APNL-MODULAR-PDU-MIB: View SNMP OID List / Download MIB

VENDOR: AP NEDERLAND BV


 Home MIB: APNL-MODULAR-PDU-MIB
Download as:   

Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 apNederland 1.3.6.1.4.1.29640
This MIB module defines the modular PDU version of AP Nederland.
             apnlDirectory 1.3.6.1.4.1.29640.1
             apnlMib 1.3.6.1.4.1.29640.2
             apnlTmp 1.3.6.1.4.1.29640.3
             apnlModules 1.3.6.1.4.1.29640.4
                 cm 1.3.6.1.4.1.29640.4.1
                 cmTraps 1.3.6.1.4.1.29640.4.2
                 pdu 1.3.6.1.4.1.29640.4.3
                     pduType 1.3.6.1.4.1.29640.4.3.1 integer read-only
Type of the Pdu. PduModular (0) Modulaire OEC2 PDU communication through SNMPV3, MOD-BUS or AP-BUS in emulation mode. PduGateway1 (1) Gateway to connect OEC1 products with external AP-BUS protocol to OEC2 Manager (SNMPV3). PduGateway2 (2) Gateway to connect OEC2 products with external MOD-BUS to OEC Manager (SNMPV3). Enumeration: 'pduGateway1': 1, 'pduGateway2': 2, 'pduModular': 0.
                     pduProductIdentifier 1.3.6.1.4.1.29640.4.3.2 integer32 read-only
Unique serial number to identify a pdu, the number is between 1 and 65535.
                     pduSerialNumber 1.3.6.1.4.1.29640.4.3.3 displaystring read-only
PDU onboard Serial Number.
                     pduStatus 1.3.6.1.4.1.29640.4.3.4 integer read-only
Status of the Pdu. pduBusy (0) Indicates that an admin command is in progress. pduReady (1) The execution of an admin command was successfull. pduAlarm (2) This state is not in use. pduError (3) The execution of an admin command failed. Enumeration: 'pduAlarm': 2, 'pduError': 3, 'pduReady1': 1, 'pduBusy': 0.
                     pduPower 1.3.6.1.4.1.29640.4.3.5 unsigned32 read-only
The total measured pdu power in Kilo Watt's*Hour.
                     pduPowerL1 1.3.6.1.4.1.29640.4.3.6 unsigned32 read-only
The total measured pdu power in Kilo Watt's*Hour for phase 1.
                     pduPowerL2 1.3.6.1.4.1.29640.4.3.7 unsigned32 read-only
The total measured pdu power in Kilo Watt's*Hour for phase 2.
                     pduPowerL3 1.3.6.1.4.1.29640.4.3.8 unsigned32 read-only
The total measured pdu power in Kilo Watt's*Hour for phase 3.
                     pduKvar 1.3.6.1.4.1.29640.4.3.9 unsigned32 read-only
The total Reactive Power of the pdu. It is the power that magnetic equipment (transformer, motor and relay) needs to produce the magnetizing flux.
                     pduKvarL1 1.3.6.1.4.1.29640.4.3.10 unsigned32 read-only
The total Reactive Power of the pdu for phase 1. It is the power that magnetic equipment (transformer, motor and relay) needs to produce the magnetizing flux.
                     pduKvarL2 1.3.6.1.4.1.29640.4.3.11 unsigned32 read-only
The total Reactive Power of the pdu for phase 2. It is the power that magnetic equipment (transformer, motor and relay) needs to produce the magnetizing flux.
                     pduKvarL3 1.3.6.1.4.1.29640.4.3.12 unsigned32 read-only
The total Reactive Power of the pdu for phase 3. It is the power that magnetic equipment (transformer, motor and relay) needs to produce the magnetizing flux.
                     pdulAcurrent 1.3.6.1.4.1.29640.4.3.13 unsigned32 read-only
The total measured ac current for the pdu (in 1/10th Amperes) .
                     pduAcurrentL1 1.3.6.1.4.1.29640.4.3.14 unsigned32 read-only
The total measured ac current for phase 1 (in 1/10th Amperes).
                     pduAcurrentL2 1.3.6.1.4.1.29640.4.3.15 unsigned32 read-only
The total measured ac current for phase 2 (in 1/10th Amperes).
                     pduAcurrentL3 1.3.6.1.4.1.29640.4.3.16 unsigned32 read-only
The total measured ac current for phase 3 (in 1/10th Amperes).
                     pduCurIpAddress 1.3.6.1.4.1.29640.4.3.17 ipaddress read-only
The current PDU IPv4 Address by which TCP/IP access is available.
                     pduCurSubNetMask 1.3.6.1.4.1.29640.4.3.18 ipaddress read-only
The current PDU IPv4 Subnet Mask used by the Ipstack (e.g: 255.255.255.0).
                     pduCurDefGwAddress 1.3.6.1.4.1.29640.4.3.19 ipaddress read-only
The current PDU IPv4 default gateway address used by the Ipstack (e.g: 192.168.1.1).
                     pduNumberOfNodes 1.3.6.1.4.1.29640.4.3.20 integer32 read-only
Number of items in the node table.
                     pduNumberOfSensors 1.3.6.1.4.1.29640.4.3.21 integer32 read-only
Number of items in the sensor table.
                     pduSoftwareVersion 1.3.6.1.4.1.29640.4.3.22 displaystring read-only
PDU software version number.
                     pduFirmwareVersion 1.3.6.1.4.1.29640.4.3.23 displaystring read-only
PDU firmware version number.
                     pduBusProtocol 1.3.6.1.4.1.29640.4.3.24 integer read-only
Selected protocol used on the external bus of the pdu. AP-BUS (0) Protocol used by OEC1 products or by OEC2 products in emulation mode. MOD-BUS (1) Protocol used by OEC2 products. Enumeration: 'modbus': 1, 'apbus': 0.
                     pduAdminCommand 1.3.6.1.4.1.29640.4.3.25 integer read-write
PDU admin management Commands: noOp (0) No operation. rebootPdu (1) Reboot the PDU (to execute new settings). rediscover (2) Not supported. updateSofware (3) Not supported. resetConfig (4) Node and group tables will be cleared . resetSNMPv3Config (5) Not supported. resetNetworkSetting (6) Reset network params: ip address, defualt gatewy, subnet mask. readDataFromBusPdu (7) Read data from a PDU connected to the external bus (address is set in pduBusAddress). writeDataToBusPdu (8) With this command modified data is writen back to the bus PDU (address is set in pduBusAddress). Enumeration: 'readDataFromBusPd': 7, 'resetConfig': 4, 'writeDataToBusPd': 8, 'updateSofware': 3, 'resetNetworkSetting': 6, 'resetSNMPv3Config': 5, 'noOp': 0, 'rebootPd': 1, 'rediscover': 2.
                     pduStartupIpAddress 1.3.6.1.4.1.29640.4.3.26 ipaddress read-write
Not supported.
                     pduStartupSubNetMask 1.3.6.1.4.1.29640.4.3.27 ipaddress read-write
Not supported.
                     pduStartupDefGwAddress 1.3.6.1.4.1.29640.4.3.28 ipaddress read-write
Not supported.
                     pduRealTimeClock 1.3.6.1.4.1.29640.4.3.29 dateandtime read-write
PDU Real-Time Clock. Maybe set by the manager.
                     pduEnableFeatures 1.3.6.1.4.1.29640.4.3.30 bits read-write
Array of bits each one an specific feature within the pdu: globalWebEnabled (0) This bit enables the PDU webpages. globalUsbEnabled (1) This bit enables the USB menu. globalSwitchEnabled (2) This bit enables switching in general. displaySwitchEnabled (3) This bit enables switching through the presentation module. webSwitchEnabled (4) This bit enables switching throuhg the web inteface. Bits: 'globalUsbEnabled': 1, 'globalWebEnabled': 0, 'displaySwitchEnabled': 3, 'webSwitchEnabled': 4, 'globalSwitchEnabled': 2.
                     pduBusAddress 1.3.6.1.4.1.29640.4.3.31 integer32 read-write
Address used to access this PDU via the external bus. When MOD-BUS protocol is used the address is valid between 1-247. When AP-BUS protocol is used the address is valid between 1-65535.
                     pduName 1.3.6.1.4.1.29640.4.3.32 displaystring read-write
Name of the PDU.
                     nodeTable 1.3.6.1.4.1.29640.4.3.33 no-access
A table of the modules on the PDU. Each entry represents an module unit.
                           nodeEntry 1.3.6.1.4.1.29640.4.3.33.1 no-access
An port entry in the port table.
                               nodeIndex 1.3.6.1.4.1.29640.4.3.33.1.1 unsigned32 no-access
The node table Index.
                               nodeType 1.3.6.1.4.1.29640.4.3.33.1.2 integer read-only
Type of the node. TypeUnknown (0) Unknown node. TypePresModChar (1) PM LCD Character Module. TypePresModMono (2) PM Mono Graphics Module. TypePresModGraph (3) PM Color Graphics Module. TypePowerMeter (4) Power meter. TypePowerMeterSwitch (5) Switchable power meter. TypeSwitch (6) Switch only. Enumeration: 'typePresModChar': 1, 'typeSwitch': 6, 'typePowerMeter': 4, 'typeUnknown': 0, 'typePresModMono': 2, 'typePresModGraph': 3, 'typePowerMeterSwitch': 5.
                               nodeOutlet 1.3.6.1.4.1.29640.4.3.33.1.3 unsigned32 read-only
The number associated with the physical outlet of the node. The special value of 0 indicates that this entry is not associated with a physical port.
                               nodeAlarmStatus 1.3.6.1.4.1.29640.4.3.33.1.4 bits read-only
Array of bits each one indicates an alarm activated in the alarm selector value. TrapCurrHi (0) The current is to high against the high current threshold. TrapCurrLo (1) The current is to low against the low current threshold. TrapVoltHi (2) The voltage is to high against the high voltage threshold. TrapVoltLo (3) The volage is to low against the low voltage threshold. SwitchOn (4) The switch is on against the switch on bitfield. SwitchOff (5) The switch is off against the switch off bitfield. Bits: 'trapVoltHi': 2, 'trapCurrLo': 1, 'trapVoltLo': 3, 'switchOff': 5, 'trapCurrHi': 0, 'switchOn': 4.
                               nodePower 1.3.6.1.4.1.29640.4.3.33.1.5 unsigned32 read-only
The measured node power in Kilo Watt's*Hour.
                               nodeAcurrent 1.3.6.1.4.1.29640.4.3.33.1.6 unsigned32 read-only
The measured ac current at the node (in 1/10th Amperes).
                               nodePeakCurrent 1.3.6.1.4.1.29640.4.3.33.1.7 unsigned32 read-only
The measured max current since last reset of the node (in 1/10th Amperes).
                               nodeVoltage 1.3.6.1.4.1.29640.4.3.33.1.8 unsigned32 read-only
The measured voltage on the node.
                               nodeMinVoltage 1.3.6.1.4.1.29640.4.3.33.1.9 unsigned32 read-only
The measured minimum voltage at the node since last reset.
                               nodeKvar 1.3.6.1.4.1.29640.4.3.33.1.10 unsigned32 read-only
The Reactive Power. It is the power that magnetic equipment (transformer, motor and relay) needs to produce the magnetizing flux.
                               nodeFrequency 1.3.6.1.4.1.29640.4.3.33.1.11 unsigned32 read-only
The frequency of alternating current in Hertz. e.g 50 in Europe or 60 in USA.
                               nodePowerFactor 1.3.6.1.4.1.29640.4.3.33.1.12 unsigned32 read-only
The effective power facton (Cosinus Phi) in percents of the node.
                               nodeSwitchOperStatus 1.3.6.1.4.1.29640.4.3.33.1.13 integer read-only
The actual operational Status of the node. Unknown (0) not known status. Off (1) switch is off. On (2) switch is on. Enumeration: 'unknown': 0, 'off': 1, 'on': 2.
                               nodeSwitchAdminStatus 1.3.6.1.4.1.29640.4.3.33.1.14 integer read-write
The desired admin Status of the switch. Unknown (0) not known. Off (1) switch is off. On (2) switch is on. Enumeration: 'unknown': 0, 'off': 1, 'on': 2.
                               nodeCurrHiThresh 1.3.6.1.4.1.29640.4.3.33.1.15 unsigned32 read-write
The current high threshold (in 1/10th Amperes).
                               nodeCurrLoThresh 1.3.6.1.4.1.29640.4.3.33.1.16 unsigned32 read-write
The current low threshold (in 1/10th Amperes).
                               nodeVoltHiThresh 1.3.6.1.4.1.29640.4.3.33.1.17 unsigned32 read-write
The voltage high threshold.
                               nodeVoltLoThresh 1.3.6.1.4.1.29640.4.3.33.1.18 unsigned32 read-write
The voltage low threshold.
                               nodeAlarmSelector 1.3.6.1.4.1.29640.4.3.33.1.19 bits read-write
Array of bits each one controls one alarm. TrapCurrHi (0) Enable/disable the high current alarm. TrapCurrLo (1) Enable/disable the low current alarm. TrapVoltHi (2) Enable/disable the high voltage alarm. TrapVoltLo (3) Enable/disable the low voltage alarm. SwitchOn (4) Enable/disable the specific switch on alarm. SwitchOff (5) Enable/disable the specific switch off alarm. Bits: 'trapVoltHi': 2, 'trapCurrLo': 1, 'trapVoltLo': 3, 'switchOff': 5, 'trapCurrHi': 0, 'switchOn': 4.
                               nodeName 1.3.6.1.4.1.29640.4.3.33.1.20 displaystring read-write
The node name. My be set by manager.
                               nodePhase 1.3.6.1.4.1.29640.4.3.33.1.21 integer read-write
The measured phase of the node. Maybe assigned when not configured in production. PhaseUnknown (0). PhaseL1 (1). PhaseL2 (2). PhaseL3 (3). Enumeration: 'phaseUnknown': 0, 'phaseL2': 2, 'phaseL3': 3, 'phaseL1': 1.
                     sensorTable 1.3.6.1.4.1.29640.4.3.34 no-access
A table of the Sensors on the PDU. Each entry represents an an Sensor unit.
                           sensorEntry 1.3.6.1.4.1.29640.4.3.34.1 no-access
An Sensor Entry in the Sensor table
                               sensorIndex 1.3.6.1.4.1.29640.4.3.34.1.1 unsigned32 no-access
The Sensor table Index.
                               sensorType 1.3.6.1.4.1.29640.4.3.34.1.2 integer read-only
Sensor Typ: Measured values are used according to sensor type. Other (0) unknown sensor type. Temperature (1) . Humidity (2). Smoke (3). CO1 (4). Vibration (5). Doorstatus (6). Enumeration: 'co1': 4, 'temperature': 1, 'vibration': 5, 'doorStatus': 6, 'humidity': 2, 'other': 0, 'smoke': 3.
                               sensorAlarmStatus 1.3.6.1.4.1.29640.4.3.34.1.3 bits read-only
Array of bits each one indicates an alarm activated in the alarm selector value. Bits: 'beeperHi': 4, 'beeperLo': 5, 'switchOff': 3, 'trapLo': 1, 'trapHi': 0, 'switchOn': 2.
                               sensorValue 1.3.6.1.4.1.29640.4.3.34.1.4 integer32 read-only
The measured value of the sensor, units are depending on sensor type.
                               sensorSwitchOperStatus 1.3.6.1.4.1.29640.4.3.34.1.5 integer read-only
The actual operational Status of the switch. Enumeration: 'unknown': 0, 'off': 1, 'on': 2.
                               sensorSwitchAdminStatus 1.3.6.1.4.1.29640.4.3.34.1.6 integer read-write
The desired admin Status of the switch. Enumeration: 'unknown': 0, 'off': 1, 'on': 2.
                               sensorHiThresh 1.3.6.1.4.1.29640.4.3.34.1.7 integer32 read-write
High threshold.
                               sensorLoThresh 1.3.6.1.4.1.29640.4.3.34.1.8 integer32 read-write
Low threshold.
                               sensorAlarmSelector 1.3.6.1.4.1.29640.4.3.34.1.9 bits read-write
Array of bits each one controls one alarm. E.g trap, beeper etc. Bits: 'beeperHi': 4, 'beeperLo': 5, 'switchOff': 3, 'trapLo': 1, 'trapHi': 0, 'switchOn': 2.
                               sensorName 1.3.6.1.4.1.29640.4.3.34.1.10 displaystring read-write
The sensor name. May be set by the manager.
                 pduTraps 1.3.6.1.4.1.29640.4.4
                     trapType 1.3.6.1.4.1.29640.4.4.1 integer no-access
An enumation value to indicate an Alarm trap: pduPduAlarm. Enumeration: 'currentHiAlarm': 2, 'switchOffAlarm': 9, 'currentLoAlarm': 3, 'blackBoxColdTrap': 11, 'tempHiAlarm': 4, 'powerHiAlarm': 10, 'voltageLoAlarm': 1, 'humidityHiAlarm': 6, 'switchOnAlarm': 8, 'humidityLoAlarm': 7, 'tempLoAlarm': 5, 'voltageHiAlarm': 0.
                     pduTableType 1.3.6.1.4.1.29640.4.4.2 integer no-access
The table type. Enumeration: 'pduSensorTable': 1, 'pduNodeTable': 0.
                     trapTableIndex 1.3.6.1.4.1.29640.4.4.3 integer32 no-access
The index of the table entry for which the trap is issued.
                     trapThreshHoldType 1.3.6.1.4.1.29640.4.4.4 integer no-access
The threshold type for which the trap is made. Enumeration: 'trapThresholdHi': 1, 'trapThresholdLo': 2, 'trapThresholdOther': 0.
                     trapThreshHold 1.3.6.1.4.1.29640.4.4.5 integer32 no-access
The threshold reference value.
                     pduVoltageAlarm 1.3.6.1.4.1.29640.4.4.6
Voltage alarm.
                     pduCurrentAlarm 1.3.6.1.4.1.29640.4.4.7
Current alaram.
                     pduPowerAlarm 1.3.6.1.4.1.29640.4.4.8
Power alarm.
                     sensorAlarm 1.3.6.1.4.1.29640.4.4.9
Sensor Alarm: Temperature, Humidity or another type. The sensorType indicates the type of alarm. The sensorValue indicate the measured value.
                     pduSwitchAlarm 1.3.6.1.4.1.29640.4.4.10
Not supported.
             apnlTest 1.3.6.1.4.1.29640.5
             apnlDemo 1.3.6.1.4.1.29640.6
             apnlMIBConformance 1.3.6.1.4.1.29640.7