.7.1.3 integer read-only
The Major Low Battery Voltage Alarm Enumeration: 'alarm': 1, 'normal': 0.
             alarmMinorLowBattVolt 1.3.6.1.4.1.12148.9.7.1.4 integer read-only
The Minor Low Battery Voltage Alarm Enumeration: 'alarm': 1, 'normal': 0.
             alarmMajorBatteryHighTemp 1.3.6.1.4.1.12148.9.7.1.5 integer read-only
The Major High Battery Temperature alarm. Enumeration: 'alarm': 1, 'normal': 0.
             alarmMinorBatteryHighTemp 1.3.6.1.4.1.12148.9.7.1.6 integer read-only
The Minor High Battery Temperature alarm. Enumeration: 'alarm': 1, 'normal': 0.
             alarmBatteryDisconnectOpen 1.3.6.1.4.1.12148.9.7.1.7 integer read-only
The Battery Disconnect Contactor alarm Enumeration: 'alarm': 1, 'normal': 0.
             alarmLVD1open 1.3.6.1.4.1.12148.9.7.1.8 integer read-only
The load Contactor 1 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected. Enumeration: 'alarm': 1, 'normal': 0.
             alarmLVD2open 1.3.6.1.4.1.12148.9.7.1.9 integer read-only
The load Contactor 2 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected. Enumeration: 'alarm': 1, 'normal': 0.
             alarmLVD3open 1.3.6.1.4.1.12148.9.7.1.10 integer read-only
The load Contactor 3 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected. Enumeration: 'alarm': 1, 'normal': 0.
             alarmACmains 1.3.6.1.4.1.12148.9.7.1.11 integer read-only
The AC voltage has dropped below critical level, or one or more AC input phases was lost. Enumeration: 'alarm': 1, 'normal': 0.
             alarmBatteryBreakerOpen 1.3.6.1.4.1.12148.9.7.1.12 integer read-only
A battery breaker/fuse alarm. Enumeration: 'alarm': 1, 'normal': 0.
             alarmDistributionBreakerOpen 1.3.6.1.4.1.12148.9.7.1.13 integer read-only
A Load Distribution breaker/fuse alarm. Enumeration: 'alarm': 1, 'normal': 0.
             alarmMajorRectifier 1.3.6.1.4.1.12148.9.7.1.14 integer read-only
This is a Major Rectifier alarm. Enumeration: 'alarm': 1, 'normal': 0.
             alarmMinorRectifier 1.3.6.1.4.1.12148.9.7.1.15 integer read-only
This is a Minor Rectifier alarm. Enumeration: 'alarm': 1, 'normal': 0.
             alarmMajorBatterySymmetry 1.3.6.1.4.1.12148.9.7.1.16 integer read-only
Battery Symmetry Delta Voltage Major alarm. Enumeration: 'alarm': 1, 'normal': 0.
             alarmMinorBatterySymmetry 1.3.6.1.4.1.12148.9.7.1.17 integer read-only
Battery Symmetry Delta Voltage Minor alarm Enumeration: 'alarm': 1, 'normal': 0.
             alarmBatteryLifeEnded 1.3.6.1.4.1.12148.9.7.1.18 integer read-only
The battery quality has dropped below critical level. A battery test has measured the fully charged capacity to be too low, and thus probably the battery lifecycle to be near expired. Enumeration: 'alarm': 1, 'normal': 0.
             alarmBatteryTestmodeEntered 1.3.6.1.4.1.12148.9.7.1.19 integer read-only
The system has lowered the battery charge voltage in order to discharge the batteries to a predefined level. When the criteria for stopping the battery testing is reached, the charge voltage is increased to commence normal charging. Enumeration: 'alarm': 1, 'normal': 0.
             alarmBatteryBoostmodeEntered 1.3.6.1.4.1.12148.9.7.1.20 integer read-only
The system has increased the battery charge voltage in order to boost the battery. When the criteria for stopping the battery boost is reached, the charge voltage is lowered to commence normal charging. Enumeration: 'alarm': 1, 'normal': 0.
             alarmIoUnitTemp1 1.3.6.1.4.1.12148.9.7.1.21 integer read-only
High or low temperature alarm 1 from any of the IO units. Enumeration: 'alarm': 1, 'normal': 0.
             alarmIoUnitTemp2 1.3.6.1.4.1.12148.9.7.1.22 integer read-only
High or low temperature alarm 2 from any of the IO units. Enumeration: 'alarm': 1, 'normal': 0.
             alarmIoUnitDeltaFanSpeed1 1.3.6.1.4.1.12148.9.7.1.23 integer read-only
Delta fan speed 1 from any of the IO units. Enumeration: 'alarm': 1, 'normal': 0.
             alarmIoUnitDeltaFanSpeed2 1.3.6.1.4.1.12148.9.7.1.24 integer read-only
Delta fan speed 2 from any of the IO units. Enumeration: 'alarm': 1, 'normal': 0.
     dcSystemTraps 1.3.6.1.4.1.12148.9.8
This branch contains the Alarm Notification Traps, which duplicate the alarmGroup OIDs. Each alarm condition is represented by a Alarm Condition Trap and an associated OFF Trap, which is optionally transmitted according to the state of OID systemSendOffTrap
         alarmMajorHighBattVoltTrap 1.3.6.1.4.1.12148.9.8.1
The Major High Battery Voltage alarm
         alarmMinorHighBattVoltTrap 1.3.6.1.4.1.12148.9.8.2
The Minor High Battery Voltage alarm
         alarmMajorLowBattVoltTrap 1.3.6.1.4.1.12148.9.8.3
The Major Low Battery Voltage Alarm
         alarmMinorLowBattVoltTrap 1.3.6.1.4.1.12148.9.8.4
The Minor Low Battery Voltage Alarm
         alarmMajorBatteryHighTempTrap 1.3.6.1.4.1.12148.9.8.5
The Major High Battery Temperature alarm.
         alarmMinorBatteryHighTempTrap 1.3.6.1.4.1.12148.9.8.6
The Minor High Battery Temperature alarm.
         alarmBatteryDisconnectOpenTrap 1.3.6.1.4.1.12148.9.8.7
The Battery Disconnect Contactor alarm
         alarmLVD1openTrap 1.3.6.1.4.1.12148.9.8.8
The load Contactor 1 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
         alarmLVD2openTrap 1.3.6.1.4.1.12148.9.8.9
The load Contactor 2 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
         alarmLVD3openTrap 1.3.6.1.4.1.12148.9.8.10
The load Contactor 3 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
         alarmACmainsTrap 1.3.6.1.4.1.12148.9.8.11
The AC voltage has dropped below critical level, or one or more AC input phases was lost.
         alarmBatteryBreakerOpenTrap 1.3.6.1.4.1.12148.9.8.12
A battery breaker/fuse alarm.
         alarmDistributionBreakerOpenTrap 1.3.6.1.4.1.12148.9.8.13
A Load Distribution breaker/fuse alarm.
         alarmMajorRectifierTrap 1.3.6.1.4.1.12148.9.8.14
This is a Major Rectifier alarm.
         alarmMinorRectifierTrap 1.3.6.1.4.1.12148.9.8.15
This is a Minor Rectifier alarm.
         alarmMajorBatterySymmetryTrap 1.3.6.1.4.1.12148.9.8.16
Battery Symmetry Delta Voltage Major alarm
         alarmMinorBatterySymmetryTrap 1.3.6.1.4.1.12148.9.8.17
Battery Symmetry Delta Voltage Minor alarm
         alarmBatteryLifeEndedTrap 1.3.6.1.4.1.12148.9.8.18
The battery quality has dropped below critical level. A battery test has measured the fully charged capacity to be too low, and thus probably the battery lifecycle to be near expired.
         alarmBatteryTestmodeEnteredTrap 1.3.6.1.4.1.12148.9.8.19
The system has lowered the battery charge voltage in order to discharge the batteries to a predefined level. When the criteria for stopping the battery testing is reached, the charge voltage is increased to commence normal charging.
         alarmBatteryBoostmodeEnteredTrap 1.3.6.1.4.1.12148.9.8.20
The system has increased the battery charge voltage in order to boost the battery. When the criteria for stopping the battery boost is reached, the charge voltage is lowered to commence normal charging.
         alarmController1proginputTrap 1.3.6.1.4.1.12148.9.8.21
Programmable input alarm for Control unit 1. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
         alarmController2proginputTrap 1.3.6.1.4.1.12148.9.8.22
Programmable input alarm for Control unit 2. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
         alarmController3proginputTrap 1.3.6.1.4.1.12148.9.8.23
Programmable input alarm for Control unit 3. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
         alarmController4proginputTrap 1.3.6.1.4.1.12148.9.8.24
Programmable input alarm for Control unit 4. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
         alarmController5proginputTrap 1.3.6.1.4.1.12148.9.8.25
Programmable input alarm for Control unit 5. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
         alarmController6proginputTrap 1.3.6.1.4.1.12148.9.8.26
Programmable input alarm for Control unit 6. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
         alarmController7proginputTrap 1.3.6.1.4.1.12148.9.8.27
Programmable input alarm for Control unit 7. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
         alarmController8proginputTrap 1.3.6.1.4.1.12148.9.8.28
Programmable input alarm for Control unit 8. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
         infoHeartBeatTrap 1.3.6.1.4.1.12148.9.8.29
When enabled, this trap will be transmitted at regular inervals. This trap is not intended to be an alarm but more like some information that the system is alive and the link is up.
         alarmIoUnitTemp1Trap 1.3.6.1.4.1.12148.9.8.30
High or low temperature alarm 1 from any of the IO units.
         alarmIoUnitTemp2Trap 1.3.6.1.4.1.12148.9.8.31
High or low temperature alarm 2 from any of the IO units.
         alarmIoUnitDeltaFanSpeed1Trap 1.3.6.1.4.1.12148.9.8.32
Delta fan speed 1 from any of the IO units. Occurs if the fan speed deviation is above/below the configured level.
         alarmIoUnitDeltaFanSpeed2Trap 1.3.6.1.4.1.12148.9.8.33
Delta fan speed 2 from any of the IO units. Occurs if the fan speed deviation is above/below the configured level.
         alarmIoUnit1proginputTrap 1.3.6.1.4.1.12148.9.8.34
Programmable input alarm for IO Unit 1. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
         alarmIoUnit2proginputTrap 1.3.6.1.4.1.12148.9.8.35
Programmable input alarm for IO Unit 2. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
         alarmIoUnit3proginputTrap 1.3.6.1.4.1.12148.9.8.36
Programmable input alarm for IO Unit 3. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
         alarmIoUnit4proginputTrap 1.3.6.1.4.1.12148.9.8.37
Programmable input alarm for IO Unit 4. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
         alarmIoUnit5proginputTrap 1.3.6.1.4.1.12148.9.8.38
Programmable input alarm for IO Unit 5. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
         alarmIoUnit6proginputTrap 1.3.6.1.4.1.12148.9.8.39
Programmable input alarm for IO Unit 6. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
         alarmIoUnit7proginputTrap 1.3.6.1.4.1.12148.9.8.40
Programmable input alarm for IO Unit 7. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
         alarmIoUnit8proginputTrap 1.3.6.1.4.1.12148.9.8.41
Programmable input alarm for IO Unit 8. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
         alarmIoUnit9proginputTrap 1.3.6.1.4.1.12148.9.8.42
Programmable input alarm for IO Unit 9. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
         alarmIoUnit10proginputTrap 1.3.6.1.4.1.12148.9.8.43
Programmable input alarm for IO Unit 10. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
         alarmIoUnit11proginputTrap 1.3.6.1.4.1.12148.9.8.44
Programmable input alarm for IO Unit 11. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
         alarmIoUnit12proginputTrap 1.3.6.1.4.1.12148.9.8.45
Programmable input alarm for IO Unit 12. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
         alarmIoUnit13proginputTrap 1.3.6.1.4.1.12148.9.8.46
Programmable input alarm for IO Unit 13. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.
         alarmIoUnit14proginputTrap 1.3.6.1.4.1.12148.9.8.47
Programmable input alarm for IO Unit 14. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x.