CAREL-RITTAL-LCP-3311-MIB: View SNMP OID List / Download MIB
VENDOR: CAREL
Home | MIB: CAREL-RITTAL-LCP-3311-MIB | |||
---|---|---|---|---|
Download as: |
Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
|
|||
Object Name | OID | Type | Access | Info |
carel | 1.3.6.1.4.1.9839 |
Custom MIB for Rittal LCP 3311 chillers connected to a pco web card |
||
rittal | 1.3.6.1.4.1.9839.2606 | |||
rittalLCP3311 | 1.3.6.1.4.1.9839.2606.2 | |||
sensors | 1.3.6.1.4.1.9839.2606.2.1 | |||
digital | 1.3.6.1.4.1.9839.2606.2.1.1 | |||
compressorOverloadAlarm | 1.3.6.1.4.1.9839.2606.2.1.1.2 | integer | read-only |
Compressor overload alarm ok (0), alarm (1) Enumeration: 'alarm': 1, 'ok': 0. |
highPressureAlarm | 1.3.6.1.4.1.9839.2606.2.1.1.3 | integer | read-only |
High pressure alarm ok (0), alarm (1) Enumeration: 'alarm': 1, 'ok': 0. |
remoteOnOff | 1.3.6.1.4.1.9839.2606.2.1.1.8 | integer | read-only |
Remote On/Off off (0), on (1) Enumeration: 'on': 1, 'off': 0. |
inverterAlarm | 1.3.6.1.4.1.9839.2606.2.1.1.11 | integer | read-only |
Inverter alarm ok (0), alarm (1) Enumeration: 'alarm': 1, 'ok': 0. |
driveAlarm | 1.3.6.1.4.1.9839.2606.2.1.1.12 | integer | read-only |
Power+ drive off-line alarm ok (0), alarm (1) Enumeration: 'alarm': 1, 'ok': 0. |
inverterOnOff | 1.3.6.1.4.1.9839.2606.2.1.1.17 | integer | read-only |
Inverter On/Off off (0), on (1) Enumeration: 'on': 1, 'off': 0. |
generalAlarm | 1.3.6.1.4.1.9839.2606.2.1.1.23 | integer | read-only |
General alarm alarm (0), ok (1) Enumeration: 'alarm': 1, 'ok': 0. |
resetAllAlarms | 1.3.6.1.4.1.9839.2606.2.1.1.29 | integer | read-write |
Reset all alarms no (0), yes (1) Enumeration: 'yes': 1, 'no': 0. |
compressorEnvelopeAlarm | 1.3.6.1.4.1.9839.2606.2.1.1.30 | integer | read-only |
Compressor forced off working out envelope ok (0), alarm (1) Enumeration: 'alarm': 1, 'ok': 0. |
compressorStartupFailureAlarm | 1.3.6.1.4.1.9839.2606.2.1.1.31 | integer | read-only |
Compressor startup failure alarm, reached max retries ok (0), alarm (1) Enumeration: 'alarm': 1, 'ok': 0. |
maxDischargeTemperatureAlarm | 1.3.6.1.4.1.9839.2606.2.1.1.33 | integer | read-only |
Maximum discharge temperature has been reached ok (0), alarm (1) Enumeration: 'alarm': 1, 'ok': 0. |
compressorDeltaPressureAlarm | 1.3.6.1.4.1.9839.2606.2.1.1.35 | integer | read-only |
Delta pressure too big to startup compressor ok (0), alarm (1) Enumeration: 'alarm': 1, 'ok': 0. |
oilReturnAlarm | 1.3.6.1.4.1.9839.2606.2.1.1.36 | integer | read-only |
Oil return alarm for when the compressor is running. Lubrication issue. ok (0), alarm (1) Enumeration: 'alarm': 1, 'ok': 0. |
outputTemperatureTopProbeAlarm | 1.3.6.1.4.1.9839.2606.2.1.1.38 | integer | read-only |
Top output temperature probe broken ok (0), alarm (1) Enumeration: 'alarm': 1, 'ok': 0. |
outputTemperatureMidProbeAlarm | 1.3.6.1.4.1.9839.2606.2.1.1.39 | integer | read-only |
Mid output temperature probe broken ok (0), alarm (1) Enumeration: 'alarm': 1, 'ok': 0. |
outputTemperatureBottomProbeAlarm | 1.3.6.1.4.1.9839.2606.2.1.1.40 | integer | read-only |
Bottom output temperature probe broken ok (0), alarm (1) Enumeration: 'alarm': 1, 'ok': 0. |
inputTemperatureTopProbeAlarm | 1.3.6.1.4.1.9839.2606.2.1.1.42 | integer | read-only |
Top input temperature probe broken ok (0), alarm (1) Enumeration: 'alarm': 1, 'ok': 0. |
inputTemperatureMidProbeAlarm | 1.3.6.1.4.1.9839.2606.2.1.1.43 | integer | read-only |
Mid input temperature probe broken ok (0), alarm (1) Enumeration: 'alarm': 1, 'ok': 0. |
inputTemperatureBottomProbeAlarm | 1.3.6.1.4.1.9839.2606.2.1.1.44 | integer | read-only |
Bottom input temperature probe broken ok (0), alarm (1) Enumeration: 'alarm': 1, 'ok': 0. |
compressorDischargeTemperatureProbeAlarm | 1.3.6.1.4.1.9839.2606.2.1.1.45 | integer | read-only |
Compressor discharge temperature probe broken ok (0), alarm (1) Enumeration: 'alarm': 1, 'ok': 0. |
compressorSuctionTemperatureProbeAlarm | 1.3.6.1.4.1.9839.2606.2.1.1.46 | integer | read-only |
Compressor suction temperature probe broken ok (0), alarm (1) Enumeration: 'alarm': 1, 'ok': 0. |
compressorDischargePressureProbeAlarm | 1.3.6.1.4.1.9839.2606.2.1.1.47 | integer | read-only |
Compressor discharge pressure probe broken ok (0), alarm (1) Enumeration: 'alarm': 1, 'ok': 0. |
compressorSuctionPressureProbeAlarm | 1.3.6.1.4.1.9839.2606.2.1.1.48 | integer | read-only |
Compressor suction pressure probe broken ok (0), alarm (1) Enumeration: 'alarm': 1, 'ok': 0. |
reboot | 1.3.6.1.4.1.9839.2606.2.1.1.100 | integer | read-write |
Reboot the system no (0), yes (1) Enumeration: 'yes': 1, 'no': 0. |
analog | 1.3.6.1.4.1.9839.2606.2.1.2 | |||
outputTemperatureTopSensor | 1.3.6.1.4.1.9839.2606.2.1.2.2 | divby10 | read-only |
Top sensor output temperature in Celcius |
outputTemperatureMidSensor | 1.3.6.1.4.1.9839.2606.2.1.2.3 | divby10 | read-only |
Mid sensor output temperature in Celcius |
outputTemperatureBottomSensor | 1.3.6.1.4.1.9839.2606.2.1.2.4 | divby10 | read-only |
Bottom sensor output temperature in Celcius |
inputTemperatureTopSensor | 1.3.6.1.4.1.9839.2606.2.1.2.6 | divby10 | read-only |
Top sensor input temperature in Celcius |
inputTemperatureMidSensor | 1.3.6.1.4.1.9839.2606.2.1.2.7 | divby10 | read-only |
Mid sensor input temperature in Celcius |
inputTemperatureBottomSensor | 1.3.6.1.4.1.9839.2606.2.1.2.8 | divby10 | read-only |
Bottom sensor input temperature in Celcius |
compressorDischargeTemperature | 1.3.6.1.4.1.9839.2606.2.1.2.9 | divby10 | read-only |
Compressor discharge temperature |
compressorSuctionTemperature | 1.3.6.1.4.1.9839.2606.2.1.2.10 | divby10 | read-only |
Compressor suction temperature |
compressorDischargePressure | 1.3.6.1.4.1.9839.2606.2.1.2.11 | divby10 | read-only |
Compressor discharge pressure |
compressorSuctionPressure | 1.3.6.1.4.1.9839.2606.2.1.2.12 | divby10 | read-only |
Compressor suction pressure |
evaporatorTemperature | 1.3.6.1.4.1.9839.2606.2.1.2.13 | divby10 | read-only |
Evaporator temperature from Low pressure conversion |
condensingTemperature | 1.3.6.1.4.1.9839.2606.2.1.2.14 | divby10 | read-only |
Condensing temperature from High pressure conversion |
inputTemperatureAverage | 1.3.6.1.4.1.9839.2606.2.1.2.21 | divby10 | read-only |
Average input temperature in Celcius |
outputTemperatureAverage | 1.3.6.1.4.1.9839.2606.2.1.2.22 | divby10 | read-only |
Average output temperature in Celcius |
compressorRotorSpeed | 1.3.6.1.4.1.9839.2606.2.1.2.45 | divby10 | read-only |
Compressor rotor speed |
compressorMotorCurrent | 1.3.6.1.4.1.9839.2606.2.1.2.46 | divby10 | read-only |
Compressor motor current |
lcpSetpoint | 1.3.6.1.4.1.9839.2606.2.1.2.48 | divby10 | read-write |
Main LCP setpoint |
integer | 1.3.6.1.4.1.9839.2606.2.1.3 | |||
compressorRotorSpeedHz | 1.3.6.1.4.1.9839.2606.2.1.3.1 | integer | read-only |
Compressor rotor speed in Hz |
driverPowerStatus | 1.3.6.1.4.1.9839.2606.2.1.3.2 | integer | read-only |
Driver power status stop (1), run (2), alarm (3) Enumeration: 'run': 2, 'alarm': 3, 'stop': 1. |
currentErrorCode | 1.3.6.1.4.1.9839.2606.2.1.3.3 | integer | read-only |
Current error code Enumeration: 'ALW04': 33, 'ALL01': 30, 'ALL02': 31, 'ALD04': 24, 'ALD05': 25, 'ALD06': 26, 'ALD07': 27, 'ALD02': 22, 'ALD03': 23, 'ALD08': 28, 'ALD09': 29, 'ALA12': 12, 'ALA10': 10, 'ALA11': 11, 'ALL99': 32, 'ALB02': 14, 'ALB03': 15, 'ALB01': 13, 'ALC03': 17, 'ALC01': 16, 'ALC06': 20, 'ALC05': 19, 'ALC04': 18, 'ALA09': 9, 'ALA08': 8, 'OK': 0, 'ALF01': 21, 'ALA03': 3, 'ALA02': 2, 'ALA05': 5, 'ALA04': 4, 'ALA07': 7, 'ALA06': 6. |
driverTemperature | 1.3.6.1.4.1.9839.2606.2.1.3.4 | divby10 | read-only |
Driver Power+ Temperature |
dcBusVoltage | 1.3.6.1.4.1.9839.2606.2.1.3.5 | divby10 | read-only |
Power+ DC Voltage |
motorVoltage | 1.3.6.1.4.1.9839.2606.2.1.3.6 | divby10 | read-only |
Motor Voltage |
powerRequest | 1.3.6.1.4.1.9839.2606.2.1.3.7 | divby10 | read-only |
Request of power for inverter after envelop |
unitOnOff | 1.3.6.1.4.1.9839.2606.2.1.3.13 | integer | read-write |
Unit on/off state off (0), on (1), energy-save (2), auto (3) Enumeration: 'on': 1, 'off': 0, 'auto': 3, 'energy-save': 2. |
envelopeZone | 1.3.6.1.4.1.9839.2606.2.1.3.14 | integer | read-only |
envelope zone ok (0), maximum compression ratio (1), maximum discharge power (2), current limit (3), maximum suction power(4), minimum compression ratio (5), minimum delta power (6), minimum discharge power(7), minimum suction power (8) Enumeration: 'current-limit': 3, 'maximum-discharge-power': 2, 'minimum-discharge-power': 7, 'minimum-suction-power': 8, 'maximum-compression-ratio': 1, 'maximum-suction-power': 4, 'ok': 0, 'minimum-compression-ratio': 5, 'minimum-delta-power': 6. |
coolingCapacity | 1.3.6.1.4.1.9839.2606.2.1.3.16 | integer | read-only |
Actual EVD valve cooling capacity |
evdValveSteps | 1.3.6.1.4.1.9839.2606.2.1.3.17 | integer | read-only |
EVD valve steps position |
fanSpeedPercent | 1.3.6.1.4.1.9839.2606.2.1.3.28 | integer | read-only |
The fan speed percentage |
fanSpeedRpm | 1.3.6.1.4.1.9839.2606.2.1.3.29 | integer | read-only |
The fan speed rpm |
evdValveOpening | 1.3.6.1.4.1.9839.2606.2.1.3.30 | integer | read-only |
Actual EVD valve opening |