ALGPOWER-v2-MIB: View SNMP OID List / Download MIB
VENDOR: ALGCOM
Home | MIB: ALGPOWER-v2-MIB | |||
---|---|---|---|---|
Download as: |
Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
|
|||
Object Name | OID | Type | Access | Info |
algcom | 1.3.6.1.4.1.49136 | |||
upsObjects | 1.3.6.1.4.1.49136.1 | |||
output | 1.3.6.1.4.1.49136.1.1 | |||
outputVoltage | 1.3.6.1.4.1.49136.1.1.1 | integer | read-only |
Numeric value of instantaneous output voltage from the source in tenths of a volt. To get the value actual in volt should be divided by 10. Example: Read value 241, actual value 24.1V. |
outputCurrent | 1.3.6.1.4.1.49136.1.1.2 | integer | read-only |
Numeric value of current output of converter AC/DC. Real value reading in milli ampere. Example: Read value 1087, Actual value 1.087 milli ampere or 1.087A. If the output is '0' the AC/DC is off and the output for the equipments is provide from batteries |
oidNotUsed0 | 1.3.6.1.4.1.49136.1.1.3 | integer | read-only |
OID not used. |
oidNotUsed1 | 1.3.6.1.4.1.49136.1.1.4 | integer | read-only |
OID not used. |
battery | 1.3.6.1.4.1.49136.1.2 | |||
batteryVoltage | 1.3.6.1.4.1.49136.1.2.1 | integer | read-only |
Numeric value of instantaneous voltage of battery bank. To get the actual value in volt must be divided by 10. Example: Read value 240, actual value 24.0V. |
batteryCurrent | 1.3.6.1.4.1.49136.1.2.2 | integer | read-only |
Numeric value of current in Battery bank. Real value reading in milli ampere. If the value is negative the Battery bank is provide energy for the output. If the value is positive the Battery bank is under charger Example: Read value -2230, Actual value 2,230 ampere and the battery bank is provide this current. Read value 3000, Actual value 3.000 milli ampere and the battery bank is absorve this current. |
chargerStatus | 1.3.6.1.4.1.49136.1.2.3 | integer | read-only |
Show the status of battery charger: 0 - The battery is not connected in DC UPS; 1 - The battery is voltage incompatible with DC UPS; 2 - The DC UPS is in nobreak mode; 3 - The charger of Battery is in Bulk stage; 4 - The charger of Battery is Absorption stage; 5 - The charger of Battery is Float stage; 6 - The Battery will be disconnected in 30s due to low voltage and the DC-UPS output will be turned off. 7 - The Battery is under test |
input | 1.3.6.1.4.1.49136.1.3 | |||
alarmOnBattery | 1.3.6.1.4.1.49136.1.3.1 | integer | read-only |
Shows the operation mode of DC-UPS: 0 - The DC-UPS output is provide by AC energy. 1 - The DC-UPS output is provide by Battery |
acFail | 1.3.6.1.4.1.49136.1.3.2 | integer | read-only |
Alarm that alert about AC outages in the last 10 minutes: 0 - DC-UPS in normal operation. 1 - Occur a AC fail in the last 10 minutes. |
batteryCharging | 1.3.6.1.4.1.49136.1.3.3 | integer | read-only |
Show the status of charging Battery: 1 - The battery is on charging. 0 - The battery is on discharging. |
batteryDischarging | 1.3.6.1.4.1.49136.1.3.4 | integer | read-only |
Show the status of discharging Battery: 1 - The battery is on discharging. 0 - The battery is on charging. |
overheat | 1.3.6.1.4.1.49136.1.3.5 | integer | read-only |
Alarm that alert about overtemperature of DC-UPS 1 - The DC-UPS is in condition of overtemperature. 0 - The DC-UPS is in normal condition. |
overload | 1.3.6.1.4.1.49136.1.3.6 | integer | read-only |
Alarm that alert about overload of DC-UPS 1 - The DC-UPS is in condition of overload. 0 - The DC-UPS is in normal condition. |
fanAfail | 1.3.6.1.4.1.49136.1.3.7 | integer | read-only |
Alarm that alert about fail in internal FAN A 1 - Internal FAN with fail. 0 - Internal FAN ok |
fanBfail | 1.3.6.1.4.1.49136.1.3.8 | integer | read-only |
Alarm that alert about fail in internal FAN B 1 - Internal FAN with fail. 0 - Internal FAN ok |
oidNotUsed2 | 1.3.6.1.4.1.49136.1.3.9 | integer | read-only |
OID not used. |
oidNotUsed3 | 1.3.6.1.4.1.49136.1.3.10 | integer | read-only |
OID not used. |
upTime | 1.3.6.1.4.1.49136.1.3.11 | integer | read-only |
System Up time in hours |
temperature | 1.3.6.1.4.1.49136.1.4 | |||
innerTemperature | 1.3.6.1.4.1.49136.1.4.1 | integer | read-only |
Show the internal temperature of power supply. Uses the unit degree Celsius. Example Read value: 25, temperature is 25degC. |
outerTemperature | 1.3.6.1.4.1.49136.1.4.2 | integer | read-only |
Show the temperature of external sensor (cable that comes with power supply). Uses the unit degree Celsius. Example Read value: 25, temperature is 25degC. |
heatSinkTemperature | 1.3.6.1.4.1.49136.1.4.3 | integer | read-only |
Show the temperature of sensor in the heatsink of power supply use the unit degree Celsius. Example Read value: 25, temperature is 25degC. |
watchdog | 1.3.6.1.4.1.49136.1.5 | |||
watchdogPing1 | 1.3.6.1.4.1.49136.1.5.1 | integer | read-only |
Alarm indicating the action of watchdog 1 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from IP ping command configured. 1 - The watchdog 1 acted on the output the last 10 minutes. 0 - The Watchdog 1 has not acted in the last 10 minutes. |
watchdogPing2 | 1.3.6.1.4.1.49136.1.5.2 | integer | read-only |
Alarm indicating the action of watchdog 2 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from IP ping command configured. 1 - The watchdog 2 acted on the output the last 10 minutes. 0 - The Watchdog 2 has not acted in the last 10 minutes. |
watchdogPing3 | 1.3.6.1.4.1.49136.1.5.3 | integer | read-only |
Alarm indicating the action of watchdog 3 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from IP ping command configured. 1 - The watchdog 3 acted on the output the last 10 minutes. 0 - The Watchdog 3 has not acted in the last 10 minutes. |
watchdogPing4 | 1.3.6.1.4.1.49136.1.5.4 | integer | read-only |
Alarm indicating the action of watchdog 4 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from IP ping command configured. 1 - The watchdog 4 acted on the output the last 10 minutes. 0 - The Watchdog 4 has not acted in the last 10 minutes. |
watchdogPing5 | 1.3.6.1.4.1.49136.1.5.5 | integer | read-only |
Alarm indicating the action of watchdog 5 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from IP ping command configured. 1 - The watchdog 5 acted on the output the last 10 minutes. 0 - The Watchdog 5 has not acted in the last 10 minutes. |
watchdogPing6 | 1.3.6.1.4.1.49136.1.5.6 | integer | read-only |
Alarm indicating the action of watchdog 6 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from IP ping command configured. 1 - The watchdog 6 acted on the output the last 10 minutes. 0 - The Watchdog 6 has not acted in the last 10 minutes. |
watchdogPing7 | 1.3.6.1.4.1.49136.1.5.7 | integer | read-only |
Alarm indicating the action of watchdog 7 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from IP ping command configured. 1 - The watchdog 7 acted on the output the last 10 minutes. 0 - The Watchdog 7 has not acted in the last 10 minutes. |
watchdogPing8 | 1.3.6.1.4.1.49136.1.5.8 | integer | read-only |
Alarm indicating the action of watchdog 8 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from IP ping command configured. 1 - The watchdog 8 acted on the output the last 10 minutes. 0 - The Watchdog 8 has not acted in the last 10 minutes. |
watchdogPing9 | 1.3.6.1.4.1.49136.1.5.9 | integer | read-only |
Alarm indicating the action of watchdog 9 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from IP ping command configured. 1 - The watchdog 9 acted on the output the last 10 minutes. 0 - The Watchdog 9 has not acted in the last 10 minutes. |
watchdogPing10 | 1.3.6.1.4.1.49136.1.5.10 | integer | read-only |
Alarm indicating the action of watchdog 10 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from IP ping command configured. 1 - The watchdog 10 acted on the output the last 10 minutes. 0 - The Watchdog 10 has not acted in the last 10 minutes. |
supply | 1.3.6.1.4.1.49136.1.6 | |||
supplyVoltage | 1.3.6.1.4.1.49136.1.6.1 | integer | read-only |
The supply AC voltage decivolt [dV] Numeric value of instantaneous input voltage. An optional sensor is required to read this value. To get the actual value in volt it should be divided by 10. Example: Read value 2410, actual value 241 Vac. |
installation | 1.3.6.1.4.1.49136.1.7 | |||
popName | 1.3.6.1.4.1.49136.1.7.1 | displaystring | read-only |
PoP name |
facilityAddr | 1.3.6.1.4.1.49136.1.7.2 | displaystring | read-only |
Facility address |
facilityCity | 1.3.6.1.4.1.49136.1.7.3 | displaystring | read-only |
Facility city |
instDate | 1.3.6.1.4.1.49136.1.7.4 | displaystring | read-only |
Installation date |
batCapacity | 1.3.6.1.4.1.49136.1.7.5 | integer | read-only |
Battery capacity |
batBrand | 1.3.6.1.4.1.49136.1.7.6 | displaystring | read-only |
Battery brand |
batInstDate | 1.3.6.1.4.1.49136.1.7.7 | displaystring | read-only |
Battery installation date |
respPers | 1.3.6.1.4.1.49136.1.7.8 | displaystring | read-only |
Responsible person |
bat_tst | 1.3.6.1.4.1.49136.1.8 | |||
btst_date | 1.3.6.1.4.1.49136.1.8.1 | displaystring | read-only |
Battery test execution date (dd/mm/yyyy) |
btst_status | 1.3.6.1.4.1.49136.1.8.2 | integer | read-only |
Battery test status 0 - NEVER DONE 1 - Passed 2 - Running 3 - Aborted 4 - Failed |
btst_duration | 1.3.6.1.4.1.49136.1.8.3 | integer | read-only |
Programmed test duration in minutes * 999 - Perform the test until battery is fully discharged |
btst_elapsed | 1.3.6.1.4.1.49136.1.8.4 | integer | read-only |
Elapsed time in current\last battery test |
btst_volt_i | 1.3.6.1.4.1.49136.1.8.5 | integer | read-only |
The battery initial voltage [dV] Numeric value of battery voltage when starting the battery test. Example: Read value 241, actual value 24.1 V. |
btst_amp_i | 1.3.6.1.4.1.49136.1.8.6 | integer | read-only |
The battery initial cuurent [mA] Numeric value of battery current when starting the battery test. Example: Read value 1522, actual value 1.55 A. |
btst_volt_f | 1.3.6.1.4.1.49136.1.8.7 | integer | read-only |
The battery final voltage [dV] Numeric value of battery voltage when the battery test is done. Example: Read value 225, actual value 22.5 V. |
btst_amp_f | 1.3.6.1.4.1.49136.1.8.8 | integer | read-only |
The battery initial cuurent [mA] Numeric value of battery current when the battery test is done. Example: Read value 1485, actual value 1.48 A. |