ELTEK-DISTRIBUTED-PLANT-MIB: View SNMP OID List / Download MIB
VENDOR: ELTEK ENERGY AS
Home | MIB: ELTEK-DISTRIBUTED-PLANT-MIB | |||
---|---|---|---|---|
Download as: |
Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
|
|||
Object Name | OID | Type | Access | Info |
eltekDistributedPlant | 1.3.6.1.4.1.12148.8 | |||
controlSystem | 1.3.6.1.4.1.12148.8.1 | |||
systemTime | 1.3.6.1.4.1.12148.8.1.1 | |||
systemTimeTime | 1.3.6.1.4.1.12148.8.1.1.1 | displaystring | read-only |
The system date and time. Used for event timestamps and logging |
systemInfoRefresh | 1.3.6.1.4.1.12148.8.1.2 | integer | read-write |
This object will re-initialize the agent, updating MIB data values. Enumeration: 'pushbutton': 0, 'refreshdata': 1. |
systemTrapRepeatRate | 1.3.6.1.4.1.12148.8.1.3 | integer32 | read-write |
This object sets the repeat rate of any active traps, in seconds. Entering 0 (zero) will prevent repeating traps - one trap only will be sent per alarm event. |
systemSendOffTrap | 1.3.6.1.4.1.12148.8.1.4 | integer | read-write |
A separate off-trap will be issued when an alarm condition goes off, if this flag is set to 1. Entering 0 (zero) will prevent OFF traps from being transmitted. Enumeration: 'on': 1, 'off': 0. |
systemNumOfControlUnits | 1.3.6.1.4.1.12148.8.1.5 | integer32 | read-only |
The number of expected system controllers (smartpacks, smartnodes stc.) in a distributed system |
systemControlUnitIndex | 1.3.6.1.4.1.12148.8.1.6 | integer32 | no-access |
Index used for navigating int the table of 1 to 8 system controller input groups |
systemControlUnitTable | 1.3.6.1.4.1.12148.8.1.7 | no-access | ||
1.3.6.1.4.1.12148.8.1.7.1 | no-access | |||
inputControlUnitID | 1.3.6.1.4.1.12148.8.1.7.1.1 | integer32 | read-only |
|
inputUserConfigurable1 | 1.3.6.1.4.1.12148.8.1.7.1.2 | integer | read-only |
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. Enumeration: 'alarm': 1, 'normal': 0. |
inputUserConfigurable2 | 1.3.6.1.4.1.12148.8.1.7.1.3 | integer | read-only |
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. Enumeration: 'alarm': 1, 'normal': 0. |
inputUserConfigurable3 | 1.3.6.1.4.1.12148.8.1.7.1.4 | integer | read-only |
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. Enumeration: 'alarm': 1, 'normal': 0. |
inputUserConfigurable4 | 1.3.6.1.4.1.12148.8.1.7.1.5 | integer | read-only |
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. Enumeration: 'alarm': 1, 'normal': 0. |
inputUserConfigurable5 | 1.3.6.1.4.1.12148.8.1.7.1.6 | integer | read-only |
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. Enumeration: 'alarm': 1, 'normal': 0. |
inputUserConfigurable6 | 1.3.6.1.4.1.12148.8.1.7.1.7 | integer | read-only |
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. Enumeration: 'alarm': 1, 'normal': 0. |
inputUserConfigurable7 | 1.3.6.1.4.1.12148.8.1.7.1.8 | integer | read-only |
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. Enumeration: 'alarm': 1, 'normal': 0. |
inputUserConfigurable8 | 1.3.6.1.4.1.12148.8.1.7.1.9 | integer | read-only |
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. Enumeration: 'alarm': 1, 'normal': 0. |
inputUserConfigurable9 | 1.3.6.1.4.1.12148.8.1.7.1.10 | integer | read-only |
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. Enumeration: 'alarm': 1, 'normal': 0. |
inputUserConfigurable10 | 1.3.6.1.4.1.12148.8.1.7.1.11 | integer | read-only |
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. Enumeration: 'alarm': 1, 'normal': 0. |
systemLinkStatus | 1.3.6.1.4.1.12148.8.1.8 | integer | read-only |
A flag showing the status of the serial port used between the Webpower adapter and the Control system. If this flag shows status linkdown, the propable cause is that the wrong baudrate is set, which again is likely to happen when booting a brand new board. Execute a 'systemInitiateEEPROM' command to fix. Enumeration: 'linkup': 1, 'linkdown': 0. |
systemInitiateEEPROM | 1.3.6.1.4.1.12148.8.1.9 | integer | read-write |
pushbutton function that initiates a forced write of baudrate of 38400bps for the serial port. It also writes default data to the eeprom. This function is used for productiontest only. The 3rd party OS used in this application are not able to write default data to EEPROM at boot time. A minimum set of configuration is thus created in RAM. A production test facility must therefore run this command as a part of the production test for the unit to function properly. Enumeration: 'start': 1, 'pushbutton': 0. |
dcSystem | 1.3.6.1.4.1.12148.8.2 | |||
dcPlant | 1.3.6.1.4.1.12148.8.2.1 | |||
systemSiteInfo | 1.3.6.1.4.1.12148.8.2.1.3 | |||
systemSiteInfoCustomer | 1.3.6.1.4.1.12148.8.2.1.3.1 | displaystring | read-only |
The Customer name (as stored in the Smartpack Control Unit) |
systemSiteInfoLocation | 1.3.6.1.4.1.12148.8.2.1.3.2 | displaystring | read-only |
The system/site Location details (as stored in the Smartpack Control Unit). |
systemSiteInfoMessage1 | 1.3.6.1.4.1.12148.8.2.1.3.3 | displaystring | read-only |
The system/site Info Message record #1 (as stored in the Smartpack Control Unit). 31 Bytes. |
systemSiteInfoMessage2 | 1.3.6.1.4.1.12148.8.2.1.3.4 | displaystring | read-only |
The system/site Info Message record #2 (as stored in the Smartpack Control Unit). 31 Bytes. |
systemSiteInfoInstalledDate | 1.3.6.1.4.1.12148.8.2.1.3.5 | displaystring | read-only |
The system's Installed Date text string (as stored in the Smartpack Control Unit) 16bytes. |
systemSiteInfoControllerType | 1.3.6.1.4.1.12148.8.2.1.3.6 | integer | read-only |
The system Controller Module currently connected. AL175/MCU=0; AEON Gold=1; AL6000=2; Smartpack=3 Enumeration: 'al175': 0, 'smartpack': 3, 'al4000': 1, 'al6000': 2. |
systemSiteInfoSystemSeriaNum | 1.3.6.1.4.1.12148.8.2.1.3.7 | displaystring | read-only |
The serial number for the complete system |
systemSiteInfoControllerSeriaNum | 1.3.6.1.4.1.12148.8.2.1.3.8 | displaystring | read-only |
The serial number for the system controller |
systemNominalVoltage | 1.3.6.1.4.1.12148.8.2.1.4 | integer | read-only |
The nominal voltage rating. 12V/24V/48V/60V systems 0=48V 1=24V 2=12V 3=26V 4=60V Enumeration: 'prs12v': 2, 'prs24v': 1, 'prs48v': 0, 'prs26v': 3, 'prs60v': 4. |
systemOperationalStatus | 1.3.6.1.4.1.12148.8.2.2 | integer | read-only |
A summary status showing if the system is testing, boosting, floating etc. 0=Float, voltage regulated 1=Float, temperature comp. regulated; 2=equalize 3=battery test Enumeration: 'floattempcomp': 1, 'batteryboost': 2, 'batterytest': 3, 'floatvoltreg': 0. |
battery | 1.3.6.1.4.1.12148.8.3 | |||
batteryName | 1.3.6.1.4.1.12148.8.3.1 | displaystring | read-only |
A descriptive name of the battery installed in the system |
batteryVoltage | 1.3.6.1.4.1.12148.8.3.2 | integer32 | read-only |
The measured battery voltage. |
batteryCurrent | 1.3.6.1.4.1.12148.8.3.3 | integer32 | read-only |
The measured battery current. |
batteryTemp | 1.3.6.1.4.1.12148.8.3.4 | integer32 | read-only |
The battery temperature |
batteryBreakerStatus | 1.3.6.1.4.1.12148.8.3.5 | integer | read-only |
The state of the battery fuse/breaker can be either closed(0) or open(1) Enumeration: 'open': 1, 'closed': 0. |
batteryChargeCurrentLimitCtrl | 1.3.6.1.4.1.12148.8.3.6 | integer | read-write |
Control field for the battery charge limitation feature; 0=inactive, 1=active. Enumeration: 'deactivate': 0, 'activate': 1. |
batteryChargeCurrentLimitValue | 1.3.6.1.4.1.12148.8.3.7 | integer32 | read-write |
Battery charging current limit value |
batteryTempCompEnable | 1.3.6.1.4.1.12148.8.3.8 | integer | read-write |
Enable (0) or Disable (1) Battery Temperature Compensated output regulation mode Enumeration: 'enable': 1, 'disable': 0. |
batteryFloatVoltConfig | 1.3.6.1.4.1.12148.8.3.9 | integer32 | read-write |
The Voltage at which the DC System float charges. |
batteryEqualizeVoltConfig | 1.3.6.1.4.1.12148.8.3.10 | integer32 | read-write |
The Voltage at which the DC System boost charges the batteries. |
batteryHighMajorAlarmVoltageConfig | 1.3.6.1.4.1.12148.8.3.11 | integer32 | read-write |
The High Battery Voltage alarm limit set voltage |
batteryHighMinorAlarmVoltageConfig | 1.3.6.1.4.1.12148.8.3.12 | integer32 | read-write |
The High Battery Voltage alarm limit set voltage |
batteryLowMajorAlarmVoltageConfig | 1.3.6.1.4.1.12148.8.3.13 | integer32 | read-write |
The Low Battery Voltage Alarm limit set voltage |
batteryLowMinorAlarmVoltageConfig | 1.3.6.1.4.1.12148.8.3.14 | integer32 | read-write |
The Very Low Battery Voltage Alarm limit set voltage |
batteryStartManualTest | 1.3.6.1.4.1.12148.8.3.15 | integer | read-write |
This pushbutton will start a manual battery test if otherwise the system allows it. Enumeration: 'starttest': 1, 'pushbutton': 0, 'stoptest': 2. |
batteryStartManualBoost | 1.3.6.1.4.1.12148.8.3.16 | integer | read-write |
This pushbutton will start a manual battery boost if otherwise the system allows it. Enumeration: 'stopboost': 2, 'pushbutton': 0, 'startboost': 1. |
batteryLVD | 1.3.6.1.4.1.12148.8.3.17 | |||
batteryLVDStatus | 1.3.6.1.4.1.12148.8.3.17.1 | integer | read-only |
Contactor is closed(0) or open(1) Enumeration: 'disable': 2, 'disconnect': 1, 'connect': 0. |
batteryLVDDisconnectVoltage | 1.3.6.1.4.1.12148.8.3.17.2 | integer32 | read-write |
The Contactor Disconnect Voltage |
batteryLVDConnectVoltage | 1.3.6.1.4.1.12148.8.3.17.3 | integer32 | read-write |
The Contactor Reconnect Voltage |
batteryBanksNumofBanks | 1.3.6.1.4.1.12148.8.3.18 | integer32 | read-only | |
batteryBanks | 1.3.6.1.4.1.12148.8.3.19 | |||
batterySymmetryDeltaLimitVoltage | 1.3.6.1.4.1.12148.8.3.19.1 | integer32 | read-write |
The allowable deviation of the midpoint battery voltage from the theoretical. Exceeding this value in either direction (+/-) causes an alarm state |
batteryBanksIndex | 1.3.6.1.4.1.12148.8.3.19.2 | integer32 | no-access |
Index used for navigating int the table of 1 to 8 batterybank symmetry groups |
batteryBanksTable | 1.3.6.1.4.1.12148.8.3.19.3 | no-access |
A table of up to 8 battery banks. Each bank may have up to 8 symmetry or midpoint measuments |
|
1.3.6.1.4.1.12148.8.3.19.3.1 | no-access |
a distributed control system may contain up to 8 battery banks. |
||
batteryBankID | 1.3.6.1.4.1.12148.8.3.19.3.1.1 | integer32 | read-only | |
batteryBanksSymmetry1enable | 1.3.6.1.4.1.12148.8.3.19.3.1.2 | integer | read-write |
When set to 'on' the the symmetry input is activated. when turned off, measuments for this input is turned off and the correcponding value will read 0 volts and the alarm flag will be turned off Enumeration: 'enable': 1, 'disable': 0. |
batteryBanksSymmetry1status | 1.3.6.1.4.1.12148.8.3.19.3.1.3 | integer | read-only |
Status (0=Normal; 1=Alarm) of the Battery Monitor channel which corresponds to the batteryMidpointIndex value Enumeration: 'minorAlarm': 1, 'majorAlarm': 2, 'ok': 0, 'disabled': 3, 'error': 4. |
batteryBanksSymmetry1deltaVoltage | 1.3.6.1.4.1.12148.8.3.19.3.1.4 | integer32 | read-only |
The measured battery voltage deviation from midpoint of the Battery Monitor channel which corresponds to the batteryMidpointIndex value. |
batteryBanksSymmetry2enable | 1.3.6.1.4.1.12148.8.3.19.3.1.5 | integer | read-write |
When set to 'on' the the symmetry input is activated. when turned off, measuments for this input is turned off and the correcponding value will read 0 volts and the alarm flag will be turned off Enumeration: 'enable': 1, 'disable': 0. |
batteryBanksSymmetry2status | 1.3.6.1.4.1.12148.8.3.19.3.1.6 | integer | read-only |
Status (0=Normal; 1=Alarm) of the Battery Monitor channel which corresponds to the batteryMidpointIndex value Enumeration: 'minorAlarm': 1, 'majorAlarm': 2, 'ok': 0, 'disabled': 3, 'error': 4. |
batteryBanksSymmetry2deltaVoltage | 1.3.6.1.4.1.12148.8.3.19.3.1.7 | integer32 | read-only |
The measured battery voltage deviation from midpoint of the Battery Monitor channel which corresponds to the batteryMidpointIndex value. |
batteryBanksSymmetry3enable | 1.3.6.1.4.1.12148.8.3.19.3.1.8 | integer | read-write |
When set to 'on' the the symmetry input is activated. when turned off, measuments for this input is turned off and the correcponding value will read 0 volts and the alarm flag will be turned off Enumeration: 'enable': 1, 'disable': 0. |
batteryBanksSymmetry3status | 1.3.6.1.4.1.12148.8.3.19.3.1.9 | integer | read-only |
Status (0=Normal; 1=Alarm) of the Battery Monitor channel which corresponds to the batteryMidpointIndex value Enumeration: 'minorAlarm': 1, 'majorAlarm': 2, 'ok': 0, 'disabled': 3, 'error': 4. |
batteryBanksSymmetry3deltaVoltage | 1.3.6.1.4.1.12148.8.3.19.3.1.10 | integer32 | read-only |
The measured battery voltage deviation from midpoint of the Battery Monitor channel which corresponds to the batteryMidpointIndex value. |
batteryBanksSymmetry4enable | 1.3.6.1.4.1.12148.8.3.19.3.1.11 | integer | read-write |
When set to 'on' the the symmetry input is activated. when turned off, measuments for this input is turned off and the correcponding value will read 0 volts and the alarm flag will be turned off Enumeration: 'enable': 1, 'disable': 0. |
batteryBanksSymmetry4status | 1.3.6.1.4.1.12148.8.3.19.3.1.12 | integer | read-only |
Status (0=Normal; 1=Alarm) of the Battery Monitor channel which corresponds to the batteryMidpointIndex value Enumeration: 'minorAlarm': 1, 'majorAlarm': 2, 'ok': 0, 'disabled': 3, 'error': 4. |
batteryBanksSymmetry4deltaVoltage | 1.3.6.1.4.1.12148.8.3.19.3.1.13 | integer32 | read-only |
The measured battery voltage deviation from midpoint of the Battery Monitor channel which corresponds to the batteryMidpointIndex value. |
batteryBanksSymmetry5enable | 1.3.6.1.4.1.12148.8.3.19.3.1.14 | integer | read-write |
When set to 'on' the the symmetry input is activated. when turned off, measuments for this input is turned off and the correcponding value will read 0 volts and the alarm flag will be turned off Enumeration: 'enable': 1, 'disable': 0. |
batteryBanksSymmetry5status | 1.3.6.1.4.1.12148.8.3.19.3.1.15 | integer | read-only |
Status (0=Normal; 1=Alarm) of the Battery Monitor channel which corresponds to the batteryMidpointIndex value Enumeration: 'minorAlarm': 1, 'majorAlarm': 2, 'ok': 0, 'disabled': 3, 'error': 4. |
batteryBanksSymmetry5deltaVoltage | 1.3.6.1.4.1.12148.8.3.19.3.1.16 | integer32 | read-only |
The measured battery voltage deviation from midpoint of the Battery Monitor channel which corresponds to the batteryMidpointIndex value. |
batteryBanksSymmetry6enable | 1.3.6.1.4.1.12148.8.3.19.3.1.17 | integer | read-write |
When set to 'on' the the symmetry input is activated. when turned off, measuments for this input is turned off and the correcponding value will read 0 volts and the alarm flag will be turned off Enumeration: 'enable': 1, 'disable': 0. |
batteryBanksSymmetry6status | 1.3.6.1.4.1.12148.8.3.19.3.1.18 | integer | read-only |
Status (0=Normal; 1=Alarm) of the Battery Monitor channel which corresponds to the batteryMidpointIndex value Enumeration: 'minorAlarm': 1, 'majorAlarm': 2, 'ok': 0, 'disabled': 3, 'error': 4. |
batteryBanksSymmetry6deltaVoltage | 1.3.6.1.4.1.12148.8.3.19.3.1.19 | integer32 | read-only |
The measured battery voltage deviation from midpoint of the Battery Monitor channel which corresponds to the batteryMidpointIndex value. |
batteryBanksSymmetry7enable | 1.3.6.1.4.1.12148.8.3.19.3.1.20 | integer | read-write |
When set to 'on' the the symmetry input is activated. when turned off, measuments for this input is turned off and the correcponding value will read 0 volts and the alarm flag will be turned off Enumeration: 'enable': 1, 'disable': 0. |
batteryBanksSymmetry7status | 1.3.6.1.4.1.12148.8.3.19.3.1.21 | integer | read-only |
Status (0=Normal; 1=Alarm) of the Battery Monitor channel which corresponds to the batteryMidpointIndex value Enumeration: 'minorAlarm': 1, 'majorAlarm': 2, 'ok': 0, 'disabled': 3, 'error': 4. |
batteryBanksSymmetry7deltaVoltage | 1.3.6.1.4.1.12148.8.3.19.3.1.22 | integer32 | read-only |
The measured battery voltage deviation from midpoint of the Battery Monitor channel which corresponds to the batteryMidpointIndex value. |
batteryBanksSymmetry8enable | 1.3.6.1.4.1.12148.8.3.19.3.1.23 | integer | read-write |
When set to 'on' the the symmetry input is activated. when turned off, measuments for this input is turned off and the correcponding value will read 0 volts and the alarm flag will be turned off Enumeration: 'enable': 1, 'disable': 0. |
batteryBanksSymmetry8status | 1.3.6.1.4.1.12148.8.3.19.3.1.24 | integer | read-only |
Status (0=Normal; 1=Alarm) of the Battery Monitor channel which corresponds to the batteryMidpointIndex value Enumeration: 'minorAlarm': 1, 'majorAlarm': 2, 'ok': 0, 'disabled': 3, 'error': 4. |
batteryBanksSymmetry8deltaVoltage | 1.3.6.1.4.1.12148.8.3.19.3.1.25 | integer32 | read-only |
The measured battery voltage deviation from midpoint of the Battery Monitor channel which corresponds to the batteryMidpointIndex value. |
loadDistribution | 1.3.6.1.4.1.12148.8.4 | |||
loadDistributionCurrent | 1.3.6.1.4.1.12148.8.4.1 | integer32 | read-only |
The total load current |
loadDistributionBreakerStatus | 1.3.6.1.4.1.12148.8.4.2 | integer | read-only |
The state of the load fuse/breaker can be either closed(0) or open(1) Enumeration: 'open': 1, 'closed': 0. |
loadDistributionLVDStatus | 1.3.6.1.4.1.12148.8.4.3 | |||
loadLVD1EnableStatus | 1.3.6.1.4.1.12148.8.4.3.1 | integer | read-only |
The status of contactors configuration. 'enabled' means that the contactor is i n use. 'disabled' means that the contactor is disconfigured and not in use. Enumeration: 'disabled': 0, 'enabled': 1. |
loadLVD1Status | 1.3.6.1.4.1.12148.8.4.3.2 | integer | read-only |
The primary load Contactor is closed(0) or open(1) Enumeration: 'disable': 2, 'disconnect': 1, 'connect': 0. |
loadLVD1ConnectVoltage | 1.3.6.1.4.1.12148.8.4.3.3 | integer32 | read-write |
The primary loads Contactor Connect Voltage |
loadLVD1DisconnectVoltage | 1.3.6.1.4.1.12148.8.4.3.4 | integer32 | read-write |
The primary load Contactor Disconnect Voltage |
loadLVD2EnableStatus | 1.3.6.1.4.1.12148.8.4.3.5 | integer | read-only |
The status of contactors configuration. 'enabled' means that the contactor is i n use. 'disabled' means that the contactor is disconfigured and not in use. Enumeration: 'disabled': 0, 'enabled': 1. |
loadLVD2Status | 1.3.6.1.4.1.12148.8.4.3.6 | integer | read-only |
The secondary load Contactor is closed(0) or open(1) Enumeration: 'disable': 2, 'disconnect': 1, 'connect': 0. |
loadLVD2ConnectVoltage | 1.3.6.1.4.1.12148.8.4.3.7 | integer32 | read-write |
The secondary load Contactor Connect Voltage |
loadLVD2DisconnectVoltage | 1.3.6.1.4.1.12148.8.4.3.8 | integer32 | read-write |
The secondary loads Contactor Disconnect Voltage |
loadLVD3EnableStatus | 1.3.6.1.4.1.12148.8.4.3.9 | integer | read-only |
The status of contactors configuration. 'enabled' means that the contactor is i n use. 'disabled' means that the contactor is disconfigured and not in use. Enumeration: 'disabled': 0, 'enabled': 1. |
loadLVD3Status | 1.3.6.1.4.1.12148.8.4.3.10 | integer | read-only |
The third critical loads Contactor is closed(0) or open(1) Enumeration: 'disable': 2, 'disconnect': 1, 'connect': 0. |
loadLVD3ConnectVoltage | 1.3.6.1.4.1.12148.8.4.3.11 | integer32 | read-write |
The third critical load Contactor Connect Voltage |
loadLVD3DisconnectVoltage | 1.3.6.1.4.1.12148.8.4.3.12 | integer32 | read-write |
The third critical loads Contactor Disconnect Voltage |
rectifier | 1.3.6.1.4.1.12148.8.5 | |||
rectifierInstalledRectifiers | 1.3.6.1.4.1.12148.8.5.1 | integer32 | read-only |
The installed number of rectifiers for this DC Power System. |
rectifierRectifiersActive | 1.3.6.1.4.1.12148.8.5.2 | integer32 | read-only |
The actual number of active rectifiers in this DC Power System. |
rectifierTotalCurrent | 1.3.6.1.4.1.12148.8.5.3 | integer32 | read-only |
The DC system's total available current |
rectifierUtilization | 1.3.6.1.4.1.12148.8.5.4 | integer32 | read-only |
Utilization in % of available rectifier capacity |
rectifierStatus | 1.3.6.1.4.1.12148.8.5.5 | |||
rectifierStatusNoIndex | 1.3.6.1.4.1.12148.8.5.5.1 | integer32 | read-write |
A starting index for the rectifierStatusTable array |
rectifierStatusTable | 1.3.6.1.4.1.12148.8.5.5.2 | no-access |
A table listing up to sixteen sequential recifiers, starting from the rectifier number specified by rectifierStatusNoIndex |
|
1.3.6.1.4.1.12148.8.5.5.2.1 | no-access |
A row of rectifier status data corresponding to the rectifierStatusNoIndex value |
||
rectifierStatusID | 1.3.6.1.4.1.12148.8.5.5.2.1.1 | integer32 | read-only |
The rectifier ID number of the rectifier record. |
rectifierStatusStatus | 1.3.6.1.4.1.12148.8.5.5.2.1.2 | integer | read-only |
The operational status of the rectifier record. absent (0), active (1), failed (2), walkin (3), disabledbycommand (4) Enumeration: 'active': 1, 'absent': 0, 'disabledbycommand': 4, 'walkin': 3, 'failed': 2. |
rectifierStatusOutputCurrent | 1.3.6.1.4.1.12148.8.5.5.2.1.3 | integer32 | read-only |
The rectifier current of the rectifier record. |
rectifierStatusOutputVoltage | 1.3.6.1.4.1.12148.8.5.5.2.1.4 | integer32 | read-only |
The rectifier voltage of the rectifier record. |
rectifierStatusTemp | 1.3.6.1.4.1.12148.8.5.5.2.1.5 | integer32 | read-only |
The heatsink temperature of the rectifier record. |
rectifierStatusType | 1.3.6.1.4.1.12148.8.5.5.2.1.6 | displaystring | read-only |
The rectifier article number string of the rectifier record. |
rectifierStatusSKU | 1.3.6.1.4.1.12148.8.5.5.2.1.7 | displaystring | read-only |
The rectifier Stock Keeping Unit number or other user-defined ID of the rectifier record. |
rectifierStatusSerialNo | 1.3.6.1.4.1.12148.8.5.5.2.1.8 | displaystring | read-only |
The rectifier serial number string of the rectifier record. |
rectifierStatusRevisionLevel | 1.3.6.1.4.1.12148.8.5.5.2.1.9 | displaystring | read-only |
The rectifier version number string of the rectifier record. |
acDistribution | 1.3.6.1.4.1.12148.8.6 | |||
acVoltage1 | 1.3.6.1.4.1.12148.8.6.1 | integer32 | read-only |
The AC Voltage of phase 1 |
acVoltage2 | 1.3.6.1.4.1.12148.8.6.2 | integer32 | read-only |
The AC Voltage of phase 2 |
acVoltage3 | 1.3.6.1.4.1.12148.8.6.3 | integer32 | read-only |
The AC Voltage of phase 3 |
alarmGroup | 1.3.6.1.4.1.12148.8.7 | |||
alarmWellknownAlarms | 1.3.6.1.4.1.12148.8.7.1 | |||
alarmMajorHighBattVolt | 1.3.6.1.4.1.12148.8.7.1.1 | integer | read-only |
The Very High Battery Voltage Alarm Enumeration: 'alarm': 1, 'normal': 0. |
alarmMinorHighBattVolt | 1.3.6.1.4.1.12148.8.7.1.2 | integer | read-only |
The High Battery Voltage alarm Enumeration: 'alarm': 1, 'normal': 0. |
alarmMajorLowBattVolt | 1.3.6.1.4.1.12148.8.7.1.3 | integer | read-only |
The Very Low Battery Voltage Alarm Enumeration: 'alarm': 1, 'normal': 0. |
alarmMinorLowBattVolt | 1.3.6.1.4.1.12148.8.7.1.4 | integer | read-only |
The Low Battery Voltage Alarm Enumeration: 'alarm': 1, 'normal': 0. |
alarmMajorBatteryHighTemp | 1.3.6.1.4.1.12148.8.7.1.5 | integer | read-only |
Temperature much too high alarm, or temperature compensation circuit / probe failure alarm Enumeration: 'alarm': 1, 'normal': 0. |
alarmMinorBatteryHighTemp | 1.3.6.1.4.1.12148.8.7.1.6 | integer | read-only |
Temperature much too high alarm Enumeration: 'alarm': 1, 'normal': 0. |
alarmBatteryDisconnectOpen | 1.3.6.1.4.1.12148.8.7.1.7 | integer | read-only |
The Battery Disconnect Contactor alarm Enumeration: 'alarm': 1, 'normal': 0. |
alarmLVD1open | 1.3.6.1.4.1.12148.8.7.1.8 | integer | read-only |
The A Bus (primary loads) Contactor alarm. The contactor dropout voltage has been reached and the contactor will release. Enumeration: 'alarm': 1, 'normal': 0. |
alarmLVD2open | 1.3.6.1.4.1.12148.8.7.1.9 | integer | read-only |
The B Bus (secondary loads) Contactor alarm. The contactor dropout voltage has been reached and the contactor will release. Enumeration: 'alarm': 1, 'normal': 0. |
alarmLVD3open | 1.3.6.1.4.1.12148.8.7.1.10 | integer | read-only |
The C Bus (critical loads) Contactor alarm. The contactor dropout voltage has been reached and the contactor will release. Enumeration: 'alarm': 1, 'normal': 0. |
alarmACmains | 1.3.6.1.4.1.12148.8.7.1.11 | integer | read-only |
The AC voltage has dropped below critical level, or one or more AC input phases was lost. Enumeration: 'alarm': 1, 'normal': 0. |
alarmBatteryBreakerOpen | 1.3.6.1.4.1.12148.8.7.1.12 | integer | read-only |
Battery string disconnect breaker/fuse alarm Enumeration: 'alarm': 1, 'normal': 0. |
alarmDistributionBreakerOpen | 1.3.6.1.4.1.12148.8.7.1.13 | integer | read-only |
The Load Distribution breaker/fuse alarm Enumeration: 'alarm': 1, 'normal': 0. |
alarmMajorRectifier | 1.3.6.1.4.1.12148.8.7.1.14 | integer | read-only |
This is a 'multiple rectifiers have failed' alarm Enumeration: 'alarm': 1, 'normal': 0. |
alarmMinorRectifier | 1.3.6.1.4.1.12148.8.7.1.15 | integer | read-only |
This is a 'one rectifier has failed' alarm Enumeration: 'alarm': 1, 'normal': 0. |
alarmMajorBatteryMidpoint | 1.3.6.1.4.1.12148.8.7.1.16 | integer | read-only |
Battery Symmetry (midpoint) Delta Voltage is badly out of limits alarm Enumeration: 'alarm': 1, 'normal': 0. |
alarmMinorBatteryMidpoint | 1.3.6.1.4.1.12148.8.7.1.17 | integer | read-only |
Battery Symmetry (midpoint) Delta Voltage out of limits alarm Enumeration: 'alarm': 1, 'normal': 0. |
alarmBatteryLifeEnded | 1.3.6.1.4.1.12148.8.7.1.18 | integer | read-only |
The battery capacity has dropped below critical level. A battery test has measured the fully charged capacity to be too low, and thus probably the battery lifecycle to be near expired. Enumeration: 'alarm': 1, 'normal': 0. |
alarmBatteryTestmodeEntered | 1.3.6.1.4.1.12148.8.7.1.19 | integer | read-only |
The system has lowered the battery charge voltage in order to discharge the batteries to a predefinend level. When the criteria for stopping the battery testing is reached, the charge voltage is increased to commence normal charging. Enumeration: 'alarm': 1, 'normal': 0. |
alarmBatteryBoostmodeEntered | 1.3.6.1.4.1.12148.8.7.1.20 | integer | read-only |
The system has increased the battery charge voltage in order to equalize the battery cells charging. When the criteria for stopping the battery equalizing is reached, the charge voltage is lowered to commence normal charging. Enumeration: 'alarm': 1, 'normal': 0. |
dcSystemTraps | 1.3.6.1.4.1.12148.8.8 |
This branch contains the Alarm Notification Traps, which duplicate the alarmGroup OIDs. Each alarm condition is represented by a Alarm Condition Trap and an associated OFF Trap, which is optionally transmitted according to the state of OID systemSendOffTrap |
||
alarmMajorHighBattVoltTrap | 1.3.6.1.4.1.12148.8.8.1 |
The Very High Battery Voltage alarm |
||
alarmMinorHighBattVoltTrap | 1.3.6.1.4.1.12148.8.8.2 |
The High Battery Voltage alarm |
||
alarmMajorLowBattVoltTrap | 1.3.6.1.4.1.12148.8.8.3 |
The Very Low Battery Voltage Alarm |
||
alarmMinorLowBattVoltTrap | 1.3.6.1.4.1.12148.8.8.4 |
The Low Battery Voltage Alarm |
||
alarmMajorBatteryHighTempTrap | 1.3.6.1.4.1.12148.8.8.5 |
High Battery temperature alarm or Temperature Compensation circuit / probe failure alarm |
||
alarmMinorBatteryHighTempTrap | 1.3.6.1.4.1.12148.8.8.6 |
High Battery temperature alarm |
||
alarmBatteryDisconnectOpenTrap | 1.3.6.1.4.1.12148.8.8.7 |
The Battery Disconnect Contactor alarm |
||
alarmLVD1openTrap | 1.3.6.1.4.1.12148.8.8.8 |
The A Bus (primary loads) Contactor is open alarm |
||
alarmLVD2openTrap | 1.3.6.1.4.1.12148.8.8.9 |
The B Bus (secondary loads) Contactor is open alarm |
||
alarmLVD3openTrap | 1.3.6.1.4.1.12148.8.8.10 |
The C Bus (critical loads) Contactor alarm. The contactor dropout voltage has been reached and the contactor is released. |
||
alarmACmainsTrap | 1.3.6.1.4.1.12148.8.8.11 |
The AC voltage has dropped below critical level, or one or more AC input phases was lost. |
||
alarmBatteryBreakerOpenTrap | 1.3.6.1.4.1.12148.8.8.12 |
Battery string disconnect breaker/fuse alarm |
||
alarmDistributionBreakerOpenTrap | 1.3.6.1.4.1.12148.8.8.13 |
The Load Distribution breaker/fuse alarm |
||
alarmMajorRectifierTrap | 1.3.6.1.4.1.12148.8.8.14 |
This is a 'multiple rectifiers have failed' alarm |
||
alarmMinorRectifierTrap | 1.3.6.1.4.1.12148.8.8.15 |
This is a 'one rectifier has failed' alarm |
||
alarmMajorBatteryMidpointTrap | 1.3.6.1.4.1.12148.8.8.16 |
Battery Symmetry (midpoint) Delta Voltage out of 'major fault' limits alarm |
||
alarmMinorBatteryMidpointTrap | 1.3.6.1.4.1.12148.8.8.17 |
Battery Symmetry (midpoint) Delta Voltage out of limits alarm |
||
alarmBatteryLifeEndedTrap | 1.3.6.1.4.1.12148.8.8.18 |
The battery capacity has dropped below critical level. A battery test has measured the fully charged capacity to be too low, and thus probably the battery lifecycle to be near expired. |
||
alarmBatteryTestmodeEnteredTrap | 1.3.6.1.4.1.12148.8.8.19 |
The system has lowered the battery charge voltage in order to discharge the batteries to a predefinend level. When the criteria for stopping the battery testing is reached, the charge voltage is increased to commence normal charging. |
||
alarmBatteryBoostmodeEnteredTrap | 1.3.6.1.4.1.12148.8.8.20 |
The system has increased the battery charge voltage in order to equalize the battery cells charging. When the criteria for stopping the battery equalizing is reached, the charge voltage is lowered to commence normal charging. |
||
alarmController1proginputTrap | 1.3.6.1.4.1.12148.8.8.21 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. |
||
alarmController2proginputTrap | 1.3.6.1.4.1.12148.8.8.22 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. |
||
alarmController3proginputTrap | 1.3.6.1.4.1.12148.8.8.23 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. |
||
alarmController4proginputTrap | 1.3.6.1.4.1.12148.8.8.24 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. |
||
alarmController5proginputTrap | 1.3.6.1.4.1.12148.8.8.25 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. |
||
alarmController6proginputTrap | 1.3.6.1.4.1.12148.8.8.26 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. |
||
alarmController7proginputTrap | 1.3.6.1.4.1.12148.8.8.27 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. |
||
alarmController8proginputTrap | 1.3.6.1.4.1.12148.8.8.28 |
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. |