EATON-PDU-MIB: View SNMP OID List / Download MIB

VENDOR: EATON CORPORATION


 Home MIB: EATON-PDU-MIB
Download as:   

Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 eatonPduMIB 1.3.6.1.4.1.534.6.6.4
The MIB module for Eaton PDUs (Power Distribution Units). Copyright (C) Eaton Corporation (2007).
     eatonPduMIBObjects 1.3.6.1.4.1.534.6.6.4.1
         mainPdu 1.3.6.1.4.1.534.6.6.4.1.1
             pduNameplate 1.3.6.1.4.1.534.6.6.4.1.1.1
                 pduRatingVA 1.3.6.1.4.1.534.6.6.4.1.1.1.1 positiveinteger read-only
The full VA rating of this PDU (for all phases).
                 pduNominalOutputVoltage 1.3.6.1.4.1.534.6.6.4.1.1.1.2 positiveinteger read-only
The nominal Output Voltage of this PDU (as distributed to the panels). May differ from the nominal Input Voltage if the PDU has an input transformer. This is either Line-to-Line or Line-to-Neutral, as indicated in pduOutputVoltageUnits.
                 pduNumPhases 1.3.6.1.4.1.534.6.6.4.1.1.1.3 positiveinteger read-only
The number of lines (phases) for this PDU. The number of Input phases must equal the number of Output phases.
                 pduNumPanels 1.3.6.1.4.1.534.6.6.4.1.1.1.4 positiveinteger read-only
The number of panels or subfeeds contained in this PDU system. This determines the number of rows found in the panel tables.
             pduInput 1.3.6.1.4.1.534.6.6.4.1.1.2
                 pduFrequency 1.3.6.1.4.1.534.6.6.4.1.1.2.1 nonnegativeinteger read-only
The present frequency reading for the full PDU.
                 pduInputVA 1.3.6.1.4.1.534.6.6.4.1.1.2.2 nonnegativeinteger read-only
The present VA input demand of the full PDU system.
                 pduInputPower 1.3.6.1.4.1.534.6.6.4.1.1.2.3 nonnegativeinteger read-only
The present input power demand of the full PDU system.
                 pduInputPowerFactor 1.3.6.1.4.1.534.6.6.4.1.1.2.4 integer32 read-only
The input power factor for the full PDU system. Varies from -1.00 to 1.00, multiplied by 100. If negative values are used, they indicate lagging pf.
                 pduGroundCurrent 1.3.6.1.4.1.534.6.6.4.1.1.2.5 nonnegativeinteger read-only
The present current in the PDU's ground phase. Ideally, this value stays at 0.
                 pduInputVoltageUnits 1.3.6.1.4.1.534.6.6.4.1.1.2.6 displaystring read-only
Indicates whether the pduInputPhaseVoltage readings are 'Vrms Line-Line' or 'Vrms Line-Neutral'.
                 pduInputNumPhases 1.3.6.1.4.1.534.6.6.4.1.1.2.7 positiveinteger read-only
The number of input phases for this PDU. This variable indicates the number of rows in the pduInputTable.
                 pduInputTable 1.3.6.1.4.1.534.6.6.4.1.1.2.8 no-access
A list of input table entries. The number of entries is given by the value of pduInputNumPhases.
                     pduInputEntry 1.3.6.1.4.1.534.6.6.4.1.1.2.8.1 no-access
An entry containing information applicable to a particular input phase.
                         pduInputPhaseIndex 1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.1 positiveinteger no-access
The input line identifier.
                         pduInputPhaseVoltage 1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.2 nonnegativeinteger read-only
The present input voltage for this phase.
                         pduInputPhaseCurrent 1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.3 nonnegativeinteger read-only
The present input current for this phase.
                         pduInputPhasePercentLoad 1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.4 integer32 read-only
The percentage of the pdu power capacity presently being used on this line, normally based on the ratio of pduInputPhaseCurrent to the rated input current.
             pduOutput 1.3.6.1.4.1.534.6.6.4.1.1.3
                 pduOutputKilowattHours 1.3.6.1.4.1.534.6.6.4.1.1.3.1 nonnegativeinteger read-only
The accumulated kilowatt-hour value for the full PDU system since the last reset.
                 pduOutputVA 1.3.6.1.4.1.534.6.6.4.1.1.3.2 nonnegativeinteger read-only
The present VA output of the full PDU system.
                 pduOutputPower 1.3.6.1.4.1.534.6.6.4.1.1.3.3 nonnegativeinteger read-only
The present output power of the full PDU system.
                 pduOutputPowerFactor 1.3.6.1.4.1.534.6.6.4.1.1.3.4 integer32 read-only
The output power factor for the full PDU system. Varies from -1.00 to 1.00, multiplied by 100. If negative values are used, they indicate lagging pf.
                 pduNeutralCurrent 1.3.6.1.4.1.534.6.6.4.1.1.3.5 nonnegativeinteger read-only
The present current in the PDU's output neutral phase. Ideally, this value stays at 0.
                 pduRatedOutputCurrent 1.3.6.1.4.1.534.6.6.4.1.1.3.6 positiveinteger read-only
The rated current value for one PDU Output phase at full load (100%).
                 pduOutputVoltageUnits 1.3.6.1.4.1.534.6.6.4.1.1.3.7 displaystring read-only
Indicates whether the pduOutputPhaseVoltage readings are 'Vrms Line-Line' or 'Vrms Line-Neutral'.
                 pduOutputNumPhases 1.3.6.1.4.1.534.6.6.4.1.1.3.8 positiveinteger read-only
The number of output phases for this PDU. This variable indicates the number of rows in the pduOutputTable.
                 pduOutputTable 1.3.6.1.4.1.534.6.6.4.1.1.3.9 no-access
A list of output table entries. The number of entries is given by the value of pduOutputNumPhases.
                     pduOutputEntry 1.3.6.1.4.1.534.6.6.4.1.1.3.9.1 no-access
An entry containing information applicable to a particular output phase.
                         pduOutputPhaseIndex 1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.1 positiveinteger no-access
The output line identifier.
                         pduOutputPhaseVoltage 1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.2 nonnegativeinteger read-only
The present output voltage for this phase.
                         pduOutputPhaseCurrent 1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.3 nonnegativeinteger read-only
The present output current for this phase.
                         pduOutputPhasePercentLoad 1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.4 integer32 read-only
The percentage of the pdu power capacity presently being used on this line, normally based on the ratio of pduOutputPhaseCurrent to pduRatedOutputCurrent.
         pduPanel 1.3.6.1.4.1.534.6.6.4.1.2
             panelRatingsTable 1.3.6.1.4.1.534.6.6.4.1.2.1 no-access
A sparsely populated (ie, not sequentially numbered) table of ratings for each panel. The number of entries is given by the value of pduNumPanels.
                 panelRatingsEntry 1.3.6.1.4.1.534.6.6.4.1.2.1.1 no-access
An entry containing information applicable to a particular output phase.
                     panelNumber 1.3.6.1.4.1.534.6.6.4.1.2.1.1.1 positiveinteger no-access
Index for the Panel Ratings and Meters tables. Corresponds to the physical panel number in the PDU system. There must be a #1. The maximum value is 16. Panels are not required to be numbered sequentially.
                     panelRatedVoltage 1.3.6.1.4.1.534.6.6.4.1.2.1.1.2 positiveinteger read-only
The nominal Voltage of this panel (as distributed to the breakers or subfeeds). This is either Line-to-Line or Line-to-Neutral, as indicated in panelVoltageUnits.
                     panelRatedBreakerCurrent 1.3.6.1.4.1.534.6.6.4.1.2.1.1.3 positiveinteger read-only
The rated current value for one panel (input) phase at full load (100%). This is set by the panel's input breaker; if there is no input breaker for this panel, then this object is not accessible.
                     panelNumPhases 1.3.6.1.4.1.534.6.6.4.1.2.1.1.4 positiveinteger read-only
The number of lines (phases) for this panel.
                     panelNumBreakers 1.3.6.1.4.1.534.6.6.4.1.2.1.1.5 positiveinteger read-only
The number of breakers contained in this panel. This determines the number of rows found in the breaker tables.
                     panelVoltageUnits 1.3.6.1.4.1.534.6.6.4.1.2.1.1.6 displaystring read-only
Indicates whether the panelPhaseVoltage readings are 'Vrms Line-Line' or 'Vrms Line-Neutral'.
             panelMetersTable 1.3.6.1.4.1.534.6.6.4.1.2.2 no-access
A sparsely populated (ie, not sequentially numbered) table of ratings for each panel. The number of entries is given by the value of pduNumPanels.
                 panelMetersEntry 1.3.6.1.4.1.534.6.6.4.1.2.2.1 no-access
An entry containing meter readings applicable to a particular panel.
                     panelTotalKilowattHours 1.3.6.1.4.1.534.6.6.4.1.2.2.1.1 nonnegativeinteger read-only
The accumulated kilowatt-hours for this panel since it was commissioned and put into service, or since the last reset of the system KHW measures.
                     panelMonthlyKilowattHours 1.3.6.1.4.1.534.6.6.4.1.2.2.1.2 nonnegativeinteger read-only
The accumulated kilowatt-hours for this panel since the beginning of this calendar month, or since the last reset of the system KHW measures.
                     panelYtdKilowattHours 1.3.6.1.4.1.534.6.6.4.1.2.2.1.3 nonnegativeinteger read-only
The accumulated kilowatt-hours for this panel since the beginning of this calendar year (YTD), or since the last reset of the system KHW measures.
                     panelVA 1.3.6.1.4.1.534.6.6.4.1.2.2.1.4 nonnegativeinteger read-only
The present VA (input) demand of this panel.
                     panelPower 1.3.6.1.4.1.534.6.6.4.1.2.2.1.5 nonnegativeinteger read-only
The present power (input) demand of this panel.
                     panelPowerFactor 1.3.6.1.4.1.534.6.6.4.1.2.2.1.6 integer32 read-only
The input power factor for this panel. Varies from -1.00 to 1.00, multiplied by 100. If negative values are used, they indicate lagging pf.
                     panelNeutralCurrent 1.3.6.1.4.1.534.6.6.4.1.2.2.1.7 nonnegativeinteger read-only
The present neutral phase current for this panel.
             panelPhaseMetersTable 1.3.6.1.4.1.534.6.6.4.1.2.3 no-access
A sparsely populated (ie, not sequentially panel numbered) table of ratings for each panel. The number of entries is given by the sum of panelNumPhases for pduNumPanels.
                 panelPhaseMetersEntry 1.3.6.1.4.1.534.6.6.4.1.2.3.1 no-access
An entry containing meter readings applicable to a particular phase of a particular panel.
                     panelPhaseIndex 1.3.6.1.4.1.534.6.6.4.1.2.3.1.1 positiveinteger no-access
The line or phase identifier.
                     panelPhaseVoltage 1.3.6.1.4.1.534.6.6.4.1.2.3.1.2 nonnegativeinteger read-only
The present voltage for this phase.
                     panelPhaseCurrent 1.3.6.1.4.1.534.6.6.4.1.2.3.1.3 nonnegativeinteger read-only
The present current for this phase.
                     panelPhasePercentLoad 1.3.6.1.4.1.534.6.6.4.1.2.3.1.4 integer32 read-only
The percentage of the panel power capacity presently being used on this line, normally based on the ratio of panelPhaseCurrent to the rated phase current.
         pduBreaker 1.3.6.1.4.1.534.6.6.4.1.3
             breakerRatingsTable 1.3.6.1.4.1.534.6.6.4.1.3.1 no-access
A sparsely populated (ie, not sequentially numbered) table of ratings and fixed values for each breaker. The number of entries is given by the value of panelNumBreakers for this panel.
                 breakerRatingsEntry 1.3.6.1.4.1.534.6.6.4.1.3.1.1 no-access
An entry containing information applicable to a particular output phase.
                     breakerNumber 1.3.6.1.4.1.534.6.6.4.1.3.1.1.1 positiveinteger no-access
Index for the Breaker Ratings and Meters tables. Corresponds to the physical breaker number in the PDU system. Breakers are not required to be numbered sequentially.
                     breakerName 1.3.6.1.4.1.534.6.6.4.1.3.1.1.2 displaystring read-only
Name given by the administrator to identify this breaker.
                     breakerRatedCurrent 1.3.6.1.4.1.534.6.6.4.1.3.1.1.3 positiveinteger read-only
The rated current value of this breaker (for one phase) at full load (100%).
                     breakerNumPhases 1.3.6.1.4.1.534.6.6.4.1.3.1.1.4 positiveinteger read-only
The number of lines (phases) for this breaker.
             breakerMetersTable 1.3.6.1.4.1.534.6.6.4.1.3.2 no-access
A sparsely populated (ie, not sequentially numbered) table of ratings for each breaker. The number of entries is given by the value of panelNumBreakers for this panel.
                 breakerMetersEntry 1.3.6.1.4.1.534.6.6.4.1.3.2.1 no-access
An entry containing meter readings applicable to a particular breaker.
                     breakerTotalKilowattHours 1.3.6.1.4.1.534.6.6.4.1.3.2.1.1 nonnegativeinteger read-only
The accumulated kilowatt-hours for this breaker since it was commissioned and put into service, or since the last reset of the panel KHW measures.
                     breakerMonthlyKilowattHours 1.3.6.1.4.1.534.6.6.4.1.3.2.1.2 nonnegativeinteger read-only
The accumulated kilowatt-hours for this breaker since the beginning of this calendar month, or since the last reset of the panel KHW measures.
                     breakerYtdKilowattHours 1.3.6.1.4.1.534.6.6.4.1.3.2.1.3 nonnegativeinteger read-only
The accumulated kilowatt-hours for this breaker since the beginning of this calendar year (YTD), or since the last reset of the panel KHW measures.
             breakerPhaseMetersTable 1.3.6.1.4.1.534.6.6.4.1.3.3 no-access
A sparsely populated (ie, not sequentially breaker numbered) table of ratings for each breaker. The number of entries is given by the sum of breakerNumPhases for panelNumBreakers for all panels (pduNumPanels).
                 breakerPhaseMetersEntry 1.3.6.1.4.1.534.6.6.4.1.3.3.1 no-access
An entry containing meter readings applicable to a particular phase of a particular breaker on a particular panel.
                     breakerPhaseIndex 1.3.6.1.4.1.534.6.6.4.1.3.3.1.1 positiveinteger no-access
The line or phase identifier.
                     breakerPhaseVA 1.3.6.1.4.1.534.6.6.4.1.3.3.1.2 nonnegativeinteger read-only
The present VA (input) demand of this phase on this breaker.
                     breakerPhasePower 1.3.6.1.4.1.534.6.6.4.1.3.3.1.3 nonnegativeinteger read-only
The present power (input) demand of phase on this breaker.
                     breakerPhasePowerFactor 1.3.6.1.4.1.534.6.6.4.1.3.3.1.4 integer32 read-only
The input power factor for this phase on this breaker. Varies from -1.00 to 1.00, multiplied by 100. If negative values are used, they indicate lagging pf.
                     breakerPhaseCurrent 1.3.6.1.4.1.534.6.6.4.1.3.3.1.5 nonnegativeinteger read-only
The present current for this phase of this breaker.
                     breakerPhasePercentLoad 1.3.6.1.4.1.534.6.6.4.1.3.3.1.6 integer32 read-only
The percentage of the breaker power capacity presently being used on this line, normally based on the ratio of breakerPhaseCurrent to the breakerRatedCurrent.
     eatonPduConformance 1.3.6.1.4.1.534.6.6.4.2
         pduNameplateGroup 1.3.6.1.4.1.534.6.6.4.2.1
The pduNameplate subgroup objects.
         pduInputGroup 1.3.6.1.4.1.534.6.6.4.2.2
The pduInput Meters subgroup objects.
         pduOutputGroup 1.3.6.1.4.1.534.6.6.4.2.3
The pduOutput Meters subgroup objects.
         panelRatingsGroup 1.3.6.1.4.1.534.6.6.4.2.4
The panelRatings table objects.
         panelMetersGroup 1.3.6.1.4.1.534.6.6.4.2.5
The BreakerMeters Table objects.
         panelPhaseMetersGroup 1.3.6.1.4.1.534.6.6.4.2.6
The BreakerPhaseMeters Table objects.
         breakerRatingsGroup 1.3.6.1.4.1.534.6.6.4.2.7
The breakerRatings table objects.
         breakerMetersGroup 1.3.6.1.4.1.534.6.6.4.2.8
The breakerMeters table objects.
         breakerPhaseMetersGroup 1.3.6.1.4.1.534.6.6.4.2.9
The breakerPhaseMeters table objects.
         pdu3phaseCompliance 1.3.6.1.4.1.534.6.6.4.2.10
The compliance statement for a normal 3-phase PDU, which implements the full set of objects.