CYCLADES-ACS5K-PM-MIB: View SNMP OID List / Download MIB

VENDOR: CYCLADES CORPORATION


 Home MIB: CYCLADES-ACS5K-PM-MIB
Download as:   

Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 cyACS5KPM 1.3.6.1.4.1.2925.8.5
This module defines objects of the Proxy for PM
     cyNumberOfPM 1.3.6.1.4.1.2925.8.5.1 integer32 read-only
The total number of PM's connected on the unit
     cyPMTable 1.3.6.1.4.1.2925.8.5.2 no-access
Allows to read information about each connected PM
         cyPMEntry 1.3.6.1.4.1.2925.8.5.2.1 no-access
Information about the connected PM
             cyPMSerialPortNumber 1.3.6.1.4.1.2925.8.5.2.1.1 interfaceindex read-only
The number of the serial port when the PM is connected.
             cyPMNumberOutlets 1.3.6.1.4.1.2925.8.5.2.1.2 integer32 read-only
Number of outlets.
             cyPMNumberUnits 1.3.6.1.4.1.2925.8.5.2.1.3 integer32 read-only
Total number of PM unists that are accessed by this serial port.
             cyPMCurrent 1.3.6.1.4.1.2925.8.5.2.1.4 displaystring read-only
Current reading for the PM.
             cyPMVersion 1.3.6.1.4.1.2925.8.5.2.1.5 displaystring read-only
The software version of the PM.
             cyPMCommand 1.3.6.1.4.1.2925.8.5.2.1.7 displaystring read-write
A character string for the user to send commands to PM. He can use it to does the save command. Or to list the outlets that need to be turned off, or turned on , or cycled or locked or unlocked as a group. The command is the first word and is followed by a space and the outlet list (otulets commands). Valid commands are 'on', 'off', 'cycle', 'lock', 'unlock', 'save'.
     cyPMUnitTable 1.3.6.1.4.1.2925.8.5.3 no-access
Allow operations on specific PM unit connected
         cyPMUnitEntry 1.3.6.1.4.1.2925.8.5.3.1 no-access
Allow operations on outlet
             cyPMUnitNumber 1.3.6.1.4.1.2925.8.5.3.1.1 interfaceindex no-access
The number of the PM unit in the daisy-chained mode.
             cyPMUnitVersion 1.3.6.1.4.1.2925.8.5.3.1.2 displaystring read-only
The software version of this PM unit.
             cyPMUnitOutlets 1.3.6.1.4.1.2925.8.5.3.1.3 integer32 read-only
Number of outlets of this PM unit.
             cyPMUnitFirstOutlet 1.3.6.1.4.1.2925.8.5.3.1.4 integer32 read-only
Number of the first outlet of this PM unit.
             cyPMUnitCurrent 1.3.6.1.4.1.2925.8.5.3.1.5 integer32 read-only
Current of this PM unit in AMP. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.)
             cyPMUnitMaxCurrent 1.3.6.1.4.1.2925.8.5.3.1.6 integer32 read-only
Maximum current of this PM unit in AMP. The value of this object is the maximum current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the maximum current is 0.5 AMP.)
             cyPMUnitSequenceInterval 1.3.6.1.4.1.2925.8.5.3.1.9 integer32 read-only
Sequence interval delay. Valid values are 2 to 15 (seconds).
             cyPMUnitCycleInterval 1.3.6.1.4.1.2925.8.5.3.1.10 integer32 read-only
Number of seconds that a socket stays off before turning it back on.
             cyPMUnitID 1.3.6.1.4.1.2925.8.5.3.1.11 displaystring read-only
PDU identification.
             cyPMUnitPhases 1.3.6.1.4.1.2925.8.5.3.1.12 integer read-only
Number of phases of this PDU unit. Enumeration: 'three-phase': 3, 'single-phase': 0.
             cyPMUnitBanks 1.3.6.1.4.1.2925.8.5.3.1.13 integer32 read-only
Number of banks of this PDU unit.
             cyPMUnitNominalVoltage 1.3.6.1.4.1.2925.8.5.3.1.14 integer32 read-only
Nominal Voltage configured for this PDU unit, when it does not have voltage sensor
             cyPMUnitPower 1.3.6.1.4.1.2925.8.5.3.1.15 integer32 read-only
Power Consumption of this PDU unit (it is estimated when PDU does not have voltage sensor).
     cyOutletTable 1.3.6.1.4.1.2925.8.5.4 no-access
Allow operations on outlet
         cyOutletEntry 1.3.6.1.4.1.2925.8.5.4.1 no-access
Allow operations on outlet
             cyOutletNumber 1.3.6.1.4.1.2925.8.5.4.1.1 interfaceindexorzero no-access
The outlet number on the PM. Zero is ALL outlets.
             cyOutletName 1.3.6.1.4.1.2925.8.5.4.1.2 displaystring read-write
The name given to a particular outlet Maximum size is 8 characters.
             cyOutletServer 1.3.6.1.4.1.2925.8.5.4.1.3 displaystring read-only
Alias of the Server connected to this outlet .
             cyOutletPower 1.3.6.1.4.1.2925.8.5.4.1.4 integer read-write
Getting this object will return the power state of the outlet. Valid return states are UNKNOW, OFF and ON. Setting this object will change the power state of the outlet. Enumeration: 'on': 1, 'off': 0, 'unknow': 3, 'cycle': 2.
             cyOutletLock 1.3.6.1.4.1.2925.8.5.4.1.5 integer read-write
Getting this object will return the lock state of the outlet. Setting this object will change the lock state of the outlet. Enumeration: 'lock': 1, 'unlock': 0, 'unknow': 2.
             cyOutletPUInterval 1.3.6.1.4.1.2925.8.5.4.1.6 integer32 read-write
The power unit interval of this outlet in seconds. The value of this object is the actual interval in seconds * 10. You need to translate the readed value (Ex. : value is 5, the interval is 0.5 seconds.)
             cyOutletMinimumOnInterval 1.3.6.1.4.1.2925.8.5.4.1.7 integer32 read-only
Minimum time in seconds an outlet will stay on before turning it off.
             cyOutletMinimumOffInterval 1.3.6.1.4.1.2925.8.5.4.1.8 integer32 read-only
Minimum time in seconds an outlet will stay off before turning it on.
             cyOutletWakeupState 1.3.6.1.4.1.2925.8.5.4.1.9 integer32 read-only
Outlet state after a cold boot. It can be set to on or off.
             cyOutletPduID 1.3.6.1.4.1.2925.8.5.4.1.10 displaystring read-only
PDU identification.
             cyOutletPduNumber 1.3.6.1.4.1.2925.8.5.4.1.11 integer32 no-access
The number of the PDU unit in the daisy-chained mode.
     cyPMElecPduTable 1.3.6.1.4.1.2925.8.5.5 no-access
Allow operations on elecmon element of the PDUs
         cyPMElecPduTableEntry 1.3.6.1.4.1.2925.8.5.5.1 no-access
each entry has the information about the elecmon element of the PDUs.
             cyPMElecPduTablePortNumber 1.3.6.1.4.1.2925.8.5.5.1.1 interfaceindex read-only
Serial Port number where the PDU is connected.
             cyPMElecPduTablePduNumber 1.3.6.1.4.1.2925.8.5.5.1.2 interfaceindex read-only
The number of the PDU unit in the daisy-chained mode
             cyPMElecPduTableCurrentValue 1.3.6.1.4.1.2925.8.5.5.1.3 integer32 read-only
Actual value of current in the element (A x 10).
             cyPMElecPduTableCurrentMax 1.3.6.1.4.1.2925.8.5.5.1.4 integer32 read-write
Maximum detected value of current in the element (A x 10). Write operation accepts only 0 for reset action.
             cyPMElecPduTablePowerValue 1.3.6.1.4.1.2925.8.5.5.1.5 integer32 read-only
Actual value of power in the element (W x 10).
             cyPMElecPduTablePowerMax 1.3.6.1.4.1.2925.8.5.5.1.6 integer32 read-write
Maximum value of power in the element (W x 10). Write operation accepts only 0 for reset action.
             cyPMElecPduTableVoltageValue 1.3.6.1.4.1.2925.8.5.5.1.7 integer32 read-only
Actual value of voltage in the element (V).When element does not have voltage sensor, it returns 0.
             cyPMElecPduTableVoltageMax 1.3.6.1.4.1.2925.8.5.5.1.8 integer32 read-write
Maximum value of voltage in the element (V). When element does not have voltage sensor, it returns 0. Write operation accepts only 0 for reset action.
             cyPMElecPduTablePowerFactorValue 1.3.6.1.4.1.2925.8.5.5.1.9 integer32 read-only
Actual value of power factor in the element (Pf x 10). When element does not have power factor sensor, returns 0.
             cyPMElecPduTablePowerFactorMax 1.3.6.1.4.1.2925.8.5.5.1.10 integer32 read-write
Maximum value of power factor in the element (Pf x 10). When element does not have power factor sensor, returns 0. Write operation accepts only 0 for reset action.
             cyPMElecPduTablePowerType 1.3.6.1.4.1.2925.8.5.5.1.11 integer read-only
This PDU unit's Power sensor type. Enumeration: 'estimated': 1, 'measured': 2.
             cyPMElecPduTableVoltageType 1.3.6.1.4.1.2925.8.5.5.1.12 integer read-only
This PDU unit's has voltage sensor type. Enumeration: 'estimated': 1, 'measured': 2.
             cyPMElecPduTablePowerFactorType 1.3.6.1.4.1.2925.8.5.5.1.13 integer read-only
This PDU unit's Power Factor sensor type. Enumeration: 'estimated': 1, 'measured': 2.
     cyPMElecPhaseTable 1.3.6.1.4.1.2925.8.5.6 no-access
Allow operations on elecmon element for phases
         cyPMElecPhaseTableEntry 1.3.6.1.4.1.2925.8.5.6.1 no-access
each entry has the information about the elecmon for phase.
             cyPMElecPhaseTablePortNumber 1.3.6.1.4.1.2925.8.5.6.1.1 interfaceindex read-only
Serial Port number where the PDU is connected.
             cyPMElecPhaseTablePduNumber 1.3.6.1.4.1.2925.8.5.6.1.2 interfaceindex read-only
The number of the PDU unit in the daisy-chained mode
             cyPMElecPhaseTableIndex 1.3.6.1.4.1.2925.8.5.6.1.3 interfaceindex read-only
index of the phase in the PDU. Index can be 1,2 or 3.
             cyPMElecPhaseTableName 1.3.6.1.4.1.2925.8.5.6.1.4 displaystring read-only
Sys-name of the phase.
             cyPMElecPhaseTableCurrentValue 1.3.6.1.4.1.2925.8.5.6.1.5 integer32 read-only
Actual value of current in the phase (A x 10).
             cyPMElecPhaseTableCurrentMax 1.3.6.1.4.1.2925.8.5.6.1.6 integer32 read-write
Maximum detected value of current in the phase (A x 10). Write operation accepts only 0 for reset action.
             cyPMElecPhaseTablePowerValue 1.3.6.1.4.1.2925.8.5.6.1.7 integer32 read-only
Actual value of power in the phase (W x 10).
             cyPMElecPhaseTablePowerMax 1.3.6.1.4.1.2925.8.5.6.1.8 integer32 read-write
Maximum value of power in the phase (W x 10).Write operation accepts only 0 for reset action.
             cyPMElecPhaseTableVoltageValue 1.3.6.1.4.1.2925.8.5.6.1.9 integer32 read-only
Actual value of voltage in the phase (V).When phase does not have voltage sensor, it returns 0.
             cyPMElecPhaseTableVoltageMax 1.3.6.1.4.1.2925.8.5.6.1.10 integer32 read-write
Maximum value of voltage in the phase (V). When phase does not have voltage sensor, it returns 0. Write operation accepts only 0 for reset action.
             cyPMElecPhaseTablePowerFactorValue 1.3.6.1.4.1.2925.8.5.6.1.11 integer32 read-only
Actual value of power factor in the phase (Pf x 10). When phase does not have power factor sensor, returns 0.
             cyPMElecPhaseTablePowerFactorMax 1.3.6.1.4.1.2925.8.5.6.1.12 integer32 read-write
Maximum value of power factor in the phase (Pf x 10). When phase does not have power factor sensor, returns 0.Write operation accepts only 0 for reset action.
             cyPMElecPhaseTablePowerType 1.3.6.1.4.1.2925.8.5.6.1.13 integer read-only
The type of Power sensor for this elecmon Enumeration: 'estimated': 1, 'measured': 2.
             cyPMElecPhaseTableVoltageType 1.3.6.1.4.1.2925.8.5.6.1.14 integer read-only
The type of Voltage sensor for this elecmon Enumeration: 'estimated': 1, 'measured': 2.
             cyPMElecPhaseTablePowerFactorType 1.3.6.1.4.1.2925.8.5.6.1.15 integer read-only
The type of Power Factor sensor for this elecmon Enumeration: 'estimated': 1, 'measured': 2.
     cyPMElecBankTable 1.3.6.1.4.1.2925.8.5.7 no-access
Allow operations on elecmon element for banks
         cyPMElecBankTableEntry 1.3.6.1.4.1.2925.8.5.7.1 no-access
each entry has the information about the elecmon for Bank.
             cyPMElecBankTablePortNumber 1.3.6.1.4.1.2925.8.5.7.1.1 interfaceindex read-only
Serial Port number where the PDU is connected.
             cyPMElecBankTablePduNumber 1.3.6.1.4.1.2925.8.5.7.1.2 interfaceindex read-only
The number of the PDU unit in the daisy-chained mode
             cyPMElecBankTableIndex 1.3.6.1.4.1.2925.8.5.7.1.3 interfaceindex read-only
index of the Bank in the PDU. Index can be 1,2, ... number of banks of the PDU.
             cyPMElecBankTableName 1.3.6.1.4.1.2925.8.5.7.1.4 displaystring read-only
Sys-name of the Bank.
             cyPMElecBankTableCurrentValue 1.3.6.1.4.1.2925.8.5.7.1.5 integer32 read-only
Actual value of current in the Bank (A x 10).
             cyPMElecBankTableCurrentMax 1.3.6.1.4.1.2925.8.5.7.1.6 integer32 read-write
Maximum detected value of current in the Bank (A x 10). Write operation accepts only 0 for reset action.
             cyPMElecBankTablePowerValue 1.3.6.1.4.1.2925.8.5.7.1.7 integer32 read-only
Actual value of power in the Bank (W x 10).
             cyPMElecBankTablePowerMax 1.3.6.1.4.1.2925.8.5.7.1.8 integer32 read-write
Maximum value of power in the Bank (W x 10).Write operation accepts only 0 for reset action.
             cyPMElecBankTableVoltageValue 1.3.6.1.4.1.2925.8.5.7.1.9 integer32 read-only
Actual value of voltage in the Bank (V).When Bank does not have voltage sensor, it returns 0.
             cyPMElecBankTableVoltageMax 1.3.6.1.4.1.2925.8.5.7.1.10 integer32 read-write
Maximum value of voltage in the Bank (V). When Bank does not have voltage sensor, it returns 0. Write operation accepts only 0 for reset action.
             cyPMElecBankTablePowerFactorValue 1.3.6.1.4.1.2925.8.5.7.1.11 integer32 read-only
Actual value of power factor in the Bank (Pf x 10). When Bank does not have power factor sensor, returns 0.
             cyPMElecBankTablePowerFactorMax 1.3.6.1.4.1.2925.8.5.7.1.12 integer32 read-write
Maximum value of power factor in the Bank (Pf x 10). When Bank does not have power factor sensor, returns 0.Write operation accepts only 0 for reset action.
             cyPMElecBankTablePowerType 1.3.6.1.4.1.2925.8.5.7.1.13 integer read-only
The type of Power sensor for this elecmon Enumeration: 'estimated': 1, 'measured': 2.
             cyPMElecBankTableVoltageType 1.3.6.1.4.1.2925.8.5.7.1.14 integer read-only
The type of Voltage sensor for this elecmon Enumeration: 'estimated': 1, 'measured': 2.
             cyPMElecBankTablePowerFactorType 1.3.6.1.4.1.2925.8.5.7.1.15 integer read-only
The type of Power Factor sensor for this elecmon Enumeration: 'estimated': 1, 'measured': 2.
     cyPMElecOutletTable 1.3.6.1.4.1.2925.8.5.8 no-access
Allow operations on elecmon element for outlets
         cyPMElecOutletTableEntry 1.3.6.1.4.1.2925.8.5.8.1 no-access
each entry has the information about the elecmon for Outlet.
             cyPMElecOutletTablePortNumber 1.3.6.1.4.1.2925.8.5.8.1.1 interfaceindex read-only
Serial Port number where the PDU is connected.
             cyPMElecOutletTablePduNumber 1.3.6.1.4.1.2925.8.5.8.1.2 interfaceindex read-only
The number of the PDU unit in the daisy-chained mode
             cyPMElecOutletTableNumber 1.3.6.1.4.1.2925.8.5.8.1.3 interfaceindex read-only
outlet number in the PDU
             cyPMElecOutletTableName 1.3.6.1.4.1.2925.8.5.8.1.4 displaystring read-only
name of the Outlet.
             cyPMElecOutletTableCurrentValue 1.3.6.1.4.1.2925.8.5.8.1.5 integer32 read-only
Actual value of current in the Outlet (A x 10).
             cyPMElecOutletTableCurrentMax 1.3.6.1.4.1.2925.8.5.8.1.6 integer32 read-write
Maximum detected value of current in the Outlet (A x 10). Write operation accepts only 0 for reset action.
             cyPMElecOutletTablePowerValue 1.3.6.1.4.1.2925.8.5.8.1.7 integer32 read-only
Actual value of power in the Outlet (W x 10).
             cyPMElecOutletTablePowerMax 1.3.6.1.4.1.2925.8.5.8.1.8 integer32 read-write
Maximum value of power in the Outlet (W x 10).Write operation accepts only 0 for reset action.
             cyPMElecOutletTableVoltageValue 1.3.6.1.4.1.2925.8.5.8.1.9 integer32 read-only
Actual value of voltage in the Outlet (V).When Outlet does not have voltage sensor, it returns 0.
             cyPMElecOutletTableVoltageMax 1.3.6.1.4.1.2925.8.5.8.1.10 integer32 read-write
Maximum value of voltage in the Outlet (V). When Outlet does not have voltage sensor, it returns 0. Write operation accepts only 0 for reset action.
             cyPMElecOutletTablePowerFactorValue 1.3.6.1.4.1.2925.8.5.8.1.11 integer32 read-only
Actual value of power factor in the Outlet (Pf x 10). When Outlet does not have power factor sensor, returns 0.
             cyPMElecOutletTablePowerFactorMax 1.3.6.1.4.1.2925.8.5.8.1.12 integer32 read-write
Maximum value of power factor in the Outlet (Pf x 10). When Outlet does not have power factor sensor, returns 0.Write operation accepts only 0 for reset action.
             cyPMElecOutletTablePowerType 1.3.6.1.4.1.2925.8.5.8.1.13 integer read-only
The type of Power sensor for this elecmon Enumeration: 'estimated': 1, 'measured': 2.
             cyPMElecOutletTableVoltageType 1.3.6.1.4.1.2925.8.5.8.1.14 integer read-only
The type of Voltage sensor for this elecmon Enumeration: 'estimated': 1, 'measured': 2.
             cyPMElecOutletTablePowerFactorType 1.3.6.1.4.1.2925.8.5.8.1.15 integer read-only
The type of Power Factor sensor for this elecmon Enumeration: 'estimated': 1, 'measured': 2.
     cyPMEnvMonTable 1.3.6.1.4.1.2925.8.5.9 no-access
Allow operations on environmental monitors
         cyPMEnvMonTableEntry 1.3.6.1.4.1.2925.8.5.9.1 no-access
each entry has the information about the environmental monitors.
             cyPMEnvMonTablePortNumber 1.3.6.1.4.1.2925.8.5.9.1.1 interfaceindex read-only
Serial Port number where the PDU is connected.
             cyPMEnvMonTablePduNumber 1.3.6.1.4.1.2925.8.5.9.1.2 interfaceindex read-only
The number of the PDU unit in the daisy-chained mode
             cyPMEnvMonTableIndex 1.3.6.1.4.1.2925.8.5.9.1.3 interfaceindex read-only
index of the environmental monitor in the PDU.
             cyPMEnvMonTableName 1.3.6.1.4.1.2925.8.5.9.1.4 displaystring read-only
Name of the environmental monitor.
             cyPMEnvMonTableType 1.3.6.1.4.1.2925.8.5.9.1.5 integer read-only
The type of environmental monitor. Enumeration: 'temperature': 2, 'dry-concact': 6, 'water-level': 7, 'unknown': 10, 'humidity': 3, 'motion': 8, 'temp-internal': 1, 'smoke': 5, 'unplugged': 9, 'air-flow': 4.
             cyPMEnvMonTableStatus 1.3.6.1.4.1.2925.8.5.9.1.6 integer read-only
The status of Dry-Contact/Water-level/Smoke/Motion monitors. Dry-Contact sensor: Opened(1), closed(2). Water level: Normal (1), Triggered(2). Smoke sensor: not-detected(1), detected(2). Motion sensor: not-detected(1), detected(2). Enumeration: 'not-applicable': 3, 'triggered': 2, 'normal': 1.
             cyPMEnvMonTableValue 1.3.6.1.4.1.2925.8.5.9.1.7 integer32 read-only
Actual value of Temperature/Humidity/Air-flow monitors (x 10).
             cyPMEnvMonTableMaxValue 1.3.6.1.4.1.2925.8.5.9.1.8 integer32 read-write
Maximum detected value of Temperature/Humidity/Air-flow monitor (x 10). Write operation accepts only 0 for reset action.