Argus-Power-System-MIB: View SNMP OID List / Download MIB

VENDOR: ARGUS TECHNOLOGIES


 Home MIB: Argus-Power-System-MIB
Download as:   

Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 argus 1.3.6.1.4.1.7309
This MIB defines the information block(s) available in CXC RMU as defined by the following list: - upsDevice: the CXC-series of controllers
           upsPower 1.3.6.1.4.1.7309.6
               upsDevice 1.3.6.1.4.1.7309.6.1
                   upsIdent 1.3.6.1.4.1.7309.6.1.1
                       upsIdentManufacturer 1.3.6.1.4.1.7309.6.1.1.1 displaystring read-only
The name of the UPS manufacturer.
                       upsIdentProductCode 1.3.6.1.4.1.7309.6.1.1.2 displaystring read-only
The UPS Model designation.
                       upsIdentModel 1.3.6.1.4.1.7309.6.1.1.3 displaystring read-only
The UPS Product code designation.
                       upsIdentUPSSoftwareVersion 1.3.6.1.4.1.7309.6.1.1.4 displaystring read-only
The UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.
                       upsIdentAgentSoftwareVersion 1.3.6.1.4.1.7309.6.1.1.5 displaystring read-only
The UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.
                       upsIdentName 1.3.6.1.4.1.7309.6.1.1.6 displaystring read-only
A string identifying the UPS. This object should be set by the administrator.
                       upsIdentAttachedDevices 1.3.6.1.4.1.7309.6.1.1.7 displaystring read-only
A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.
                       upsIdentSiteName 1.3.6.1.4.1.7309.6.1.1.8 displaystring read-write
Site Name
                       upsIdentSiteCity 1.3.6.1.4.1.7309.6.1.1.9 displaystring read-write
Site City
                       upsIdentSiteRegion 1.3.6.1.4.1.7309.6.1.1.10 displaystring read-write
Site Region
                       upsIdentSiteCountry 1.3.6.1.4.1.7309.6.1.1.11 displaystring read-write
Site Country
                       upsIdentContactName 1.3.6.1.4.1.7309.6.1.1.12 displaystring read-write
Contact Name
                       upsIdentPhoneNumber 1.3.6.1.4.1.7309.6.1.1.13 displaystring read-write
Phone Number
                       upsIdentDate 1.3.6.1.4.1.7309.6.1.1.14 displaystring read-write
Date of the RMU-Novus
                       upsIdentTime 1.3.6.1.4.1.7309.6.1.1.15 displaystring read-write
Time of the RMU-Novus
                   upsBattery 1.3.6.1.4.1.7309.6.1.2
                       upsBatteryStatus 1.3.6.1.4.1.7309.6.1.2.1 integer read-only
The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output). Enumeration: 'unknown': 1, 'batteryNormal': 2, 'batteryDepleted': 4, 'batteryLow': 3.
                       upsMinutesOnBattery 1.3.6.1.4.1.7309.6.1.2.2 integer read-only
The accumulated elapsed time that the UPS system have been on battery.
                       upsBatteryVoltage 1.3.6.1.4.1.7309.6.1.2.3 integer read-only
The magnitude of the present battery voltage.
                       upsBatteryChargingCurrent 1.3.6.1.4.1.7309.6.1.2.4 integer read-only
The present battery charging current.
                       upsBatteryCapacity 1.3.6.1.4.1.7309.6.1.2.5 integer read-only
The present battery capacity.
                       upsBatteryTemperature 1.3.6.1.4.1.7309.6.1.2.6 integer read-only
The ambient temperature at or near the UPS Battery casing.
                       upsBatteryLowWarning 1.3.6.1.4.1.7309.6.1.2.7 integer read-write
The set battery capacity percentage at which the unit will raise an alarm.
                   upsInput 1.3.6.1.4.1.7309.6.1.3
                       upsInputNumLines 1.3.6.1.4.1.7309.6.1.3.1 integer read-only
The number of input lines utilized in this device. This variable indicates the number of rows in the input table.
                       upsInputTable 1.3.6.1.4.1.7309.6.1.3.2 no-access
A list of input table entries. The number of entries is given by the value of upsInputNumLines.
                           upsInputEntry 1.3.6.1.4.1.7309.6.1.3.2.1 no-access
An entry containing information applicable to a particular input line.
                               upsInputLineIndex 1.3.6.1.4.1.7309.6.1.3.2.1.1 integer no-access
The input line identifier.
                               upsInputFrequency 1.3.6.1.4.1.7309.6.1.3.2.1.2 integer read-only
The present input frequency.
                               upsInputVoltage 1.3.6.1.4.1.7309.6.1.3.2.1.3 integer read-only
The magnitude of the present input voltage.
                   upsOutput 1.3.6.1.4.1.7309.6.1.4
                       upsOutputSource 1.3.6.1.4.1.7309.6.1.4.1 integer read-only
The present source of output power. The enumeration line(2) indicates that the Novus is in line mode. Enumeration: 'bypass': 11, 'standby': 1, 'transfer': 9, 'retransfer': 8, 'shutdown': 10, 'buck2': 6, 'inverter': 7, 'line': 2, 'buck1': 5, 'boost1': 4, 'boost2': 3.
                       upsOutputFrequency 1.3.6.1.4.1.7309.6.1.4.2 integer read-only
The present output frequency.
                       upsOutputNumLines 1.3.6.1.4.1.7309.6.1.4.3 integer read-only
The number of output lines utilized in this device. This variable indicates the number of rows in the output table.
                       upsOutputTable 1.3.6.1.4.1.7309.6.1.4.4 no-access
A list of output table entries. The number of entries is given by the value of upsOutputNumLines.
                           upsOutputEntry 1.3.6.1.4.1.7309.6.1.4.4.1 no-access
An entry containing information applicable to a particular output line.
                               upsOutputLineIndex 1.3.6.1.4.1.7309.6.1.4.4.1.1 integer no-access
The output line identifier.
                               upsOutputVoltage 1.3.6.1.4.1.7309.6.1.4.4.1.2 integer read-only
The present output voltage.
                               upsOutputCurrent 1.3.6.1.4.1.7309.6.1.4.4.1.3 integer read-only
The present output current.
                               upsOutputPowerVA 1.3.6.1.4.1.7309.6.1.4.4.1.4 integer read-only
The present output VA.
                               upsOutputPowerWatt 1.3.6.1.4.1.7309.6.1.4.4.1.5 integer read-only
The present output true power.
                               upsPowerFactor 1.3.6.1.4.1.7309.6.1.4.4.1.6 integer read-only
The present power factor.
                               upsOutputPercentLoad 1.3.6.1.4.1.7309.6.1.4.4.1.7 integer read-only
The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.
                   upsAlarm 1.3.6.1.4.1.7309.6.1.5
                       upsAlarmsPresent 1.3.6.1.4.1.7309.6.1.5.1 integer read-only
The present number of active alarm conditions.
                       upsAlarmTable 1.3.6.1.4.1.7309.6.1.5.2 no-access
A list of alarm table entries.
                           upsAlarmEntry 1.3.6.1.4.1.7309.6.1.5.2.1 no-access
An entry containing information applicable to a particular alarm.
                               upsAlarmId 1.3.6.1.4.1.7309.6.1.5.2.1.1 integer no-access
A unique identifier for an alarm condition. This value must remain constant.
                               upsAlarmDescr 1.3.6.1.4.1.7309.6.1.5.2.1.2 displaystring read-only
A unique description of the alarm.
                               upsAlarmStatus 1.3.6.1.4.1.7309.6.1.5.2.1.3 integer read-only
1 - ON or 0 - OFF.
                   upsConfig 1.3.6.1.4.1.7309.6.1.6
                       upsConfigLineQualifyTime 1.3.6.1.4.1.7309.6.1.6.1 integer read-only
This objects displays the line qualify time.
                       upsConfigLineOutputVoltageHighLimit 1.3.6.1.4.1.7309.6.1.6.2 integer read-only
This object represents the Line output High Voltage Limit.
                       upsConfigLineOutputVoltageLowLimit 1.3.6.1.4.1.7309.6.1.6.3 integer read-only
This object represents the Line output Low Voltage Limit.
                       upsConfigFanOnTemperature 1.3.6.1.4.1.7309.6.1.6.4 integer read-only
This object represents the Fan on temperature.
                       upsShutdownStatus 1.3.6.1.4.1.7309.6.1.6.5 integer read-write
This object tells us if output is disabled or enabled.
                       upsInverterOffDelayTime 1.3.6.1.4.1.7309.6.1.6.6 integer read-write
This object represents the inverter off delay time.
                       upsConfigIPAddress 1.3.6.1.4.1.7309.6.1.6.7 displaystring read-write
This objects displays the IP address of the RMU.
                       upsConfigNetMask 1.3.6.1.4.1.7309.6.1.6.8 displaystring read-write
This object displays the Net Mask of the RMU.
                       upsConfigGateway 1.3.6.1.4.1.7309.6.1.6.9 displaystring read-write
This object displays the Gateway of the RMU.
                       upsConfigSnmpCommunity 1.3.6.1.4.1.7309.6.1.6.10 displaystring read-write
This object displays the SNMP community
                       upsConfigSnmpTrapIPDestination 1.3.6.1.4.1.7309.6.1.6.11 displaystring read-write
This object displays the SNMP Trap IP destination.
                   upsTraps 1.3.6.1.4.1.7309.6.1.7
                       upsTrap 1.3.6.1.4.1.7309.6.1.7.0
                           upsAlarmTrap 1.3.6.1.4.1.7309.6.1.7.0.1
A trap issued from a change in state in one of the Alarms on the Novus controller
                           upsAgentStartupTrap 1.3.6.1.4.1.7309.6.1.7.0.2
A trap to indicate that the agent software has started up.
                           upsAgentShutdownTrap 1.3.6.1.4.1.7309.6.1.7.0.3
A trap to indicate that the agent software has shutdown.
                           upsAgentFaultTrap 1.3.6.1.4.1.7309.6.1.7.0.4
A trap issued from a change in state in one of the Faults on the Novus controller
                           upsAgentEventTrap 1.3.6.1.4.1.7309.6.1.7.0.5
A trap issued from a change in state in one of the Events on the Novus controller
                   upsExtra 1.3.6.1.4.1.7309.6.1.8
                       upsExtraCount 1.3.6.1.4.1.7309.6.1.8.1 integer read-only
Number of extra variables
                       upsExtraTable 1.3.6.1.4.1.7309.6.1.8.2 no-access
A table of CXC upstem controller extra variables
                           upsExtraEntry 1.3.6.1.4.1.7309.6.1.8.2.1 no-access
An entry into the CXC upstem controller extra variable table
                               upsExtraIndex 1.3.6.1.4.1.7309.6.1.8.2.1.1 integer read-only
The index of the extra variable in the CXC upstem controller table
                               upsExtraName 1.3.6.1.4.1.7309.6.1.8.2.1.2 displaystring read-only
The description of the extra variable as reported by the CXC upstem controller
                               upsExtraIntegerValue 1.3.6.1.4.1.7309.6.1.8.2.1.3 integer read-only
The integer value of the extra variable as reported by the CXC upstem controller
                               upsExtraStringValue 1.3.6.1.4.1.7309.6.1.8.2.1.4 displaystring read-only
The string value of the extra variable as reported by the CXC upstem controller