ATEN-PE-CFG: View SNMP OID List / Download MIB

VENDOR: ATEN INTERNATIONAL CO.


 Home MIB: ATEN-PE-CFG
Download as:   

Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 aten 1.3.6.1.4.1.21317
ATEN PE MIB
             atenProducts 1.3.6.1.4.1.21317.1
                 overip 1.3.6.1.4.1.21317.1.3
                     poweroverip 1.3.6.1.4.1.21317.1.3.2
                         pe 1.3.6.1.4.1.21317.1.3.2.2
                             userManagement 1.3.6.1.4.1.21317.1.3.2.2.1
                                 usrListTable 1.3.6.1.4.1.21317.1.3.2.2.1.1 no-access
A list of user. The number of user is given by the value of usrcfgNumber.
                                     usrListEntry 1.3.6.1.4.1.21317.1.3.2.2.1.1.1 no-access
Status and parameter values for a pe8208 user.
                                         usrIndex 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.1 integer read-only
The value of usrIndex for the user. We have 1 administrator and 8 users. The index 9 will be the administrator.
                                         usrType 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.2 integer read-only
The user's type. Enumeration: 'administrator': 1, 'user': 2.
                                         usrName 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.3 displaystring read-write
A textual string containing name of the user. string length: 1~16
                                         usrPassword 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.4 displaystring read-write
A textual string containing password of the user. string length: 1~16
                                         usrPort1Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.5 integer read-write
Display or set this user's outlet 1 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort2Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.6 integer read-write
Display or set this user's outlet 2 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort3Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.7 integer read-write
Display or set this user's outlet 3 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort4Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.8 integer read-write
Display or set this user's outlet 4 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort5Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.9 integer read-write
Display or set this user's outlet 5 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort6Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.10 integer read-write
Dispaly or set this user's outlet 6 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort7Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.11 integer read-write
Display or set this user's outlet 7 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort8Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.12 integer read-write
Display or set this user's outlet 8 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort9Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.13 integer read-write
Display or set this user's outlet 9 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort10Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.14 integer read-write
Display or set this user's outlet 10 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort11Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.15 integer read-write
Display or set this user's outlet 11 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort12Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.16 integer read-write
Display or set this user's outlet 12 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort13Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.17 integer read-write
Display or set this user's outlet 13 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort14Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.18 integer read-write
Display or set this user's outlet 14 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort15Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.19 integer read-write
Display or set this user's outlet 15 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort16Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.20 integer read-write
Display or set this user's outlet 16 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort17Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.21 integer read-write
Display or set this user's outlet 17 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort18Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.22 integer read-write
Display or set this user's outlet 18 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort19Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.23 integer read-write
Display or set this user's outlet 19 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort20Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.24 integer read-write
Display or set this user's outlet 20 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort21Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.25 integer read-write
Display or set this user's outlet 21 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort22Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.26 integer read-write
Display or set this user's outlet 22 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort23Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.27 integer read-write
Display or set this user's outlet 23 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort24Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.28 integer read-write
Display or set this user's outlet 24 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort25Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.29 integer read-write
Display or set this user's outlet 25 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort26Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.30 integer read-write
Display or set this user's outlet 26 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort27Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.31 integer read-write
Display or set this user's outlet 27 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort28Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.32 integer read-write
Display or set this user's outlet 28 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort29Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.33 integer read-write
Display or set this user's outlet 29 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort30Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.34 integer read-write
Display or set this user's outlet 30 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort31Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.35 integer read-write
Display or set this user's outlet 31 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort32Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.36 integer read-write
Display or set this user's outlet 32 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort33Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.37 integer read-write
Display or set this user's outlet 33 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort34Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.38 integer read-write
Display or set this user's outlet 34 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort35Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.39 integer read-write
Display or set this user's outlet 35 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort36Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.40 integer read-write
Display or set this user's outlet 36 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort37Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.41 integer read-write
Display or set this user's outlet 37 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort38Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.42 integer read-write
Display or set this user's outlet 38 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort39Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.43 integer read-write
Display or set this user's outlet 39 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort40Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.44 integer read-write
Display or set this user's outlet 40 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort41Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.45 integer read-write
Display or set this user's outlet 41 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrPort42Auth 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.46 integer read-write
Display or set this user's outlet 42 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. Enumeration: 'not-support': 4, 'disable': 1, 'modify': 3, 'view': 2.
                                         usrEnable 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.47 integer read-write
Display or set this user is enable or not Enumeration: 'enable': 2, 'disable': 1.
                             control 1.3.6.1.4.1.21317.1.3.2.2.2
                                 device 1.3.6.1.4.1.21317.1.3.2.2.2.1
                                     modelName 1.3.6.1.4.1.21317.1.3.2.2.2.1.1 displaystring read-only
Indicate PE device model name.
                                     deviceName 1.3.6.1.4.1.21317.1.3.2.2.2.1.2 displaystring read-write
The name of PE device. string length: 1~39 NOTE: Input string as /empty to set this object to NULL.
                                     deviceValueTable 1.3.6.1.4.1.21317.1.3.2.2.2.1.3 no-access
Device value table. This table displays device's current, voltage, power and power dissipation.
                                         deviceValueEntry 1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1 no-access
Single deviceValue entry containing device info.
                                             deviceValueIndex 1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.1 integer read-only
Index of deviceValue.
                                             deviceCurrent 1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.2 displaystring read-only
Device electric current value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support.
                                             deviceVoltage 1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.3 displaystring read-only
Device voltage value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support.
                                             devicePower 1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.4 displaystring read-only
Device power value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support.
                                             devicePowerDissipation 1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.5 displaystring read-only
Device power dissipation value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support.
                                             inputMaxVoltage 1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.6 integer read-only
Device input Voltage value. unit:(V) If the device does not support this OID, we show value 0.
                                             inputMaxCurrent 1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.7 integer read-only
Device input Current value. unit:(A) If the device does not support this OID, we show value 0.
                                             powerCapacity 1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.8 integer read-only
Device power Capacity value.unit:(VA) If the device does not support this OID, we show value 0.
                                             devicePowerFactor 1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.9 displaystring read-only
Device power Factor value. If the device does not support this OID, it returns: not-support.
                                     sensorValueTable 1.3.6.1.4.1.21317.1.3.2.2.2.1.4 no-access
Device's sensor value table. This table displays sensor's temperature, humidity and pressure.
                                         sensorValueEntry 1.3.6.1.4.1.21317.1.3.2.2.2.1.4.1 no-access
Single device's sensor value entry containing device info.
                                             sensorValueIndex 1.3.6.1.4.1.21317.1.3.2.2.2.1.4.1.1 integer read-only
Index of sensor number.
                                             sensorTemperature 1.3.6.1.4.1.21317.1.3.2.2.2.1.4.1.2 displaystring read-only
Sensor's Temperature value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support.
                                             sensorHumidity 1.3.6.1.4.1.21317.1.3.2.2.2.1.4.1.3 displaystring read-only
Sensor's Humidity value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support.
                                             sensorPressure 1.3.6.1.4.1.21317.1.3.2.2.2.1.4.1.4 displaystring read-only
Sensor's Pressure value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support.
                                             sensorProperty 1.3.6.1.4.1.21317.1.3.2.2.2.1.4.1.5 integer read-only
Sensor's Property. Enumeration: 'exhaust': 2, 'intake': 1, 'floor': 3.
                                     deviceOutletStatusTable 1.3.6.1.4.1.21317.1.3.2.2.2.1.5 no-access
Device outlet status value table.
                                         deviceOutletStatusEntry 1.3.6.1.4.1.21317.1.3.2.2.2.1.5.1 no-access
Single deviceOutletStatus entry containing device info.
                                             deviceOutletStatusIndex 1.3.6.1.4.1.21317.1.3.2.2.2.1.5.1.1 integer read-only
Index of deviceOutletStatus
                                             displayOutletStatus 1.3.6.1.4.1.21317.1.3.2.2.2.1.5.1.2 integer read-only
Display outlet status. Enumeration: 'on': 2, 'not-support': 6, 'off': 1, 'fault': 4, 'pop': 7, 'noauth': 5, 'pending': 3.
                                     deviceConfigTable 1.3.6.1.4.1.21317.1.3.2.2.2.1.6 no-access
Device configuration table
                                         deviceConfigEntry 1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1 no-access
Single deviceConfig entry containing device info.
                                             deviceConfigIndex 1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.1 integer read-only
Index of deviceConfig
                                             deviceMinCurMT 1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.2 integer read-write
Display or set device minimum electric current measurement threshold. Example: range 0.0~32.0 represents 0~320. NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
                                             deviceMaxCurMT 1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.3 integer read-write
Display or set device maximum electric current measurement threshold. Example: range 0.0~32.0 represents 0~320 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
                                             deviceMinVolMT 1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.4 integer read-write
Display or set device minimum voltage measurement threshold. Exapmple: range 90.0~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
                                             deviceMaxVolMT 1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.5 integer read-write
Display or set device maximum voltage measurement threshold. Example: range 90.0~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
                                             deviceMinPMT 1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.6 integer read-write
Display or set device minimum power measurement threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
                                             deviceMaxPMT 1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.7 integer read-write
Display or set device maximum power measurement threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
                                             deviceMaxPDMT 1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.8 integer read-write
Display or set device maximum power dissipation measurement threshold. Example: range 0.0 ~ 99999.0 represents 0~999990 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
                                     deviceSensorTresholdTable 1.3.6.1.4.1.21317.1.3.2.2.2.1.7 no-access
Device environment value table
                                         deviceSensorTresholdEntry 1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1 no-access
Device's sensor Environment entry containing sensor info.
                                             deviceSensorTresholdIndex 1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.1 integer read-only
Index of sensor number
                                             sensorMinTempMT 1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.2 integer read-write
Display or set sensor minimum temperature measurement threshold. Example: range -20.0 ~ 60.0 represents -200~600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
                                             sensorMaxTempMT 1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.3 integer read-write
Display or set sensor maximum temperature measurement threshold. Example: range -20.0 ~ 60.0 represents -200~600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
                                             sensorMinHumMT 1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.4 integer read-write
Display or set sensor minimum humidity measurement threshold. Example: range 15.0 ~ 95.0 represents 150~950 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
                                             sensorMaxHumMT 1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.5 integer read-write
Display or set sensor maximum humidity measurement threshold. Example: range 15.0 ~ 95.0 represents 150~950 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
                                             sensorMinPressMT 1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.6 integer read-write
Display or set sensor minimum pressure measurement threshold. Example: range -250.0 ~ 250.0 represents -2500 ~ 2500 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
                                             sensorMaxPressMT 1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.7 integer read-write
Display or set sensor maximum pressure measurement threshold. Example: range -250.0 ~ 250.0 represents -2500 ~ 2500 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
                                     deviceOutletControl 1.3.6.1.4.1.21317.1.3.2.2.2.1.8 integer read-write
This function is used for all outlet ports control. Set off(1) to turn off for all outlet ports. Set on(2) to turn on for all outlet ports. Get this object always return nostatus(3), because there is no device status. Enumeration: 'on': 2, 'not-support': 4, 'nostatus': 3, 'off': 1.
                                     deviceOutletReboot 1.3.6.1.4.1.21317.1.3.2.2.2.1.9 integer read-write
This function is used for all outlet ports to reboot. Only when outlet status is ON can do outlet reboot action to all ports. Set yes(2) to reboot all outlet ports. Get this object always return no(1). Enumeration: 'yes': 2, 'not-support': 4, 'no': 1.
                                     switchable 1.3.6.1.4.1.21317.1.3.2.2.2.1.10 integer read-only
Outlet is switchable or not. Enumeration: 'mix': 3, 'yes': 2, 'no': 1.
                                     perportreading 1.3.6.1.4.1.21317.1.3.2.2.2.1.11 integer read-only
Outlet is per-port reading or not. Enumeration: 'yes': 2, 'no': 1.
                                     sensornumber 1.3.6.1.4.1.21317.1.3.2.2.2.1.12 integer read-only
Sensor number.
                                     outletnumber 1.3.6.1.4.1.21317.1.3.2.2.2.1.13 integer read-only
Outlet number.
                                     banknumber 1.3.6.1.4.1.21317.1.3.2.2.2.1.14 integer read-only
Bank number.
                                     doorSensor 1.3.6.1.4.1.21317.1.3.2.2.2.1.16
                                           doorSensorStatus 1.3.6.1.4.1.21317.1.3.2.2.2.1.16.1 integer read-only
Display door sensor status. close(0) represents door close. open(1) represents door open. not-attached(2) represents door sensor don't attach to device. Enumeration: 'close': 0, 'not-support': 4, 'not-attached': 2, 'open': 1.
                                           doorSensorType 1.3.6.1.4.1.21317.1.3.2.2.2.1.16.2 integer read-write
Door Sensor Type Selection Enumeration: 'photo': 1, 'inductiveproximity': 2, 'notinstalled': 0, 'reed': 3.
                                     pop 1.3.6.1.4.1.21317.1.3.2.2.2.1.17
                                           enablePOPmode 1.3.6.1.4.1.21317.1.3.2.2.2.1.17.1 integer read-write
Enable/Disable POP mode. Enumeration: 'yes': 2, 'no': 1.
                                           popThreshold 1.3.6.1.4.1.21317.1.3.2.2.2.1.17.2 integer read-write
(-1)means default value same as Bank Max Current 16 A. Example: range 0.0~32.0 represents 0~320 You can define the POP threshold or set as default(-1) value.
                                           enableOutletPOPmode 1.3.6.1.4.1.21317.1.3.2.2.2.1.17.3 integer read-write
Enable/Disable Outlet POP mode. Enumeration: 'yes': 2, 'not-support': 3, 'no': 1.
                                           enableLIFOPOPmode 1.3.6.1.4.1.21317.1.3.2.2.2.1.17.4 integer read-write
Enable/Disable LIFO POP mode. Enumeration: 'yes': 2, 'not-support': 3, 'no': 1.
                                           enablePriorityPOPmode 1.3.6.1.4.1.21317.1.3.2.2.2.1.17.5 integer read-write
Enable/Disable Priority POP mode. Enumeration: 'yes': 2, 'not-support': 3, 'no': 1.
                                     cap 1.3.6.1.4.1.21317.1.3.2.2.2.1.18
                                           enableCAPmode 1.3.6.1.4.1.21317.1.3.2.2.2.1.18.1 integer read-write
Enable/Disable CAP mode. Enumeration: 'yes': 2, 'no': 1.
                                           outletCAPTable 1.3.6.1.4.1.21317.1.3.2.2.2.1.18.2 no-access
Outlet CAP table
                                               outletCAPEntry 1.3.6.1.4.1.21317.1.3.2.2.2.1.18.2.1 no-access
Outlet CAP entry containing CAP info.
                                                   outletCAPIndex 1.3.6.1.4.1.21317.1.3.2.2.2.1.18.2.1.1 integer read-only
Index of outlet's CAP configuration
                                                   outletCAPPriority 1.3.6.1.4.1.21317.1.3.2.2.2.1.18.2.1.2 integer read-write
Display or set the CAP Priority of outlet. Priority 0 means this outlet does not support this OID.
                                     outletInitMode 1.3.6.1.4.1.21317.1.3.2.2.2.1.19 integer read-write
choose outlet init mode you want. Enumeration: 'not-support': 3, 'delaytime': 2, 'no-delaytime': 1.
                                     deviceIntegerValueTable 1.3.6.1.4.1.21317.1.3.2.2.2.1.99 no-access
Device value table. This table displays device's current, voltage, power and power dissipation.
                                           deviceIntegerValueEntry 1.3.6.1.4.1.21317.1.3.2.2.2.1.99.1 no-access
Single deviceValue entry containing device info.
                                               deviceIntegerValueIndex 1.3.6.1.4.1.21317.1.3.2.2.2.1.99.1.1 integer read-only
Index of deviceValue.
                                               deviceIntegerCurrent 1.3.6.1.4.1.21317.1.3.2.2.2.1.99.1.2 integer read-only
Device electric current value. This value indicates that 1,000 times. If the device does not support this OID, it returns value -2000000.
                                               deviceIntegerVoltage 1.3.6.1.4.1.21317.1.3.2.2.2.1.99.1.3 integer read-only
Device voltage value. This value indicates that 1,000 times. If the device does not support this OID, it returns value -2000000.
                                               deviceIntegerPower 1.3.6.1.4.1.21317.1.3.2.2.2.1.99.1.4 integer read-only
Device power value. This value indicates that 1,000 times. If the device does not support this OID, it returns value -2000000.
                                               deviceIntegerPowerDissipation 1.3.6.1.4.1.21317.1.3.2.2.2.1.99.1.5 integer read-only
Device power dissipation value. This value indicates that 1,000 times. If the device does not support this OID, it returns value -2000000.
                                     sensorIntegerValueTable 1.3.6.1.4.1.21317.1.3.2.2.2.1.100 no-access
Device's sensor value table. This table displays sensor's temperature, humidity and pressure.
                                             sensorIntegerValueEntry 1.3.6.1.4.1.21317.1.3.2.2.2.1.100.1 no-access
Single device's sensor value entry containing device info.
                                                 sensorIntegerValueIndex 1.3.6.1.4.1.21317.1.3.2.2.2.1.100.1.1 integer read-only
Index of sensor number.
                                                 sensorIntegerTemperature 1.3.6.1.4.1.21317.1.3.2.2.2.1.100.1.2 integer read-only
Sensor's Temperature value. This value indicates that 1,000 times. If this measurement value is not available, it returns value -1000000. If the device does not support this OID, it returns value -2000000.
                                                 sensorIntegerHumidity 1.3.6.1.4.1.21317.1.3.2.2.2.1.100.1.3 integer read-only
Sensor's Humidity value. This value indicates that 1,000 times. If this measurement value is not available, it returns value -1000000. If the device does not support this OID, it returns value -2000000.
                                                 sensorIntegerPressure 1.3.6.1.4.1.21317.1.3.2.2.2.1.100.1.4 integer read-only
Sensor's Pressure value. This value indicates that 1,000 times. If this measurement value is not available, it returns value -1000000. If the device does not support this OID, it returns value -2000000.
                                 outlet 1.3.6.1.4.1.21317.1.3.2.2.2.2
                                     outletValueTable 1.3.6.1.4.1.21317.1.3.2.2.2.2.1 no-access
Display total outlet value table
                                         outletValueEntry 1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1 no-access
Single outletValue entry containing outlet info.
                                             outletValueIndex 1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1.1 integer read-only
Index of outlet number
                                             outletCurrent 1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1.2 displaystring read-only
Outlet electric current value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support.
                                             outletVoltage 1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1.3 displaystring read-only
Outlet voltage value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support.
                                             outletPower 1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1.4 displaystring read-only
Outlet power value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support.
                                             outletPowerDissipation 1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1.5 displaystring read-only
Outlet power dissipation value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support.
                                             outletMaxCurrent 1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1.6 integer read-only
Outlet Max Current value. unit: (A). If the device does not support this OID, we show value 0.
                                             outletPowerFactor 1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1.7 displaystring read-only
Outlet Power Factor value. If the device does not support this OID, it returns: not-support.
                                     outlet1Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.2 integer read-write
Display and control outlet 1 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet2Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.3 integer read-write
Display and control outlet 2 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet3Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.4 integer read-write
Display and control outlet 3 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet4Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.5 integer read-write
Display and control outlet 4 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet5Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.6 integer read-write
Display and control outlet 5 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet6Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.7 integer read-write
Display and control outlet 6 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet7Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.8 integer read-write
Display and control outlet 7 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet8Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.9 integer read-write
Display and control outlet 8 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outletConfigTable 1.3.6.1.4.1.21317.1.3.2.2.2.2.10 no-access
Outlet configuration table
                                           outletConfigEntry 1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1 no-access
Outlet Config entry containing outlet info.
                                               outletConfigIndex 1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.1 integer read-only
Index of outlet number
                                               outletName 1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.2 displaystring read-write
Display or set the name of outlet. If the device does not support this OID, we show n/a. string length: 0~15 NOTE: Input string as /empty to set this object to NULL.
                                               outletConfirmation 1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.3 integer read-write
Display or set the confirmation of outlet. Enumeration: 'yes': 2, 'noauth': 3, 'not-support': 4, 'no': 1.
                                               outletOnDelayTime 1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.4 integer read-write
Display or set the ON delay time of outlet. When this model does not support the OID, we show value -1.
                                               outletOffDelayTime 1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.5 integer read-write
Display or set the OFF delay time of outlet. When this model does not support the OID, we show value -1.
                                               outletShutdownMethod 1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.6 integer read-write
Display or set the shutdown mehtod of outlet. Enumeration: 'after-ac-back': 3, 'not-support': 4, 'wake-on-lan': 2, 'kill-the-power': 1.
                                               outletMAC 1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.7 displaystring read-write
Display or set the MAC address of ShutdownMethod. If the device does not support this OID, we show n/a. string length: 12
                                               outletMinCurMT 1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.8 integer read-write
Display or set the outlet minimum electric current measurment threshold. Example: range 0.0 ~16.0 rerpresnts 0~160 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
                                               outletMaxCurMT 1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.9 integer read-write
Display or set the outlet maximum electric current measurment threshold. Example: range 0.0 ~16.0 represents 0~160 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
                                               outletMinVolMT 1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.10 integer read-write
Display or set the outlet minimum voltage measurment threshold. Example: range 90.0 ~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
                                               outletMaxVolMT 1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.11 integer read-write
Display or set the outlet maximum voltage measurment threshold. Example: range 90.0 ~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
                                               outletMinPMT 1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.12 integer read-write
Display or set the outlet minimum power measurment threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
                                               outletMaxPMT 1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.13 integer read-write
Display or set the outlet maximum power measurment threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
                                               outletMaxPDMT 1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.14 integer read-write
Display or set the outlet maximum power dissipation measurment threshold. Example: range 0.0 ~ 99999.0 represents 0~999990 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
                                     outlet9Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.11 integer read-write
Display and control outlet 9 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet10Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.12 integer read-write
Display and control outlet 10 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet11Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.13 integer read-write
Display and control outlet 11 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet12Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.14 integer read-write
Display and control outlet 12 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet13Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.15 integer read-write
Display and control outlet 13 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet14Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.16 integer read-write
Display and control outlet 14 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet15Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.17 integer read-write
Display and control outlet 15 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet16Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.18 integer read-write
Display and control outlet 16 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet17Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.19 integer read-write
Display and control outlet 17 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet18Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.20 integer read-write
Display and control outlet 18 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet19Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.21 integer read-write
Display and control outlet 19 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet20Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.22 integer read-write
Display and control outlet 20 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet21Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.23 integer read-write
Display and control outlet 21 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet22Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.24 integer read-write
Display and control outlet 22 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet23Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.25 integer read-write
Display and control outlet 23 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet24Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.26 integer read-write
Display and control outlet 24 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet25Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.27 integer read-write
Display and control outlet 25 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet26Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.28 integer read-write
Display and control outlet 26 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet27Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.29 integer read-write
Display and control outlet 27 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet28Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.30 integer read-write
Display and control outlet 28 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet29Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.31 integer read-write
Display and control outlet 29 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet30Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.32 integer read-write
Display and control outlet 30 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet31Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.33 integer read-write
Display and control outlet 31 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet32Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.34 integer read-write
Display and control outlet 32 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet33Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.35 integer read-write
Display and control outlet 33 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet34Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.36 integer read-write
Display and control outlet 34 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet35Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.37 integer read-write
Display and control outlet 35 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet36Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.38 integer read-write
Display and control outlet 36 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet37Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.39 integer read-write
Display and control outlet 37 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet38Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.40 integer read-write
Display and control outlet 38 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet39Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.41 integer read-write
Display and control outlet 39 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet40Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.42 integer read-write
Display and control outlet 40 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet41Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.43 integer read-write
Display and control outlet 41 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outlet42Status 1.3.6.1.4.1.21317.1.3.2.2.2.2.44 integer read-write
Display and control outlet 42 status. Can't set pending status. Enumeration: 'on': 2, 'not-support': 7, 'off': 1, 'fault': 5, 'reboot': 4, 'pop': 8, 'noauth': 6, 'pending': 3.
                                     outletSwitchableTable 1.3.6.1.4.1.21317.1.3.2.2.2.2.70 no-access
                                           outletSwitchableEntry 1.3.6.1.4.1.21317.1.3.2.2.2.2.70.1 no-access
                                               outletSwitchableIndex 1.3.6.1.4.1.21317.1.3.2.2.2.2.70.1.1 integer read-only
Index of outlet number.
                                               outletSwitchable 1.3.6.1.4.1.21317.1.3.2.2.2.2.70.1.2 integer read-only
Enumeration: 'yes': 2, 'no': 1.
                                     outletIntegerValueTable 1.3.6.1.4.1.21317.1.3.2.2.2.2.99 no-access
Display total outlet value table
                                           outletIntegerValueEntry 1.3.6.1.4.1.21317.1.3.2.2.2.2.99.1 no-access
Single outletValue entry containing outlet info.
                                               outletIntegerValueIndex 1.3.6.1.4.1.21317.1.3.2.2.2.2.99.1.1 integer read-only
Index of outlet number.
                                               outletIntegerCurrent 1.3.6.1.4.1.21317.1.3.2.2.2.2.99.1.2 integer read-only
Outlet electric current value. This value indicates that 1,000 times. If the device does not support this OID, it returns value -2000000.
                                               outletIntegerVoltage 1.3.6.1.4.1.21317.1.3.2.2.2.2.99.1.3 integer read-only
Outlet voltage value. This value indicates that 1,000 times. If the device does not support this OID, it returns value -2000000.
                                               outletIntegerPower 1.3.6.1.4.1.21317.1.3.2.2.2.2.99.1.4 integer read-only
Outlet power value. This value indicates that 1,000 times. If the device does not support this OID, it returns value -2000000.
                                               outletIntegerPowerDissipation 1.3.6.1.4.1.21317.1.3.2.2.2.2.99.1.5 integer read-only
Outlet power dissipation value. This value indicates that 1,000 times. If the device does not support this OID, it returns value -2000000.
                                 bank 1.3.6.1.4.1.21317.1.3.2.2.2.3
                                     breakerStatusTable 1.3.6.1.4.1.21317.1.3.2.2.2.3.1 no-access
Display total bank value table
                                         breakerStatusEntry 1.3.6.1.4.1.21317.1.3.2.2.2.3.1.1 no-access
Single bankValue entry containing bank info.
                                             breakerStatusIndex 1.3.6.1.4.1.21317.1.3.2.2.2.3.1.1.1 integer read-only
Index of breaker number.
                                             breakerStatus 1.3.6.1.4.1.21317.1.3.2.2.2.3.1.1.2 integer read-only
Breaker status. Enumeration: 'on': 2, 'not-support': 3, 'off': 1.
                                     bankValueTable 1.3.6.1.4.1.21317.1.3.2.2.2.3.2 no-access
Display total bank value table
                                         bankValueEntry 1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1 no-access
Single bankValue entry containing bank info.
                                             bankValueIndex 1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.1 integer read-only
Index of bank number
                                             bankCurrent 1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.2 displaystring read-only
Bank electric current value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support.
                                             bankVoltage 1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.3 displaystring read-only
Bank voltage value. We put this OID to write access type for user to set the reference voltage on EC1000 model. And the setting should be the numbers. You can set 0 to clear the setting. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support.
                                             bankPower 1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.4 displaystring read-only
Bank power value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support.
                                             bankPowerDissipation 1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.5 displaystring read-only
Bank power dissipation value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support.
                                             bankMaxCurrent 1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.6 integer read-only
The Bank Max Current value. unit: (A) EC1000:0A~320A
                                             bankAttachStatus 1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.7 integer read-only
The status of Energy sensor Bank attached status. Enumeration: 'noexisted': 4, 'noattached': 1, 'attached': 2, 'error': 3.
                                             bankPowerFactor 1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.8 displaystring read-only
Bank Power Factor value. If the device does not support this OID, it returns: not-support.
                                     bankConfigTable 1.3.6.1.4.1.21317.1.3.2.2.2.3.3 no-access
Bank configuration table
                                         bankConfigEntry 1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1 no-access
Bank Config entry containing Bank info.
                                             bankConfigIndex 1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.1 integer read-only
Index of bank number
                                             bankName 1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.2 displaystring read-write
Display or set the name of bank. When this model does not support the OID, we show n/a. string length: 0~15 NOTE: Input string as /empty to set this object to NULL.
                                             bankMinCurMT 1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.3 integer read-write
Display or set the outlet minimum electric current measurment threshold. Example: range 0.0 ~16.0 rerpresnts 0~160 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
                                             bankMaxCurMT 1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.4 integer read-write
Display or set the outlet maximum electric current measurment threshold. Example: range 0.0 ~16.0 represents 0~160 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
                                             bankMinVolMT 1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.5 integer read-write
Display or set the outlet minimum voltage measurment threshold. Example: range 90.0 ~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
                                             bankMaxVolMT 1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.6 integer read-write
Display or set the outlet maximum voltage measurment threshold. Example: range 90.0 ~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
                                             bankMinPMT 1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.7 integer read-write
Display or set the outlet minimum power measurment threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
                                             bankMaxPMT 1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.8 integer read-write
Display or set the outlet maximum power measurment threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
                                             bankMaxPDMT 1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.9 integer read-write
Display or set the outlet maximum power dissipation measurment threshold. Example: range 0.0 ~ 99999.0 represents 0~999990 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
                                     bankControlTable 1.3.6.1.4.1.21317.1.3.2.2.2.3.4 no-access
Bank Control table
                                         bankControlEntry 1.3.6.1.4.1.21317.1.3.2.2.2.3.4.1 no-access
Bank control entry.
                                             bankControlIndex 1.3.6.1.4.1.21317.1.3.2.2.2.3.4.1.1 integer read-only
Index of bank number
                                             bankControlStatus 1.3.6.1.4.1.21317.1.3.2.2.2.3.4.1.2 integer read-write
This function is used for outlet control of bank. Set off(1) to turn off for outlet control of bank. Set on(2) to turn on for all outlet control of bank. Set reboot(3) to turn on for outlet control of bank. Get this object always return nostatus(3), because there is no bank status. Enumeration: 'on': 2, 'not-support': 5, 'nostatus': 4, 'off': 1, 'reboot': 3.
                                     bankIntegerValueTable 1.3.6.1.4.1.21317.1.3.2.2.2.3.99 no-access
Display total bank value table
                                           bankIntegerValueEntry 1.3.6.1.4.1.21317.1.3.2.2.2.3.99.1 no-access
Single bankValue entry containing bank info.
                                               bankIntegerValueIndex 1.3.6.1.4.1.21317.1.3.2.2.2.3.99.1.1 integer read-only
Index of bank number.
                                               bankIntegerCurrent 1.3.6.1.4.1.21317.1.3.2.2.2.3.99.1.2 integer read-only
Bank electric current value. This value indicates that 1,000 times. If this measurement value is not available, it returns value -1000000. If the device does not support this OID, it returns value -2000000.
                                               bankIntegerVoltage 1.3.6.1.4.1.21317.1.3.2.2.2.3.99.1.3 integer read-only
Bank voltage value. This value indicates that 1,000 times. We put this OID to write access type for user to set the reference voltage on EC1000 model. And the setting should be the numbers. You can set 0 to clear the setting. If this measurement value is not available, it returns value -1000000. If the device does not support this OID, it returns value -2000000.
                                               bankIntegerPower 1.3.6.1.4.1.21317.1.3.2.2.2.3.99.1.4 integer read-only
Bank power value. This value indicates that 1,000 times. If this measurement value is not available, it returns value -1000000. If the device does not support this OID, it returns value -2000000.
                                               bankIntegerPowerDissipation 1.3.6.1.4.1.21317.1.3.2.2.2.3.99.1.5 integer read-only
Bank power dissipation value. This value indicates that 1,000 times. If this measurement value is not available, it returns value -1000000. If the device does not support this OID, it returns value -2000000.
                             deviceManagement 1.3.6.1.4.1.21317.1.3.2.2.3
                                 config 1.3.6.1.4.1.21317.1.3.2.2.3.4
                                     deviceMAC 1.3.6.1.4.1.21317.1.3.2.2.3.4.1 displaystring read-only
Display device MAC address.
                                     deviceIPv4 1.3.6.1.4.1.21317.1.3.2.2.3.4.2 ipaddress read-only
Display device IP address.
                                     deviceFWversion 1.3.6.1.4.1.21317.1.3.2.2.3.4.3 displaystring read-only
Display device FW version.
                                     dashBoard 1.3.6.1.4.1.21317.1.3.2.2.3.4.4
                                         dashboardRow 1.3.6.1.4.1.21317.1.3.2.2.3.4.4.1 integer read-write
Display or set device's dashboard row number.
                                         dashboardColumn 1.3.6.1.4.1.21317.1.3.2.2.3.4.4.2 integer read-write
Display or set device's dashboard column number.
                                         dashboardRackName 1.3.6.1.4.1.21317.1.3.2.2.3.4.4.3 displaystring read-write
Display or set device's dashboard rack name. string length: 1~32 NOTE: Input string as /empty to set this object to NULL.
                                     servicePorts 1.3.6.1.4.1.21317.1.3.2.2.3.4.5
                                         httpPort 1.3.6.1.4.1.21317.1.3.2.2.3.4.5.1 integer read-write
Display or set the HTTP port of PE device.
                                         httpsPort 1.3.6.1.4.1.21317.1.3.2.2.3.4.5.2 integer read-write
Display or set the HTTPs port of PE device.
                                         httpsOnlyEnable 1.3.6.1.4.1.21317.1.3.2.2.3.4.5.3 integer read-write
Enable to use Webpage HTTPs only or disable to use Webpage HTTP/HTTPs Enumeration: 'yes': 1, 'no': 2.
                                     ipv4config 1.3.6.1.4.1.21317.1.3.2.2.3.4.6
                                         staticIPEnabled 1.3.6.1.4.1.21317.1.3.2.2.3.4.6.1 integer read-write
Display or set IPv4 address automatically or not Enumeration: 'yes': 2, 'no': 1.
                                         fixedIPv4 1.3.6.1.4.1.21317.1.3.2.2.3.4.6.2 ipaddress read-write
Display or set fixed IPv4 address
                                         subnetMask 1.3.6.1.4.1.21317.1.3.2.2.3.4.6.3 ipaddress read-write
Display or set subnet mask address
                                         gateway 1.3.6.1.4.1.21317.1.3.2.2.3.4.6.4 ipaddress read-write
Display or set gateway address
                                         staticDNSEnabled 1.3.6.1.4.1.21317.1.3.2.2.3.4.6.5 integer read-write
Display or set DNS address automatically or not Enumeration: 'yes': 2, 'no': 1.
                                         dnsPreferIPv4 1.3.6.1.4.1.21317.1.3.2.2.3.4.6.6 ipaddress read-write
Display or set prefer DNS address
                                         dnsAlternateIPv4 1.3.6.1.4.1.21317.1.3.2.2.3.4.6.7 ipaddress read-write
Display or set alternate DNS address
                                     eventNotification 1.3.6.1.4.1.21317.1.3.2.2.3.4.7
                                         devicesnmp 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1
                                             trapEnabled 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.1 integer read-write
Indicates if this trap entry is enabled or not. You should set the username/auth-password/priv-password first, when choosing snmpv3. You should set the community string first, when choosing snmpv1/v2c. Enumeration: 'yes': 2, 'no': 1.
                                             trapVersion 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.2 integer read-write
Choose SNMP Trap version to send trap. You should set the username/auth-password/priv-password first, when choosing snmpv3. You should set the community string first, when choosing snmpv1/v2c. Enumeration: 'v2c': 2, 'v1': 1, 'v3': 3.
                                             snmpTrapTable 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3 no-access
PE SNMP agent trap setup table. If users want to use trap, they must set enable trap, ip and community first.
                                                 snmpTrapEntry 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1 no-access
Single trap entry containing trap receiver info.
                                                     trapReceiverNumber 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.1 integer read-only
Index of trap receiver
                                                     trapReceiverIPAddress 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.2 ipaddress read-write
Trap receiver IP address
                                                     trapPort 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.3 integer read-write
NMS trap port to be used by agent to send trap
                                                     trapCommunity 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.4 displaystring read-write
If use SNMPv1/v2c to receive trap should set this Community string. MAX string length: 20 NOTE: Input string as /empty to set this object to NULL.
                                                     trapUsername 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.5 displaystring read-write
If use SNMPv3 to receive trap should set this string. NOTE: Input string as /empty to set this object to NULL. MAX string length: 20
                                                     trapAuthpassword 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.6 displaystring read-write
If use SNMPv3 to receive trap should set this string. MAX string length: 20 NOTE: Input string as /empty to set this object to NULL.
                                                     trapPrivpassword 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.7 displaystring read-write
If use SNMPv3 to receive trap should set this string. MAX string length: 20 NOTE: Input string as /empty to set this object to NULL.
                                         syslog 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.2
                                             sysLogServerEnabled 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.2.1 integer read-write
Display or set syslog server address automatically or not Enumeration: 'yes': 2, 'no': 1.
                                             sysLogServerIPv4 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.2.2 ipaddress read-write
Display or set syslog server address
                                             sysLogServerPort 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.2.3 integer read-write
Display or set syslog server port
                                         smtp 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.3
                                             smtpServerEnabled 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.3.1 integer read-write
Display or set SMTP server enable status. Enumeration: 'yes': 2, 'no': 1.
                                             smtpServerName 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.3.2 displaystring read-write
Display or set a SMTP server name. NOTE: Input string as /empty to set this object to NULL.
                                             smtpAuthEnabled 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.3.3 integer read-write
Display or set authentication of SMTP server. Enumeration: 'yes': 2, 'no': 1.
                                             smtpAccountName 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.3.4 displaystring read-write
Display or set a user's name of SMTP server. NOTE: Input string as /empty to set this object to NULL.
                                             smtpAccountPwd 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.3.5 displaystring read-write
Display or set a user's password of SMTP server. NOTE: Input string as /empty to set this object to NULL.
                                             smtpMailFrom 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.3.6 displaystring read-write
Display or set a mail of SMTP server. NOTE: Input string as /empty to set this object to NULL.
                                             smtpMailTo 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.3.7 displaystring read-write
Display or set a mail of SMTP server. NOTE: Input string as /empty to set this object to NULL.
                                         configurationNotification 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.9
                                             configurationNotifyEnabled 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.9.1 integer read-write
Enumeration: 'yes': 2, 'no': 1.
                                             configurationNotifyTrapMSG 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.9.2
                                     dateTime 1.3.6.1.4.1.21317.1.3.2.2.3.4.8
                                         timeZone 1.3.6.1.4.1.21317.1.3.2.2.3.4.8.1
                                             timeZoneSetting 1.3.6.1.4.1.21317.1.3.2.2.3.4.8.1.1 integer read-write
Display or set the time zone of PE device. (0) [GMT-12:00] Eniwetok Kwajalein (1) [GMT-11:00] Midway Island Samoa (2) [GMT-10:00] Hawaii (3) [GMT-09:00] Alaska (4) [GMT-08:00] Pacific Time (US & Canada); Tijuana (5) [GMT-07:00] Mountain Time (US & Canada) (6) [GMT-07:00] Arizona (7) [GMT-06:00] Central Time (US & Canada) (8) [GMT-06:00] Mexico City (9) [GMT-06:00] Saskatchewan (10)[GMT-06:00] Central America (11)[GMT-05:00] Eastern Time (US & Canada) (12)[GMT-05:00] Indiana (East) (13)[GMT-05:00] Bogota Lima Quito (14)[GMT-04:00] Atlantic Time (Canada) (15)[GMT-04:00] Caracas La Paz (16)[GMT-04:00] Santiago (17)[GMT-03:30] Newfoundland (18)[GMT-03:00] Buenos Aires Georgetown (19)[GMT-03:00] Brasilia (20)[GMT-03:00] Greenland (21)[GMT-02:00] Mid-Atlantic (22)[GMT-01:00] Azores (23)[GMT-01:00] Cape Verde Is (24)[GMT] Casablanca Monrovia (25)[GMT] Greenwich Mean Time: Dublin Edinburgh Lisbon London (26)[GMT+01:00] Amsterdam Copenhagen Madrid Paris Vilnius (27)[GMT+01:00] West Central Africa (28)[GMT+01:00] Belgrade Sarajevo Skopje Sofija Zagreb (29)[GMT+01:00] Bratislava Budapest Ljubljana Prague Warsaw (30)[GMT+01:00] Brussels Berlin Bern Rome Stockholm Vienna (31)[GMT+02:00] Cairo (32)[GMT+02:00] Harare Pretoria (33)[GMT+02:00] Jerusalem (34)[GMT+02:00] Bucharest (35)[GMT+02:00] Helsinki Riga Tallinn (36)[GMT+02:00] Athens Istanbul Minsk (37)[GMT+03:00] Kuwait Riyadh (38)[GMT+03:00] Nairobi (39)[GMT+03:00] Baghdad (40)[GMT+03:00] Moscow St. Petersburg Volgograd (41)[GMT+03:30] Tehran (42)[GMT+04:00] Abu Dhabi Muscat (43)[GMT+04:00] Baku Tbilisi Yerevan (44)[GMT+04:30] Kabul (45)[GMT+05:00] Islamabad Karachi Tashkent (46)[GMT+05:00] Ekaterinburg (47)[GMT+05:30] Calcutta Chennai Mumbai New Delhi (48)[GMT+05:45] Kathmandu (49)[GMT+06:00] Astana Dhaka (50)[GMT+06:00] Sri Jayawardenepura (51)[GMT+06:00] Almaty Novosibirsk (52)[GMT+06:30] Rangoon (53)[GMT+07:00] Bangkok Hanoi Jakarta (54)[GMT+07:00] Krasnoyarsk (55)[GMT+08:00] Beijing Chongqing Hong Kong Urumqi (56)[GMT+08:00] Perth (57)[GMT+08:00] Kuala Lumpur Singapore (58)[GMT+08:00] Taipei (59)[GMT+08:00] Irkutsk Ulaan Bataar (60)[GMT+09:00] Osaka Sapporo Tokyo (61)[GMT+09:00] Seoul (62)[GMT+09:00] Yakutsk (63)[GMT+09:30] Darwin (64)[GMT+09:30] Adelaide (65)[GMT+10:00] Canberra Melbourne Sydney (66)[GMT+10:00] Brisbane (67)[GMT+10:00] Guam Port Moresby (68)[GMT+10:00] Hobart (69)[GMT+10:00] Vladivostok (70)[GMT+11:00] Magadan Solomon Is New Caledonia (71)[GMT+12:00] Fiji Kamchatka Marshall Is. (72)[GMT+12:00] Auckland Wellington (73)[GMT+13:00] Nuku'alofa
                                             dstEnabled 1.3.6.1.4.1.21317.1.3.2.2.3.4.8.1.2 integer read-write
Display or set daylight savings time . Enumeration: 'yes': 2, 'no': 1.
                                         manualInput 1.3.6.1.4.1.21317.1.3.2.2.3.4.8.2
                                             dateSetting 1.3.6.1.4.1.21317.1.3.2.2.3.4.8.2.1 displaystring read-write
Display or set date in a manual way.(This is Greenwich Mean Time, GMT) string length: 10 This value format must match the following form: YYYY-MM-DD ex. 2011-01-01 Note: range of year: 2000-2099 range of month: 01-12 range of day: 01-31
                                             timeSetting 1.3.6.1.4.1.21317.1.3.2.2.3.4.8.2.2 displaystring read-write
Display or set time in a manual way.(This is Greenwich Mean Time, GMT) string length: 8 This value format must match the following form: HH:MM:SS ex. 02:02:02 Note: range of hour: 00-24 range of minute: 00-60 range of second: 00-60
                                         networkTime 1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3
                                             autoAdjustEnabled 1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.1 integer read-write
Display or set date time useing auto adjustment way. Enumeration: 'yes': 2, 'no': 1.
                                             preferNTP 1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.2 integer read-write
Display or set prefer NTP server. AU | ntp1.cs.mu.OZ.AU(0), AU | ntp0.cs.mu.OZ.AU(1), BE | ntp2.oma.be(2), BE | ntp1.oma.be(3), BR | ntps1.pads.ufrj.br(4), CH | swisstime.ethz.ch(5), CL | ntp.shoa.cl(6), CZ | ntp.nic.cz(7), DE | ntp.stairweb.de(8), DE | ntps1-0.cs.tu-berlin.de(9), DE | ptbtime1.ptb.de(10), DE | ntp1.fau.de(11), DE | ptbtime2.ptb.de(12), DE | time1.one4vision.de(13), DE | rustime01.rus.uni-stuttgart.de(14), DE | ntp.probe-networks.de(15), DE | ntp2.fau.de(16), ES | hora.roa.es(17), HK | stdtime.gov.hk(18), IE | ntp-galway.hea.net(19), IT | ntp1.inrim.it(20), IT | ntp2.inrim.it(21), JP | clock.tl.fukuoka-u.ac.jp(22), JP | ntp.nict.jp(23), JP | clock.nc.fukuoka-u.ac.jp(24), KR | ntp.xbsd.kr(25), MX | cronos.cenam.mx(26), NL | ntp0.nl.uu.net(27), NL | ntp1.nl.uu.net(28), NL | ntp.remco.org(29), NL | ntp0.nl.net(30), PL | vega.cbk.poznan.pl(31), PL | ntp.ntp-servers.com(32), RO | ntp3.usv.ro(33), RO | ntp2.usv.ro(34), RU | ntp1.vniiftri.ru; ntp1.imvp.ru(35), RU | ntp2.vniiftri.ru; ntp2.imvp.ru(36), SE | ntp1.mmo.netnod.se(37), SE | ntp1.sth.netnod.se(38), SE | ntp2.mmo.netnod.se(39), SE | ntp2.sth.netnod.se(40), SE | time2.stupi.se(41), SE | ntp1.sp.se(42), SE | timehost.lysator.liu.se(43), SI | ntp.mostovna.com(44), US CA | timekeeper.isi.edu(45), US CA | clock.sjc.he.net(46), US CA | nist1.symmetricom.com(47), US CA | clock.via.net(48), US CA | nist1.aol-ca.truetime.com(49), US CA | clock.isc.org(50), US CA | clepsydra.dec.com(51), US CA | gps.layer42.net(52), US CA | time.no-such-agency.net(53), US CA | nist1-sj.WiTime.net(54), US CA | clock.fmt.he.net(55), US CO | time-b.timefreq.bldrdoc.gov(56), US CO | time-a.timefreq.bldrdoc.gov(57), US CO | utcnist.colorado.edu(58), US CO | time-c.timefreq.bldrdoc.gov(59), US DE | rackety.udel.edu(60), US DE | mizbeaver.udel.edu(61), US GA | nist1.columbiacountyga.gov(62), US IL | ntp.your.org(63), US MA | bonehed.lcs.mit.edu(64), US MA | time.keneli.org(65), US MA | ntp0.broad.mit.edu(66), US MD | time-a.nist.gov(67), US MD | time-b.nist.gov(68), US MI | nist.netservicesgroup.com(69), US NY | nist1-ny.WiTime.net(70), US NY | clock.nyc.he.net(71), US UT | time.xmission.com(72), US VA | nist1-dc.WiTime.net(73), US VA | nist1.aol-va.truetime.com(74), US WA | time-nw.nist.gov(75), FR | utp.univ-lyon1.fr(76), FR | ntp-sop.inria.fr(77), FR | ntp.tuxfamily.net(78), UK | bear.zoo.bt.co.uk(79)
                                             preferServerIPenable 1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.3 integer read-write
Enable or disable prefer custom server IP. Enumeration: 'yes': 2, 'no': 1.
                                             preferNTPIp 1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.4 ipaddress read-write
Display or set prefer NTP server IP.
                                             alternateNtpEnabled 1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.5 integer read-write
Display or set date time using alternate NTP server. Enumeration: 'yes': 2, 'no': 1.
                                             alternateNtp 1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.6 integer read-write
Display or set alternative NTP server. AU | ntp1.cs.mu.OZ.AU(0), AU | ntp0.cs.mu.OZ.AU(1), BE | ntp2.oma.be(2), BE | ntp1.oma.be(3), BR | ntps1.pads.ufrj.br(4), CH | swisstime.ethz.ch(5), CL | ntp.shoa.cl(6), CZ | ntp.nic.cz(7), DE | ntp.stairweb.de(8), DE | ntps1-0.cs.tu-berlin.de(9), DE | ptbtime1.ptb.de(10), DE | ntp1.fau.de(11), DE | ptbtime2.ptb.de(12), DE | time1.one4vision.de(13), DE | rustime01.rus.uni-stuttgart.de(14), DE | ntp.probe-networks.de(15), DE | ntp2.fau.de(16), ES | hora.roa.es(17), HK | stdtime.gov.hk(18), IE | ntp-galway.hea.net(19), IT | ntp1.inrim.it(20), IT | ntp2.inrim.it(21), JP | clock.tl.fukuoka-u.ac.jp(22), JP | ntp.nict.jp(23), JP | clock.nc.fukuoka-u.ac.jp(24), KR | ntp.xbsd.kr(25), MX | cronos.cenam.mx(26), NL | ntp0.nl.uu.net(27), NL | ntp1.nl.uu.net(28), NL | ntp.remco.org(29), NL | ntp0.nl.net(30), PL | vega.cbk.poznan.pl(31), PL | ntp.ntp-servers.com(32), RO | ntp3.usv.ro(33), RO | ntp2.usv.ro(34), RU | ntp1.vniiftri.ru; ntp1.imvp.ru(35), RU | ntp2.vniiftri.ru; ntp2.imvp.ru(36), SE | ntp1.mmo.netnod.se(37), SE | ntp1.sth.netnod.se(38), SE | ntp2.mmo.netnod.se(39), SE | ntp2.sth.netnod.se(40), SE | time2.stupi.se(41), SE | ntp1.sp.se(42), SE | timehost.lysator.liu.se(43), SI | ntp.mostovna.com(44), US CA | timekeeper.isi.edu(45), US CA | clock.sjc.he.net(46), US CA | nist1.symmetricom.com(47), US CA | clock.via.net(48), US CA | nist1.aol-ca.truetime.com(49), US CA | clock.isc.org(50), US CA | clepsydra.dec.com(51), US CA | gps.layer42.net(52), US CA | time.no-such-agency.net(53), US CA | nist1-sj.WiTime.net(54), US CA | clock.fmt.he.net(55), US CO | time-b.timefreq.bldrdoc.gov(56), US CO | time-a.timefreq.bldrdoc.gov(57), US CO | utcnist.colorado.edu(58), US CO | time-c.timefreq.bldrdoc.gov(59), US DE | rackety.udel.edu(60), US DE | mizbeaver.udel.edu(61), US GA | nist1.columbiacountyga.gov(62), US IL | ntp.your.org(63), US MA | bonehed.lcs.mit.edu(64), US MA | time.keneli.org(65), US MA | ntp0.broad.mit.edu(66), US MD | time-a.nist.gov(67), US MD | time-b.nist.gov(68), US MI | nist.netservicesgroup.com(69), US NY | nist1-ny.WiTime.net(70), US NY | clock.nyc.he.net(71), US UT | time.xmission.com(72), US VA | nist1-dc.WiTime.net(73), US VA | nist1.aol-va.truetime.com(74), US WA | time-nw.nist.gov(75), FR | utp.univ-lyon1.fr(76), FR | ntp-sop.inria.fr(77), FR | ntp.tuxfamily.net(78), UK | bear.zoo.bt.co.uk(79)
                                             alternateServerIPenable 1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.7 integer read-write
Enable or disable alternate custom server IP. Enumeration: 'yes': 2, 'no': 1.
                                             alternateNtpIp 1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.8 ipaddress read-write
Display or set alternative NTP server IP.
                                             adjustTimeEveryDays 1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.9 integer read-write
Display or set frequency of adjustment in days.
                                 devicesecurity 1.3.6.1.4.1.21317.1.3.2.2.3.5
                                     loginFailures 1.3.6.1.4.1.21317.1.3.2.2.3.5.1
                                         loginAllowTimes 1.3.6.1.4.1.21317.1.3.2.2.3.5.1.1 integer read-write
Display or set time of login faliure.
                                         loginTimeOut 1.3.6.1.4.1.21317.1.3.2.2.3.5.1.2 integer read-write
Display or set login time out.
                                     workingMode 1.3.6.1.4.1.21317.1.3.2.2.3.5.2
                                         icmpEnabled 1.3.6.1.4.1.21317.1.3.2.2.3.5.2.1 integer read-write
Display or set status of ICMP. Enumeration: 'yes': 2, 'no': 1.
                                     accountPolicy 1.3.6.1.4.1.21317.1.3.2.2.3.5.3
                                         minUserNameLen 1.3.6.1.4.1.21317.1.3.2.2.3.5.3.1 integer read-write
Display or set minimum length of user name.
                                         minUserPwdLen 1.3.6.1.4.1.21317.1.3.2.2.3.5.3.2 integer read-write
Display or set minimum length of user password.
                                         upperCaseEnabled 1.3.6.1.4.1.21317.1.3.2.2.3.5.3.3 integer read-write
Display or set one upper case rule in user password. Enumeration: 'yes': 2, 'no': 1.
                                         lowerCaseEnabled 1.3.6.1.4.1.21317.1.3.2.2.3.5.3.4 integer read-write
Display or set one lower case rule in user password. Enumeration: 'yes': 2, 'no': 1.
                                         numberEnabled 1.3.6.1.4.1.21317.1.3.2.2.3.5.3.5 integer read-write
Display or set one number rule in user password. Enumeration: 'yes': 2, 'no': 1.
                                         disableDuplicateLogin 1.3.6.1.4.1.21317.1.3.2.2.3.5.3.6 integer read-write
Display or set status of disabled duplicate login rule. Enumeration: 'yes': 2, 'no': 1.
                                     loginRestriction 1.3.6.1.4.1.21317.1.3.2.2.3.5.4
                                         loginString 1.3.6.1.4.1.21317.1.3.2.2.3.5.4.1 displaystring read-write
Display or set a login string. string length: 0~32 NOTE: Input string as /empty to set this object to NULL.
                                         ipFilter 1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2
                                             ipFilterEnabled 1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.1 integer read-write
Display or set status of ip filter. Enumeration: 'yes': 2, 'no': 1.
                                             ipFilterRule 1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.2 integer read-write
Display or set status of ip filter rule. Enumeration: 'exclude': 2, 'include': 1.
                                             ipFilterTable 1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.3 no-access
A list of restricted ip.
                                                 ipFilterEntry 1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.3.1 no-access
Status and parameter values for a PE's restricted IP.
                                                     ipFilterIndex 1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.3.1.1 integer read-only
The value of index for the ip filter.
                                                     ipFilterFrom 1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.3.1.2 ipaddress read-write
A set of restricted ip. ex. 192.168.0.1 Note: Users must follow in order to set the ip address. Note: To clear the settings to set the ip 0.0.0.0
                                                     ipFilterTo 1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.3.1.3 ipaddress read-write
A set of restricted ip. ex. 192.168.0.255 Note: Users must follow in order to set the ip address. Note: To clear the settings to set the ip 0.0.0.0
                                         macFilter 1.3.6.1.4.1.21317.1.3.2.2.3.5.4.3
                                             macFilterEnabled 1.3.6.1.4.1.21317.1.3.2.2.3.5.4.3.1 integer read-write
Display or set status of mac filter. Enumeration: 'yes': 2, 'no': 1.
                                             macFilterRule 1.3.6.1.4.1.21317.1.3.2.2.3.5.4.3.2 integer read-write
Display or set status of mac filter rule. Enumeration: 'exclude': 2, 'include': 1.
                                             macFilterTable 1.3.6.1.4.1.21317.1.3.2.2.3.5.4.3.3 no-access
A list of restricted mac.
                                                 macFilterEntry 1.3.6.1.4.1.21317.1.3.2.2.3.5.4.3.3.1 no-access
Status and parameter values for a PE's restricted MAC.
                                                     macFilterIndex 1.3.6.1.4.1.21317.1.3.2.2.3.5.4.3.3.1.1 integer read-only
The value of index for the mac filter.
                                                     macFilterSet 1.3.6.1.4.1.21317.1.3.2.2.3.5.4.3.3.1.2 displaystring read-write
A set of restricted mac. string length: 12 ex. 004854655511 Note: Users must follow in order to set the MAC address. Note: To clear the settings to set the MAC 000000000000
                                     authentication 1.3.6.1.4.1.21317.1.3.2.2.3.5.5
                                         radius 1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1
                                             radiusEnabled 1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1.1 integer read-write
Display or set status of RADIUS server. Enumeration: 'yes': 2, 'no': 1.
                                             preferRadiusIp 1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1.2 ipaddress read-write
Display or set prefer RADIUS server IP.
                                             preferRadiusPort 1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1.3 integer read-write
Display or set prefer RADIUS server port.
                                             alternateRadiusIp 1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1.4 ipaddress read-write
Display or set alternative RADIUS server IP.
                                             alternateRadiusPort 1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1.5 integer read-write
Display or set alternative RADIUS server port.
                                             radiusTimeOut 1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1.6 integer read-write
Display or set time out of authentication using RADIUS server. The unit is sec.
                                             radiusRetry 1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1.7 integer read-write
Display or set retry times of authentication using RADIUS server.
                                             radiusSecret 1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1.8 displaystring read-write
Display or set shared secret of RADIUS server. string length: 6~15 At least 6 characters. NOTE: Input string as /empty to set this object to NULL.
                             customTrapMSG 1.3.6.1.4.1.21317.1.3.2.2.5
Display custom trap message.
                             rebootDevice 1.3.6.1.4.1.21317.1.3.2.2.6 integer read-write
Reboot PE Device Enumeration: 'yes': 2, 'no': 1.