CYCLADES-ACS5K-PM-MIB: View SNMP OID List / Download MIB
VENDOR: CYCLADES CORPORATION
Home | MIB: CYCLADES-ACS5K-PM-MIB | |||
---|---|---|---|---|
Download as: |
Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
|
|||
Object Name | OID | Type | Access | Info |
cyACS5KPM | 1.3.6.1.4.1.2925.8.5 |
This module defines objects of the Proxy for PM |
||
cyNumberOfPM | 1.3.6.1.4.1.2925.8.5.1 | integer32 | read-only |
The total number of PM's connected on the unit |
cyPMTable | 1.3.6.1.4.1.2925.8.5.2 | no-access |
Allows to read information about each connected PM |
|
1.3.6.1.4.1.2925.8.5.2.1 | no-access |
Information about the connected PM |
||
cyPMSerialPortNumber | 1.3.6.1.4.1.2925.8.5.2.1.1 | interfaceindex | read-only |
The number of the serial port when the PM is connected. |
cyPMNumberOutlets | 1.3.6.1.4.1.2925.8.5.2.1.2 | integer32 | read-only |
Number of outlets. |
cyPMNumberUnits | 1.3.6.1.4.1.2925.8.5.2.1.3 | integer32 | read-only |
Total number of PM unists that are accessed by this serial port. |
cyPMCurrent | 1.3.6.1.4.1.2925.8.5.2.1.4 | displaystring | read-only |
Current reading for the PM. |
cyPMVersion | 1.3.6.1.4.1.2925.8.5.2.1.5 | displaystring | read-only |
The software version of the PM. |
cyPMCommand | 1.3.6.1.4.1.2925.8.5.2.1.7 | displaystring | read-write |
A character string for the user to send commands to PM. He can use it to does the save command. Or to list the outlets that need to be turned off, or turned on , or cycled or locked or unlocked as a group. The command is the first word and is followed by a space and the outlet list (otulets commands). Valid commands are 'on', 'off', 'cycle', 'lock', 'unlock', 'save'. |
cyPMUnitTable | 1.3.6.1.4.1.2925.8.5.3 | no-access |
Allow operations on specific PM unit connected |
|
1.3.6.1.4.1.2925.8.5.3.1 | no-access |
Allow operations on outlet |
||
cyPMUnitNumber | 1.3.6.1.4.1.2925.8.5.3.1.1 | interfaceindex | no-access |
The number of the PM unit in the daisy-chained mode. |
cyPMUnitVersion | 1.3.6.1.4.1.2925.8.5.3.1.2 | displaystring | read-only |
The software version of this PM unit. |
cyPMUnitOutlets | 1.3.6.1.4.1.2925.8.5.3.1.3 | integer32 | read-only |
Number of outlets of this PM unit. |
cyPMUnitFirstOutlet | 1.3.6.1.4.1.2925.8.5.3.1.4 | integer32 | read-only |
Number of the first outlet of this PM unit. |
cyPMUnitCurrent | 1.3.6.1.4.1.2925.8.5.3.1.5 | integer32 | read-only |
Current of this PM unit in AMP. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.) |
cyPMUnitMaxCurrent | 1.3.6.1.4.1.2925.8.5.3.1.6 | integer32 | read-only |
Maximum current of this PM unit in AMP. The value of this object is the maximum current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the maximum current is 0.5 AMP.) |
cyPMUnitSequenceInterval | 1.3.6.1.4.1.2925.8.5.3.1.9 | integer32 | read-only |
Sequence interval delay. Valid values are 2 to 15 (seconds). |
cyPMUnitCycleInterval | 1.3.6.1.4.1.2925.8.5.3.1.10 | integer32 | read-only |
Number of seconds that a socket stays off before turning it back on. |
cyPMUnitID | 1.3.6.1.4.1.2925.8.5.3.1.11 | displaystring | read-only |
PDU identification. |
cyPMUnitPhases | 1.3.6.1.4.1.2925.8.5.3.1.12 | integer | read-only |
Number of phases of this PDU unit. Enumeration: 'three-phase': 3, 'single-phase': 0. |
cyPMUnitBanks | 1.3.6.1.4.1.2925.8.5.3.1.13 | integer32 | read-only |
Number of banks of this PDU unit. |
cyPMUnitNominalVoltage | 1.3.6.1.4.1.2925.8.5.3.1.14 | integer32 | read-only |
Nominal Voltage configured for this PDU unit, when it does not have voltage sensor |
cyPMUnitPower | 1.3.6.1.4.1.2925.8.5.3.1.15 | integer32 | read-only |
Power Consumption of this PDU unit (it is estimated when PDU does not have voltage sensor). |
cyOutletTable | 1.3.6.1.4.1.2925.8.5.4 | no-access |
Allow operations on outlet |
|
1.3.6.1.4.1.2925.8.5.4.1 | no-access |
Allow operations on outlet |
||
cyOutletNumber | 1.3.6.1.4.1.2925.8.5.4.1.1 | interfaceindexorzero | no-access |
The outlet number on the PM. Zero is ALL outlets. |
cyOutletName | 1.3.6.1.4.1.2925.8.5.4.1.2 | displaystring | read-write |
The name given to a particular outlet Maximum size is 8 characters. |
cyOutletServer | 1.3.6.1.4.1.2925.8.5.4.1.3 | displaystring | read-only |
Alias of the Server connected to this outlet . |
cyOutletPower | 1.3.6.1.4.1.2925.8.5.4.1.4 | integer | read-write |
Getting this object will return the power state of the outlet. Valid return states are UNKNOW, OFF and ON. Setting this object will change the power state of the outlet. Enumeration: 'on': 1, 'off': 0, 'unknow': 3, 'cycle': 2. |
cyOutletLock | 1.3.6.1.4.1.2925.8.5.4.1.5 | integer | read-write |
Getting this object will return the lock state of the outlet. Setting this object will change the lock state of the outlet. Enumeration: 'lock': 1, 'unlock': 0, 'unknow': 2. |
cyOutletPUInterval | 1.3.6.1.4.1.2925.8.5.4.1.6 | integer32 | read-write |
The power unit interval of this outlet in seconds. The value of this object is the actual interval in seconds * 10. You need to translate the readed value (Ex. : value is 5, the interval is 0.5 seconds.) |
cyOutletMinimumOnInterval | 1.3.6.1.4.1.2925.8.5.4.1.7 | integer32 | read-only |
Minimum time in seconds an outlet will stay on before turning it off. |
cyOutletMinimumOffInterval | 1.3.6.1.4.1.2925.8.5.4.1.8 | integer32 | read-only |
Minimum time in seconds an outlet will stay off before turning it on. |
cyOutletWakeupState | 1.3.6.1.4.1.2925.8.5.4.1.9 | integer32 | read-only |
Outlet state after a cold boot. It can be set to on or off. |
cyOutletPduID | 1.3.6.1.4.1.2925.8.5.4.1.10 | displaystring | read-only |
PDU identification. |
cyOutletPduNumber | 1.3.6.1.4.1.2925.8.5.4.1.11 | integer32 | no-access |
The number of the PDU unit in the daisy-chained mode. |
cyPMElecPduTable | 1.3.6.1.4.1.2925.8.5.5 | no-access |
Allow operations on elecmon element of the PDUs |
|
1.3.6.1.4.1.2925.8.5.5.1 | no-access |
each entry has the information about the elecmon element of the PDUs. |
||
cyPMElecPduTablePortNumber | 1.3.6.1.4.1.2925.8.5.5.1.1 | interfaceindex | read-only |
Serial Port number where the PDU is connected. |
cyPMElecPduTablePduNumber | 1.3.6.1.4.1.2925.8.5.5.1.2 | interfaceindex | read-only |
The number of the PDU unit in the daisy-chained mode |
cyPMElecPduTableCurrentValue | 1.3.6.1.4.1.2925.8.5.5.1.3 | integer32 | read-only |
Actual value of current in the element (A x 10). |
cyPMElecPduTableCurrentMax | 1.3.6.1.4.1.2925.8.5.5.1.4 | integer32 | read-write |
Maximum detected value of current in the element (A x 10). Write operation accepts only 0 for reset action. |
cyPMElecPduTablePowerValue | 1.3.6.1.4.1.2925.8.5.5.1.5 | integer32 | read-only |
Actual value of power in the element (W x 10). |
cyPMElecPduTablePowerMax | 1.3.6.1.4.1.2925.8.5.5.1.6 | integer32 | read-write |
Maximum value of power in the element (W x 10). Write operation accepts only 0 for reset action. |
cyPMElecPduTableVoltageValue | 1.3.6.1.4.1.2925.8.5.5.1.7 | integer32 | read-only |
Actual value of voltage in the element (V).When element does not have voltage sensor, it returns 0. |
cyPMElecPduTableVoltageMax | 1.3.6.1.4.1.2925.8.5.5.1.8 | integer32 | read-write |
Maximum value of voltage in the element (V). When element does not have voltage sensor, it returns 0. Write operation accepts only 0 for reset action. |
cyPMElecPduTablePowerFactorValue | 1.3.6.1.4.1.2925.8.5.5.1.9 | integer32 | read-only |
Actual value of power factor in the element (Pf x 10). When element does not have power factor sensor, returns 0. |
cyPMElecPduTablePowerFactorMax | 1.3.6.1.4.1.2925.8.5.5.1.10 | integer32 | read-write |
Maximum value of power factor in the element (Pf x 10). When element does not have power factor sensor, returns 0. Write operation accepts only 0 for reset action. |
cyPMElecPduTablePowerType | 1.3.6.1.4.1.2925.8.5.5.1.11 | integer | read-only |
This PDU unit's Power sensor type. Enumeration: 'estimated': 1, 'measured': 2. |
cyPMElecPduTableVoltageType | 1.3.6.1.4.1.2925.8.5.5.1.12 | integer | read-only |
This PDU unit's has voltage sensor type. Enumeration: 'estimated': 1, 'measured': 2. |
cyPMElecPduTablePowerFactorType | 1.3.6.1.4.1.2925.8.5.5.1.13 | integer | read-only |
This PDU unit's Power Factor sensor type. Enumeration: 'estimated': 1, 'measured': 2. |
cyPMElecPhaseTable | 1.3.6.1.4.1.2925.8.5.6 | no-access |
Allow operations on elecmon element for phases |
|
1.3.6.1.4.1.2925.8.5.6.1 | no-access |
each entry has the information about the elecmon for phase. |
||
cyPMElecPhaseTablePortNumber | 1.3.6.1.4.1.2925.8.5.6.1.1 | interfaceindex | read-only |
Serial Port number where the PDU is connected. |
cyPMElecPhaseTablePduNumber | 1.3.6.1.4.1.2925.8.5.6.1.2 | interfaceindex | read-only |
The number of the PDU unit in the daisy-chained mode |
cyPMElecPhaseTableIndex | 1.3.6.1.4.1.2925.8.5.6.1.3 | interfaceindex | read-only |
index of the phase in the PDU. Index can be 1,2 or 3. |
cyPMElecPhaseTableName | 1.3.6.1.4.1.2925.8.5.6.1.4 | displaystring | read-only |
Sys-name of the phase. |
cyPMElecPhaseTableCurrentValue | 1.3.6.1.4.1.2925.8.5.6.1.5 | integer32 | read-only |
Actual value of current in the phase (A x 10). |
cyPMElecPhaseTableCurrentMax | 1.3.6.1.4.1.2925.8.5.6.1.6 | integer32 | read-write |
Maximum detected value of current in the phase (A x 10). Write operation accepts only 0 for reset action. |
cyPMElecPhaseTablePowerValue | 1.3.6.1.4.1.2925.8.5.6.1.7 | integer32 | read-only |
Actual value of power in the phase (W x 10). |
cyPMElecPhaseTablePowerMax | 1.3.6.1.4.1.2925.8.5.6.1.8 | integer32 | read-write |
Maximum value of power in the phase (W x 10).Write operation accepts only 0 for reset action. |
cyPMElecPhaseTableVoltageValue | 1.3.6.1.4.1.2925.8.5.6.1.9 | integer32 | read-only |
Actual value of voltage in the phase (V).When phase does not have voltage sensor, it returns 0. |
cyPMElecPhaseTableVoltageMax | 1.3.6.1.4.1.2925.8.5.6.1.10 | integer32 | read-write |
Maximum value of voltage in the phase (V). When phase does not have voltage sensor, it returns 0. Write operation accepts only 0 for reset action. |
cyPMElecPhaseTablePowerFactorValue | 1.3.6.1.4.1.2925.8.5.6.1.11 | integer32 | read-only |
Actual value of power factor in the phase (Pf x 10). When phase does not have power factor sensor, returns 0. |
cyPMElecPhaseTablePowerFactorMax | 1.3.6.1.4.1.2925.8.5.6.1.12 | integer32 | read-write |
Maximum value of power factor in the phase (Pf x 10). When phase does not have power factor sensor, returns 0.Write operation accepts only 0 for reset action. |
cyPMElecPhaseTablePowerType | 1.3.6.1.4.1.2925.8.5.6.1.13 | integer | read-only |
The type of Power sensor for this elecmon Enumeration: 'estimated': 1, 'measured': 2. |
cyPMElecPhaseTableVoltageType | 1.3.6.1.4.1.2925.8.5.6.1.14 | integer | read-only |
The type of Voltage sensor for this elecmon Enumeration: 'estimated': 1, 'measured': 2. |
cyPMElecPhaseTablePowerFactorType | 1.3.6.1.4.1.2925.8.5.6.1.15 | integer | read-only |
The type of Power Factor sensor for this elecmon Enumeration: 'estimated': 1, 'measured': 2. |
cyPMElecBankTable | 1.3.6.1.4.1.2925.8.5.7 | no-access |
Allow operations on elecmon element for banks |
|
1.3.6.1.4.1.2925.8.5.7.1 | no-access |
each entry has the information about the elecmon for Bank. |
||
cyPMElecBankTablePortNumber | 1.3.6.1.4.1.2925.8.5.7.1.1 | interfaceindex | read-only |
Serial Port number where the PDU is connected. |
cyPMElecBankTablePduNumber | 1.3.6.1.4.1.2925.8.5.7.1.2 | interfaceindex | read-only |
The number of the PDU unit in the daisy-chained mode |
cyPMElecBankTableIndex | 1.3.6.1.4.1.2925.8.5.7.1.3 | interfaceindex | read-only |
index of the Bank in the PDU. Index can be 1,2, ... number of banks of the PDU. |
cyPMElecBankTableName | 1.3.6.1.4.1.2925.8.5.7.1.4 | displaystring | read-only |
Sys-name of the Bank. |
cyPMElecBankTableCurrentValue | 1.3.6.1.4.1.2925.8.5.7.1.5 | integer32 | read-only |
Actual value of current in the Bank (A x 10). |
cyPMElecBankTableCurrentMax | 1.3.6.1.4.1.2925.8.5.7.1.6 | integer32 | read-write |
Maximum detected value of current in the Bank (A x 10). Write operation accepts only 0 for reset action. |
cyPMElecBankTablePowerValue | 1.3.6.1.4.1.2925.8.5.7.1.7 | integer32 | read-only |
Actual value of power in the Bank (W x 10). |
cyPMElecBankTablePowerMax | 1.3.6.1.4.1.2925.8.5.7.1.8 | integer32 | read-write |
Maximum value of power in the Bank (W x 10).Write operation accepts only 0 for reset action. |
cyPMElecBankTableVoltageValue | 1.3.6.1.4.1.2925.8.5.7.1.9 | integer32 | read-only |
Actual value of voltage in the Bank (V).When Bank does not have voltage sensor, it returns 0. |
cyPMElecBankTableVoltageMax | 1.3.6.1.4.1.2925.8.5.7.1.10 | integer32 | read-write |
Maximum value of voltage in the Bank (V). When Bank does not have voltage sensor, it returns 0. Write operation accepts only 0 for reset action. |
cyPMElecBankTablePowerFactorValue | 1.3.6.1.4.1.2925.8.5.7.1.11 | integer32 | read-only |
Actual value of power factor in the Bank (Pf x 10). When Bank does not have power factor sensor, returns 0. |
cyPMElecBankTablePowerFactorMax | 1.3.6.1.4.1.2925.8.5.7.1.12 | integer32 | read-write |
Maximum value of power factor in the Bank (Pf x 10). When Bank does not have power factor sensor, returns 0.Write operation accepts only 0 for reset action. |
cyPMElecBankTablePowerType | 1.3.6.1.4.1.2925.8.5.7.1.13 | integer | read-only |
The type of Power sensor for this elecmon Enumeration: 'estimated': 1, 'measured': 2. |
cyPMElecBankTableVoltageType | 1.3.6.1.4.1.2925.8.5.7.1.14 | integer | read-only |
The type of Voltage sensor for this elecmon Enumeration: 'estimated': 1, 'measured': 2. |
cyPMElecBankTablePowerFactorType | 1.3.6.1.4.1.2925.8.5.7.1.15 | integer | read-only |
The type of Power Factor sensor for this elecmon Enumeration: 'estimated': 1, 'measured': 2. |
cyPMElecOutletTable | 1.3.6.1.4.1.2925.8.5.8 | no-access |
Allow operations on elecmon element for outlets |
|
1.3.6.1.4.1.2925.8.5.8.1 | no-access |
each entry has the information about the elecmon for Outlet. |
||
cyPMElecOutletTablePortNumber | 1.3.6.1.4.1.2925.8.5.8.1.1 | interfaceindex | read-only |
Serial Port number where the PDU is connected. |
cyPMElecOutletTablePduNumber | 1.3.6.1.4.1.2925.8.5.8.1.2 | interfaceindex | read-only |
The number of the PDU unit in the daisy-chained mode |
cyPMElecOutletTableNumber | 1.3.6.1.4.1.2925.8.5.8.1.3 | interfaceindex | read-only |
outlet number in the PDU |
cyPMElecOutletTableName | 1.3.6.1.4.1.2925.8.5.8.1.4 | displaystring | read-only |
name of the Outlet. |
cyPMElecOutletTableCurrentValue | 1.3.6.1.4.1.2925.8.5.8.1.5 | integer32 | read-only |
Actual value of current in the Outlet (A x 10). |
cyPMElecOutletTableCurrentMax | 1.3.6.1.4.1.2925.8.5.8.1.6 | integer32 | read-write |
Maximum detected value of current in the Outlet (A x 10). Write operation accepts only 0 for reset action. |
cyPMElecOutletTablePowerValue | 1.3.6.1.4.1.2925.8.5.8.1.7 | integer32 | read-only |
Actual value of power in the Outlet (W x 10). |
cyPMElecOutletTablePowerMax | 1.3.6.1.4.1.2925.8.5.8.1.8 | integer32 | read-write |
Maximum value of power in the Outlet (W x 10).Write operation accepts only 0 for reset action. |
cyPMElecOutletTableVoltageValue | 1.3.6.1.4.1.2925.8.5.8.1.9 | integer32 | read-only |
Actual value of voltage in the Outlet (V).When Outlet does not have voltage sensor, it returns 0. |
cyPMElecOutletTableVoltageMax | 1.3.6.1.4.1.2925.8.5.8.1.10 | integer32 | read-write |
Maximum value of voltage in the Outlet (V). When Outlet does not have voltage sensor, it returns 0. Write operation accepts only 0 for reset action. |
cyPMElecOutletTablePowerFactorValue | 1.3.6.1.4.1.2925.8.5.8.1.11 | integer32 | read-only |
Actual value of power factor in the Outlet (Pf x 10). When Outlet does not have power factor sensor, returns 0. |
cyPMElecOutletTablePowerFactorMax | 1.3.6.1.4.1.2925.8.5.8.1.12 | integer32 | read-write |
Maximum value of power factor in the Outlet (Pf x 10). When Outlet does not have power factor sensor, returns 0.Write operation accepts only 0 for reset action. |
cyPMElecOutletTablePowerType | 1.3.6.1.4.1.2925.8.5.8.1.13 | integer | read-only |
The type of Power sensor for this elecmon Enumeration: 'estimated': 1, 'measured': 2. |
cyPMElecOutletTableVoltageType | 1.3.6.1.4.1.2925.8.5.8.1.14 | integer | read-only |
The type of Voltage sensor for this elecmon Enumeration: 'estimated': 1, 'measured': 2. |
cyPMElecOutletTablePowerFactorType | 1.3.6.1.4.1.2925.8.5.8.1.15 | integer | read-only |
The type of Power Factor sensor for this elecmon Enumeration: 'estimated': 1, 'measured': 2. |
cyPMEnvMonTable | 1.3.6.1.4.1.2925.8.5.9 | no-access |
Allow operations on environmental monitors |
|
1.3.6.1.4.1.2925.8.5.9.1 | no-access |
each entry has the information about the environmental monitors. |
||
cyPMEnvMonTablePortNumber | 1.3.6.1.4.1.2925.8.5.9.1.1 | interfaceindex | read-only |
Serial Port number where the PDU is connected. |
cyPMEnvMonTablePduNumber | 1.3.6.1.4.1.2925.8.5.9.1.2 | interfaceindex | read-only |
The number of the PDU unit in the daisy-chained mode |
cyPMEnvMonTableIndex | 1.3.6.1.4.1.2925.8.5.9.1.3 | interfaceindex | read-only |
index of the environmental monitor in the PDU. |
cyPMEnvMonTableName | 1.3.6.1.4.1.2925.8.5.9.1.4 | displaystring | read-only |
Name of the environmental monitor. |
cyPMEnvMonTableType | 1.3.6.1.4.1.2925.8.5.9.1.5 | integer | read-only |
The type of environmental monitor. Enumeration: 'temperature': 2, 'dry-concact': 6, 'water-level': 7, 'unknown': 10, 'humidity': 3, 'motion': 8, 'temp-internal': 1, 'smoke': 5, 'unplugged': 9, 'air-flow': 4. |
cyPMEnvMonTableStatus | 1.3.6.1.4.1.2925.8.5.9.1.6 | integer | read-only |
The status of Dry-Contact/Water-level/Smoke/Motion monitors. Dry-Contact sensor: Opened(1), closed(2). Water level: Normal (1), Triggered(2). Smoke sensor: not-detected(1), detected(2). Motion sensor: not-detected(1), detected(2). Enumeration: 'not-applicable': 3, 'triggered': 2, 'normal': 1. |
cyPMEnvMonTableValue | 1.3.6.1.4.1.2925.8.5.9.1.7 | integer32 | read-only |
Actual value of Temperature/Humidity/Air-flow monitors (x 10). |
cyPMEnvMonTableMaxValue | 1.3.6.1.4.1.2925.8.5.9.1.8 | integer32 | read-write |
Maximum detected value of Temperature/Humidity/Air-flow monitor (x 10). Write operation accepts only 0 for reset action. |