EATON-EPDU-MA-MIB: View SNMP OID List / Download MIB

VENDOR: EATON CORPORATION


 Home MIB: EATON-EPDU-MA-MIB
Download as:   

Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 eatonEpduMa 1.3.6.1.4.1.534.6.6.6
The MIB module for Eaton ePDUs (Enclosed Power Distribution Units) -Managed Model.
     traps 1.3.6.1.4.1.534.6.6.6.0
         rebootStarted 1.3.6.1.4.1.534.6.6.6.0.1
The reboot process has started
         rebootCompleted 1.3.6.1.4.1.534.6.6.6.0.2
The reboot process is complete
         userLogin 1.3.6.1.4.1.534.6.6.6.0.3
A user logged in
         userLogout 1.3.6.1.4.1.534.6.6.6.0.4
A user logged out
         userAuthenticationFailure 1.3.6.1.4.1.534.6.6.6.0.5
A user authentication attempt failed
         userSessionTimeout 1.3.6.1.4.1.534.6.6.6.0.8
A user timed out from the device
         userAdded 1.3.6.1.4.1.534.6.6.6.0.11
A user was added to the system
         userModified 1.3.6.1.4.1.534.6.6.6.0.12
A user account was modified
         userDeleted 1.3.6.1.4.1.534.6.6.6.0.13
A user was deleted from the system
         groupAdded 1.3.6.1.4.1.534.6.6.6.0.14
A group was added to the system
         groupModified 1.3.6.1.4.1.534.6.6.6.0.15
A group was modified
         groupDeleted 1.3.6.1.4.1.534.6.6.6.0.16
A group was deleted from the system
         deviceUpdateStarted 1.3.6.1.4.1.534.6.6.6.0.20
The device update has started
         userBlocked 1.3.6.1.4.1.534.6.6.6.0.22
A blocked user tried to log in
         powerControl 1.3.6.1.4.1.534.6.6.6.0.23
An outlet has been switched
         userPasswordChanged 1.3.6.1.4.1.534.6.6.6.0.24
A user password was changed
         passwordSettingsChanged 1.3.6.1.4.1.534.6.6.6.0.28
Strong password settings changed
         firmwareFileDiscarded 1.3.6.1.4.1.534.6.6.6.0.36
A firmware file discarded
         firmwareValidationFailed 1.3.6.1.4.1.534.6.6.6.0.38
A firmware validation failed
         securityViolation 1.3.6.1.4.1.534.6.6.6.0.39
Security violation.
         logFileCleared 1.3.6.1.4.1.534.6.6.6.0.41
The log file has been cleared.
         thresholdAlarm 1.3.6.1.4.1.534.6.6.6.0.45
Configured sensor theshold event. The 'thresholdType' variable will indicate whether or not the threshold triggered or cleared
         outletGroupingConnectivityLost 1.3.6.1.4.1.534.6.6.6.0.50
Master PDU lost contact with the slave PDU in an outlet grouping configuration.
     board 1.3.6.1.4.1.534.6.6.6.1
         info 1.3.6.1.4.1.534.6.6.6.1.1
             firmwareVersion 1.3.6.1.4.1.534.6.6.6.1.1.1 displaystring read-only
The current firmware version
             serialNumber 1.3.6.1.4.1.534.6.6.6.1.1.2 displaystring read-only
The serial number.
             ipAddress 1.3.6.1.4.1.534.6.6.6.1.1.3 ipaddress read-only
The current IP address. A value of 0.0.0.0 indicates an error or an unset option.
             netmask 1.3.6.1.4.1.534.6.6.6.1.1.4 ipaddress read-only
The current Netmask. A value of 0.0.0.0 indicates an error or an unset option.
             gateway 1.3.6.1.4.1.534.6.6.6.1.1.5 ipaddress read-only
The current Gateway. A value of 0.0.0.0 indicates an error or an unset option.
             mac 1.3.6.1.4.1.534.6.6.6.1.1.6 macaddress read-only
The current MAC address.
             hardwareRev 1.3.6.1.4.1.534.6.6.6.1.1.7 integer32 read-only
The hardware revision number.
             userName 1.3.6.1.4.1.534.6.6.6.1.1.10 displaystring no-access
The login of a user.
             objectName 1.3.6.1.4.1.534.6.6.6.1.1.12 displaystring no-access
The model type of the device
             objectInstance 1.3.6.1.4.1.534.6.6.6.1.1.13 displaystring no-access
The device name
             targetUser 1.3.6.1.4.1.534.6.6.6.1.1.14 displaystring no-access
The user record being operated on
             groupName 1.3.6.1.4.1.534.6.6.6.1.1.15 displaystring no-access
The group record being operated on
             imageVersion 1.3.6.1.4.1.534.6.6.6.1.1.18 displaystring no-access
The version of the Upgrade image
             sensorDescr 1.3.6.1.4.1.534.6.6.6.1.1.19 displaystring no-access
Sensor description indicating which sensor experienced a threshold exceeded event. When applicable the description will indicate the sensor number.
             thresholdDescr 1.3.6.1.4.1.534.6.6.6.1.1.20 displaystring no-access
Threshold description indicating which configured threshold has been triggered (or cleared).
             thresholdSeverity 1.3.6.1.4.1.534.6.6.6.1.1.21 displaystring no-access
String (Warning, Critical, etc...) indicating the severity of the threshold which has been triggered (or cleared).
             thresholdEventType 1.3.6.1.4.1.534.6.6.6.1.1.22 displaystring no-access
String (triggered, cleared) indicating if the threshold event indicates that a configured threshold has been triggered or cleared.
             status 1.3.6.1.4.1.534.6.6.6.1.1.23 displaystring no-access
The success status of an operation
             slaveIpAddress 1.3.6.1.4.1.534.6.6.6.1.1.24 ipaddress read-only
In a shepherding configuration, this is the IP address of slave PDU. A value of 0.0.0.0 indicates an error or an unset option.
         outlets 1.3.6.1.4.1.534.6.6.6.1.2
             outletCount 1.3.6.1.4.1.534.6.6.6.1.2.1 integer32 read-only
The number of outlets (regardless of their current state) present on this pdu.
             outletTable 1.3.6.1.4.1.534.6.6.6.1.2.2 no-access
A list of outlet entries. The number of entries is given by the value of outletCount.
                 outletEntry 1.3.6.1.4.1.534.6.6.6.1.2.2.1 no-access
An outlet entry containing objects at the for a particular outlet.
                     outletIndex 1.3.6.1.4.1.534.6.6.6.1.2.2.1.1 integer32 no-access
A unique value for each outlet. Its value ranges between 1 and the value of outletCount.
                     outletLabel 1.3.6.1.4.1.534.6.6.6.1.2.2.1.2 displaystring read-write
A textual string containing information about the outlet.
                     outletOperationalState 1.3.6.1.4.1.534.6.6.6.1.2.2.1.3 integer read-write
A value for each outlet which describes the operational state of the outlet. It is also used to set the operational state of the outlet Enumeration: 'on': 1, 'cycling': 2, 'off': 0, 'error': -1.
                     outletCurrent 1.3.6.1.4.1.534.6.6.6.1.2.2.1.4 milliamps read-only
A unique value for the current sensor attached to the outlet. This value is reported in milliamps (1/1000th of an amp)
                     outletMaxCurrent 1.3.6.1.4.1.534.6.6.6.1.2.2.1.5 milliamps read-only
A unique value for the max. current sensor attached to the outlet. This value is reported in milliamps (1/1000th of an amp)
                     outletVoltage 1.3.6.1.4.1.534.6.6.6.1.2.2.1.6 millivolts read-only
A unique value for the voltage sensor attached to the outlet.This value is reported in millivolts (1/1000th of a volt)
                     outletActivePower 1.3.6.1.4.1.534.6.6.6.1.2.2.1.7 watts read-only
A unique value for the active power sensor attached to the outlet. This value is reported in Watts.
                     outletApparentPower 1.3.6.1.4.1.534.6.6.6.1.2.2.1.8 voltamps read-only
A unique value for the apparent power sensor attached to the outlet. This value is reported in Volt-Amps
                     outletPowerFactor 1.3.6.1.4.1.534.6.6.6.1.2.2.1.9 powerfactorpercentage read-only
A unique value for the power factor of the outlet. The reading represents a percentage in the range of 0% to 100%.
                     outletCurrentUpperWarning 1.3.6.1.4.1.534.6.6.6.1.2.2.1.21 milliamps read-write
The value of the upper warning (non-critical) current threshold for the outlet. This value is reported in milliamps (1/1000th of an amp)
                     outletCurrentUpperCritical 1.3.6.1.4.1.534.6.6.6.1.2.2.1.23 milliamps read-write
The value of the upper critical current threshold for the outlet. This value is reported in milliamps (1/1000th of an amp)
         unit 1.3.6.1.4.1.534.6.6.6.1.3
             unitReadings 1.3.6.1.4.1.534.6.6.6.1.3.1
                 unitCurrent 1.3.6.1.4.1.534.6.6.6.1.3.1.1 milliamps read-only
The value for the unit's current sensor in millamps.
                 unitVoltage 1.3.6.1.4.1.534.6.6.6.1.3.1.2 millivolts read-only
The value for the unit's voltage sensor in millivolts.
                 unitActivePower 1.3.6.1.4.1.534.6.6.6.1.3.1.3 watts read-only
The value for the unit's voltage sensor in volt-amps.
                 unitApparentPower 1.3.6.1.4.1.534.6.6.6.1.3.1.4 watts read-only
The value for the unit's voltage sensor in volt-amps.
                 unitCpuTemp 1.3.6.1.4.1.534.6.6.6.1.3.1.5 degreescelsius read-only
The value for the unit's CPU temperature sensor in degrees Celsius.
                 unitCircuitBreak0State 1.3.6.1.4.1.534.6.6.6.1.3.1.20 integer read-only
The value for the unit's circuit breaker state sensor 0. Enumeration: 'ok': 0, 'unavailable': -1, 'tripped': 1.
                 unitCircuitBreak1State 1.3.6.1.4.1.534.6.6.6.1.3.1.21 integer read-only
The value for the unit's circuit breaker state sensor 1. Enumeration: 'ok': 0, 'unavailable': -1, 'tripped': 1.
                 unitCircuitBreak2State 1.3.6.1.4.1.534.6.6.6.1.3.1.22 integer read-only
The value for the unit's circuit breaker state sensor 2. Enumeration: 'ok': 0, 'unavailable': -1, 'tripped': 1.
                 unitCircuitBreak0Current 1.3.6.1.4.1.534.6.6.6.1.3.1.40 milliamps read-only
The value for the unit's circuit breaker current sensor 0.
                 unitCircuitBreak1Current 1.3.6.1.4.1.534.6.6.6.1.3.1.41 milliamps read-only
The value for the unit's circuit breaker current sensor 1.
                 unitCircuitBreak2Current 1.3.6.1.4.1.534.6.6.6.1.3.1.42 milliamps read-only
The value for the unit's circuit breaker current sensor 2.
                 unitVoltageLowerWarning 1.3.6.1.4.1.534.6.6.6.1.3.1.60 millivolts read-write
The value of the lower warning (non-critical) unit level voltage threshold.
                 unitVoltageLowerCritical 1.3.6.1.4.1.534.6.6.6.1.3.1.61 millivolts read-write
The value of the lower critical unit level voltage threshold.
                 unitVoltageUpperWarning 1.3.6.1.4.1.534.6.6.6.1.3.1.62 millivolts read-write
The value of the upper warning (non-critical) unit level voltage threshold.
                 unitVoltageUpperCritical 1.3.6.1.4.1.534.6.6.6.1.3.1.63 millivolts read-write
The value of the upper critical unit level voltage threshold.
                 unitCurrentUpperWarning 1.3.6.1.4.1.534.6.6.6.1.3.1.70 milliamps read-write
The value of the upper warning (non-critical) unit level current threshold.
                 unitCurrentUpperCritical 1.3.6.1.4.1.534.6.6.6.1.3.1.71 milliamps read-only
The value of the upper critical unit level current threshold. NOTE: This particular threshold is NOT settable
                 unitTempLowerWarning 1.3.6.1.4.1.534.6.6.6.1.3.1.80 degreescelsius read-write
The value of the lower warning (non-critical) unit level temperature threshold.
                 unitTempLowerCritical 1.3.6.1.4.1.534.6.6.6.1.3.1.81 degreescelsius read-write
The value of the lower critical unit level temperature threshold.
                 unitTempUpperWarning 1.3.6.1.4.1.534.6.6.6.1.3.1.82 degreescelsius read-write
The value of the upper warning (non-critical) unit level temperature threshold.
                 unitTempUpperCritical 1.3.6.1.4.1.534.6.6.6.1.3.1.83 degreescelsius read-write
The value of the upper critical unit level temperature threshold.
     environmental 1.3.6.1.4.1.534.6.6.6.2
         tempSensorCount 1.3.6.1.4.1.534.6.6.6.2.1 integer32 read-only
The number of external temperature sensors (regardless of their current state) present on this pdu.
         tempSensorTable 1.3.6.1.4.1.534.6.6.6.2.2 no-access
A list of temperature sensor entries. The number of entries is given by the value of tempSensorCount.
             tempSensorEntry 1.3.6.1.4.1.534.6.6.6.2.2.1 no-access
An entry containing sensor reading and threshold settings for a particular temperature sensor.
                 tempSensorIndex 1.3.6.1.4.1.534.6.6.6.2.2.1.1 integer32 no-access
A unique value for each temperature sensor. Its value ranges between 1 and tempSensorCount.
                 tempSensorLabel 1.3.6.1.4.1.534.6.6.6.2.2.1.2 displaystring read-write
A settable human-readable label for the external temperature sensor. One possible use for this label is to convey sensor location.
                 temperature 1.3.6.1.4.1.534.6.6.6.2.2.1.3 degreescelsius read-only
The value of the external temperature sensor reported in degrees celsius.
                 tempLowerWarning 1.3.6.1.4.1.534.6.6.6.2.2.1.4 degreescelsius read-write
The value of the lower warning (non-critical) threshold.
                 tempUpperWarning 1.3.6.1.4.1.534.6.6.6.2.2.1.5 degreescelsius read-write
The value of the upper warning (non-critical) threshold.
                 tempLowerCritical 1.3.6.1.4.1.534.6.6.6.2.2.1.6 degreescelsius read-write
The value of the lower critical threshold.
                 tempUpperCritical 1.3.6.1.4.1.534.6.6.6.2.2.1.7 degreescelsius read-write
The value of the upper critical threshold.
                 tempLowerWarningReset 1.3.6.1.4.1.534.6.6.6.2.2.1.8 degreescelsius read-write
The value of the lower warning (non-critical) reset/hysteresis value.
                 tempUpperWarningReset 1.3.6.1.4.1.534.6.6.6.2.2.1.9 degreescelsius read-write
The value of the upper warning (non-critical) reset/hysteresis value.
                 tempLowerCriticalReset 1.3.6.1.4.1.534.6.6.6.2.2.1.10 degreescelsius read-write
The value of the lower critical reset/hysteresis value.
                 tempUpperCriticalReset 1.3.6.1.4.1.534.6.6.6.2.2.1.11 degreescelsius read-write
The value of the upper critical reset/hysteresis value.
         humiditySensorCount 1.3.6.1.4.1.534.6.6.6.2.3 integer32 read-only
The number of external humidity sensors (regardless of their current state) present on this pdu.
         humiditySensorTable 1.3.6.1.4.1.534.6.6.6.2.4 no-access
A list of humidity sensor entries. The number of entries is given by the value of humiditySensorCount.
             humiditySensorEntry 1.3.6.1.4.1.534.6.6.6.2.4.1 no-access
An entry containing sensor reading and threshold settings for a particular humidity sensor.
                 humiditySensorIndex 1.3.6.1.4.1.534.6.6.6.2.4.1.1 integer32 no-access
A unique value for each humidity sensor. Its value ranges between 1 and humiditySensorCount.
                 humiditySensorLabel 1.3.6.1.4.1.534.6.6.6.2.4.1.2 displaystring read-write
A settable human-readable label for the external humidity sensor. One possible use for this label is to convey sensor location.
                 humidity 1.3.6.1.4.1.534.6.6.6.2.4.1.3 relativehumidity read-only
The value of the external humidity sensor reported as relative humidity (a percentage).
                 humidityLowerWarning 1.3.6.1.4.1.534.6.6.6.2.4.1.4 relativehumidity read-write
The value of the lower warning (non-critical) threshold.
                 humidityUpperWarning 1.3.6.1.4.1.534.6.6.6.2.4.1.5 relativehumidity read-write
The value of the upper warning (non-critical) threshold.
                 humidityLowerCritical 1.3.6.1.4.1.534.6.6.6.2.4.1.6 relativehumidity read-write
The value of the lower critical threshold.
                 humidityUpperCritical 1.3.6.1.4.1.534.6.6.6.2.4.1.7 relativehumidity read-write
The value of the upper critical threshold.
                 humidityLowerWarningReset 1.3.6.1.4.1.534.6.6.6.2.4.1.8 relativehumidity read-write
The value of the lower warning (non-critical) reset/hysteresis value.
                 humidityUpperWarningReset 1.3.6.1.4.1.534.6.6.6.2.4.1.9 relativehumidity read-write
The value of the upper warning (non-critical) reset/hysteresis value.
                 humidityLowerCriticalReset 1.3.6.1.4.1.534.6.6.6.2.4.1.10 relativehumidity read-write
The value of the lower critical reset/hysteresis value.
                 humidityUpperCriticalReset 1.3.6.1.4.1.534.6.6.6.2.4.1.11 relativehumidity read-write
The value of the upper critical reset/hysteresis value.
     conformance 1.3.6.1.4.1.534.6.6.6.9
         compliances 1.3.6.1.4.1.534.6.6.6.9.1
             compliance 1.3.6.1.4.1.534.6.6.6.9.1.1
The requirements for conformance to the PDU-MIB.
         groups 1.3.6.1.4.1.534.6.6.6.9.2
             infoGroup 1.3.6.1.4.1.534.6.6.6.9.2.1
A collection of objects providing basic information about the pdu.
             outletsGroup 1.3.6.1.4.1.534.6.6.6.9.2.2
A collection of objects providing basic information about the outlets, including sensor readings.
             unitSensorsGroup 1.3.6.1.4.1.534.6.6.6.9.2.4
A collection of objects providing unit level sensor readings.
             externalTemperatureGroup 1.3.6.1.4.1.534.6.6.6.9.2.6
A collection of objects providing external temperature sensor readings and threshold settings.
             externalHumidityGroup 1.3.6.1.4.1.534.6.6.6.9.2.7
A collection of objects providing external humidity sensor readings and threshold settings.
             trapsGroup 1.3.6.1.4.1.534.6.6.6.9.2.9
A collection of traps.