DESCH-PSC3-BASE-MIB: View SNMP OID List / Download MIB

VENDOR: DELTA ELECTRONICS (SWITZERLAND) AG


 Home MIB: DESCH-PSC3-BASE-MIB
Download as:   

Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 deschPsc3BaseMibModule 1.3.6.1.4.1.20246.2.1.1.2
MIB for managing a DC power system with PSC 3.
     deschPsc3BaseMib 1.3.6.1.4.1.20246.2.3.1.1.1
         deschControllerConfs 1.3.6.1.4.1.20246.2.3.1.1.1.1
             deschControllerGroups 1.3.6.1.4.1.20246.2.3.1.1.1.1.1
                 deschSystemInfoGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.1
The collection of system info scalar objects.
                 deschSystemAlarmGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.2
The collection of system alarm scalar objects.
                 deschSystemMonitorGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.3
The collection of system monitor scalar objects.
                 deschRectifiersGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.4
The collection of rectifier scalar objects.
                 deschEventHistoryTableGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.5
The collection of event history table objects.
                 deschAlarmTableGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.6
The collection of alarm table objects.
                 deschRectifierTableGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.7
The collection of rectifier table objects.
                 deschNotificationsGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.8
The group of all controller notifications.
                 deschGenericAlarmTableGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.9
Assignment of events to alarm table entries.
                 deschBatteryGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.10
The collection of battery scalar objects.
                 deschControlEventTableGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.11
Assignment of control events to table entries.
                 deschTrapDestinationTableGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.12
Trap destionation table.
                 deschMiscGroup 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.13
The collection of miscellaneous objects.
             deschControllerCompl 1.3.6.1.4.1.20246.2.3.1.1.1.1.2
                 deschControllerBasicCompl 1.3.6.1.4.1.20246.2.3.1.1.1.1.2.1
The basic implementation requirements for the controller MIB.
         deschControllerObjects 1.3.6.1.4.1.20246.2.3.1.1.1.2
             dcSystemInfo 1.3.6.1.4.1.20246.2.3.1.1.1.2.1
                 dcSiteName 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.1 displaystring read-only
An administratively-assigned site name for this DC-power system.
                 dcSystemName 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.2 displaystring read-only
An administratively-assigned system name for this DC-power system.
                 dcSystemDateTime 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.3 displaystring read-write
ISO 8601 representation of controller's local date/time. The value is in the format YYYY-MM-DDThh:mm:ss. An example of a valid string is: '2004-10-04T13:45:00'.
                 dcSoftwareVersion 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.4 displaystring read-only
The controller's software version e.g V2.50Build1.
             dcSystemAlarms 1.3.6.1.4.1.20246.2.3.1.1.1.2.2
                 dcEventHistoryTable 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1 no-access
Controller's event history table that shows the content of the default log file.
                     dcEventHistoryEntry 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1 no-access
A particular Event History entry.
                         dcEventHistoryIndex 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.1 integer32 no-access
Table index.
                         dcEventHistoryTimestamp 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.2 displaystring read-only
ISO8601 timestamp representation of a particular entry in the form YYYY-MM-DDThh:mm:ss.
                         dcEventHistoryMessage 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.3 displaystring read-only
Event message of a particular entry.
                 dcAlarmTable 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2 no-access
Table that shows all currently active alarm sources causing urgent or non-urgent alarm(s).
                     dcAlarmEntry 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1 no-access
A particular active alarm source entry.
                         dcAlarmIndex 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.1 integer32 no-access
Table index.
                         dcAlarmEventCategory 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.2 integer read-only
Specifies the type of alarm source. Enumeration: 'unknown': 1, 'nonUrgent': 3, 'urgent': 2.
                         dcAlarmEventName 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.3 displaystring read-only
Name of a particular alarm source entry.
                         dcAlarmEventIdentifier 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.4 gauge32 read-only
Unique alarm event identifier.
                         dcAlarmEventValue 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.5 integer read-only
Event status that corresponds to alarm event identifier. Enumeration: 'true': 3, 'indeterminate': 2, 'false': 1.
                 dcNumberUrgentAlarms 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.3 gauge32 read-only
Number of currently active urgent alarm sources. A zero value indicates that urgent alarm is not active.
                 dcNumberNonUrgentAlarms 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.4 gauge32 read-only
Number of currently active non urgent alarm sources. A zero value indicates that non urgent alarm is not active.
                 dcMainsFailureAlarm 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.5 integer read-only
Mains failure alarm. Enumeration: 'active': 2, 'inactive': 1.
                 dcUrgentAlarmIdentifier 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.6 gauge32 read-only
Current unique urgent alarm event identifier. A zero value indicates that urgent alarm is not active.
                 dcUrgentAlarmValue 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.7 integer read-only
Current urgent alarm event status that corresponds to the urgent alarm identifier. If the urgent alarm identifier is zero then the alarm value is false. Enumeration: 'true': 3, 'indeterminate': 2, 'false': 1.
                 dcNonUrgentAlarmIdentifier 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.8 gauge32 read-only
Current unique non urgent alarm event identifier. A zero value indicates that non urgent alarm is not active.
                 dcNonUrgentAlarmValue 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.9 integer read-only
Current non urgent alarm event status that corresponds to non urgent alarm identifier. If the non urgent alarm identifier is zero then the alarm value is false. Enumeration: 'true': 3, 'indeterminate': 2, 'false': 1.
                 dcUrgentAlarmName 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.10 displaystring read-only
Current alarm name for urgent alarm that corresponds to urgent alarm identifier.
                 dcNonUrgentAlarmName 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.11 displaystring read-only
Current alarm name for active non urgent alarm that corresponds to non urgent alarm identifier.
                 dcGenericAlarmTable 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12 no-access
Table that shows ten alarm event assignments that can be configured via WEB interface.
                       dcGenericAlarmEntry 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1 no-access
A particular generic alarm entry.
                           dcGenericAlarmIndex 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.1 integer32 no-access
Table index.
                           dcGenericAlarmEventName 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.2 displaystring read-only
Plain text name of the assigned alarm event. Empty if not configured.
                           dcGenericAlarmEventIdentifier 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.3 gauge32 read-only
Unique numeric identifier of the assigned alarm event. Zero if not configured.
                           dcGenericAlarmEventValue 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.4 integer read-only
Current value of the assigned alarm event. Value is false if not configured. Enumeration: 'true': 2, 'false': 1.
             dcSystemMonitor 1.3.6.1.4.1.20246.2.3.1.1.1.2.3
                 dcSystemVoltage 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.1 integer32 read-only
The measured system voltage. The max. value 2147483647 is used to indicate an invalid value.
                 dcLoadCurrent 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.2 integer32 read-only
The measured load current. The max. value 2147483647 is used to indicate an invalid value.
                 dcBatteryCurrent 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.3 integer32 read-only
The measured battery current. The max. value 2147483647 is used to indicate an invalid value.
                 dcBatteryTemperature 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.4 integer32 read-only
The measured battery temperature. The max. value 2147483647 is used to indicate an invalid value.
                 dcChargeState 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.5 integer read-only
Battery charge state. Enumeration: 'sepCharge': 7, 'float': 1, 'battTest': 5, 'evCtrlCharge': 8, 'equalize': 3, 'discharge': 2, 'boost': 4, 'recharge': 6.
                 dcCurrentLimit 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.6 integer read-only
Battery current limit. Enumeration: 'active': 2, 'inactive': 1.
                 dcRectifierCurrent 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.7 integer32 read-only
Total current of all working rectifier modules. The maximum value 2147483647 is used to indicate an invalid value.
                 dcSystemPower 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.8 gauge32 read-only
Calculated system power. The maximum value 4294967295 is used to indicate an invalid value.
             dcRectifier 1.3.6.1.4.1.20246.2.3.1.1.1.2.4
                 dcNumberRectifiers 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.1 gauge32 read-only
The configured number of rectifiers plugged into the system. The maximum number of rectifiers is 128.
                 dcNumberRectifiersFailure 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.2 gauge32 read-only
Number of rectifiers that are not properly working.
                 dcNumberRectifiersOkay 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.3 gauge32 read-only
Number of rectifiers that are properly working.
                 dcRectifierTable 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4 no-access
Table that shows all currently active rectifier modules.
                     dcRectifierEntry 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1 no-access
A particular rectifier entry.
                         dcRectifierIndex 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.1 integer32 no-access
Table index.
                         dcRectifierIdentifier 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.2 displaystring read-only
Unique rectifier identifier. If positioning active the position number scheme is used otherwise the rectifier instance is used to identify a rectifier.
                         dcRectifierStatus 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.3 integer read-only
Specifies status of rectifiers. Enumeration: 'unknown': 1, 'off': 2, 'on': 3.
             dcBattery 1.3.6.1.4.1.20246.2.3.1.1.1.2.5
                 dcFloatCharge 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.1
                     dcUsys20 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.1.1 integer32 read-only
Voltage to regulate to at 20oC. If temperature compensation is used, this voltage will vary. The maximum value 2147483647 is used to indicate an invalid value.
                     dcTcoeff 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.1.2 integer32 read-only
Temperature compensation coefficient for system voltage. The maximum value 2147483647 is used to indicate an invalid value.
                     dcTcLow 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.1.3 integer32 read-only
Low limit for the area in which the temperature compensation is active. The maximum value 2147483647 is used to indicate an invalid value.
                     dcTcHigh 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.1.4 integer32 read-only
High limit for the area in which the temperature compensation is active. The maximum value 2147483647 is used to indicate an invalid value.
                 dcBatteryTest 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2
                     dcBatteryTestParameter 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1
                         dcUsupport 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.1 integer32 read-only
Support charge voltage for the battery. The maximum value 2147483647 is used to indicate an invalid value.
                         dcDuration 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.2 gauge32 read-only
Battery test duration. Zero indicates that this value is not set.
                         dcInterval 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.3 gauge32 read-only
Minimal time between programmed battery tests. Zero indicates that this value is not set.
                         dcDischargeCurrent 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.4 integer32 read-only
Battery discharge current. The maximum value 2147483647 is used to indicate an invalid value.
                     dcBatteryTestResult 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2
                         dcTestDateTime 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2.1 displaystring read-only
ISO 8601 representation of the last performed battery test. The value is in the format YYYY-MM-DDThh:mm:ss. This parameter is valid only if there is a test result available.
                         dcTestResult 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2.2 integer read-only
Result of last performed battery test. Enumeration: 'failed': 2, 'none': 1, 'okay': 5, 'aborted': 3, 'loadFailure': 4.
                         dcTestEndVoltage 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2.3 integer32 read-only
System voltage at the end of the last performed battery test. The maximum value 2147483647 is used to indicate an invalid value.
                     dcBatteryTestControl 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.3 integer read-write
Start/stop of battery test. This special charge mode is used to check the capacity of a battery. Please not that a battery test can be started even if the battery is not fully charged. In this case the test result is ambiguous and the set failure event will become active. Enumeration: 'start': 1, 'stop': 2.
                     dcBatteryTestStatus 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.4 integer read-only
Current status of battery test. Enumeration: 'constantCurrent': 4, 'recovery': 7, 'realLoad': 8, 'timeBased': 5, 'stop': 9, 'inactive': 1, 'stopping': 3, 'starting': 2, 'energyBased': 6.
                     dcBatteryTestFailureEvent 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.5 integer read-write
Reset battery test failure event. Enumeration: 'reset': 1.
                 dcBatteryParameter 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3
                     dcTotalBatteryCapacity 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.1 gauge32 read-only
Total battery capacity for all available batteries.
                 dcEqualize 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4
                     dcEqualizeControl 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.1 integer read-write
Start/stop of battery equalize which is a special charge mode that applies a higher voltage to the batteries than the float charge. This ensures that the cells are all equally charged. Enumeration: 'start': 1, 'stop': 2.
                     dcEqualizeStatus 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.2 integer read-only
Current status of battery equalize. Enumeration: 'recovering': 6, 'cooking': 5, 'inactive': 1, 'preparing': 4, 'stopping': 3, 'starting': 2.
                 dcBoostCharge 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5
                     dcBoostChargeControl 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.1 integer read-write
Start/stop of boost charge which is a special charge mode that applies a higher voltage to the batteries than the float charge. This mode is started after a discharge phase to recharge the batteries faster. Enumeration: 'start': 1, 'stop': 2.
                     dcBoostChargeStatus 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.2 integer read-only
Current status of boost charge. Enumeration: 'stopping': 3, 'inactive': 1, 'starting': 2, 'cooking': 4, 'recovering': 5.
             dcInputOutput 1.3.6.1.4.1.20246.2.3.1.1.1.2.6
                 dcControlEventTable 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1 no-access
Table that shows ten output event assignments that can be configured via WEB interface.
                     dcControlEventEntry 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1 no-access
A particular generic output entry.
                         dcControlEventIndex 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.1 integer32 no-access
Table index.
                         dcControlEventName 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.2 displaystring read-only
Plain text name of the assigned control event. Empty if not configure.
                         dcControlEventIdentifier 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.3 gauge32 read-only
Unique numeric identifier of the assigned control event. Zero if not configured.
                         dcControlEventValue 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.4 integer read-write
Current value of the assigned control event. Value is false if not configured. Enumeration: 'true': 2, 'false': 1.
             dcMisc 1.3.6.1.4.1.20246.2.3.1.1.1.2.7
                 dcTrapDestinationTable 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1 no-access
Trap table that shows all configured trap destinations.
                     dcTrapDestinationEntry 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1 no-access
A particular trap destination entry.
                         dcTrapDestinationIndex 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.1 integer32 no-access
Table index.
                         dcTrapDestinationIp 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.2 ipaddress read-write
IP address of the trap destination. Value is 0.0.0.0 if IP address is not configured.
                         dcTrapDestinationPort 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.3 gauge32 read-write
Port number of the trap destination. By default port 162 is used.
                 dcFileProcessingStatus 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.2 integer read-only
File processing status for software and setup up/downloads. Enumeration: 'successful': 3, 'unknown': 5, 'idle': 1, 'inProgress': 2, 'error': 4.
                 dcSetupConfiguration 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.3 integer read-write
Save current setup configuration to non-volatile memory. Enumeration: 'save': 1.
         deschControllerEvents 1.3.6.1.4.1.20246.2.3.1.1.1.3
             deschControllerEventObjects 1.3.6.1.4.1.20246.2.3.1.1.1.3.1
                 deschControllerEventsV2 1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0
                     systemNonUrgentAlarm 1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0.1
The controller reports that one or more elements have changed into none urgent alarm state.
                     systemUrgentAlarm 1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0.2
The controller reports that one or more elements have changed into urgent alarm state.